Transformer Protection
Transformer Protection
Transformer Protection
Protection
g Digital Energy
Multilin
139
Transformer Principles
Transformer Principles
Introduction
Transformer Protection
The purpose of a transformer in the power system is to step-up, Typical Step-Down Distribution
step-down transmission or distribution voltages to the desired Transformer
levels, reduce power system losses, and provide isolation for the two
power system circuits ending at magnetically coupled windings.
The power induced into the coils can either be stepped-down, Steel
Laminations
meaning an increase in current and a decrease in voltage, usually
required for distribution, or stepped-up meaning a decrease in Oil-Cooling
current and an increase in voltage, usually required for Radiators
transmission.
Primary
Winding
Transformers can range in size from very small coupling transformers
hidden within a device, to large units that are used to interconnect Secondary
power grids. Transformers have become an essential component Winding
Medium - High Voltage High Voltage Medium - High Voltage Medium - Low Voltage
Step-Up Transformer Step-Down Transformer Step-Down Transformer Step-Down Transformer
100 MVA + 7500 kVA - 100 MVA 500 kVA - 7500 kVA 75 kVA - 500 kVA
140 www.GEDigitalEnergy.com
Transformer Principles
Transformer Protection
As most power is distributed in the form of three-phase AC, there • Lower operating voltage as equipment is connected Line-to-
are various types of three-phase transformers that support the Neutral (L-N) as opposed to the higher voltage required by Line-
three-phase power system. The three phase transformers are to-Line connections (L-L)
designed with three primary windings - one per phase and three • Smaller transformer size required as equipment is connected at
secondary windings mounted on a three-legged core. a lower voltage
• Easier to detect line-to-ground faults as any fault current
The windings within a three-phase transformer may be connected generated, either as an overcurrent or a short-circuit would
in several ways. The primaries may be connected in a “delta“ result in a significant of current on the neutral
configuration and the secondaries in a “wye” configuration or visa
versa. Advantages of a Delta connected transformer
• Polarity end of one winding is connected to the non-polarity end
Delta vs. Wye transformers of the next, allowing for an isolated ground
• One transformer can be removed (when connected in a bank)
while the remaining units deliver three-phase power at 58% of
the original output
• Easy system to keep balanced electrical loads with the
transformer being electrically grounded or ungrounded, making
it more versatile.
www.GEDigitalEnergy.com 141
Transformer Principles
Defined by codes and standards, depending on the kVA rating of a transformer, there is a minimum amount of data that must be shown on a
nameplate. For transformers rated above 500 kVA the following information is required:
• Name of manufacturer • Approximate mass of the entire unit. Individual weights are
• Serial number provided for the core and coils, as well as the tank and fittings
142 www.GEDigitalEnergy.com
Transformer Protection
Transformer Protection
Introduction
Transformer Protection
Transformers are a critical and expensive component of the power
system. Due to the long lead time for repair of and replacement of
transformers, a major goal of transformer protection is limiting the
damage to a faulted transformer. Some protection functions, such
as overexcitation protection and temperature-based protection,
may aid this goal by identifying operating conditions that may
cause transformer failure. The comprehensive transformer
protection provided by multiple function protective relays is
appropriate for critical transformers of all applications.
The major operating challenge to transformer differential protection Overvoltage Overvoltage (59)
is maintaining security during CT saturation for external faults while Overfluxing Volts/Hz (24)
maintaining sensitivity to detect low magnitude internal faults. CT External system short Time overcurrent (51, 51G),
saturation reduces the secondary output current from the CT, and circuits Instantaneous overcurrent (50, 50G)
causes a false differential current to appear to the relay. GE Multilin
differential relays meet this challenge in the following ways:
www.GEDigitalEnergy.com 143
Transformer Protection
The differential current present during transformer energization Transformer overfluxing can be a result of system overvoltages, or
resembles the condition of an internal fault . If no inhibiting low system frequency. A transformer is designed to operate at or
mechanism is provided, the differential element will trip. Since the below a maximum magnetic flux density in the transformer core.
magnetizing inrush current has significant 2nd harmonic content, Above this design limit the eddy currents in the core and nearby
the level of 2nd harmonic current can be used to differentiate conductive components cause overheating which within a very
between inrush and a fault condition. The UR T60 and T35 GE short time may cause severe damage. The magnetic flux in the core
Multilin transformer relays use two different 2nd harmonic modes is proportional to the voltage applied to the winding divided by the
to inhibit the differential element for inrush. impedance of the winding. The flux in the core increases with either
Traditional 2nd harmonic blocking – The traditional 2nd harmonic increasing voltage or decreasing frequency. During startup or
restraint responds to the ratio of the magnitudes of the 2nd shutdown of generator-connected transformers, or following a load
harmonic and the fundamental frequency currents. rejection, the transformer may experience an excessive ratio of
volts to hertz, that is, become overexcited. When a transformer core
Adaptive 2nd harmonic blocking– The adaptive 2nd harmonic
is overexcited, the core is operating in a non-linear magnetic region,
blocking responds to both magnitudes and phase angles of the 2nd
and creates harmonic components in the exciting current . A
harmonic and the fundamental frequency currents. The differential
significant amount of current at the 5th harmonic is characteristic
element correctly distinguishes between faults and transformer
of overexcitation.
energization, when the 2nd harmonic current is less than the
entered 2nd harmonic setting. While levels of 2nd harmonic during Available in the 745, T60, and T35.
inrush often do not go below 20%, many transformers are
susceptible of generating lower 2nd harmonic current during
energization. Setting the 2nd harmonic restraint below 20% may
result in incorrect inhibit of the differential element during some
internal fault events. The adaptive 2nd harmonic blocking allows
settings in the traditional 20% range, while maintaining the security
of the differential element against inrush.
Available in the T60, T35.
An alternative method for inrush inhibit is also available, where
current, voltage, or breaker status is used to indicate a de-energized
transformer. The threshold can be lowered during energization of
the transformer as indicated either by breaker contact, current or
voltage sensing, and will last for a settable time delay. This allows Differential vs. Restraint
settings of less than 20% for inrush inhibit during transformer Characteristic (ld vs.lr)
energization.
Differential
Available in the 745.
Current (Id) Slope 2
Sensitive Ground Fault Protection to limit Transformer
Damage
Break Point 2
Differential protection and overcurrent protection are not sensitive
enough to detect faults close to the neutral of wye-connected
Transition Region
transformers with grounded neutrals. Such faults produce less fault
current as shown by the current distribution curve. The restricted
ground fault function can be used to provide differential protection
for such ground faults, down to faults at 5% of the transformer Break 1
winding. Restricted ground fault protection can be a low impedance Slope 1
differential function or a high impedance differential function. The
low impedance function can precisely set the sensitivity to meet
the application requirement. This sensitive protection limits the
damage to the transformer for faults close to the neutral. The Restraint Current (Ir)
restricted ground fault element uses adaptive restraint based on
The settings for the dual-slope, dual-breakpoint characteristic provides
symmetrical components to provide security during external phase
higher flexibility for shaping up the characteristic and achieve better
faults with significant CT error. This permits the function to maximize sensitivity and security.
sensitivity without any time delay.
Available in the 745, T60.
144 www.GEDigitalEnergy.com
Transformer Protection
Transformer Protection
relays can be applied on more advanced applications.
Application Capabilities
GE Multilin transformer protection relays are suitable for different
transformer protection applications, including medium voltage and
high voltage transformers of any size, dual secondary transformers,
auto-transformers, three-winding transformers, transformers with
dual-breaker terminals.
In addition, these relays are designed for both new and retrofit
installations. New installations typically use wye-connected CTs,
and internally compensate the measured currents for the phase
shift of the protected transformer. Traditional installations may use
delta-connected or wye-connected CTs that externally compensate
the measured currents for the phase shift of the protected
transformer. GE Multilin accommodates both methods as simple
configuration settings.
www.GEDigitalEnergy.com 145
Typical Applications
Transformer Protection
Typical Applications
Transformer Protection
Lockout
Standalone HEA61-A-RU-220-X2
Integrated T35-N00-HPH-F8N-H6P-MXX-P4L-UXX-WXX
T60-N00-HPH-F8N-H6P-MXX-P4L-UXX-WXX
Lockout
Standalone HEA61-A-RU-220-X2
Integrated T35-N00-HPH-F8L-H6P-M8N -P4L-UXX-WXX
T60-N00-HPH-F8L-H6P-M8N -P4L-UXX-WXX
146 www.GEDigitalEnergy.com
Typical Applications
Transformer Protection
86 Lockout auxiliary 67 Directional overcurrent
50/51 Overcurrent and short circuit 24 Volts per Hertz
(two windings) 59 Overvoltage
50G Ground fault
V, S Voltage and Power metering
Lockout
Standalone HEA61-A-RU-220-X2
Integrated T35-N00-HPH-F8L-H6P-M8N-P4L-UXX-WXX
T60-N00-HPH-F8L-H6P-M8N-P4L-UXX-WXX
Lockout
Standalone HEA61-A-RU-220-X2
Integrated T35-N00-HPH-F8N-H6P-MXX-P4L-UXX-WXX
T60-N00-HPH-F8N-H6P-MXX-P4L-UXX-WXX
Auto-Transformer
Typical Functions Additional Functions
87T Differential 87RGF Restricted Ground Fault
86 Lockout auxiliary 67 Directional overcurrent
50/51 Overcurrent and short circuit 24 Volts per Hertz
(both sources) 59 Overvoltage
50G Ground fault
V, S Voltage and Power metering
Lockout
Standalone HEA61-A-RU-220-X2
Integrated T35-N00-HPH-F8N-H6P-MXX-P4L-UXX-WXX
T60-N00-HPH-F8N-H6P-MXX-P4L-UXX-WXX
www.GEDigitalEnergy.com 147
Typical Applications
86 Lockout auxiliary
50/51 Overcurrent and short circuit
(three windings)
50G Ground fault
Lockout
Standalone HEA61-A-RU-220-X2
Integrated T35-N00-HPH-F8L-H6P-M8N-P4L-U8N-W6P
Lockout
Standalone HEA61-A-RU-220-X2
Integrated T35-N00-HPH-F8L-H6P-M8N-P4L-UXX-WXX
T60-N00-HPH-F8L-H6P-M8N-P4L-UXX-WXX
Lockout
Standalone HEA61-A-RU-220-X2
Integrated T60-N00-HPH-F8L-H6P-M8N-P4L-UXX-WXX
148 www.GEDigitalEnergy.com
Typical Applications
Typical Functions
87T Differential
Transformer Protection
86 Lockout auxiliary
51 Overcurrent and short circuit
(two windings)
50G Ground fault
Lockout
Standalone HEA61-A-RU-220-X2
Integrated T35-N00-HPH-F8N-H6P-M8N-P4L-U8N-WXX
Lockout
Standalone HEA61-A-RU-220-X2
Integrated T60-N00-HPH-F8N-H6P-MXX-P4L-UXX-W5E
www.GEDigitalEnergy.com 149
Application Spotlight
Increase the life of your transformer, optimize your capital expenditure and improve reliability
of service by implementing a preventative asset maintenance & management tool using the
Multilin T60, T35 and 745 transformer protective relays
Increased equipment use, deferred capital expenditures and The transformer top-oil temperature can be directly measured, or
reduced maintenance expenses are challenges faced by most calculated from the ambient temperature, load current, and other
capital asset owners today. Therefore, managing critical electrical transformer characteristics. The protective relays can be set to
system assets such as large power transformers require a alarm or trip in cases where the computed hottest-spot
preventative maintenance plan that can screen device degradation temperature is above the pickup threshold for a user specified
and make intelligent device protection decisions. time (considered as transformer overheating).
Excessive heat and mechanical stress are major reasons for Multilin relays use IEEE C57.91 compliant thermal models to
transformer damage. These factors can cause hot spots, calculate the winding hot-spot temperature, detect abnormal
breakdown of winding insulation, short circuits, and catastrophic temperatures inside the transformer, and prevent loss of life of the
failures. The good news, however, is that transformer failures are winding insulation. The loss of life element detects the accumulated
attributable to manageable problems and new technology in total consumed transformer life. This element can be set to issue
transformer protective relays enable Engineers to implement a an alarm or trip when the actual accumulated transformer life
diagnostic approach to assess the health of power transformers. becomes larger than the user-specified loss of life pick up value.
Measurable indicators of transformer health include electrical The protective relay aging element detects the transformer aging
load, hottest-spot, ambient temperature, loss of life etc, Users who in per unit normal insulation aging. This element can be set for
use protective relays to monitor these indicators, plan optimal alarm or trip whenever the computed aging factor is greater than
transformer loading and maintenance, and thereby increase life of the maximum permissible user-defined pickup setting under
their asset and improve quality of their service. emergency loading conditions and maximum ambient
temperature.
Application Spotlight
Transformer Protection
Delivering fast, adaptive, sensitive and secure protection for small, medium and
large power transformer applications. Multilin protection relays include advanced
Health Diagnostics capabilities, coupled with advanced communications including
IEC 61850 for remote data and engineering access to increase asset life and
improve quality of service.
Transformer Protection
High Performance Multi-Winding High-Speed,
Transformer Protection Differential Protection Draw-out Protection
• Up to five current sources (windings) • Back-up protection for transmission • Automatic tap-changer
schemes monitoring
• Transformer – Bus protection for • Auto-transformer banks
small distribution systems
152 www.GEDigitalEnergy.com
Product Selector Guide
Transformer Protection
Selector Guide
Transformer Protection
Features Device 745 T35 T60
Protection & Control
Transformer Differential 87T • • •
Maximum Number of Windings 3 6 5
Harmonic Restraint • • •
Internal Winding Phase Shift Compensation • • •
Dynamic CT Ratio-Matching • • •
CT Mismatch Range 16/1 32/1 32/1
Restricted Ground Fault 87RGF • •
Over-Fluxing (Voltz Per Hertz) 24 • •
Phase Undervoltage 27P •
IOC, Ground/Neutral/Phase 50G/N/P G/N/P G/N/P
TOC, Ground/Neutral/Phase 51G/N/P G/N/P G/P G/N/P
Custom programmable overcurrent curves • • •
Overvoltage, Neutral/Phase/Auxiliary 59N/P/X N/P/X
Overvoltage, Symmetrical Component 59N •
Current Directional, Neutral/Phase. 67 N/P P/N
Voltage Transformer Fuse Failure VTFF •
Under/Overfrequency 81U/O • •
Synchrocheck 25 •
Transformer Overload 49 • • •
Lockout 86 • •
Automation
Settings Groups 4 6 6
Contact Inputs (Up to) 16 96 96
Contact Outputs (Up to) 8 64 64
Non-volatile latches • •
Programmable Logic • • •
FlexElements™ • •
Virtual Inputs/Outputs 16/16 64/96 64/96
Direct Inputs/Outputs 32/32 32/32
Programmable Pushbuttons 12 12
Trip/Close Coil Supervision Trip Trip/Close Trip/Close
User-Programmable LEDs 48 48
User-Programmable Self Test • •
Selector Switch • •
Digital Counters • •
Digital Elements • •
Analog Inputs/Outputs (Up to) 1 24/12 24/12
RTD Inputs (Up to) 1 24 24
Monitoring & Metering
Power Factor • • •
Current – RMS • • •
Current – Phasor • •
Current – Demand • •
Current - Unbalance •
Voltage • • •
Power - Apparent, Real, Reactive • • •
MW, MVA, Mvar Demand •
Breaker Arc Current • •
Energy • • •
Frequency • • •
Temperature • •
Current Harmonics (Up to) 21 25
Loss of Life Calculations • •
Fault Report • • •
User Programmable Trip Reports • •
Event Recorder - Number of Events 40 1024 1024
Oscillography - Sampling Rate 12 64 64
Trip Counters • •
Data Logger • • •
Simulation Mode •
Communications
RS232 Port • • •
RS485 Port • • •
RS422, G.703, C37.94 • •
Ethernet • • •
Fiber (800nm, 1300nm, 1550nm) • •
Protocols
ModBus (RTU & TCP/IP) • • •
DNP3 • • •
EGD Protocol • •
IEC61850 • •
IEC 60870-5-104 • •
Simple Network Time Protocol • •
TCP/IP • •
HTTP • • •
IRIG-B Input • • •
Process Bus (IEC 61850-9-2) • •
www.GEDigitalEnergy.com 153
Product Listing
Transformer Protection
Product Listing
Transformer Protection