QCDD Compliance Photos

Download as pdf or txt
Download as pdf or txt
You are on page 1of 26

Client: Consultant: Contractor  

  
 

QCDD Compliance Photos  

3 - Handrails shall be provided on stair, in accordance with NFPA 101


a. Stairs with two steps or more shall be provided with handrails on both sides,
and along the natural path of travel At the time of inspection, the mosque entrance
having 3 steps without handrail.
Client: Consultant: Contractor

QCDD Compliance Photos  

4 - Push to Open - ‫ﺍﺩﻓﻊ‬


All exit doors shall be provided with the signage above as per NFPA 101

 
Client: Consultant: Contractor

QCDD Compliance Photos  

5 - Fire Engine Hard Standing location and marking shall be provided in


accordance with Civil Defence approved drawing
The Fire Engine Hard Standing shall be provided as stated above in letter markings of at least 50-
mm in height

 
Client: Consultant: Contractor

QCDD Compliance Photos  

6 a. Fire Pump room shall be enclosed with fire rated walls as per NFPA 101 and
approved Civil Defence drawings (Pls. see c.)

 
Client: Consultant: Contractor

QCDD Compliance Photos  

6 b - A stock of spare sprinklers with a quantity prescribed by NFPA 13 (minimum 6


pieces) with special sprinkler wrench shall be maintained, provided and kept in the
cabinet

 
Client: Consultant: Contractor

QCDD Compliance Photos  

7 II. Sprinkler head inside the elevator pit shall be mounted not more than 24
inches (600mm) above the elevator pit (Tapping point. Ref. dwg. FF-114)
III. Sprinkler heads cover plates shall not be painted and free of dirt
At Mosque and Administration - During inspection, it has been noticed some
escutcheon plates was painted and some imbedded with majoon/putty.

 
Client: Consultant: Contractor

QCDD Compliance Photos  

7 III. Sprinkler heads cover plates shall not be painted and free of dirt
At Mosque and Administration - During inspection, it has been noticed some
escutcheon plates was painted and some imbedded with majoon/putty.

 
Client: Consultant: Contractor

QCDD Compliance Photos  

8a. During inspection, the isolation valve lever was removed.


NFPA 20. 11.4.4.5.1 The valve shall be locked in the open position.

 
Client: Consultant: Contractor

QCDD Compliance Photos  

9 a - Breeching inlet location shall be provided with appropriate marking (wet or


dry)

 
Client: Consultant: Contractor

QCDD Compliance Photos  

9 b - BS336 Hydrants, breaching inlets and Landing valve shall be installed in


accordance with NFPA 14 and NFPA 24 All Connection types shall be in BS336
(Snap-on type)

 
Client: Consultant: Contractor

QCDD Compliance Photos  

9b.ii - Each fire hydrant shall be provided isolation gate valve. Ref. drwg. FF-102

 
Client: Consultant: Contractor

QCDD Compliance Photos  

9.b - III. NFPA 14 Chapter 6.1.2 Protection of Aboveground Piping: Standpipe


system piping shall be protected from mechanical damage.

 
Client: Consultant: Contractor

QCDD Compliance Photos  

9d - Sprinkler Floor/Zone Control Valve location shall be provided with appropriate


marking

 
Client: Consultant: Contractor

QCDD Compliance Photos  

10a. Initiating devices inside the protected room did not activate.
Note: Manual release did not activate during test for the MDF Room (2nd floor).

 
Client: Consultant: Contractor

QCDD Compliance Photos  

15a. Using Emergency Power Supply System (EPSS) for ventilation fans failed
during testing.

 
Client: Consultant: Contractor

QCDD Compliance Photos  

 
Client: Consultant: Contractor

QCDD Compliance Photos  

15b - Justify the ventilation system at the fire pump room shall be supply and
exhaust. (Ref. drwg AC34-101)

 
Client: Consultant: Contractor

QCDD Compliance Photos  

16a. Using Emergency Power Supply System (EPSS) for smoke control fans failed
during testing

 
Client: Consultant: Contractor

QCDD Compliance Photos  

16b - Duct smoke detector shall be provided to shut down fans upon activation
Duct detector did not shutdown fans during testing.

 
Client: Consultant: Contractor

QCDD Compliance Photos  

17a. Functional test of Fire-fighter's smoke control panel;

 
Client: Consultant: Contractor

QCDD Compliance Photos  

17d - Identification marking of fans and outlets/inlets shall be provided (e.g. “Fresh
Air Supply”/ “Exhaust Air”)
- Ref. drwg. AC1-501-1& 2- (Fire Mode Operation and miscellaneous features) for
validation on next schedule of inspection.

 
Client: Consultant: Contractor

QCDD Compliance Photos  

18 - Provide access opening for all fire/ smoke or motorizes damper.


- NFPA 90 A , A .4.3.4.1 Access doors for fire dampers should be located so that the spring catch
and fusible links are accessible when the damper is closed. Where the size of the duct permits, the
minimum access door size should be 457 mm × 406 mm (18 in. × 16 in.). For dampers that are too
large for an ordinary person's arms to reach from outside the duct to reset the damper and replace
the fusible link, the minimum size for the access door should be increased to 610 mm × 406 mm (24
in. × 16 in.) to allow the entrance of an individual. Access doors should be located as close as
practicable to fire dampers and smoke dampers. If feasible, the underside of the duct should be
used rather than a side door. Many fire dampers and smoke dampers are preloaded with powerful
springs that force the damper to shut. These dampers need to be opened against these springs
which could necessitate the ability to get two arms into the duct.

 
Client: Consultant: Contractor

QCDD Compliance Photos  

19. Emergency Power Supply System (EPSS) functionality comments


As per declaration of the consultant, Emergency Power Supply System (EPSS) not yet
commissioned. NO TESTING DONE in EPSS during inspection. For testing on next schedule of
inspection.

 
Client: Consultant: Contractor

QCDD Compliance Photos  
20 - An illuminating approved exit sign shall be installed in accordance with Civil Defence approved
drawings and NFPA 101
Illuminated Directional and Exit signs shall be visible from 30 meters

 
Client: Consultant: Contractor

QCDD Compliance Photos  

21 - Identification and warning signs comments


a. Appropriate identification signs shall be installed in all utility/ service rooms in both
languages Arabic and English

 
Client: Consultant: Contractor

QCDD Compliance Photos  

21 - Identification and warning signs comments


b. Following warning signs shall be installed in all elevators and elevator lobbies: