ISA-TR84.00.02-2002 - Part 1
ISA-TR84.00.02-2002 - Part 1
ISA-TR84.00.02-2002 - Part 1
ISA-TR84.00.02-2002 - Part 1
NOTICE OF COPYRIGHT
This is a copyrighted document and may not be copied or distributed in any
form or manner without the permission of ISA. This copy of the document was
made for the sole use of the person to whom ISA provided it and is subject to
the restrictions stated in ISA’s license to that person. It may not be provided to
any other person in print, electronic, or any other form. Violations of ISA’s
copyright will be prosecuted to the fullest extent of the law and may result in
substantial civil and criminal penalties.
ISA–The Instrumentation,
Systems, and
Automation Society --``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
ISA-TR84.00.02-2002 – Part 1
Safety Instrumented Functions (SIF) Safety Integrity Level (SIL) Evaluation Techniques Part 1:
Introduction
ISBN: 1-55617-802-6
Copyright © 2002 by ISA —The Instrumentation, Systems, and Automation Society. All rights reserved.
Not for resale. Printed in the United States of America. No part of this publication may be reproduced,
stored in a retrieval system, or transmitted in any form or by any means (electronic mechanical,
photocopying, recording, or otherwise), without the prior written permission of the Publisher.
ISA
67 Alexander Drive
P.O. Box 12277
Research Triangle Park, North Carolina 27709
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
−3− ISA-TR84.00.02-2002 - Part 1
Preface
This preface, as well as all footnotes and annexes, is included for information purposes and is not part of
ISA-TR84.00.02-2002 – Part 1.
This document has been prepared as part of the service of ISAthe Instrumentation, Systems, and
Automation Societytoward a goal of uniformity in the field of instrumentation. To be of real value, this
document should not be static but should be subject to periodic review. Toward this end, the Society
welcomes all comments and criticisms and asks that they be addressed to the Secretary, Standards and
Practices Board; ISA; 67 Alexander Drive; P. O. Box 12277; Research Triangle Park, NC 27709;
Telephone (919) 549-8411; Fax (919) 549-8288; E-mail: standards@isa.org.
The ISA Standards and Practices Department is aware of the growing need for attention to the metric
system of units in general, and the International System of Units (SI) in particular, in the preparation of
instrumentation standards. The Department is further aware of the benefits to USA users of ISA
standards of incorporating suitable references to the SI (and the metric system) in their business and
professional dealings with other countries. Toward this end, this Department will endeavor to introduce
SI-acceptable metric units in all new and revised standards, recommended practices, and technical
reports to the greatest extent possible. Standard for Use of the International System of Units (SI): The
Modern Metric System, published by the American Society for Testing & Materials as IEEE/ASTM SI 10-
97, and future revisions, will be the reference guide for definitions, symbols, abbreviations, and
conversion factors.
It is the policy of ISA to encourage and welcome the participation of all concerned individuals and
interests in the development of ISA standards, recommended practices, and technical reports.
Participation in the ISA standards-making process by an individual in no way constitutes endorsement by
the employer of that individual, of ISA, or of any of the standards, recommended practices, and technical
reports that ISA develops.
EVEN IF ISA IS UNAWARE OF ANY PATENT COVERING THIS STANDARD, THE USER IS
CAUTIONED THAT IMPLEMENTATION OF THE STANDARD MAY REQUIRE USE OF TECHNIQUES,
PROCESSES, OR MATERIALS COVERED BY PATENT RIGHTS. ISA TAKES NO POSITION ON THE
EXISTENCE OR VALIDITY OF ANY PATENT RIGHTS THAT MAY BE INVOLVED IN IMPLEMENTING
THE STANDARD. ISA IS NOT RESPONSIBLE FOR IDENTIFYING ALL PATENTS THAT MAY
REQUIRE A LICENSE BEFORE IMPLEMENTATION OF THE STANDARD OR FOR INVESTIGATING
THE VALIDITY OR SCOPE OF ANY PATENTS BROUGHT TO ITS ATTENTION. THE USER SHOULD
CAREFULLY INVESTIGATE RELEVANT PATENTS BEFORE USING THE STANDARD FOR THE
USER’S INTENDED APPLICATION.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
HOWEVER, ISA ASKS THAT ANYONE REVIEWING THIS STANDARD WHO IS AWARE OF ANY
PATENTS THAT MAY IMPACT IMPLEMENTATION OF THE STANDARD NOTIFY THE ISA
STANDARDS AND PRACTICES DEPARTMENT OF THE PATENT AND ITS OWNER.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 −4−
PROFESSIONAL JUDGMENT CONCERNING ITS USE AND APPLICABILITY UNDER THE USER’S
PARTICULAR CIRCUMSTANCES. THE USER MUST ALSO CONSIDER THE APPLICABILITY OF
ANY GOVERNMENTAL REGULATORY LIMITATIONS AND ESTABLISHED SAFETY AND HEALTH
PRACTICES BEFORE IMPLEMENTING THIS STANDARD.
THE USER OF THIS DOCUMENT SHOULD BE AWARE THAT THIS DOCUMENT MAY BE IMPACTED
BY ELECTRONIC SECURITY ISSUES. THE COMMITTEE HAS NOT YET ADDRESSED THE
POTENTIAL ISSUES IN THIS VERSION.
NAME COMPANY
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
J. Gilman Consultant
W. Goble exida.com LLC
D. Green* Rohm & Haas Company
P. Gruhn Siemens
C. Hardin CDH Consulting Inc.
J. Harris UOP LLC
D. Haysley Albert Garaody & Associates
M. Houtermans TUV Product Service Inc.
J. Jamison Bantrel Inc.
W. Johnson* E I du Pont
D. Karydas* Factory Mutual Research Corporation
L. Laskowski Solutia Inc.
T. Layer Emerson Process Management
D. Leonard D J Leonard Consultants
E. Lewis Consultant
E. Marszal Exida.com
N. McLeod Atofina
W. Mostia WLM Engineering Company
D. Ogwude Creative Systems International
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
−5− ISA-TR84.00.02-2002 - Part 1
This standard was approved for publication by the ISA Standards and Practices Board on 17 June 2002.
NAME COMPANY
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
This page intentionally left blank.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
−7− ISA-TR84.00.02-2002 - Part 1
Contents
Foreword ....................................................................................................................................................... 9
Introduction ................................................................................................................................................. 11
1 Scope................................................................................................................................................... 17
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
2 References .......................................................................................................................................... 17
5.8 Failure rate data for commonly used field instrumentation .......................................................... 54
Annex A (informative) Methodology for quantifying the effect of hardware-related common cause
failures in Safety Instrumented Functions................................................................................................... 67
Annex D (informative) Failure mode effect, hazard and criticality analysis ........................................... 85
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
−9− ISA-TR84.00.02-2002 - Part 1
Part 1: Introduction
Foreword
The information contained in ISA-TR84.00.02-2002 is provided for information only and is not part of the
(1)
ANSI/ISA-84.01-1996 Standard requirements.
(2)
The purpose of ISA-TR84.00.02-2002 is to provide the process industry with a description of various
methodologies that can be used to evaluate the Safety Integrity Level (SIL) of Safety Instrumented
Functions (SIF).
ANSI/ISA-84.01-1996 provides the minimum requirements for implementing a SIS given that a set of
functional requirements have been defined and a SIL requirement has been established for each safety
instrumented function. Additional information of an informative nature is provided in the Annexes to
ANSI/ISA-84.01-1996 to assist the designer in applying the concepts necessary to achieve an acceptable
design. However, Standards Project 84 (SP84) determined that it was appropriate to provide
supplemental information that would assist the user in evaluating the capability of any given SIF design to
achieve its required SIL. A secondary purpose of this document is to reinforce the concept of the
performance based evaluation of SIF. The performance parameters that satisfactorily service the process
industry are derived from the SIL and reliability evaluation of SIF, namely the probability of the SIF to fail
to respond to a demand and the probability that the SIF creates a nuisance trip. Such evaluation
addresses the design elements (hardware, software, redundancy, etc.) and the operational attributes
(inspection/maintenance policy, frequency and quality of testing, etc.) of the SIF. The basis for the
performance evaluation of the SIF is safety targets determined through hazard analysis and risk
(6)
assessment of the process. This document demonstrates methodologies for the SIL and reliability
evaluation of SIF.
The document focuses on methodologies that can be used without promoting a single methodology. It
provides information on the benefits of various methodologies as well as some of the drawbacks they may
have.
• Process Hazards Analysis teams that wish to develop understanding of different methodologies in
determining SIL
• SIS designers who want a better understanding of how redundancy, diagnostic coverage, diversity,
etc., fit into the development of a proper SIS architecture
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 10 −
• National and International standard bodies providing guidance in the use of reliability techniques for
SIS architectures
• Reliability engineers (or any engineer performing this function) can use this information to develop
better methods for determining SIL in the rapidly changing SIS field
• Parties who do not have a large installed base of operating equipment sufficient to establish
spurious
appropriate statistical analysis for PFDavg and MTTF for SIS components
ISA-TR84.00.02-2002 consists of the following parts, under the general title “Safety Instrumented
Functions (SIF) Safety Integrity Level (SIL) Evaluation Techniques."
Part 1: Introduction
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 11 − ISA-TR84.00.02-2002 - Part 1
Introduction
ANSI/ISA-84.01-1996 describes a safety lifecycle model for the implementation of risk reduction
measures for the process industry (Clause 4). The standard then proceeds to provide specific guidance in
the application of SIS, which may be one of the risk reduction methods used. The standard defines three
levels of safety integrity (Safety Integrity Levels, SIL) that may be used to specify the capability that a
safety instrumented function must achieve to accomplish the required risk reduction. ISA-TR84.00.02-
2002 provides methodologies for evaluating SIF to determine if they achieve the specific SIL. This may be
referred to as a probability of failure on demand (PFD) evaluation of the SIF.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
The evaluation approaches outlined in this document are performance-based approaches and do not
provide specific results that can be used to select a specific architectural configuration for a given SIL.
The evaluation processes described in this document take place before the SIS detailed design phase of
the life cycle (see Figure I.1, Safety Lifecycle Model).
This document assumes that a SIS is required. It does not provide guidance in the determination of the
need for a SIS. The user is referred to ANSI/ISA-84.01-1996 Annex A for methodologies that might be
used in making this determination.
This document involves the evaluation of the whole SIF from the sensors through the logic solver
to the final elements. Process industry experience shows that sensors and final elements are
major contributors to loss of SIS integrity (high PFD). When evaluating the performance of
sensors and final elements, issues such as component technology, installation, and maintenance
should be considered.
Frequently multiple safety instrumented functions are included in a single logic solver. The logic solver
should be carefully evaluated since a problem in the logic solver may adversely impact the performance
of all of the safety instrumented functions (i.e., the logic solver could be the common cause failure that
disables all of the SIFs.).
• element of a SIS that is common to more than one safety instrumented function; and
Each element should be evaluated with respect to all the safety instrumented functions with which it is
associated
• to ensure that it meets the integrity level required for each safety instrumented function;
This document does not provide guidance in the determination of the specific SIL required (e.g., SIL 1, 2,
and 3) for the SIS. The user is again referred to ANSI/ISA-84.01-1996 or to other references.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 12 −
The primary focus of this document is on evaluation methodologies for assessing the capability of the
SIS. The SIS lifecycle model is defined in ANSI/ISA-84.01-1996. Figure I.2 shows the boundaries of the
SIS and how it relates to other systems.
Start
Establish
Develop * Operation &
Safety Maintenance
Conceptual Requirements Procedures
Process Specification
Design
Yes Decommision
Legend:
Safety Life Cycle *
Safety Life Cycle Safety Life Cycle steps where
steps covered steps not covered TR84.00.02
by 84.01 by 84.01 is applicable
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 13 − ISA-TR84.00.02-2002 - Part 1
Logic Final
Sensors Solver Elements
Logic
SIS Boundary
The safety requirements specification addresses the design elements (hardware, software, redundancy,
etc.) and the operational attributes (inspection/maintenance policy, frequency and quality of testing, etc.)
of the SIS. These elements affect the PFD of each safety instrumented function.
The PFD of these systems can be determined using historical system performance data (e.g., statistical
analysis). Where systems, subsystems, components, etc. have not been in use for a sufficiently long time
and in large enough numbers to have a statistically significant population available for the evaluation of
their performance solely based on actuarial data, a systematic evaluation of the performance of a system
may be obtained through the use of PFD analysis techniques.
PFD analysis techniques employ systematic methodologies that decompose a complex system to its
basic components. The performance and interactions of these basic components are merged into
reliability models (such as simplified equations, fault trees, Markov models) to determine the overall
system safety availability.
This document provides users with a number of PFD evaluation techniques that allow a user to determine
if a SIF meets the required safety integrity level.
Safety integrity is defined as “The probability of a Safety Instrumented Function satisfactorily performing
the required safety functions under all stated conditions within a stated period of time.” Safety integrity
consists of two elements: 1) hardware safety integrity and 2) systematic safety integrity. Hardware safety
integrity which is based upon random hardware failures can normally be estimated to a reasonable level
of accuracy. ANSI/ISA-84.01-1996 addresses the hardware safety integrity by specifying target failure
measures for each SIL. For SIF operating in the demand mode the target failure measure is PFDavg
(average probability of failure to perform its design function on demand). PFDavg is also commonly
referred to as the average probability of failure on demand. Systematic integrity is difficult to quantify due
to the diversity of causes of failures; systematic failures may be introduced during the specification,
design, implementation, operational and modification phase and may affect hardware as well as software.
ANSI/ISA-84.01-1996 addresses systematic safety integrity by specifying procedures, techniques,
measures, etc. that reduce systematic failures.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 14 −
An acceptable safe failure rate is also normally specified for a SIF. The safe failure rate is commonly
referred to as the false trip, nuisance trip, or spurious trip rate. The spurious trip rate is included in the
evaluation of a SIF, since process start up and shutdown are frequently periods where chances of a
hazardous event are high. Hence in many cases, the reduction of spurious trips will increase the safety of
the process. The acceptable safe failure rate is typically expressed as the mean time to a spurious trip
spurious
(MTTF ).
NOTE In addition to the safety issue(s) associated with spurious trips the user of the SIS may also want the acceptable
MTTFspurious to be increased to reduce the effect of spurious trips on the productivity of the process under control. This increase in
the acceptable MTTFspurious can usually be justified because of the high cost associated with a spurious trip.
The objective of this technical report is to provide users with techniques for the evaluation of the hardware
spurious
safety integrity of SIF (PFDavg) and the determination of MTTF . Methods of modeling systematic
failures are also presented so a quantitative analysis can be performed if the systematic failure rates are
known.
ISA-TR84.00.02-2002 shows how to model complete SIF, which includes the sensors, the logic solver
and final elements. To the extent possible the system analysis techniques allow these elements to be
independently analyzed. This allows the safety system designer to select the proper system configuration
to achieve the required safety integrity level.
• a detailed listing of the definition of all terms used in this document. These are consistent with the
ANSI/ISA-84.01-1996, IEC 61508 and IEC 61511 standards.
• the background information on how to model all the elements or components of a SIF. It focuses on
the hardware components, provides some component failure rate data that are used in the examples
calculations and discusses other important parameters such as common cause failures and functional
failures.
• a brief introduction to the methodologies that will be used in the examples shown in this document.
(3) (4) (5)
They are Simplified equations , Fault Tree Analysis , and Markov Analysis .
ISA-TR84.00.02-2002 - Part 2 provides simplified equations for calculating the SIL values for Demand
Mode Safety Instrumented Functions (SIF) installed in accordance with ANSI/ISA-84.01-1996,
“Applications of Safety Instrumented Systems for the Process Industries." Part 2 should not be
interpreted as the only evaluation technique that might be used. It does, however, provide the
engineer(s) performing design for a SIS with an overall technique for assessing the capability of the
designed SIF.
ISA-TR84.00.02-2002 - Part 3 provides fault tree analysis techniques for calculating the SIL for Demand
Mode Safety Instrumented Functions (SIF) installed in accordance with ANSI/ISA-84.01-1996,
“Applications of Safety Instrumented Systems for the Process Industries." Part 3 should not be
interpreted as the only evaluation technique that might be used. It does, however, provide the
engineer(s) performing design for a SIS with an overall technique for assessing the capability of the
designed SIF.
ISA-TR84.00.02-2002 - Part 4 provides Markov analysis techniques for calculating the SIL values for
Demand Mode Safety Instrumented Functions (SIF) installed in accordance with ANSI/ISA-84.01-1996,
“Applications of Safety Instrumented Systems for the Process Industries." Part 4 should not be
interpreted as the only evaluation technique that might be used. It does, however, provide the
engineer(s) performing design for a SIS with an overall technique for assessing the capability of the
designed SIF.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 15 − ISA-TR84.00.02-2002 - Part 1
ISA-TR84.00.02-2002 - Part 5 addresses the logic solver only, using Markov Models for calculating the
PFD of E/E/PE logic solvers because it allows the modeling of maintenance and repairs as a function of
time, treats time as a model parameter, explicitly allows the treatment of diagnostic coverage, and models
the systematic failures (i.e., operator failures, software failures, etc.) and common cause failures.
Figure I.3 illustrates the relationship of each part to all other parts.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 16 −
Part 1
Part 2 Part 5
Guidance in
determining
Part 3 the PFD of
E/E/PE logic
Development of SIL for SIF using
solver(s) via
Fault Tree Analysis Methodology.
Markov
Analysis.
Part 4
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 17 − ISA-TR84.00.02-2002 - Part 1
1 Scope
1.1 ISA-TR84.00.02-2002 - Part 1 is informative and does not contain any mandatory clauses. ISA-
TR84.00.02-2002 is intended to be used only with a thorough understanding of ANSI/ISA-84.01-1996
(see Figure I.1). Prior to proceeding with use of ISA-TR84.00.02-2002 in a safety application, the
Hazards and Risk Analysis must have been completed and the following information provided
c) discussion of failure rates and failure modes (Annex D) of SIS and their components;
d) discussion of diagnostic coverage, covert faults, common cause, systematic failures, redundancy of
SIF;
1.3 The objective of ISA-TR84.00.02-2002 - Part 1 is to introduce the reader to the performance based
approach for evaluating the reliability of SIF and to present system reliability methodologies that can be
used to evaluate the system performance parameters, namely, the probability that the SIF fails to respond
to a demand and the probability that the SIF creates a nuisance trip. ISA-TR84.00.02-2002 - Part 1
serves as an introduction for all other parts.
2 References
1. ANSI/ISA-84.01-1996 “Application of Safety Instrumented Systems for the Process Industries," ISA,
Research Triangle Park, NC, 27709, February 1996.
4. “Guidelines for Safe Automation of Chemical Processes," Center for Chemical Process Safety,
American Institute of Chemical Engineers, New York, NY 10017, 1993
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 18 −
6. “Introduction to Reliability Engineering," E.E. Lewis, John Wiley & Sons, New York, NY 10158, 1987.
7. “Assurance Technologies - Principles and Practices," D.G. Raheja, McGraw and Hill Inc., New York,
NY, 1991.
8. “Safeware - System Safety and Computers," N.G. Levenson, Addison-Wesley Publishing Co.,
Reading, MA, 1995.
9. “Reliability by Design," A.C. Brombacher, John Wiley & Sons, New York, NY 10158, 1992.
10. “Software Reliability Handbook," P. Rook, Elsevier Science Press, New York, NY 10010, 1990.
11. “Guidelines for Chemical Process Quantitative Risk Analysis, Center for Chemical Process Safety,
New York, NY, American Institute of Chemical Engineers, 1989.
12. “The 'Why’s' of Grounding Isolated Ground Planes and Power Supplies, ISBN 0-941247-00-7,
Licensing Division, Bell Communications Research, Inc., 290 W. Mt. Pleasant Ave., Livingston, NJ
07039-2729, 1989.
13. “Reliability Evaluation of Engineering Systems," R. Billinton, R.N. Allan, Pitman Advanced Publishing
Program, Marshfield, MA 02050, 1983.
14. OREDA-92 (Offshore Reliability Data) DNV Industry, 1992, ISBN 82-515-0188-1.
15. Guidelines For Process Equipment Reliability Data With Data Tables, American Institute of Chemical
Engineers, Center for Chemical Process Safety, 1989, ISBN 8169-0422-7.
16. IEEE Std 500-1984, Equipment Reliability Data for Nuclear Power Generating Stations, IEEE and
John Wiley & Sons, 1974, ISBN 471-80785-0.
19. Programmable electronic systems in safety-related applications, Part 2: General technical guidelines,
Health and Safety Executive, HMSO, ISBN 0 11 883906 3, 1987.
20. Assigning a numerical value to the beta factor common cause evaluation, Humphreys, R. A.,
Reliability '87.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
21. UPM3.1: A pragmatic approach to dependent failures assessment for standard systems, AEA
Technology, ISBN 085 356 4337.
22. G. Apostolakis, S. Kaplan, "Methodology for Probabilistic Risk Assessment of Nuclear Power Plants,"
Technical Report, Pickard, Lowe and Garrick Inc., 1981.
23. G. Apostolakis, J.S. Wu and D. OKrent, "Uncertainties in System Reliability: Probabilistic versus
Nonprobabilistic Theories," Reliability Engineering and System Safety, Vol. 30, 1991.
nd
24. M. Evans, N. Hastings and B. Peacock, “Statistical Distributions," 2 edition, John Wiley & Sons, NY,
1993.
25. G. Fishman, "Concepts and Methods in Discrete Event Simulation," John Wiley & Sons, NY, 1983.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 19 − ISA-TR84.00.02-2002 - Part 1
27. A.L. Sweet, "On the Hazard Rate of Lognormal Distribution," IEEE Transactions on Reliability, Vol.
39, 1990.
28. A.C. Brombacher, Reliability by Design, John Wiley & Sons, New York, NY 10158, 1992.
29. R. Spence, Tolerance Design of Electronic Circuits (Electronic Systems Engineering Series),
Addison-Wesley Pub Co, June 1998.
30. R. Spence, R. Singh Soin, Tolerance Design of Electronic Circuits, Harvill Pr, March 1997.
31. Montgomery D.C., Runger G.C., Montgomery D., Applied Statistics and Probability for Engineers,
John Wiley and Sons, January 1994.
32. Rouvroye J.L., Robust Design Toolbox Reference Manual, Toolbox version 2.3. Eindhoven University
of Technology, 1997.
33. Henley, Ernest J. and Kumamoto, Hiromitsu, Probabilistic Risk Assessment, IEEE Press, New York,
New York, 1992.
34. “What Went Wrong? Case Histories of Process Plant Disasters," Trevor A. Kletz, Gulf Publishing
Company, Houston, Texas, 1988.
35. “Learning From Disaster: How Organizations Have No Memory," Trevor A. Kletz, Gulf Publishing
Company, Houston, Texas, 1993.
3.1.3 architecture:
the arrangement of hardware and/or software elements in a system e.g., (1) arrangement of safety
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
instrumented system (SIS) subsystems; (2) internal structure of a SIS subsystem; (3) arrangement of
software programs; (4) voting.
3.1.4 availability:
see “safety availability.”
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 20 −
3.1.6 channel:
a channel is an element or a group of elements that independently perform(s) a function. The elements
within a channel could include input/output(I/O) modules, logic system, sensors, and final elements. The
term can be used to describe a complete system, or a portion of a system (for example, sensors or final
elements).
NOTE A dual channel (i.e., a two channel) configuration is one with two channels that independently perform the same function.
3.1.8 communication:
3.1.9 coverage:
see “diagnostic coverage.”
3.1.10 overt:
see "undetected."
NOTE Whether or not the potential is realised may depend on the channel architecture of the system; in systems with multiple
channels to improve safety, a dangerous hardware failure is less likely to lead to the overall hazardous or fail-to-function state.
3.1.13 decommissioning:
the permanent removal of a complete SIS from active service.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 21 − ISA-TR84.00.02-2002 - Part 1
3.1.15 demand:
a condition or event that requires the SIS to take appropriate action to prevent a hazardous event from
occurring or to mitigate the consequence of a hazardous event.
3.1.16 detected:
in relation to hardware and software, detected by the diagnostic tests, or through normal operation.
NOTE 1 For example, physical inspection and manual tests, or through normal operation.
NOTE 2 These adjectives are used in detected fault and detected failure.
NOTE 2 The diagnostic coverage is used to compute the detected (λD) and undetected failure rates (λU) from the total failure rate
(λT) as follows: λD = DC x λT and λU = (1-DC) x λT
NOTE 3 Diagnostic coverage is applied to components or subsystems of a safety instrumented system. For example the
diagnostic coverage is typically determined for a sensor, final element, or a logic solver.
NOTE 4 For safety applications the diagnostic coverage is typically applied to the safe and dangerous failures of a component or
subsystem. For example the diagnostic coverage for the dangerous failures of a component or subsystem is DC = λDD/λDT , where
λDD is the dangerous detected failure rates and λDT is the total dangerous failure rate.
3.1.18 diverse:
use of different technologies, equipment or design methods to perform a common function with the intent
to minimize common cause faults.
3.1.19 Electrical (E)/ Electronic (E)/ Programmable Electronic Systems (PES) [E/E/PES]:
when used in this context, electrical refers to logic functions performed by electromechanical techniques,
(e.g., electromechanical relay, motor driven timers, etc.), electronic refers to logic functions performed by
electronic techniques, (e.g., solid state logic, solid state relay, etc.), and programmable electronic system
refers to logic performed by programmable or configurable devices [e.g., Programmable Logic Controller
(PLC), Single Loop Digital Controller (SLDC), etc.]. Field devices are not included in E/E/PES.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 22 −
3.1.24 fail-to-danger:
the state of a SIF in which the SIF cannot respond to a demand. Fail-to-function is used in this document
(see fail-to-function).
3.1.25 fail-to-function:
the state of a SIF during which the SIF cannot respond to a demand.
3.1.26 fail-safe:
the capability to go to a predetermined safe state in the event of a specific malfunction.
3.1.27 failure:
the termination of the ability of a functional unit to perform a required function.
NOTE 1 Performance of required functions necessarily excludes certain behaviour, and some functions may be specified in terms
of behaviour to be avoided. The occurrence of such behaviour is a failure.
3.1.29 fault:
an abnormal condition that may cause a reduction in, or loss of, the capability of a functional unit to
perform a required function.
NOTE 1 Examples are valves, switch gear, motors including their auxiliary elements e.g., a solenoid valve and actuator if involved
in the safety instrumented function.
3.1.33 firmware:
special purpose memory units containing embedded software in protected memory required for the
operation of programmable electronics.
NOTE 1 This term is not used in ANSI/ISA-84.01-1996. It is used in the IEC 61508 and IEC 61511 standards.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
NOTE 2 This definition is from IEC 61511 and it deviates from the definition in IEC 61508-4 to reflect differences in the process
sector.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 23 − ISA-TR84.00.02-2002 - Part 1
NOTE 1 This term is not used in ANSI/ISA-84.01-1996. It is used in the IEC 61508 and IEC 61511 standards.
NOTE 2 This definition is from IEC 61511 and it deviates from the definition in IEC 61508-4 to reflect differences in the process
sector.
NOTE A functional safety audit may be carried out as part of a functional safety assessment.
3.1.39 harm:
physical injury or damage to the health of people either directly, or indirectly as a result of damage to
property or to the environment.
3.1.40 hazard:
potential source of harm.
NOTE The term includes danger to persons arising within a short time scale (for example, fire and explosion) and also those that
have a long term effect on a person’s health (for example, release of a toxic substance).
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 24 −
NOTE 1 In ANS/ISA-84.01-1996 and IEC 61511 the following logic systems are used:
NOTE 2 Examples are: electrical systems, electronic systems, programmable electronic systems, pneumatic systems, hydraulic
systems, etc. Sensors and final elements are not part of the logic solver.
NOTE 3 This term deviates from the definition in IEC 61508-4 to reflect differences in the process sector.
spurious
3.1.46 mean time to fail - spurious (MTTF ):
the mean time to a failure of the SIS which results in a spurious or false trip of the process or equipment
under control (EUC).
3.1.48 off-line:
process, to which the SIS is connected, is shutdown.
3.1.49 on-line:
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
process, to which the SIS is connected, is operating.
3.1.51 overt:
see "detected."
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 25 − ISA-TR84.00.02-2002 - Part 1
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
encompasses both hardware and software and input and output units.
NOTE 1 This term covers micro-electronic devices based on one or more central processing units (CPUs) together with
associated memories, etc. Examples of process sector programmable electronics include:
smart sensors;
programmable controllers;
NOTE 2 This term differs from the definition in IEC 61508-4 to reflect differences in the process sector.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 26 −
Other Systems
MAN –
MACHINE
INTERFACE
functions
Communication
functions
Programming,
debugging and
testing functions
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
Signal OPERATING
processing SYSTEM
functions functions
Mains Power
APPLICATION APPLICATION
supply supply
PROGRAM PROGRAM
function
Execution storage functions
DATA
storage
functions
INTERFACE functions to
sensors and actuators
Machine/Process
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 27 − ISA-TR84.00.02-2002 - Part 1
NOTE The structure of a PES is shown in Figure 3.2 (A). (B) illustrates the way in which a PES is represented with the
programmable electronics shown as a unit distinct from sensors and actuators on the process and their interfaces but the
programmable electronics could exist at several places in the PES. (C) illustrates a PES with two discrete units of programmable
electronics. (D) illustrates a PES with dual programmable electronics (i.e., two channels) but with a single sensor and a single
actuator. (E) illustrates a system based on non-programmable hardware.
Programmable
electronics (PE)
(see note)
PE2
(B) Single PES with single (C) Single PES with dual (D) Single PES with dual PE (E) Single non-programmable
PE (i.e., one PES comprised PE linked in a serial but with shared sensors and system (e.g., electrical/
of a single channel of PE) manner (e.g., intelligent final elements (i.e., one PES electronic/pneumatic/hydraulic)
sensor and programmable comprised of two channels
controller) of PE)
NOTE: The programmable electronics are shown centrally located but could exist at several places in the PES
NOTE 1 It could be a process engineering mechanism, such as the size of vessels containing hazardous chemicals; a mechanical
engineering mechanism, such as a relief valve; a safety instrumented system; or an administrative procedure, such as an
emergency plan against an imminent hazard. These responses may be automated or initiated by human actions.
NOTE 2 This term deviates from the definition in IEC 61508-4 to reflect differences in the process sector.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 28 −
NOTE 1 There are many degradation mechanisms occurring at different rates in different components and since manufacturing
tolerances cause components to fail due to these mechanisms after different times in operation, failures of a total equipment
comprising many components occur at predictable rates but at unpredictable (i.e., random) times.
NOTE 2 A major distinguishing feature between random hardware failures and systematic failures (see definition below), is that
system failure rates (or other appropriate measures), arising from random hardware failures, can be predicted with reasonable
accuracy but systematic failures, by their very nature, cannot be accurately predicted. That is, system failure rates arising from
random hardware failures can be quantified with reasonable accuracy but those arising from systematic failures cannot be
accurately statistically quantified because the events leading to them cannot easily be predicted.
3.1.63 redundancy:
use of multiple elements or systems to perform the same function. Redundancy can be implemented by
identical elements (identical redundancy) or by diverse elements (diverse redundancy).
NOTE 1 Examples are the use of duplicate functional components and the addition of parity bits.
3.1.64 reliability:
probability that a system can perform a defined function under stated conditions for a given period of time.
3.1.66 risk:
the combination of the probability of occurrence of harm and the severity of that harm.
NOTE Other used names for safe failures are: nuisance failure, spurious failure, false trip failure or fail to safe failure.
3.1.70 safety:
freedom from unacceptable risk.
NOTE 1 In going from a potentially hazardous condition to the final safe state the process may have to go through a number of
intermediate safe-states. For some situations a safe state exists only so long as the process is continuously controlled. Such
continuous control may be for a short or an indefinite period of time.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 29 − ISA-TR84.00.02-2002 - Part 1
NOTE 2 This term deviates from the definition in IEC 61508-4 to reflect differences in the process sector.
NOTE This term deviates from the definition in IEC 61508-4 to reflect differences in the process sector.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
Figure 3.3 – Example SIS arc hitecture
NOTE 1 The higher the level of safety integrity of the safety instrumented function (SIF), the lower the probability that the SIF
should fail to carry out the required safety instrumented functions.
NOTE 2 ANSI/ISA-84.01-1996 recognizes three levels of safety integrity for safety instrumented functions. IEC 61508 and IEC
61511 recognize four levels of safety integrity.
NOTE 3 In determining safety integrity, all causes of failures (both random hardware failures and systematic failures) which lead to
an unsafe state should be included; for example, hardware failures, software induced failures and failures due to electrical
interference. Some of these types of failure, in particular random hardware failures, may be quantified using such measures as the
failure rate in the dangerous mode of failure or the probability of a safety instrumented function failing to operate on demand.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 30 −
However, the safety integrity of a SIF also depends on many factors, which cannot be accurately quantified but can only be
considered qualitatively.
NOTE Safety integrity comprises hardware safety integrity and systematic safety integrity.
NOTE 1 ANSI/ISA-84.01-1996 recognizes only three Safety Integrity Levels. The above definition is used in this document to
provide compatibility with IEC 61508 and IEC 61511.
NOTE 2 The target failure measures for the safety integrity levels are specified in Table 3.1.
NOTE 3 It is possible to use several lower safety integrity level systems to satisfy the need for a higher level function (e.g., using a
SIL 2 and a SIL 1 system together to satisfy the need for a SIL 3 function). See IEC 61511-2 for guidance on how to apply this
principle.
NOTE 4 This term differs from the definition in IEC 61508-4 to reflect differences in the process sector.
1 10-1 to 10-2
2 10-2 to 10-3
3 10-3 to 10-4
4 10-4 to 10-5
NOTE The term “functional safety lifecycle “ is strictly more accurate, but the adjective “functional” is not considered necessary in
this case within the context of this technical report.
3.1.80 sensor:
a device or combination of devices, which measure the process condition (e.g., transmitters, transducers,
process switches, position switches, etc.).
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 31 − ISA-TR84.00.02-2002 - Part 1
3.1.81 separation:
the use of multiple devices or systems to segregate control from safety instrumented functions.
Separation can be implemented by identical elements (identical separation) or by diverse elements
(diverse separation).
3.1.83 software:
an intellectual creation comprising the programs, procedures, data, rules and any associated
documentation pertaining to the operation of a data processing system.
The functional specification of the FPL should be documented either in the suppliers’ data sheets, user
manual or the like.
The user should be unable to alter the function of the product, but limited to adjust a few parameters (e.g.,
range of the pressure transmitter).
NOTE Typical example of systems with FPL: smart sensor (e.g., pressure transmitter), sequence of events controller, dedicated
smart alarm box, small data logging systems.
The documentation of the LVL should consist of a comprehensive specification which defines the basic
functional components and the method of configuring them into an application program. In addition an
engineering tool and a library of application specific functions should be given together with a user
manual.
The user should be able to configure/program the required application functions according to the
functional requirement specification.
NOTE 1 Typical examples of LVL are ladder logic, function block diagram and sequential function chart.
NOTE 2 Typical example of a system using LVL is a standard programmable logic controller (PLC) performing burner
management.
The FVL application will often be unique for a specific application. As a result most of the specification will
be special-to-project.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 32 −
NOTE 1 Typical example of a system using FVL is a personal computer which performs supervisory control or process modeling.
NOTE 2 In the process sector FVL is found in embedded software and rarely in application software.
NOTE 1 A software lifecycle typically includes a requirements phase, development phase, test phase, integration phase,
installation phase and modification phase.
NOTE 1 Corrective maintenance without modification should usually not eliminate the failure cause.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 33 − ISA-TR84.00.02-2002 - Part 1
3.1.91 undetected:
in relation to hardware and software, not found by the diagnostic tests or during normal operation.
NOTE 1 For example, physical inspection and manual tests, or through normal operation.
NOTE 2 These adjectives are used in undetected fault and undetected failure.
NOTE 4 This term deviates from the definition in IEC 61508-4 to reflect differences in the process sector.
see “software.”
3.1.93 verification:
process of confirming for certain steps of the Safety Life Cycle that the objectives are met.
3.1.95 watchdog:
a combination of diagnostics and an output device (typically a switch) for monitoring the correct operation
of the programmable electronic (PE) device and taking action upon detection of an incorrect operation.
NOTE 1 The watchdog confirms that the software system is operating correctly by the regular resetting of an external device (e.g.,
hardware electronic watchdog timer) by an output device controlled by the software.
NOTE 2 The watchdog can be used to de-energize a group of safety outputs when dangerous failures are detected in order to put
the process into a safe state. The watchdog is used to increase the on-line diagnostic coverage of the PE logic solver.
NOTE Symbols specific to the analysis of the logic solver portion are included in ISA-TR84.00.02-2002 - Part 5.
β is the fraction of single module or circuit failures that result in the failure of an additional
module or circuit. Hence two modules or circuits performing the same function fail. This
parameter is used to model common cause failures that are related to hardware failures.
βD is the fraction of a single module or circuit failures that result in the failure of an additional
module or circuit taking diagnostic coverage into account.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 34 −
C is the diagnostic coverage factor. It is the fraction of failures that are detected by on-line
diagnostics.
D
C is the fraction of dangerous failures that are detected by on-line diagnostics.
S
C is the fraction of safe failures that are detected by on-line diagnostics.
D
C A
is the fraction of dangerous final element failures that are detected by on-line diagnostics.
D
C S
is the fraction of dangerous sensor failures that are detected by on-line diagnostics.
S
C A
is the fraction of safe final element failures that are detected by on-line diagnostics.
S
C S
is the fraction of safe sensor failures that are detected by on-line diagnostics.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
D
C IC
is the fraction of dangerous input circuit failures that are detected by on-line diagnostics.
D
C IP
is the fraction of dangerous input processor failures that are detected by on-line diagnostics.
D
C MP
is the fraction of dangerous main processor failures that are detected by on-line diagnostics.
D
C OC
is the fraction of dangerous output circuit failures that are detected by on-line diagnostics.
D
C OP
is the fraction of dangerous output processor failures that are detected by on-line diagnostics.
D
C PS
is the fraction of dangerous power supply failures that are detected by on-line diagnostics.
S
C IC
is the fraction of safe input circuit failures that are detected by on-line diagnostics.
S
C IP
is the fraction of safe input processor failures that are detected by on-line diagnostics.
S
C MP
is the fraction of safe main processor failures that are detected by on-line diagnostics.
S
C OC
is the fraction of safe output circuit failures that are detected by on-line diagnostics.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 35 − ISA-TR84.00.02-2002 - Part 1
S
C OP
is the fraction of safe output processor failures that are detected by on-line diagnostics.
S
C PS
is the fraction of safe power supply failures that are detected by on-line diagnostics.
fICO is the average number of output modules affected by the failure of an input circuit on an input
module (typically fICO = fIPO/nIC).
fIPO is the average number of output modules affected by the failure of the input processor on an
input module (typically fIPO = m/n).
fOCI is the average number of output circuits on output modules affected by the failure of an input
module (typically fOCI = fOPI/nOC).
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
fOPI is the average number of output processors on output modules affected by the failure of an
input module (typically fOPI = 1/fIPO).
D
MTTF is the mean time to the occurrence of a dangerous event. Dimension (Time)
spurious
MTTF is the mean time to the occurrence of a spurious trip. This is also referred to as the mean
time to the occurrence of a safe system failure. Dimension (Time)
MTTROT is the mean time to repair failures that are detected through on-line tests. Dimension (Time)
MTTRPT is the mean time to repair failures that are detected through periodic testing off-line. This
time is essentially equal to one half the time between the periodic off-line tests (TI/2) (see
MTTROT). Dimension (Time)
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 36 −
P is probability vector.
PFD is the probability of failure on demand (See definition in Clause 3.1). Dimensionless
PFDA is the average probability of the final elements failing to respond to a process demand.
(PFDAi is used to indicate PFDA for a final element configuration).
PFDL is the average probability of the logic solver failing to respond to a process demand.
PFDS is the average probability of the sensor failing to respond to a process demand.
PFDPS is the average probability of the power supply failing to respond to a process demand.
PFDavg is the average probability of the SIF failing to respond to a process demand. It is commonly
referred to as the average probability of failure on demand. It is also referred to as average
safety unavailability or average fractional dead time. Dimensionless
pn is conditional probability.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 37 − ISA-TR84.00.02-2002 - Part 1
STRA is the safe failure rate for all final elements. (STRAi is used to indicate STRA for a final
element configuration).
TI is the time interval between periodic off-line testing of the system or an element of the
system. Dimension (Time)
XPE is the scoring factor for programmable electronics from Table A.1 that provides credit for
automatic diagnostics that are in operation.
XSA is the scoring factor for sensors and actuators from Table A.1 that provides credit for
automatic diagnostics that are in operation.
YPE is the scoring factor for sensors and actuators from Table A.1 that provides credit for
automatic diagnostics that are in operation.
YSA is the scoring factor for sensors and actuators from Table A.1 that corresponds to those
measures whose contribution will not be improved by the use of automatic diagnostics.
λ is used to denote the failure rate of a module or a portion of a module [normally expressed in
-6
failures per million (10 ) hours].
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 38 −
λ
C
is used to denote the common cause failure rate for a module or portion of a module.
D
λ is used to denote the dangerous failure rate for a module or portion of a module. These
failures can result in a dangerous condition.
λ
N
is the normal mode failure rate.
S
λ is used to denote the safe or false trip failure rate for a module or portion of a module. These
failures typically result in a safe shutdown or false trip.
DD
λ is the dangerous (e.g., fail in a direction that would defeat the purpose of the SIS) detected
failure rate for a module or portion of a module. Detected dangerous failures are failures that
DD
can be detected by on-line tests. λ is computed by multiplying the dangerous failure rate for
D D
a module (λ ) by the diagnostic coverage for dangerous failures (C ).
DU
λ is used to denote the dangerous undetected (covert) failure rate for a module or portion of a
module. Dangerous undetected failures are failures that cannot be detected by on-line tests.
DU
λ is computed by multiplying the dangerous failure rate for a module (λ ) by one minus the
D
D
diagnostic coverage for dangerous failures (1-C ).
SD SD S S
λ is the safe detected failure rate for a module or portion of a module. λ is equal to λ • C .
SU SU S
λ is the safe undetected failure rate for a module or portion of a module. λ is equal to λ • (1-
S
C ).
DDC
λ is the dangerous detected common cause failure rate.
DDN
λ is the dangerous detected normal mode failure rate.
DUC
λ is the dangerous undetected common cause failure rate.
DUN
λ is the dangerous undetected normal mode failure rate.
SDC
λ is the safe detected common cause failure rate.
SDN
λ is the safe detected normal mode failure rate.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 39 − ISA-TR84.00.02-2002 - Part 1
SUC
λ is the safe undetected common cause failure rate.
SUN
λ is the safe undetected normal mode failure rate.
λA is the failure rate for a final element or other output field device.
λI is the failure rate for an input module (λI = λIP + nIC λIC).
D S
λD is the failure rate of a device (λD= λ + λ ).
λI is the failure rate for an input module (λI = λIP + nIC λIC).
λO is the failure rate for an output module (λO = λOP + nOC λOC).
λIC is the failure rate for each individual input circuit on the input module.
λIP is the failure rate for the input processor and associated circuitry (portion of input module that
is common to all inputs).
λOC is the failure rate for each individual output circuit on the output module.
λOP is the failure rate for the output processor and associated circuitry (portion of the output
module that is common to all output points).
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 40 −
λ
D
A
is the dangerous failure rate for a final element or other output field device.
λ
D
F
is the systematic failure rate that results in a dangerous state of the system. This is used to
model systematic failures that affect the operation of all legs of a SIS configuration.
Examples include SIS design errors, software implementation errors, wiring errors, human
interaction errors, etc.
D
λ I
is the dangerous failure rate for an input module.
D
λ L
is the dangerous failure rate for the logic solver.
D
λ O
is the dangerous failure rate for an output module.
λ
D
S
is the dangerous failure rate for a sensor or other input field device.
λ
S
A
is the safe failure rate for a final element or other output field device.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
S
λ F
is the systematic failure rate that results in a safe state of the system. This is used to model
systematic failures that affect the operation of all legs of a SIS configuration, where the cause
cannot be related directly to hardware failures. Examples include SIS design errors, software
implementation errors, wiring errors, human interaction errors, etc.
S
λ I
is the safe failure rate for an input module.
S
λ L
is the safe failure rate for the logic solver.
S
λ O
is the safe failure rate for an output module.
λ
S
S
is the safe failure rate for a sensor or other input field device.
λ
D
FA
is the systematic failure rate that results in a dangerous state of a final element.
λ
D
FS
is the systematic failure rate that results in a dangerous state of a sensor.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 41 − ISA-TR84.00.02-2002 - Part 1
D
λ IC
is the dangerous failure rate for each individual input circuit.
D
λ IP
is the dangerous failure rate for the input processor and associated circuitry.
D
λ IV
is the dangerous failure rate for the input voter.
D
λ MP
is the dangerous failure rate for the main processor.
D
λ OC
is the dangerous failure rate for each individual output circuit.
D
λ OP
is the dangerous failure rate for the output processor and associated circuitry.
λ
D
PS
is the dangerous failure rate for a power supply.
S
λ FA
is the systematic failure rate that results in a safe state of a final element.
S
λ FS
is the systematic failure rate that results in a safe state of a sensor.
S
λ IC
is the safe failure rate for each individual input circuit.
S
λ IP
is the safe failure rate for the input processor and associated circuitry.
S
λ IV
is the safe failure rate for the input voter.
S
λ MP
is the safe failure rate for the main processor.
S
λ OC
is the safe failure rate for each individual output circuit.
S
λ OP
is the safe failure rate for the output processor and associated circuitry.
λ
S
PS
is the safe failure rate for a power supply.
D
λ LEG
is the dangerous failure rate for each individual leg or channel.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 42 −
λ
D
TOTAL
is the total dangerous failure rate of the system.
λ
S
TOTAL
is the total safe failure rate of the system.
DD
λ LEG
is the dangerous detected failure rate for each individual leg or channel.
DU
λ LEG
is the dangerous undetected failure rate for each individual leg or channel.
D
µ A
is the effective repair rate for the dangerous failures of the final element.
D
µ S
is the effective repair rate for the dangerous failures of the sensor.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
S
µ A
is the effective repair rate for the safe failures of the final element.
S
µ S
is the effective repair rate for the safe failures of the sensor.
µ
D
IC
is the effective repair rate for the dangerous failures of an individual input circuit.
µ
D
IP
is the effective repair rate for the dangerous failures of the input processor and associated
circuitry.
µ
D
MP
is the effective repair rate for the dangerous failures of the main processor.
µ
D
OC
is the effective repair rate for the dangerous failures of an individual output circuit.
µ
D
OP
is the effective repair rate for the dangerous failures of the output processor and associated
circuitry.
µ
D
PS
is the effective repair rate for the dangerous failures of the power supply.
µOT is used to denote the repair rate for failures that are detected through on-line tests
(µOT=1/MTTROT).
µ
S
IC
is the effective repair rate for the safe failures of an individual input circuit.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 43 − ISA-TR84.00.02-2002 - Part 1
S
µ IP
is the effective repair rate for the safe failures of the input processor and associated circuitry.
µ
S
MP
is the effective repair rate for the safe failures of the main processor.
µ
S
OC
is the effective repair rate for the safe failures of an individual output circuit.
µ
S
OP
is the effective repair rate for the safe failures of the output processor and associated
circuitry.
µ
S
PS
is the effective repair rate for the safe failures of the power supply.
To satisfy the requirements of a given SIL, the PFDavg should be less than the upper limit as provided in
ANSI/ISA-84.01-1996.
PFD = f (failure rate, repair rate, test interval, common cause, etc.)
The specific functionality (f) is an attribute of the system architecture selected for the SIS (E/E/PES and
field devices).
The functional test interval is that period of time over which the SIF must operate within the PFD limits of
the specified SIL. It could be equal to a “mission time” and should be as long as possible to reduce the
possibility of human error associated with frequent functional testing of the SIS.
The dangerous undetected failure rate is strongly impacted by the diagnostic coverage factor of the
system (for random hardware failures). Comprehensive internal diagnostics dramatically improves the
diagnostic coverage factor; thereby, reducing the possibility of a dangerous undetected failure, and
consequently minimizing the PFD.
It is important to recognize that the SIF configuration, including the number and quality of field
DU
devices, has a major impact on the PFD for the SIF. If one assumes a single input with a MTTF
DU DU
of 30 years, a single output with a MTTF of 50 years, and a logic solver with a MTTF of 100
years, about 85% of the SIF PFD will fall in the field devices and about 15% in the logic solver. On
DU
the other hand, using redundant inputs and outputs with similar MTTF , configured for high
safety availability and with the same logic solver, the PFD for the field devices may account for
only 30% and the logic solver may account for 70% of the SIF PFD. The distribution of SIF PFD
will change as the number and type of system elements and the configuration vary. Therefore,
enhancing the PFD of the logic solver (E/E/PES) of the SIF without corresponding enhancement of
the field devices may not be effective in improving the SIF SIL. Making a change to improve one
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 44 −
portion of the system (e.g., adding a redundant PES) may not have significant impact on the
overall SIF. Thus, the overall SIF must be evaluated.
The modeling of the system includes all possible types of failures. Failures can be grouped into 2 major
categories:
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
(6)
a) Physical Failures
1) Independent failures
NOTE Systematic failures may be separated into independent and common cause failures. Systematic failures may impact single
and/or multiple system elements, simultaneously.
Since systematic failures are in addition to the physical failures, they are shown in the models of the
overall system architecture, as an additional failure rate.
A failure is classified as physical when some physical stress (or combination of stressors) exceeds the
capability of the installed components (e.g. associated susceptibility).
Hardware common cause failures must be modeled differently since multiple failures occur
simultaneously. Common cause failures are the direct result of a shared root cause. An example is radio
frequency interference that causes simultaneous failure of multiple modules.
Common cause susceptibility is an important characteristic in the safety rating of a SIF. The Beta model
(Annex A) partitions the failure rate into those failures due to stress events high enough to fail multiple
units if they are exposed to the same stress. Annex A discusses a technique to evaluate the β factor and
proposes a methodology to apply it to the reliability models.
Systematic failures occur when the physical hardware is operating but unable to perform the specified
function due to errors of omission or errors of commission.
In the models, the systematic failures are separated into safe failures and dangerous failures. It is
assumed that a systematic safe failure, λ F, will have the potential to result in a spurious trip. In a similar
S
manner, a systematic dangerous failure, λ F will have the potential to result in a fail-to-function state of the
D
SIF. The estimation of the systematic failure rate must consider many possible causes. A partial list of
causes is as follows:
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 45 − ISA-TR84.00.02-2002 - Part 1
These errors include errors in the safety logic specification, incorrect selections of sensors and final
elements, and errors in the design of the interface between the E/E/PES and sensors and actuators.
Failure due to errors of this type will likely fail an entire redundant architecture.
These errors include errors in the installation, setup (calibration, initialization, set-point settings), and
start-up of SIS components which are not detected and resolved during functional testing of SIS.
Examples of such errors are
1) wiring/tubing errors;
c) Software errors
These errors include errors in vendor written and user written embedded, application, and utility
software. The vendor software typically includes the operating system, I/O routines, diagnostics,
application oriented functions and programming languages. User written software errors include
errors in the application program, diagnostics, and user interface routines (display systems, etc.).
These errors include errors in the operation of the man machine interface to the SIF, errors during
periodic testing of the SIF and during the repair of failed modules in the SIF.
These errors include errors in the manufacturer’s design or construction of selected SIF components
which prevent proper functionality and failure of component to meet specified conditions. Examples
of such errors are failure of a component to
f) Modification errors
These errors occur when altering any or all of the five categories mentioned in this clause (i.e., SIF
design, hardware implementation, software, human interaction, hardware design). These errors have
three common characteristics:
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 46 −
1) Inability to replace a component with an identical component (e.g. due to discontinued support)
and the replacement component does not fully function with adjacent components.
2) Modification reduces the load on the power source, thus raising the voltage level and causing
problems with other existing non-modified components.
Dangerous failure rates are denoted by a superscript “D.” Safe (spurious trip) failure rates are denoted by
D S
a superscript “S." Hence for a device, the dangerous and safe failure rates are λ and λ .
All failures detected on-line while the SIS is operating are classified as detected (overt) failures. Those
failures not detected on-line are classified as undetected (covert) failures. As a result of this additional
partitioning, every element failure rate can be split into four mutually exclusive failure rates:
a) Safe/ Detected - SD
b) Safe/ Undetected - SU
c) Dangerous/ Detected - DD
d) Dangerous/ Undetected - DU
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
These four categories are shown in Figure 5.1 below.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 47 − ISA-TR84.00.02-2002 - Part 1
Figure 5.1 Safe and dange rous-detected and undetected failure rate diagram
The superscript SD, SU, DD, and DU are used on the element failure rate to denote the category of
failure. The four failure rates are denoted as follows:
SD
1) λ - safe detected failure rate.
SU
2) λ - safe undetected failure rate.
DD
3) λ - dangerous detected failure rate.
DU
4) λ - dangerous undetected failure rate.
The detected and undetected failure rates are computed by determining the diagnostic coverage factor
for each element of the system. Normally the diagnostic coverage for dangerous failures is lower than the
diagnostic coverage for safe failures since dangerous failures cause the state of the element to remain
unchanged. Safe failures result in a change of state of the element and hence are easier to diagnose.
Hence, a different diagnostic coverage factor for safe and dangerous failures is assumed. As in the case
of failure rates, a superscript “D” is used on the diagnostic coverage factor “C” to denote the diagnostic
coverage for dangerous failures. In a similar manner, a superscript “S” is used on the diagnostic
coverage factor “C” to denote the diagnostic coverage for safe failures. The diagnostic coverage factors
D S
for dangerous and safe failures are C and C . Refer to Annex E for guidance in determining the split
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
ratio. The four failure rates for an element are computed as follows:
SD
λ =λ •C
S S
SU
λ = λ • (1 - C )
S S
DD
λ =λ •C
D D
DU
λ = λ • (1 - C )
D D
In the Beta model, the Beta factor (see ISA-TR84.00.02-2002 - Part 1, Annex A) is used to partition the
failure rates into independent (i.e., random) versus common cause.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 48 −
NOTE There are other common cause models available. The Beta model was chosen because it is simple and sufficient to model
configurations covered by this document.
λSDN = (1 − β)λSD
λSUN = (1 − β)λSU
λDDN = (1 − β)λDD
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 49 − ISA-TR84.00.02-2002 - Part 1
λDUN = (1 − β)λDU
A large variety of input devices are available for use in safety applications, however, most of these
devices interface to the SIF logic solver through analog input boards, digital input boards and serial
communication links.
The overall failure rate of a sensor is given by λS, where the S subscript indicates a sensor.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
The sensor failure rate must be split into four mutually exclusive failure rates:
SD
a) Safe/Detected - λ S
SU
b) Safe/Undetected - λ S
DD
c) Dangerous/Detected - λ S
DU
d) Dangerous/Undetected - λ S
S D
These failure rates are computed using the safe and dangerous failure rates (λ S
and λ S) and the sensor
S D
diagnostic coverage factors (C S
and C S).
The equations used to compute the four failure rates are as follows:
SD S S
λ S
=λ S
•C S
λ = λ S• (1 - C S)
SU S S
S
DD D D
λ S
= λ S• C S
DU D D
λ S
=λ S
• (1 - C S
)
In many cases, the sensor diagnostic coverage factors are low, and hence the undetected failure rates
are large. This requires off-line functional testing of the sensors at frequent intervals, and/or redundant
sensors to achieve the desired safety integrity level.
A large variety of output devices are available for use in safety applications, however, most of these
devices interface to the SIF logic solver through analog output boards, digital output boards and serial
communication links.
The overall failure rate of a final element or output device is given by λA. The A subscript indicates a final
element.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 50 −
As with the sensors, the final element failure rate must be split into four mutually exclusive failure rates:
a) Safe/Detected - λ
SD
A
b) Safe/Undetected - λ
SU
A
c) Dangerous/Detected - λ
DD
A
d) Dangerous/Undetected - λ
DU
A
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
λ =λ
SD S S
A A
•C A
λ =λ
SU S S
A A
• (1 - C A)
λ =λ
DD D D
A A
•C A
λ =λ
DU D D
A A
• (1 - C A)
In many cases, the final element diagnostic coverage factor is typically low, and hence, the undetected
failure rates are large. This requires functional testing of the final elements at frequent intervals, and/or
redundant final elements to achieve the desired safety integrity level.
Programmable electronic systems (PESs) can vary significantly in architecture. Three typical
architectures for a single PES are:
b) Multiboard PES with main processor module and processor based I/O modules (Figure 5.4)
c) Multiboard PES with main processor module, and I/O chassis with I/O processor module and non
intelligent I/O modules (Figure 5.5)
Since there are many different kinds of I/O modules (i.e., digital inputs, digital outputs, analog inputs, etc.)
and different ways of connecting them to the main processor, the PES is broken into blocks. The blocks
used in the basic architectural model must be carefully chosen so that interactions between modules in
the PES can be described. For example, the failure of a main processor affects the operation of all I/O
modules, while the failure of an I/O processor may only affect those I/O circuits attached to it.
An examination of the PES architecture in Figure 5.2 shows that the I/O modules can be modeled using
individual input and output circuits that connect field devices to the main processor. However, Figures 5.3
and 5.4 contain PES architectures with I/O processors that process the data from the input and output
circuits which are connected to the field devices. As a result of these differences the I/O is modeled using
input processors, individual input circuits, output processors and individual output circuits. Hence the
overall failure rate of an input module, λI, is as follows:
where λIP is the failure rate of the input processor, nIC is the number of input circuits per input processor,
and λIC is the failure rate of the individual input circuits.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 51 − ISA-TR84.00.02-2002 - Part 1
where λOP is the failure rate of the output processor, noc is the number of output circuits per output
processor, and λOC is the failure rate of the individual output circuits.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 52 −
INPUT CHANNEL
MAIN OUTPUT CHANNEL
PROCESSOR
INPUT CHANNEL OUTPUT CHANNEL
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 53 − ISA-TR84.00.02-2002 - Part 1
I/O
PROCESSOR
BOARD
MAIN
PROCESSOR
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
I/O
PROCESSOR
BOARD
Figure 5.5 PES architectur e with I/O processor boards & I/O boards
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 54 −
If the PES is a single board with integral I/O, λIP and λOP are set to zero, and nIC and nOC are the total
number of input and output circuits on the single board. If the PES is like the system illustrated in Figure
5.5, nIC and nOC are the total number of input and output circuits serviced by a single I/O processor.
The rest of the modules that make up the PES are not split into sections like the I/O modules. Hence, the
elements used in the models and their respective failure rates are as follows:
These PES element failure rates can be partitioned into “Safe/ Detected” failures, “Safe/ Undetected”
failures, “Dangerous/ Detected” failures, and “Dangerous/ Undetected” failures. Using the same notation
as in Section 4.4, the failure rates for the main processor are as follows:
SD
a) λ MP
- main processor safe detected failure rate.
SU
b) λ MP
- main processor safe undetected failure rate.
DD
c) λ MP
- main processor dangerous detected failure rate.
DU
d) λ MP
- main processor dangerous undetected failure rate.
System modeling of any fault tolerant E/E/PES architecture can be done using simplified equations, fault
tree analysis, Markov analysis or other technique using the failure rate categories described above. This
failure rate classification depends on an accurate and detailed Failure Modes, Effects and Diagnostic
Analysis (FMEA). When it is impractical to do this level of analysis, simplifying assumptions can be
made, however, it is important that these assumptions be conservative. If failure modes are not known, it
must be assumed that all failures are dangerous. If diagnostic coverage capability is not known, it must
be assumed that no failures are detected. If beta factors (common cause) are not known, a value of 10%
is conservative (see Annex A).
THE NUMBERS IN TABLE 5.1 WERE COMPILED FROM USER DATA AND ARE IN NO WAY
ENDORSED BY ISA. THEY DO NOT REFLECT THE VARIABILITY OF FAILURE RATES DUE TO
THE SEVERITY OF DIFFERENT PROCESSES, THE DIFFERENT FAILURE MODES OF THE ACTUAL
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 55 − ISA-TR84.00.02-2002 - Part 1
DEVICES, NOR HOW THE DATA WAS ACTUALLY COLLECTED BY EACH COMPANY. THE USER
IS CAUTIONED IN THEIR USE AND SHOULD TRY TO COMPILE THEIR OWN DATA.
Reliability practitioners usually work with failure rates expressed as failures per million hours. Failure
rates may be inverted and expressed as mean time to failure (MTTF) and may be expressed in years.
Note that MTTF and component life are not the same.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 56 −
Table 5.1 MTTFD and MTT F spurious values (expressed in years) for common field
instrumentation
Sensors
Flow
Transmitter
Combustible 2.8
Gas Detector
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 57 − ISA-TR84.00.02-2002 - Part 1
Table 5.1 MTTFD and MTT F spurious values (expressed in years) for common field
instrumentation
Final Elements
Hydraulic 25 80
Operated Ball
Valve
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
Electro- 1500- 70 40
Mechanical Relay 2500
Annunciator 4 10
This clause outlines three statistical analysis methods that are useful in analyzing the performance of a
SIF, i.e., the PFD and PFS, taking into account the uncertainties associated with the model and the data.
The methods are statistical Uncertainty (clause 5.9.1), Sensitivity (clause 5.9.2), and Correlation Analysis
(clause 5.9.3).
For any reliability technique, the PFD and the PFS are based on a reliability model of the SIF application
and reliability data for parameters like the failure rates and the repair rates of the different elements.
Any model is just an approximation of the real world. It is impossible to model every single aspect of real
life; therefore, assumptions need to be made to simplify the modeling effort whenever a model is created.
There is uncertainty associated with each model that is created. The failure and repair rate data used in
reliability models are uncertain, for many reasons. The background of the data may be unclear; good
data might be unavailable; no data may be available because equipment might be new. In such cases,
using a single or point value for the failure and repair rates might give very misleading results. Of course,
how good (or how bad) the model is, and how good (or how bad) the failure and repair rate data used in
that model is, affects the usefulness of the PFD and PFS values calculated by the model.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 58 −
The theory behind the methods is not explained. In order to understand the theory and implement the
different methods, the reader is referred to the references as presented in the different sections. These
techniques are based on statistics, which means that the results are based on simulating a significant
(24, 25, 27)
number of SIF . These simulations are usually done by specialized software (Annex C)
applications. ISA-TR84.00.02-2002 - Part 2 and ISA-TR84.00.02-2002 – Part 3 do not use these
techniques, although in principle, it is possible to do so. ISA-TR84.00.02-2002 - Part 4 uses uncertainty
and sensitivity analysis. ISA-TR84.00.02-2002 - Part 5 uses all three methods.
Uncertainty analysis is a method that a) takes the uncertainty associated with the input parameters (i.e.,
failure rates, repair rates) to a reliability model, b) propagates this uncertainty through the model, and c)
(22, 23)
creates a range of values for the outputs . A range of values (e.g., minimum through maximum likely
values), instead of a single value, is used for failure and repair rates. This range can be based, for
example, on such factors as: the manufacturing quality, the specific application, the environment of the
component, the size of the sample used to determine the failure rate, or other factors. Using a range of
values as input means that a range of values is created for the output, i.e., the PFD or PFS. When
uncertainty analysis is applied the results are often presented as in Figure 5.6.
The result of the uncertainty analysis is a number of values for the PFD and PFS. The plots represent
th th th (26)
three levels of confidence in the results: the so-called 10 , 50 and 90 percentiles . In practice it is
th th
possible to represent any level of confidence (e.g. 5 , 95 and so on). The reader should interpret the
graphs as follows: Given this input data and reliability model,
th
10% of the cases the PFD value would be below the 10 percentile line;
th
50% of the cases the PFD value would be below the 50 percentile line; and,
th
90% of the cases the PFD value would be below the 90 percentile line.
The use of these uncertainty graphs is based on good engineering judgment. In the case of Figure 5.6, it
would be worth investigating the cause of the wide range of PFD values (it covers all three SIL levels) as
seen in the graph on the right. The following two statistical techniques provide the tools to do this
investigation. They are very useful during the architecture design of SIF. The reader is cautioned
however that the following discussions are only brief overviews of these tools. Before attempting to apply
these tools, the reader should refer to the references cited in each section.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 59 − ISA-TR84.00.02-2002 - Part 1
0.1 0.1
SIL 1 SIL 1
90%
0.01 0.01
90%
50% SIL 2 50% SIL 2
0.001 10% 0.001
SIL 3 10% SIL 3
0.0001 0.0001
0 Test 0 Test
Interval Interval
PFD and Uncertainty Analysis PFD and Uncertainty Analysis
Statistical sensitivity analysis is a method which quantifies the effect of the uncertainty associated with an
input parameter (e.g., the failure and repair rates) to the uncertainty associated with the output parameter
(28)
(e.g., the PFD or PFS) . In other words, for example, if there is a range of input values for the failure
rate of a valve, then the statistical sensitivity analysis would show how this range propagates through the
reliability model and how much influence it has on the range of PFD, as presented in Figure 5.6.
The results of a statistical sensitivity analysis are presented in a Pareto plot as in Figure 5.7. The reader
should interpret the graph as follows. The horizontal axis gives a range for the statistical sensitivity, which
(29, 30)
can vary between zero and two . Zero means that the output is not sensitive to the input while two
means that the output is very sensitive to the input. On the vertical axis the input parameters are listed in
order of their statistical sensitivity (most sensitive highest, and least sensitive lowest). In this case the
PFD value is most sensitive to the failure rate of the valve. That is, the variation in the specified values of
valve failure rate cause more variation in the PFD value than variation in any other input parameter.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 60 −
How can the reader use this kind of information while examining a SIF architecture? Suppose that
reliability data is collected for all the input parameters of the reliability model. It turns out that there is not
enough data available for the valve and input module failure rates. A conservative approach is to apply a
wide range of data based on experience and carry out the uncertainty and sensitivity analysis. The
results of the Uncertainty Analysis are presented in the right graph of Figure 5.6. From the sensitivity plot
the conclusion can be drawn that the PFD of the SIF is robust against failures of the input module. Even
though a wide range of failure data is used, the range of the PFD values is not influenced much by the
input module. On the other hand, the output is much influenced by the failure data of the valve. The PFD
is very sensitive to valve failures. The next step can be a) to get better failure data for the valve and see
how that affects the PFD values or b) to change the SIF architecture and make the design more robust
against valve failures.
When a certain input parameter has a high sensitivity factor and the cause for this high factor is unknown,
then there are two possibilities:
a) The architecture design or set-up (represented by the reliability model) is the cause of this high
sensitivity of the input parameter.
b) The spread between the Minimum and Maximum failure rate is very wide and caused the high
sensitivity of the input parameter.
A statistical correlation analysis helps to answer the question: Is it the architecture design or the range of
data for a particular input parameter that causes the variation in output?
A typical correlation result is presented in Figure 5.8. The correlation coefficient can vary between -1 and
+1; it indicates the degree or strength of the linear relation between the input parameter, e.g., a failure
(31)
rate, and the output, e.g., the PFD . A value of +1 indicates a strong positive correlation meaning that
the output (PFD) increases as the input parameter (failure rate) increases. A value of -1 indicates a
strong negative correlation meaning that the output decreases as the input parameter increases. A value
of zero means that the input parameter has no linear effect on the output. Thus if the correlation is strong
(negative or positive) then it is more likely that the architecture design is the dominant factor. If the
correlation is zero the range in input parameters is more likely to be the dominant factor.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 61 − ISA-TR84.00.02-2002 - Part 1
The particular advantage in applying the sensitivity and correlation analysis will be the ability to use less
accurate input data. Experienced technicians know that accurate single value failure and repair rate data
are seldom available for all the elements in a SIF. If this is the case, then it is necessary to generate the
best guess of the expected minimum and maximum range of values. When, after the sensitivity and
correlation analysis, this estimation proves to be important in the results (PFD or PFS), then either the
failure rate estimation range has to be very closely examined, adjusted, and justified, or else the SIF
configuration has to be examined.
c) Choose alternative sensor, logic solver or final element types (with different failure and repair rate
data).
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 62 −
Typical Systems Modeled Simple SIF SIF with complex SIF with complex
relationships relationships, time
dependent requirements, or
PE logic solvers
elements
Provides graphics that Practical for simple SIF Yes More difficult
allow easy visualization
of failure paths
NOTE A more detailed discussion on the three techniques is provided in Reference 11.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 63 − ISA-TR84.00.02-2002 - Part 1
spurious
Table 6.2 summarizes the calculation results for PFDavg and MTTF for the SIF Base Case example
problems presented in Parts 2, 3, and 4.
For the Base Case PFDavg, all three methods give essentially the same value (Figure 6.1).
spurious
For the Base Case MTTF , all three methods give similar values (Figure 6.2).
Table 6.2 Summary of SIF base case example problems presented in ISA-
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
TR84.00.02-2002 - Parts 2, 3, and 4
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 64 −
1.00E-02
PVDavg
9.00E-03
8.00E-03
7.00E-03
Probability
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
6.00E-03
5.00E-03
4.00E-03
3.00E-03
2.00E-03
1.00E-03
Part 2 Simplified Part 3 Fault Tree Part 3 Fault Tree Part 4 Markov Model
Equations Analysis ABL Analysis AAL
Method
Figure 6.1 PFDavg for SIS b ase case example problems presented in ISA-
TR84.00.02-2002 - Parts 2, 3, and 4
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 65 − ISA-TR84.00.02-2002 - Part 1
MTTFspurious
2.5
2
MTTF, yr
1.5
0.5
Part 2 Simplified Equations Part 3 Fault Tree Analysis Part 4 Markov Model
Method
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
Figure 6.2 MTTFspurious for SIS base case example problems presented in ISA-
TR84.00.02-2002 - Parts 2, 3, and 4
All three methods give similar results for this SIF Base Case example based on the configuration and
assumptions used in the Base Case. For a different SIF configuration with different assumptions, the
methods may give different values and one method may be more appropriate as suggested in Table 6.1.
Additional examples are given in ISA-TR84.00.02-2002 - Parts 3 and 4 to illustrate features of the
calculation methods.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 67 − ISA-TR84.00.02-2002 - Part 1
NOTE The source of this document is IEC 61508, Part 6, Annex A. It has been modified to harmonize with ISA-TR84.00.02-2002.
A.1 Introduction
Technical Report 84.00.02 incorporates a number of measures that deal with systematic failures.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
However, no matter how well these measures are applied, there will be a residual probability of
systematic failures occurring. Although this will not have a significant effect on the reliability calculations
for single-channel systems, the potential for failures which may affect more than one channel in a multi-
channel system, i.e., common cause failures, will result in substantial errors when reliability calculations
are applied to multi-channel systems.
This informative annex describes a methodology which will allow common cause failures to be taken into
account in the safety assessment of a multi-channel SIS. The use of the methodology will give a more
accurate estimation of the integrity of such a system than if the potential for common cause failures were
ignored. Alternative methodologies may be preferred in some cases, for example, where a more accurate
β-factor can be proven as a result of the availability of data on Common cause failures.
b) Systematic failures
The former are assumed to occur randomly in time for any component and will result in a failure of one or
more channels within a system of which the component forms part. There is a finite probability that
independent Random Hardware Failures could occur in all channels of a multi-channel system such that
all of the channels were simultaneously in a failed state.
Common cause failures may result from a systematic fault (e.g., a design or specification error) or an
external stress leading to an early random hardware failure (e.g., an excessive temperature, which
accelerates the life of the components or takes them outside their specified environment) or, possibly, a
combination of both. Because common cause failures affect more than one channel in a multi-channel
system, the probability of common cause failures is likely to be the dominant factor in determining the
overall probability of a failure of a multi-channel system and this must be taken into account if a realistic
estimate of the SIL of the combined system is to obtained.
Programmable electronic systems may provide the ability to carry out diagnostic functions during their on-
line operation. These can be employed in a number of ways, for example:
a) a single channel PES can continuously be checking its internal operation together with the
functionality of the input and output devices. A diagnostic coverage in the region of 99% is often
(19)
achievable . If 99% of internal faults are revealed before they can result in a failure, the rate of
single-channel faults which can ultimately contribute to common cause failures will be significantly
reduced.
b) In addition to self-testing, each channel in a PES can monitor the outputs of other channels in multi-
channel PES (or each PES can monitor another PES in a multi-PES). Therefore, if a failure occurs in
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 68 −
one channel, this can be detected and an appropriate action initiated by the non-failed channel(s)
which is executing the cross-monitoring test.
a) PE-based systems may have the potential to incorporate defenses against common cause failures.
b) A different β-factor may be applicable to PES-based systems when compared to other technologies.
Therefore, β-factor estimates based on historical data may be invalid. (None of the identified models
used for estimating the rate of common cause failures allow for the effect of automatic cross-
monitoring and none of the identified models have the ability to house so many safety instrumented
functions in one logic solver.)
c) Common cause failures that are distributed in time may be revealed by the automatic diagnostics
before they affect all channels, such failures may not be recognized/reported as being common cause
failures.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
Following are three avenues that can be taken to reduce the rate at which common cause failures are
likely to manifest themselves:
a) 1) Reduce the number of overall systematic failures. (This will reduce the areas of the ellipses in
Figure A.1 leading to a reduction in the area of overlap.)
b) 2) Maximize the independence and diversity of the channels. (This will reduce the amount of
overlap between the ellipses in Figure A.1 while maintaining their area.)
c) Reveal the initial failure before a second channel has been affected, i.e., use automatic diagnostics.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 69 − ISA-TR84.00.02-2002 - Part 1
Common
Cause
Failures
affecting
both
Systematic
failures for Systematic
Channel 1 failures for
channel 2
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 70 −
The methodology to be described is based on these avenues and has a three-pronged approach:
a) Apply the techniques described in ANSI/ISA-84.01-1996 to reduce the overall rate of systematic
failures to a level commensurate with the random hardware failure rate.
b) Quantify those factors that can be quantified, i.e., take into account the rate of random hardware
failures.
c) Derive, by what is considered at the present time to be the best practicable means, a factor relating
the rate of common cause failures of the hardware to the rate of random hardware failures. The
methodology described in this annex relates to the derivation of this factor.
Most methodologies for estimating the probability of common cause failures attempt to make their
predictions from the probability of random hardware failure. Clearly, the justification for any direct
relationship between these probabilities is tenuous, nevertheless, such a correlation has been found in
practice and probably results from second-order effects. For example, the higher the random hardware
failure rate of a system:
a) the higher will be the amount of maintenance required of the system. The probability of a systematic
fault being introduced during maintenance will depend on the number of times maintenance is carried
out and, subsequently, so will the rate of common cause failures. This will lead to a relationship
between the probability of random hardware failures and the probability of common cause failures.
For example:
1) A repair, followed by testing and, possibly, recalibration will be required each time a random
hardware failure occurs.
2) For a given SIL, a system with a higher probability of random hardware failure will require proof
tests to be carried out more frequently, leading to additional human interference.
b) the more complex will be the system. The probability of random hardware failure will depend on the
number of components, and, hence, the complexity of a system. A complex system will be less easily
understood, so will be more prone to the introduction of systematic faults. In addition, the complexity
will make it difficult to identify the faults, by either analysis or test, and could lead to parts of the logic
of a system not being exercised except in infrequent circumstances. Again, this will lead to a
relationship between the probability of random hardware failures and the probability of common
cause failures.
Despite the limitations of the current models, it is believed that they represent the best way forward at the
present time for providing an estimate of the probability of common cause failure of a multi-channel
system. The methodology described in this annex uses an approach similar to the well-established β-
factor model as the third part of the three-pronged approach already described.
There are two difficulties faced when using the β-factor model on a PES:
a) What value should be chosen for β? Many sources (e.g., Reference 19) suggest ranges within which
the value of β is likely to occur, however, no actual value is given, the user being left to make a
subjective choice. To overcome this problem, the methodology is based on the system originally
described in Reference 20 and recently refined in Reference 21.
b) The β-factor model does not take into account the sophisticated diagnostic capabilities of modern
PES, which can be used to identify a non-simultaneous common cause failure before it has had
sufficient time to manifest itself fully. To overcome this deficiency, the approach described in
References 20 and 21 have been modified to reflect the effect of diagnostics in the estimation of the
likely value of β.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 71 − ISA-TR84.00.02-2002 - Part 1
The diagnostic testing functions running within a PES are continuously comparing the operation of the
PES with predefined states. These states can be predefined in software or in hardware (e.g., by a
watchdog circuit).
a) the β-factor model relates the probability of common cause failure to the random hardware failure
rate. The probability of common cause failures which involve the system as a whole will depend on
the complexity of the system (possibly dominated by the user software) and not on the hardware
alone. Clearly, any calculations based on the rate of random hardware failures cannot take into
account the complexity of the software.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
b) reporting of common cause failures will generally be limited to hardware failures - the area of most
concern to the manufacturers of the hardware.
c) it is not considered practicable to model common cause failures (for example, software failures).
d) the measures described in the SRS and software design in ANSI/ISA-84.01-1996 are intended to
reduce the rate of software-related common cause failures to an acceptable level for the target SIL.
Therefore, the estimate of the probability of common cause failures derived by this methodology relates to
only those failures associated with the hardware. It should NOT be assumed that the methodology can
be used to obtain an overall failure rate which takes the probability of software-related failures into
account.
Programmable electronics channels have the potential for carrying out sophisticated diagnostic functions.
These can
A large fraction of common cause failures do not occur concurrently in all of the affected channels.
Therefore, if the repetition frequency of the diagnostic checks is sufficiently high, a large fraction of
common cause failures can be revealed and, hence, avoided before they affect all available channels.
Not all features of a multi-channel system, that will have a bearing on its immunity to common cause
failures, will be affected by diagnostics. However, those features relating to diversity or independence will
be made more effective. Any feature which is likely to increase the time between channel failures in a
non-simultaneous common cause failure (or reduce the fraction of simultaneous common cause failures)
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 72 −
will increase the probability of the automatic diagnostics identifying the failure and putting the plant into a
safe state. Therefore, the features relating to immunity to common cause failures have been divided into
those whose effect is thought would be increased by the use of automatic diagnostics and those whose
effect would not. This leads to the two columns X and Y, respectively in Table A.1.
Although the probability of common cause failures for “N” channels which will affect all “N” channels is
likely to be slightly lower than the probability of affecting “N-1” channels, in order to simplify the
methodology, it is assumed that the rate is independent of the number of affected channels, i.e., it is
assumed that, if a common cause failure occurs, it will affect all channels.
There is no known data on hardware-related common cause failures available for the calibration of the
methodology. Therefore, the tables associated with this β methodology have been based on engineering
judgement.
Diagnostic routines are sometimes not regarded as having a direct safety role so may not receive the
same level of quality assurance as the routines providing the main control functions. The methodology
was developed on the presumption that the diagnostics have an integrity commensurate with the target
SIL. Therefore, any software-based diagnostic routines should be developed using techniques
appropriate to the target SIL.
Consider the effect of common cause failures on a multi-channel system with automatic diagnostics
running within each of its channels.
Using the β-factor model, the rate of dangerous common cause failures is
D
Here, λ LEG is the rate of dangerous random hardware failures for each individual leg or channel and β is
the β-factor in the absence of diagnostics, i.e., the fraction of single-channel failures that will affect both
channels.
We shall assume that Common cause failures affect all channels, and, such that the span of time
between the first and all channels being affected is small compared to the time interval between Common
cause failures.
Suppose that there are diagnostics running in each channel, a fraction C of the failures will be detected
and revealed by the diagnostics. Therefore, we can divide the failures into two: those that lie outside the
coverage of the diagnostics (and so can never be detected) and those that lie within the coverage (so
would eventually be detected by the diagnostics).
The overall failure rate due to Common Cause dangerous failures is then given by
λ (β) + λ
DU DD
LEG LEG (β D).
λ LEG is the covert failure rate of a single channel, i.e., the rate of failures which lie outside the coverage
DU
of the diagnostics. Clearly, any reduction in the β-factor resulting from the repetition rate of the
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
λ LEG is the overt failure rate of a single channel, i.e., the rate of failures of a single channel that lie
DD
within the coverage of the diagnostics. Here, if the repetition rate of the diagnostics is high, a fraction of
the failures will be revealed leading to a reduction in the value of β, i.e., βD.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 73 − ISA-TR84.00.02-2002 - Part 1
β should be calculated for the sensors, the programmable electronics and the actuators separately.
In order to minimize the probability of occurrence of common cause failures, one must first establish
which measures will lead to an efficient defense against their occurrence. The implementation of the
appropriate measures in the system will lead to a reduction in the value of β used in estimating the failure
rate due to common cause failures.
In order to take the contribution of each of these measures into account, the methodology uses tables
which list the measures and contain an associated value representing the contribution of each. Because
sensors and actuators must be treated differently to the programmable electronics, separate columns are
used in Table A.1 for scoring the programmable electronics and the sensors or actuators.
Extensive diagnostics may be incorporated into programmable electronic systems which allow the
detection of non-simultaneous common cause failures. To allow for these to be taken into account in the
estimation of β, two sets of values are incorporated into the tables. One of these sets of values, in the
column labeled Y, corresponds to those measures whose contribution will not be improved by the use of
automatic diagnostics. The other, in the column labeled X, is thought to lead to an improvement when
automatic diagnostics are in operation.
The user of Table A.1 must ascertain which measures apply to the system in question and sum the
corresponding values shown in each of columns XPE & YPE, for the programmable electronics, or XSA and
YSA, for the sensors or actuators, the sums being referred to as X and Y, respectively.
Tables A.1 and A.2 may be used to determine a factor from the frequency and coverage of the
diagnostics, Z, taking into account the important note below Table A.2. The score S is then calculated
using the following equations, as appropriate (see previous section):
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
Here S or SD is a score which is used in Table A.4 to determine the appropriate β-factor.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 74 −
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
Separation/segregation:
Are all signal cables for the channels routed separately at all positions? 1.5 1.5 1.0 2.0
If the sensors/actuators have dedicated control electronics, is the electronics for each 2.5 1.5
channel on separate printed-circuit boards?
If the sensors/actuators have dedicated control electronics, is the electronics for each 2.5 0.5
channel indoors and in separate cabinets?
Diversity/Redundancy:
Do the devices employ different physical principles for the sensing elements 7.5
e.g., pressure and temperature, vane anemometer and Doppler transducer, etc.
Is partial diversity used, e.g. hardware watchdog same technology 2.0 1.0
Is partial diversity used, e.g. hardware watchdog other technology 3.0 1.5
Were the channels designed by different designers with no communication between them 1.0 1.0
during the design process?
Are separate test methods and people used for each channel during commissioning? 1.0 0.5 1.0 1.0
Is maintenance on each channel carried out by different people at different times? 2.5 2.5
Complexity/design/application/maturity/experience:
Does cross-connection between channels preclude the exchange of any information other 0.5 0.5 0.5 0.5
than that used for diagnostic or voting purposes?
Is the design based on techniques used in equipment that has been used successfully in the 0.5 1.0 1.0 1.0
field for > 5 years?
Is there more than 5 years experience with the same hardware used in similar 1.0 1.5 1.5 1.5
environments?
Is the system simple, e.g. no more than 10 inputs or outputs per channel? 1.0
Are inputs and outputs protected from potential levels of over-voltage and over-current? 1.5 0.5 1.5 0.5
Are all devices/components conservatively rated? (e.g., by a factor of 2 or more) 2.0 2.0
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 75 − ISA-TR84.00.02-2002 - Part 1
Have the results of the FMEA or FTA been examined to establish sources of CCF and have 3.0 3.0
identified sources of CCF been eliminated by design?
Were CCFs addressed in design reviews with the results fed back into the design? 3.0 3.0
(Documentary evidence of the design review process is required.)
Are all field failures fully analyzed with feedback into the design? (Documentary evidence of 0.5 3.5 0.5 3.5
the procedure is required.)
Is there a written system of work which will ensure that all component failures (or 1.5 0.5 1.5
degradations) are identified, the root causes established and other similar items are
inspected for similar potential causes of failure?
Are procedures in place to ensure that: maintenance (including adjustment or calibration) of 1.5 0.5 2.0 1.0
any part of the independent channels is staggered, and, in addition to the manual checks
carried out following maintenance, the automatic diagnostic checks are allowed to run
satisfactorily between the completion of maintenance on one channel and the start of
maintenance on another?
Do the documented maintenance procedures specify that all parts of redundant systems 0.5 0.5 0.5 0.50
(e.g., cables, etc.), intended to be independent of each other, must not be relocated?
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
Is all maintenance of printed-circuit boards, etc. carried out off-site at a qualified repair center 0.5 1.0 0.5 1.5
and have all the repaired items gone through a full pre-installation testing?
Do the system have low diagnostics coverage (60% to 90%) and report failures to the level 0.5
of a field-replaceable module?
Do the system have medium diagnostics coverage (90% to 99%) and report failures to the 1.5 1.0
level of a field-replaceable module?
Do the system have high diagnostics coverage (>99%) and report failures to the level of a 2.5 1.5
field-replaceable module?
Do the system diagnostics report failures to the level of a field-replaceable module? 1.0 1.0
Have designers been trained (with training record) to understand the causes and 2.0 3.0 2.0 3.0
consequences of Common cause failures
Have maintainers been trained (with training record) to understand the causes and 0.5 4.5 0.5 4.5
consequences of Common cause failures
Environmental control:
Is personnel access limited (e.g. locked cabinets, inaccessible position)? 0.5 2.5 0.5 2.5
Will the system be operating within the range of temperature, humidity, corrosion, dust, 3.0 1.0 3.0 1.0
vibration, etc., over which it has been tested, without the use of external environmental
control?
Are all signal and power cables separate at all positions? 2.0 1.0 2.0 1.0
Environmental testing:
Has a system been tested for immunity to all relevant environmental influences (e.g. EMC, 10.0 10.0 10.0 10.0
temperature, vibration, shock, humidity) to an appropriate level as defined in recognized
standards?
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 76 −
Level of coverage of the Value of Z to be used when the automatic diagnostic tests are repeated at intervals of:
automatic diagnostics
• The diagnostics shall determine the locality of the fault and be capable of localizing the fault.
• The diagnostic tests shall continue to be capable of placing the process in the safe state after the detection of any subsequent
faults.
Only if the above criteria apply, can a non-zero value be used for Z.
Level of coverage of the Value of Z to be used when the automatic diagnostic tests are repeated at intervals of:
automatic diagnostics
Less than 2 hours Between 2 hours & 2 Between 2 days & 1 Greater than 1 week
days week
NOTE 1 If sensors or actuators are PE-based, they should be treated as PE if they are enclosed within the same building (or
vehicle) as the PE that is used as the logic solver, and as sensors/actuators, if they are not.
NOTE 2 When using Table A.1, take account of the scores for all items that apply - the scoring has been designed to allow for
items which are not mutually exclusive. For example, a system with PE channels in separate racks is entitled to both the score for
"Are the PE channels in separate cabinets" and that for "Are the PE channels on separate printed-circuit boards."
NOTE 3 For a non-zero value of Z to be used, it must be ensured that the equipment under control is put into a safe state before a
non-simultaneous Common cause failure can affect the all channels. The time taken to assure this safe state must be less than the
claimed repetition time of the automatic diagnostics. A non-zero value for Z can be used only if:
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 77 − ISA-TR84.00.02-2002 - Part 1
• the system continues to run on a reduced number of channels and, following a fault, automatic shut-down will be assured
immediately that the number of operating channels, that are capable of ensuring a safe shut-down, reduces to one, or,
• a formal system of work is in place to ensure that the cause of any revealed fault will be fully investigated within the claimed
period between the automatic diagnostic tests and:
• if the fault has the potential for leading to a common cause failure, the plant will be immediately shut-down, or,
• the faulty channel will be repaired within the claimed period between the automatic diagnostic tests.
NOTE 4 The operation of the system on the identification of a fault must be taken into account. For example, a simple 2oo3
system must be shutdown (or be repaired) within the times quoted in Tables A.2 or A.3, following the identification of a single failure.
If this is not done, a failure of a second channel could result in the two failed channels outvoting the remaining (good) channel. A
system which automatically reconfigures itself to 1oo2 voting when one channel fails, and which will automatically shutdown on the
occurrence of a second failure, has an increased probability of revealing the fault in the second channel and so a non-zero value for
Z may be claimed.
NOTE 5 In the process industries, it is unlikely to be feasible to shutdown the EUC when a fault is detected within the repetition
period for the automatic diagnostics as specified in Table A.2. This methodology should not be interpreted as a requirement for
process plants to be shutdown when such faults are detected. However, if a shutdown is not implemented, no reduction in the β-
factor can be gained by the use of automatic diagnostics for the programmable electronics. In some industries, a shutdown may be
feasible within the specified time. In these cases, a non-zero value of Z may be used.
NOTE 6 Where diagnostics are carried out in a modular way, the repetition time used in Tables A.2 or A.3 is the time between the
successive completions of the full set of diagnostic modules. The diagnostic coverage is the total coverage provided by all of the
modules.
70 to 120 1% 2%
45 to 70 2% 5%
Values of βD lower than 0.5% for the PES and 1% for the sensors would be
difficult to justify. --``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 78 −
For categories not relating to diagnostics nor diversity, half the maximum score for a category was used;
this being the same for each of the examples. It should be noted that when Table A.1 is used in practice,
no such subdivision of scores is allowed.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
β 2% 2% 5% 5%
Score SD 121 56.5 81.5 42
βD 0.5% 2% 1% 5%
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 79 − ISA-TR84.00.02-2002 - Part 1
B.1 Objective
Fault simulation testing is a verification method to determine the safety integrity and diagnostic coverage
of the SIS by purposely introducing faults that simulate those that could occur in an on-line SIS, under
specified environmental conditions.
B.2 Scope
This test procedure applies to SIS elements in the process industries.
Simulate only single faults unless this fault is covert, in which case a second fault may be simulated.
Perform fault simulation testing of the SIS elements by independent third parties.
Determine the fault simulation test success/failure criteria based on the failure mode of the SIS, and the
ability of the SIS to correctly detect, diagnose and annunciate the fault.
Estimate the diagnostic coverage of the SIS from the test results.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 80 −
Resistor Open
Short
Drift
Capacitor Open
Short
Leakage
Shorted Contact
Open Coil
Closed Coil
Short Misalignment
Short of pins
Functional failures
The following fault simulations are required to be performed in each fault simulation test program:
a) Data lines
Fault several data lines of each and every data bus in the SIS.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
b) Address lines
Several address lines of each and every address bus in the SIS shall be faulted. Every address line
used for memory-mapped input/output, or to decode external logic, shall be faulted.
c) Control lines
Fault every control line of each and every control bus. Fault each CPU interrupt.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 81 − ISA-TR84.00.02-2002 - Part 1
Fault each error detection circuit in such a way as to attempt to disable error detection. If this
condition is not covered, then introduce a second fault simulating an error.
e) Watchdog circuit
Fault each watchdog circuit (internal or external to the SIS) in such a way as to attempt to disable the
time-out function.
f) Selection logic
Fault any logic which selects or decodes among a number of channels in such a way as to attempt to
select the wrong channel.
g) Memory
Simulate several single bit memory errors for each memory device type. Utilize a photographic flash
for SIS which use EPROM’s to simulate a temporary change in memory contents.
Vary the input and output of power supplies to ensure that the SIS operates properly both inside and
outside the specified voltage limits.
Fault the bus arbitration logic in such a way as to attempt to allow simultaneous access to the bus,
and to allow no access to the bus.
g) Communications misaddressing
Fault serial or parallel type communications in such a way as to attempt to select more than one
subsystem.
Fault each and every independent channel of a typical voting scheme for each type of input and
output.
Select additional faults at random so that the total number of tests allows a statistically significant
determination of the diagnostic coverage.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
This page intentionally left blank.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 83 − ISA-TR84.00.02-2002 - Part 1
C.2 Advantages
C.2.1 Advisory software packages generally speed the quantification and presentation of specific cases
of interest. This capability allows comparison of a number of test cases to illustrate the relative effect of
varying individual input parameters (functional test interval, redundancy, etc).
C.2.2 These packages make the more complex calculations less prone to random calculation errors
than hand calculations. In addition, the most complex techniques are not very practical without some type
of computer assistance.
C.3 Disadvantages
C.3.1 The user must make some effort to understand the modeling technique, assumptions, and
limitations used in the package. The relevant information may not be readily apparent to the user or well
documented by the supplier. Without this understanding, the user may be confused by the results
obtained.
C.3.2 These packages may not have been verified for accuracy by the supplier or by a third party.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
C.4 Cautions
C.4.1 Some of the advisory software packages are so easy to use and contain enough hidden
assumptions that a user with insufficient skill may calculate an incorrect SIL for a SIS. The user must be
aware that the ease of use does not dictate the skill required to perform these calculations.
C.4.2 The user must be aware of and assume the responsibility for the sufficiency and applicability of
the modeling technique, the assumptions, the limitations, and the supplier validation activities before
using one of these software packages for calculation of the SIL of a SIS.
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
This page intentionally left blank.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 85 − ISA-TR84.00.02-2002 - Part 1
D.1 Introduction
The Failure Mode Effect, Hazard and Criticality Analysis (FMEHCrA) is a widely used and effective safety
analysis technique. The standard reference for this method is US MIL-STD-1629 [MIL1629] which
describes the Failure Mode and Effect Analysis (FMEA).
Engineers have always performed a FMEA type of analysis on their design and manufacturing processes,
but the first formal applications of the FMEHCrA can be found in the mid-1960 in the American aerospace
industry. The FMEHCrA consists of three different analysis techniques.
3) Criticality analysis
FMEHCrA is a bottom up technique that is used qualitative, quantitative or as a combination of both and
is very effective in identifying critical failures of the system in consideration. Very often the FMEHCrA
technique is adjusted to the company strategy or ideas about this technique.
• to identify and evaluate the different failure modes and effects of the system in consideration.
• to determine the actions to be taken which could eliminate or reduce the chance of the different
failure modes occurring.
As part of the safety analysis process, the FMEA technique is used for two purposes. At the system level
a FMEA is used to document system behavior under failure conditions. A variation of the FMEA
technique is recommended at the electronic module level to establish diagnostic capability and failure
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
A FMEDA (Failure Mode Effect and Diagnostic Analysis) is a FMEA variation. It combines standard
FMEA techniques with extensions to identify on-line diagnostic techniques. It is a technique
recommended to generate failure rates for each important category (safe detected, safe undetected,
dangerous detected, dangerous undetected) in the safety models.
Column 1 Name
This column describes the name of the component in consideration (definition of module/component).
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 86 −
Column 2 Code
Column 3 Function
This column describes the function of the component. This is important for anybody who writes or reads
the document to understand the way in which the system works. It is an easy way to get a good
understanding of how the different components work and how eventually the system works.
This column describes the failure modes of the component. For example, leakage, fail open or close for
valves, fracture, wear out, etc.
Column 5 Cause
This column describes the cause of the failure mode of column four. For example, aging, overload,
misuse, etc.
This column describes the effect of the failure on function level of the component.
This column describes the effect of the failure one level higher than in column six. Depending on the
complexity of the system it is possible to consider more levels. This gives a good insight in how the
system works.
In this column the failure rate of the current failure mode is given, usually in failures per unit time. If no
failure rates are available it is possible to use the information of standards or databases.
This column is reserved for any comment that is of importance. For example the action to be taken to
prevent a failure mode like this, change the design, condition monitoring, better education of employees,
etc.
Column 10 Detectability
This column is an extension to the standard for the purpose of identifying that this component failure is
detectable by on-line diagnostics. The number must be in the range of 0 to 1. A number between 0 and 1
may be entered to indicate the probability of detection.
NOTE Whenever a component failure mode is claimed detectable, this may be verified with a fault simulation test in some cases
(see Annex B). The component failure mode is simulated on actual E/E/PES equipment and the diagnostic capability of the
E/E/PES is verified.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 87 − ISA-TR84.00.02-2002 - Part 1
Column 11 Diagnostic
This column is an extension to the standard used to identify the diagnostic used to detect the failure.
This column is used to numerically identify failure mode. A "1" is entered for safe failure modes. A "0" is
entered for dangerous failure modes. The number is used in spreadsheets to calculate the various failure
categories.
This column contains the calculated failure rate of safe detected failures. It is obtained by multiplying the
failure rate (Column 8) by the failure mode number (Column 12) and the detectability (Column 10).
This column contains the calculated failure rate of safe undetected failures. It is obtained by multiplying
the failure rate (Column 8) by the failure mode number (Column 12) and one minus the detectability
(Column 10).
This column contains the calculated failure rate of dangerous detected failures. It is obtained by
multiplying the failure rate (Column 8) by one minus the failure mode number (Column 12) and the
detectability (Column 10).
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
This column contains the calculated failure rate of dangerous undetected failures. It is obtained by
multiplying the failure rate (Column 8) by one minus the failure mode number (Column 12) and one minus
the detectability (Column 10).
FMEDA Example
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 88 −
• Omission of important failure modes is always possible (for example omission of possible human
failure causes) and leads to a totally unreliable FMEHCrA.
• The FMEHCrA approach is recommended primarily as a qualitative method at the system level. The
FMEHCrA cannot give an accurate quantification of the safety of a system, but only a comparison of
the effects of different failure modes within one system or a comparison between systems. More
important it can lead to misleading results due to the human selection and interpretation of failure
modes and their consequences.
• The FMEHCrA technique is poor at identifying combinations of failures that cause critical problems.
Each component is reviewed individually, combinations are not addressed.
• Common cause failures are not taken into account, Operational and maintenance failures are likely to
be missed unless the team of reviewers is skilled in human reliability analysis
• The technique can best be used to find that small failures that may not seem important at first but that
eventually, can lead to critical system failures.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 89 − ISA-TR84.00.02-2002 - Part 1
• The outputs of the FMEHCrA and FMEDA can be very well used as input values for extended
techniques like Markov, FTA and RBD to make an accurate qualitative analysis on system level.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 91 − ISA-TR84.00.02-2002 - Part 1
This includes a checklist of common cause failure and systematic failure events that may be modeled
during SIS evaluation using the techniques described in ISA-TR84.00.02-2002 - Parts 2, 3, 4, and 5.
Note that common cause failures and systematic failures can be due to a single failure event or to a
combination of systematic failure, common cause failure, poor design practices, and/or poor operation/
maintenance practices.
These common cause failures and systematic failures can include, but are not limited to, the following:
• Component
• Specification
• Manufacture
• Calibration
• Wear-out susceptibility
• Test degradation
• Maintenance degradation
• Aging
• Data sharing
• Plant Personnel
• Installation
• Management of change
• Improper bypassing
• Environmental Stress
• Vibration
• Uninhibited monomer
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 92 −
• RFI/ESD
• Temperature
• Humidity
• Corrosion
• Flood susceptibility
• Seismic susceptibility
This list is not an exhaustive catalogue of the potential common cause failures and systematic failures.
Rather, it is a partial list of common cause failures and systematic failures that have been observed by
(11, 34, 35)
industry and that have played a critical part in the PFD or real systems .
Some specific examples of common cause failures and systematic failures are as follows:
• Process chemistry disables safety function of final element (valve plugs or valve corroded);
• Valve leaks due to corrosion AND this leak is not detected by mechanical integrity inspection;
• Solenoid valve fails due to incorrect installation AND this is not detected by testing;
• Solenoid vent port is plugged by dirt daubers or plugged by insulation AND is not detected by testing;
• Poor communication of the safety requirements specification (SRS) to SIS designer and installer;
• Transmitter calibrated incorrectly (wrong specification, bad calibration standard, technician makes a
mistake);
• Wrong specification device (transmitter, solenoid valve, shutdown valve, etc.) installed.
NOTE Dirt daubers – other common names: mud dauber or mud wasp; there are three types (scientific names):
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 93 − ISA-TR84.00.02-2002 - Part 1
Annex F — Index
access 88, 95
accuracy 15, 97
alarm 38
anti-surge control 21
architecture 22, 36
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
architecture(s) 9, 10, 34, 53, 54, 55, 61, 65, 69, 71, 72
boundary(ies) 12
BPCS 29
bypassing 105
channel 22
channel(s) 22, 40, 43, 44, 51, 78, 79, 80, 83, 84, 86, 87, 90, 95
checklist 105
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 94 −
code(s) 100
commissioning 86
common cause11, 15, 16, 18, 19, 22, 24, 41, 46, 47, 54, 58, 66, 78, 79, 81, 82, 83, 84, 85, 89, 90, 105,
106
common cause failure(s) 15, 16, 41, 46, 47, 54, 78, 79, 81, 82, 83, 84, 85, 89, 90, 105, 106
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
communication 33
component 24, 31
compressor(s) 21
configuration 22
configuration(s) 9, 11, 15, 16, 27, 44, 45, 49, 53, 58, 72, 76
configuring 38
conservative 66, 71
continuous 27
control system 31
cost 15
coverage 10, 16, 18, 22, 24, 41, 46, 47, 53, 58, 60, 61, 66, 79, 83, 84, 85, 87, 89, 90, 93, 95, 102
covert failure(s) 84
covert fault(s) 18
criteria 89, 93
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 95 − ISA-TR84.00.02-2002 - Part 1
de-energized 25
detectability 101
detectable 101
diagnostic coverage 10, 16, 18, 24, 41, 46, 47, 58, 60, 66, 90, 93, 95
diagnostic testing 82
diagnostic(s)10, 16, 18, 41, 42, 46, 47, 53, 55, 58, 60, 61, 66, 78, 79, 82, 83, 84, 85, 86, 87, 89, 90, 91,
92, 93, 95, 99, 100, 101
diagram 14, 34
differences 61
dirt 106
display(s) 55
diverse redundancy 34
diverse separation 38
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 96 −
document(s) 9, 11, 12, 14, 15, 26, 58, 99, 100, 102
documents 11, 12, 14, 15, 26, 58, 78, 99, 100, 102
E/E/PE 35
electrical fault 39
electromechanical 24
electromechanical relay 24
Electronic (/E) 24
environment 27, 38
error 40
fail-to-function 26, 55
failure rate(s)15, 18, 22, 45, 46, 47, 48, 49, 50, 51, 53, 54, 55, 57, 58, 59, 60, 61, 62, 65, 66, 68, 69, 70,
71, 72, 81, 82, 84, 99, 100, 101
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 97 − ISA-TR84.00.02-2002 - Part 1
feedback 87
field device(s) 10, 29, 38, 47, 48, 49, 50, 53, 54, 61
field wiring 26
figure 5 31
figure 6 33
figure 7 35, 36
final element(s) [See field device(s)] 11, 15, 22, 41, 44, 45, 47, 49, 50, 51, 52, 55, 60, 61, 66, 72, 106
flow 34
FPL 38
fuel/air controls 21
function 11, 12, 14, 16, 18, 22, 24, 26, 34, 36, 38, 41, 44, 45, 53, 54, 55, 56, 78, 82, 83, 95, 100, 106
function(s)9, 10, 11, 12, 14, 16, 18, 22, 24, 26, 34, 36, 38, 41, 44, 45, 53, 54, 55, 56, 78, 79, 82, 83, 95,
100, 106
functional unit 26
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
ISA-TR84.00.02-2002 - Part 1 − 98 −
FVL 38, 39
ground plane(s) 39
ground(s) 39
guide words 27
guideline(s) 19
hardware 9, 14, 15, 26, 34, 39, 41, 49, 55, 56, 78, 81, 82, 84, 86, 87
hardware fault(s) 39
hard-wired 26
harm 27, 34
hazard 27, 33
hazard(s) 9, 27
hazardous 15, 24
HAZOP 27
heaters 21
historical data 79
host 22
humidity 56, 88
identical redundancy 34
identical separation 38
IEC 15, 78
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 99 − ISA-TR84.00.02-2002 - Part 1
insulation 106
interface(s) 22, 26, 28, 29, 55, 56, 59, 60, 87, 91
interfaces 22, 26, 28, 29, 55, 56, 59, 60, 87, 91
leakage 100
life cycle 11
lifecycle 37
logic function 29
logic function(s) 24
logic solver(s) 11, 15, 16, 24, 26, 38, 41, 44, 45, 48, 49, 53, 54, 66, 72, 73, 79, 89
LVL 38
maintenance 9, 10, 11, 14, 16, 22, 29, 40, 66, 81, 86, 87, 103, 105
maintenance procedures 87
maintenance/engineering interface(s) 22
manufacture 31
Markov modeling 73
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
material(s) 31
mathematical analysis 34
measure 37
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 100 −
medium 87
memory 26, 95
mitigate 24
mitigation 33
mode(s) 11, 15, 18, 31, 46, 47, 53, 66, 93, 99, 100, 101, 102
modification errors 56
modification(s) 15, 56
monitoring 100
motor(s) 24
MTTFspurious
10
numerical data 34
on-line 41, 42, 43, 46, 47, 52, 57, 78, 93, 99, 101
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
open 100
operating system(s) 55
output function 29
output(s) [See input/output devices and input/output modules]22, 23, 25, 28, 29, 34, 42, 43, 44, 45, 47,
48, 49, 50, 51, 52, 53, 54, 60, 61, 62, 65, 69, 70, 71, 79, 87, 94, 95, 103
overload 100
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 101 − ISA-TR84.00.02-2002 - Part 1
panel(s) 9
parameter(s) 9, 15, 16, 18, 41, 44, 45, 68, 69, 70, 71, 97
PFDavg 10
pharmaceutical(s) 31
physical failures 54
PLC 31, 32
plugging 106
pneumatic(s) 55
possible cause(s) 55
power 23, 25, 31, 42, 43, 44, 45, 48, 50, 51, 52, 53, 55, 56, 88, 95
power source(s) 56
power supply (supplies) 42, 43, 44, 45, 48, 50, 51, 52, 53, 55, 95
pressure transmitter 38
prevention 33
process deviation(s) 27
Programmable Electronic System(s) (PES)10, 15, 24, 28, 29, 43, 44, 53, 54, 55, 56, 61, 63, 65, 78, 79,
81, 82, 85, 90, 91, 101
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 102 −
programming 55
programming language(s) 55
protection 27, 33
quantified 81
quantitative 15, 99
redundant sensors 60
relay(s) 24, 86
reliability 9, 10, 14, 18, 34, 55, 66, 68, 69, 70, 71, 78, 103
remote I/O 22
repair(s) 16, 29, 43, 51, 52, 53, 56, 68, 69, 70, 72, 73, 81, 87
reporting 82
revealed 24
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
risk assessment 9
risk estimates 34
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 103 − ISA-TR84.00.02-2002 - Part 1
risk(s) 9, 11, 34
safe 15, 26, 31, 41, 42, 43, 45, 46, 47, 49, 50, 51, 52, 53, 55, 57, 58, 60, 65, 79, 83, 89, 90, 99, 101
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
safe state 26, 27, 35, 41
safety function 35
safety function(s) 9, 11, 12, 14, 18, 36, 38, 53, 79, 106
safety instrumented system 20, 22, 24, 26, 27, 33, 34, 35, 36, 37
Safety Instrumented System(s) (SIS)9, 10, 11, 12, 14, 15, 16, 18, 22, 23, 24, 25, 26, 27, 29, 34, 35, 36,
38, 39, 40, 44, 45, 49, 53, 54, 55, 56, 57, 59, 60, 66, 68, 69, 71, 72, 73, 74, 75, 76, 78, 93, 94, 95, 97,
105, 106
safety integrity 11, 14, 15, 53, 54, 56, 60, 61, 93
safety logic 55
scope 82, 83
sensor(s) [See field device(s)]11, 15, 22, 26, 41, 44, 45, 46, 48, 49, 50, 51, 52, 54, 55, 59, 60, 66, 72,
82, 83, 84, 85, 86, 89, 91
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 104 −
separate 22
separated 54, 55
separation 38
SEVERITY 66
shock 88
SIF 35, 36
SIL 21, 36
SIL 1 12
SIS application(s) 68
SIS applications 68
smart sensors 31
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
software 9, 14, 15, 16, 20, 24, 26, 39, 40, 49, 55, 56, 69, 82, 97, 105
software design 82
software lifecycle 39
solenoid valve 26
solid state 24
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
− 105 − ISA-TR84.00.02-2002 - Part 1
subsystem 20, 24
supplier(s) 10, 97
surge(s) 21
systematic failure(s) 15, 16, 18, 49, 50, 54, 55, 78, 79, 80, 81, 91, 105, 106
terminology 54
test 39
test(s) 18, 40, 43, 45, 46, 47, 52, 53, 79, 81, 86, 89, 90, 91, 93, 94, 95, 97, 101
testing 9, 14, 27, 33, 43, 45, 53, 55, 56, 60, 61, 79, 81, 82, 87, 88, 93, 106
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
time(s) 14, 15, 16, 29, 31, 34, 35, 36, 39, 40, 43, 44, 45, 53, 66, 73, 78, 79, 81, 82, 83, 84, 86, 90, 100
training 87, 91
transient(s) 39
trip(s) 9, 15, 18, 23, 25, 29, 39, 40, 43, 46, 47, 50, 51, 55, 57
uncertainty analysis 69
undetected 24, 40
unreliable 102
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
ISA-TR84.00.02-2002 - Part 1 − 106 −
unrevealed 24, 40
user interface(s) 55
validate(s) 40
validation 97
valve 33
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
valve(s) 70, 71, 100, 106
vent(s) 106
verification 18, 93
verify 27
vibration 56, 88
voltage(s) 56, 95
write(s) 100
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
--``,,,```,,````,``,``````,,`-`-`,,`,,`,`,,`---
COPYRIGHT 2003; The Instrumentation, Systems, and Automation Society Document provided by IHS Licensee=Fluor Corporation/2110503105, User=,
05/06/2003 12:23:04 MDT Questions or comments about this message: please call
the Document Policy Management Group at 1-800-451-1584.
Developing and promulgating sound consensus standards, recommended practices, and technical reports
is one of ISA’s primary goals. To achieve this goal the Standards and Practices Department relies on the
technical expertise and efforts of volunteer committee members, chairmen and reviewers.
ISA is an American National Standards Institute (ANSI) accredited organization. ISA administers United
States Technical Advisory Groups (USTAGs) and provides secretariat support for International
Electrotechnical Commission (IEC) and International Organization for Standardization (ISO) committees
that develop process measurement and control standards. To obtain additional information on the
Society’s standards program, please write:
ISA
Attn: Standards Department