Fundamentals of Power System Protection & Circuit Interrupting Devices
Fundamentals of Power System Protection & Circuit Interrupting Devices
Fundamentals of Power System Protection & Circuit Interrupting Devices
1.1 Introduction :
In day to day working electricity has become a vital part of life. As electricity is used every
where such as for domestic purpose, industrial applications, commercial applications, irrigation
purpose, traction systems etc; it is very difficult to survive without electricity. Continuous supply
of electricity is very necessary for over all growth of the country. Continuity of supply is
maintained by interconnected power system.
Hence it is essential to protect the entire power system from faults / abnormal conditions to
ensure maximum continuity of supply. The fault must be cleared within a fraction of a second. If a
short circuit persists on a system for a longer period, it may cause damage to some equipments /
sections in the system. This is ensured with the switching off of the certain equipments
automatically under fault condition and manually or remotely under normal condition. Such
equipments by which switching on and off operations are done are known as switch gears.
1.2 Functions of Protective Systems :
• As mentioned above, protective system should operate automatically under abnormal
condition within minimum time. Apart from this it should have following essential features :
• Quick operation : To minimize the damage to the faulty part, the switchgear must operate
as quickly as possible after the occurance of fault. If the fault current is allowed to pass for
more time then there will be considerable damage to the generators, transformers and other
equipments which are in the circuit upto the fault location. Also, if fault is not cleared
quickly, it is likely to spread into healthy parts of the system.
• Complete reliability : The ability of the portion system to operate under the
predetermined conditions is known as Reliability. The protection would be rendered largely
ineffectively and could even become a liability without the reliability.
• Discrimination : Switchgear (protective system) should be capable of identifying the faulty
section i.e. it must be able to discriminate between the faulty sections and the healthy
sections. It should isolate the faulty section from the system without affecting the healthy
section. This will ensure the continuity of supply.
• Provision for instruments : For metering purpose there should be the provision for
connecting instrument transformes to the system; so that the measuring instruments may
be mounted on main switch board or a separate panel.
The Table 1.1.1 indicates the function of various switchgears which are generally installed in
A.C substation.
Table 1.1.1
7. Potential transformer
To stepping down the magnitude of line
voltage for measurement, protection and
control.
• Mostly the faults are caused by failure of insulation. The failure of insulation results in short
circuits which are very harmful.
• Faults are also caused by breaking of conductors due to excessive heat or mechanical
stresses.
• Most of the faults on transmission lines and distribution liens are caused by over voltages
due to lightening or switching surges, or by external conducting object falling on overhead
lines.
• Unbalance currents flowing in rotating machines set up harmonics, there by heating the
machines.
• Certain faults occur due to the poor quality of system components or because of faulty
system design.
• Sometimes circuit breakers may trip due to errors in the switching operations testing or
maintenance work, wrong connections defects in protective devices.
• Other causes of faults on overhead lines are : lightening strokes, air crafts, ice and snow
loading, abnormal loading, stroms, earthquakes, creepers etc.
• A short circuit between any one of the phase conductors of 3 phase system and earth is
called a single phase to ground fault.
• It may be due to the failure of insulation between a phase conductor and earth or due to a
phase conductor breaking and falling to the ground.
Two phase to ground fault (L – L – G) :
A short circuit between any two phases and earth is called a double line to ground or a two
phase to ground fault.
Phase to phase faults (L – L) :
A short circuit between any two lines (phases) is called as line to line or phase to phase fault.
Open circuited phases :
• This type of fauslt is caused by a break in the conducting path. Such faults occur when one
or more phase conductors break or a cable joint or joint on the overhead lines fails.
• Such situation may also arise when circuit breakers or isolators open but fail to close one or
more phases.
• Due to the opening of one or two phases, unbalanced currents flows in the system, thereby
heating rotating machines.
Simultaneous faults :
• For design and application of protective scheme, it is very useful to have an idea of the
frequency of occurrence of faults on various elements of a power system.
• Usually the power stations are situated far away from the load centres, resulting in
hundreds of kilometres length of overhead lines beings exposed to atmospheric conditions.
• The chances of faults occurring due to stroms, falling of external objects on the lines, flash
overs resulting from dirt deposits on insulators, etc. are greater for overhead lines than for
other parts of the power system.
• Table 1.5.1 gives an approximate idea of the fault statistics.
Table 1.5.1
• From Table 1.5.1 it is evident that 50% of the total faults occur on overhead lines. Hence
overhead lines requires more attention while planning and designing protective scheme for a
power system.
• Table 1.5.2 shows the frequency of occurrence of different types of faults (mainly the
different types of short circuits) on overhead lines.
Table 1.5.2
• From the table it is clear that the frequency of line to ground faults is more than any other
type of fault, and hence the protection against L – G fault requires greater attention in
planning and design of protective schemes for over head lines.
• In case of cables 50% of the faults occur in cables and 50% at end junctions. Cable faults are
usually of a permanent nature and hence, automatic reclousers are not recommended for
cables.
4. Reliability : The ability of the protection system to operate under the predetermined
conditions is known as reliability. The protection would be rendered largely ineffectively and
could even become a liability without the reliability.
5. Simplicity : A simple protective system is easy to maintain Reliability and Simplicity are
closely related. The simpler the protection scheme, the greater will be its reliability.
6. Adequateness : Providing protection scheme for every abnormal condition is very costly.
Therefore, protection provided for any machine should be adequate.
Adequateness of protection is judge by following aspects :
• Cost of the machine and importance of the machine.
• Rating of the machine to be protected.
• Probability of abnormal conditions due to internal and external causes.
• Continuity of supply as affected by failure of machine.
• Location of protected machine.
7. Economy : Cost is the most important factor in the choice of a particular protection scheme.
As a rule, the protective gear should not cost more than 5% of its total cost. However, when
the apparatus to be protected is of atmost importance, then economic consideration are often
subordinated to reliability.
(% X)
V V 1000
1000 1000
=
100
V I
1000
(% X) (kV)2 10
=
kVA
(kVA) X
%X = …(2)
10 (kV)2
If ‘X’ is the only reactance element in the circuit, then the short circuit current is given by,
V
ISC =
X
ISC = I
100 [By putting the value of X from Equation (1) ] …(3)
% X
• It is clear from the expression (2) that percentage reactance of an equipment depends upon
its kVA rating.
• Generally, various equipments used in the power system have different kVA ratings.
Therefore, it is necessary to find the percentage reactance of all the elements on a common
kVA ratings.
• This common kVA rating is known as Base kVA. The value of this base – kVA is quite
unimportant and it may be
1. Equal to that of largest plant.
2. Equal to total plant capacity.
3. Any arbitary value.
The conversion can be affected by using the following relation :
Base kVA
% reactance at base kVA = % Reactance at Rated kVA. …(4)
Rated kVA
• Although the potential at the point of fault is zero, it is a normal practice to express the
short circuit current in terms of short circuit kVA based on the normal system voltage at the
point of fault.
• The product of normal system voltage and short circuit current at the point of fault
expressed in kVA is known as short circuit kVA.
Let V = normal phase voltage in volts.
I = Full load current in amperes at base kVA.
% X = Percentage reactance of the system on base kVA upto the fault point.
From Equation (2)
1.8 Steps to Calculate Symmetrical Short Circuit Current and Short Circuit kVA :
Ex. 1.9.1 : A 3 phase transmission line operating at 66 kV and connected through a 1000 kVA transformer
with 5% reactance to a generating station basbar. The generator is of 2500 kVA with 10%
reactance. The single line diagram of the system is shown in Fig. Calculate short circuit current if
fault occurs at the HT terminals of transformer.
Fig. P. 1.9.1(a)
Soln. :
Selection :
% X = 10 + 12.5
% X = 22.5%
Full load current corresponding to 2500 kVA base at 66 kV is given by,
P = 3 VI
2500 1000
I =
3 66 1000
I = 21.87 A
Short circuit current,
100
ISC = I
%X
100
= 21.87
22.5
ISC = 97.2 A …Ans.
Ex. 1.9.2 : Two alternators are connected to a bus bar operating at a 12,000 V. The alternator A is of
20,000 kVA and having 20% reactance. Alternator B is of 25,000 kVA and having 35% reactance.
Find the short circuit current that will flow in a complete three phase short circuit if fault occurs at
point ‘F’.
Fig. P. 1.9.2(a)
% RL = 10%
Fig. P. 1.9.3(b)
Total impedance is :
(i) For fault at the end of transmission line (Point F2),
Total % reactance :
%X = % X A+ % X T + % X L
= 10 + 10 + 40
% X = 60
% resistance = 10%
% Impedance from generator to fault point F2.
% Z = (60)2 + (10)2
% Z = 60.83 %
100
Short circuit kVA = Base kVA
%X
100
= 10000
60.83
Ex. 1.9.5 : Two three phase generators of ratings 1000 kVA and 1500 kVA 3.3 kV, having percentage
reactance of 10 and 20 respectively with respect to their ratings, are connected to bus bars. A
three phase short circuit occurs on the bus. Find the short circuit current.
Soln. : Let Base kVA = 1500 kVA.
% reactance of alternator with respect to base kVA
Base kVA
% XA = % reactance of rated kVA
Rated kVA
1500
= 10
1000
% XA = 15%
1500
% XB = 20
1500
% XB = 20%
(a) (b)
Fig. P. 1.9.5
Total reactance % X.
15 20
% X = XA || XB =
15 + 20
300
=
45
% X = 6.667 %
Line current at base kVA.
1500 103
I =
3 3.3 103
I = 262.74 A
100
Short circuit kVA = Base kVA
%X
100
= 1500
6.667
= 22498.87 kVA
S.C. MVA = 22.498 MVA …Ans.
100 100
ISC = I = 262.74
%X 6.667
ISC = 1751.68 A …Ans.
Ex. 1.9.6 : Two generators of 11 kV, 3-phase, 3000 kVA having subtrancient reactance of 15% operate in
parallel. The generator supply power to a transmission line through a 6000 kVA transformer of
ratio 11/22 kV and having a leakage reactance of 5%. Calculate fault current and fault MVA for
3 phase fault on (1) H.T. side (2) L.T. side of a transformer.
Soln. :
Assume base kVA = 6000 kVA.
% reactance related to base kVA.
Base kVA
%X = % reactance of rated kVA
Rated kVA
6000
XG1 = 15 %
3000
XG1 = 30%
XG2 = 30%
6000
XT = 5
6000
XT = 5%
Total reactance for fault F1
% X = XG1 || XG2
= 30 || 30
% X = 15
Rated current at base kVA
6000 103
I =
3 11 103
I = 315.29 A
100
ISC = I
%X
100
= 315.29
15
ISC = 2102 A
Fault kVA
100
i.e. S.C. kVA = Base kVA
%X
100
= 6000
15
= 40000 kVA
S.C. MVA = 40 MVA
For fault F2 , total reactance is
Total % X = (XG1 || XG2) + FT
= 15 + 5
% X = 20%
Rated current at base kVA
6000 103
I =
3 22 103
I = 157.64 A
100
ISC = I
%X
100
= 157.64
20
= 788.23 A
100 100
S.C. kVA = Base kVA = 6000
%X 20
= 30000 kVA
S.C. MVA = 30 MVA …Ans.
Ex. 1.9.7 : The plant capacity of a three phase generating station consists of two 15,000 kVA generators of
reactance 10% each and one 8000 kVA generator of reactance 18%. The generators are
connected to the station busbars from which load is taken through three 5000 kVA step up
transformers each having a reactance of 8%. Determine the maximum fault MVA which the circuit
breakers on (1) low voltage side and (2) High voltage side of transformer may have to deal with.
Soln. :
Fig. P. 1.9.7(a)
Fig. 1.9.7(c)
Fig. 1.9.8(a)
Soln. :
Select the base kVA as 12000
% reactance of generator 1 and 2 with respect to base kVA is,
12000
15 = 15%
12000
% X1 = 15% and % X2 = 15%
% reactance of generator 3 and 4 with respect to base kVA is,
12000
8 = 9.6%
10000
% X3 = 9.6% and % X4 = 9.6%
% reactance of busbar with respect to base kVA is,
12000
% XBB = 12 = 24%
6000
% X = 5.04 % …Ans.
100
Fault MVA = Base MVA Fig. 1.9.8(b)
% X
100 1
= 12000
5.04 1000
Ex. 1.9.9 : A generating station has three section bus-bars connected with a tie-bar through 6% reactors rated
at 5000 kVA. Each generator is of 5000 kVA with 12% reactance and in connected to one section
of bus-bar. Find the total steady input to a dead short circuit between the lines on one of the
sections of bus bar (i) with reactors and (ii) without reactors.
Soln. :
Fig. P. 1.9.9(a)
Let 5000 kVA be the base kVA.
As generators and reactors are rated at this kVA, therefore, their percentage reactance
remains the same.
(1) With reactors :
Suppose 3 phase short-circuit fault occurs on section 3 of the busbar (Point ‘F’). The
reactance diagram at the selected base kVA is,
% Total reactance from generator neutral upto fault point F.
% X = (9% + 6%) || 12%
15 12
=
15 + 12
% X = 6.67 %
100
Short circuit input = 5000
6.67
= 74,962 kVA
S.C. MVA = 74.962 MVA …Ans.
Fig. P. 1.9.9(b)
(2) Without reactors :
Suppose no reactors are used. Then for a fault on section 3, the total reactance upto the fault
point will be a parallel combination of the reactance of the three generators i.e.
Total reactance upto fault point F
= 12% || 12% || 12 %
12
%X =
3
% X = 4%
100
Short circuit kVA = 5000
4
= 1,25,000 kVA Fig. P. 1.9.9(c)
S.C. MVA = 125 MVA …Ans.
• When the reactors are connected in series with each feeder, they are known as feeder
reactors.
• Feeder reactor possesses following advantages :
(i) Occurance of fault on any feeder, do not disturb the bus bar voltage. So that the
tendency of generator to falls out of step is reduced considerably.
(ii) Fault on any one feeder does not affect the other feeders thus the continuity of supply
is maintained.
• But feeder reactors possesses following disadvantages :
(i) If any fault occurs on the bus bar then there is no protection provided for the
generators.
(ii) Since the reactors are all the time in circuit, there is constant power loss and voltage
drop in reactors even during normal condition.
(iii) The size of feeder reactors is directly dependent on number of generators connected to
the bus bar. Increase in the number of generators, size of feeder reactors has to be
increased to limit the short circuit currents within the feeder circuit breakers rating.
1.10.3 Bus Bar Reactors :
• In above two methods, there is considerable voltage drop and power loss even in normal
operating conditions. Thus to over come this disadvantage, reactors are connected with bus
bar. There are two methods of connecting reactors with bus bar :
(a) Ring system and
(b) Tie bar system.
(a) Ring system :
• In this system, sections are made of
generators and feeders and these
sections are connected to each other at a
common bus bar as shown in
Fig. 1.10.3(a).
• In this system normally one feeder is
fed from one generator. Fig. 1.10.3(a) : Ring system bus bar reactor
• Under normal operations, very small amount of current flows through the reactors,
therefore, voltage drop and power loss in the reactors is low.
• Thus reactors can be designed to have high ohemic value of resistance.
• In case of fault on any one feeder, only one generator feeds the fault.
• Thus heavy currents and voltage disturbances caused by a short circuit on a bus section
are reduced.
• However, bus bar reactors do not protect the generators connected to the faulty
sections.
(b) Tie bar system :
• This is the modification of the above
system. By adopting this system, the
voltage regulation between feeder
sections is improved than the above
system.
• This system is mostly suited to
generating stations where, frequently
new generators are being added. Fig. 1.10.3(b) : Tie-bar reactor for busbar
• In this system the generators are connected to the common bus bar through reactors
but the feeders are fed from the generator side of the reactors. Operation of this system
is similar to ring system.
• Additional advantage of this system is that, if the number of sections is increased, the
fault current will not exceed a certain value which is fixed by the size of individual
reactors. Thus switchgear designed to operate successfully on this limiting current will
continue operating without any harm for any increase in number sections. Thus no
modification is required.
Introduction :
An electrical power system is very complex. It needs some form of switchgear to make on and
off operations on generators, transformers, bus bars, Transmission lines etc. This on and off
operations may be manual (in case of normal condition) and automatically (in abnormal
condition). Therefore various types of switching equipments are incorporated in the power system.
These equipments are known as switchgears.
In earlier days a tumbler switch with a fuse unit was being used on large scale for switching
purpose.
Following are the switching/interrupting devices :
1. Load switches.
2. Fuses
3. Isolators.
4. Circuit breakers.
2.2 Circuit Interrupting Devices :
2.2.1 Fuses :
• Fuse is a simplest device, which breaks the circuit under abnormal condition i.e. it is only a
current interrupting device under fault condition and is not able to make or break the circuit
under normal condition.
• It is used for overload/short circuit protection in medium voltage (up to 33 kV) and low
voltage (up to 400V) installations.
Types of fuses :
Fuses are classified as :
• Semi enclosed or rewirable type.
• Totally enclosed or cartridge type.
• Dropout fuse.
• Expulsion fuse.
• H.R.C. fuse (High rupturing capacity).
• Striker fuse.
• Switch fuse.
2.2.2 Semi Enclosed or Rewirable Fuse :
• This fuse is most commonly used in house wiring and small current circuits.
• The fuse wire is fitted on porcelain ‘carrier’ which is fitted in the porcelain base.
• Whenever the fuse wire blows off due to overload or short circuit, the fuse carrier can be
pulled out, the new wire can be placed and service can be restored.
• The fuse wire may be of lead, tinned copper or an alloy of tin lead.
• The fuse wire should be replaced by a wire of correct size and of correct specifications,
otherwise it may prove dangerous with the possibility of the equipment burning out.
Rewirable fuses suffer from the following disadvantages :
3
• The filling material may be plaster of parries, chalk, quartz or marble dust.
• Filling material acts as an arc quenching and cooling medium when fuse element blows off
due to excessive heat generated under abnormal condition.
• Under normal conditions, the fuse element is at a temperature below its melting point.
Therefore, it carries the normal current without overheating.
• When a fault occurs, the current increases and the heat produced is sufficient to melt fuse
element. Fuse element melt before the fault current reaches its first peak value.
• Vaporisation of metal silver element chemically reacts with filling powder and results in the
formation of high resistance substance and helps in quenching the arc.
Advantages :
1. Speed of operation is very high.
2. Maintenance cost is practically zero.
3. They are capable of clearing high as well as low fault currents.
4. They do not deteriorate with age.
5. They provide reliable operation.
6. They are cheaper than other circuit interrupting devices of equal breaking capacity.
Disadvantages :
1. Heat produced by the arc may affect the associated switches.
2. They have to be replaced after each operation.
• Fig. 2.4.1 shows the typical time - current characteristic of a fuse, the current scale being in
multiples of the rated current and the time scale being logarithm.
• Generally this graph is plotted between prearcing time and prospective current.
• From above characteristic, it is clear that as the prospective current increases, the prearcing
time decreases i.e. fault current and operating is inversely proportional to each other.
• It is also clear that the characteristic becomes asymptotic and there is a minimum current
below which the fuse does not operate. This current is called as minimum fusing current.
• The operating time of the fuse for currents near the minimum fusing current is long.
2.5 Definitions :
The rated current of a fuse is the current it can carry without fusing.
The current at which the fuse element blows off (melts) is called the cut off current
(current ‘ic’) and is measured as an instantaneous value.
It is a MVA rating of the fuse corresponding to the largest prospective current, which the
fuse is capable of breaking or rupturing at the system voltage.
2.6 Isolators :
• Isolator (disconnecting switch) operates under no load condition. It does not have any
specified current breaking capacity or current making capacity. Isolator is not even used for
breaking load currents.
• Isolators are used in addition with circuit breakers, and are provided on each side of every
circuit breaker to provide isolation and enable maintenance.
• Isolators used in power system are of 3-pole type. 3-poles are identical one.
• Each pole consists of two or three insulators posts mounted on a fabricated support.
• The conducting parts are supported on the insulator posts. The conducting parts consist of
conducting copper or aluminium rod, fixed and moving contacts.
• During the opening operation the conducting rods swings apart and isolation is obtained.
• The simultaneous operation of 3-poles is obtained by mechanical interlocking of the three
poles. Further for all the three poles, there is a common operating mechanism.
• Sequence of operation while opening/closing a circuit.
While opening :
• Open the circuit breaker.
• Open isolator.
• Close earthing switch.
While closing :
• Open earthing switch
• Close isolator
• Close circuit breaker
Types of construction of isolators :
1. Vertical break type :
• These are outdoor air break disconnecting switches of the gang operated vertical break
type with rating of 7 kV and above.
• These isolators are designed for all outdoor applications including isolation of circuit
breakers, transformer banks and surge arresters and line sectioning.
• In case of any fault on the power system, the circuit breaker gets opened and after the fault
is been cleared. circuit breaker is again closed.
• Let the circuit breaker be closed when the any one ‘B’ terminal of 3 phase system with
respect to neutral be zero. In such case S.C. current in that same phase ‘B’ will have
maximum D.C. components and the waveform of current.
• It will be unsymmetrical about normal zero axis as shown in Fig. 2.8.1.
• This Fig. 2.8.1 shows the typical waveforms of short circuit in a phase having maximum D.C.
component.
• The generator is on no load before t = 0. Hence current is zero before t = 0, at t = 0 the short
circuit is applied and the current increases to a high value during the first quarter cycle.
The peak of the first major loop of current is ‘OM’ and this is the maximum instantaneous
value of current during the short circuit the instantaneous peak value of the first major
current loop is called the making current. In Fig. 2.8.1 the making current is ‘OM’. It is
expressed in kA peak.
• Now it may so happen that circuit breaker may close on existing fault. In such case current
increases to the maximum value at the peak of first current loop.
• The circuit breaker should able to close without hesitation as contacts touch. The circuit
breaker should be able to withstand the high mechanical force during. Such a closure. These
capabilities are provided by carrying out making current of a circuit breaker in the peak
value of first current loop of short circuit current (Ipk) which is the circuit breaker is capable
of making its rated voltage.
In above equation the factor 2 converts the rms value to peak value factor 1.8 takes into
account the doubling effect of short circuit current with consideration to slight drop in current
during the first quarter cycle.
• The circuit breaker contacts separates after few cycles. Since the relay and the operating
mechanism takes at least a couple of cycles.
• Let us assume that circuit breaker contacts separates at t = T1. The rms value of S.C. at the
time of the instant of contact. Separation is termed as breaking current.
• At the separation of contacts of the circuit breaker an arc is drawn between the contacts of
the circuit breaker an arc is drawn between the contacts the arc current varies sinusoidally
for a few cycles. At t = T2 a particular current zero the dielectric strength of the arc space
builds up sufficiently so as to prevent the continuation of arc. At the current zero this arc is
extinguishes and is been interrupted.
• Mean while what is happening to the voltage between contacts ? This voltage recorded is
shown in Fig. 2.8.1 before t = 0, the contacts are closed and the voltage across contacts
increases. In fact this voltage in the voltage drop across the arc during the arcing period.
• The voltage across arc is in the phase with current since the arc is resistive. The particular
waveform shape is a result of volt-ampere characteristics of arc-discharge to be studied later
during subsequent half cycle, the voltage across contacts increases due to increased arc
resistance.
• Finally at t = T2 when arc gets extinguished a high frequently voltage transient appear
across the contact which is superimposed on power frequency system voltage.
• This high frequency transient voltage tries to restrike the arc. Hence it is called as restriking
voltage and the power frequency system voltage appearing between the poles after arc
extinguish is called as recovery voltage.
• The transient recovery voltage appearing across the circuit breaker pole immediately after
the final arc interruption causes a high dielectric stresses between the circuit breaker
contacts.
• If the dielectric strength of the medium between the contacts does not build up faster than
the rate of rise of the time transient recovery voltage. The break down takes place-causing
reestablishment of the arc.
• If the dielectric strength of the contact builds up very rapidly so that it is more than the rate
of rise of transient recovery voltage. The circuit breaker interrupts the current successfully.
• The rate of rise of T.R.V. generally depends on the circuit parameters and the type of the
switching duty involved. The rate of the building upon dielectric strength depends upon the
effective design of interrupter and circuit breaker.
Mainly there are two factors responsible for the maintenance of arc between the contacts.
These are :
1. Potential difference between the contacts.
2. Ionised particles between the contacts.
1. Potential difference between the contacts :
• When the distance between two separated contacts is small, then the potential
difference between them is sufficient to maintain the arc.
• To extinguish the arc between the contacts, the contacts can be separated to such a
distance that potential difference becomes insufficient to maintain the arc.
• But when the system voltage is very high, this method is impracticable as a separation
of many meters may be required.
2. Ionised particles between the contacts :
• When the arc is struck between the contacts it surrounds by the ionized particles. These
particles between tend to maintain the arc.
• One way to extinguish the arc is to deionise the arc path.
• This may be achieved by cooling the arc or by bodily removing the ionised particles from
the space between the contacts.
• Further there are two methods of extinguishing the arc in circuit breaker.
1. High resistance method.
2. Low resistance or current zero method.
It is the voltage that appears across the contacts of the circuit breaker during the arcing
period.
• As soon as the contacts of the circuit breaker separate an arc is formed. The voltage that
appears across the contact during arcing period is called the arc voltage.
• Magnitude of arc voltage is low except for the period of fault current wave is at or near zero
position.
• At current zero position the arc voltage increase rapidly to peak value.
• This peak voltage causes to maintain the current flow in the form of arc.
• It is the normal frequency (50 Hz) r.m.s voltage that appears across the contact of the circuit
breaker after final arc extinction. It is approximately equal to the system voltage.
• Immediately after final current interruption the voltage that appears across the contacts has
a transient part.
• See Fig. 2.10.1 however these transient oscillations subside rapidly due to the damping
effect of system resistance and normal circuit voltage appears across the contacts.
• The voltage across the contact is of normal frequency and is known as recovery voltage.
(a)
(b)
2.11.2 Miniature Circuit Breaker (MCB), Moulded Case Circuit - Breakers (MCCB) :
• Miniature circuit breaker and moulded case circuit breaker have the features of a good
H.R.C. fuse and a good switch.
• These can be used for switching purpose under normal operating condition and a circuit
breaker under overloading and short circuit conditions.
• These are used extensively in low voltage domestic, commercial and industrial application.
They ensure high mechanical strength, high dielectric strength and virtually no ageing.
• It mainly consists of thermal relay inside it and the current carrying parts are made out of
electrolytic copper or silver alloy depending upon the rating of the breaker.
• All other metal parts are made up of nonferrous, non-rusting type materials.
• The tripping mechanism and the terminal contacts are assembled in a moulded case,
moulded out of the thermosetting powders.
• Magnetic and thermal sensing devices provided within the MCB actuate the tripping
mechanism.
• The arc chute has a special construction which increase the length of the arc by the magnetic
field created by the arc itself and the arc chute is so placed in the breakers that the hot
gases may not come in contact with any of the important part of the breakers.
Specifications :
Miniature circuit breakers are available in following ratings :
• Current rating : 5, 10, 15, 20, 30, 40, 50, 60, Amps
As well as 0.5, 1, 2, 2.5, 3, 3.5, 6, 7.5, 8, 10, 12, 35, 45, 55 Amp.
• Voltage rating : A C Voltage rating - 240 V/415.
D C Voltage rating - 50 V/110.
• Rupturing capacity : 3 kA at 50V (non-inductive) 1 kA at 110 V (non-inductive).
According to flow of forced air, air blast circuit breakers are classified as :
(i) Axial blast air circuit breakers.
(ii) Cross blast air breaker.
(i) Axial blast air circuit breakers :
(i) Dielectric properties dielectric strength of SF4 at atmospheric pressure is 2.35 times that of
air, it is 30% less than that of dielectric oil used in oil circuit breakers.
(ii) At higher pressure the dielectric strength of the gas increases. At pressure about
3 kgf/cm2 the dielectric strength of SF6 gas is more than that of dielectric oil.
The property permits smaller clearances and small size of equipments for the same kV.
1. Movable cylinder
2. Moving contacts
3. Fixed contacts
4. Nozzle
5. Fixed piston
6. Gas trapped in before compression
7. Compressed gas between (1) and (5)
8. Arc extinction by puffer action.
Fig. 2.12.2(a)
Advantages :
Vacuum circuit breaker have the following advantages :
(i) There are on file hazards.
(ii) They are compact in size.
(iii) They are reliable and have longer life
(iv) There is no generation of any type of gas during and after operation.
(v) They can interrupt any fault current. The outstanding feature of a VCB is that it can
break any heavy fault current perfectly just before the contacts reach the definite open
position.
(vi) Maintenance required is less.
(vii) Operation is quiet.
(viii) They can successfully withstand lightning surges.
(viv) They have low inertia and hence require smaller power for control mechanism.
Applications :
Vacuum circuit breakers are used where maintenance free circuit breakers should prove a
definite advantage like a remote area. These circuit breakers are being employed for outdoor
applications ranging from 22kV to 66kV and even for limited rating of say 60 to 100 MVA
3. Minimum oil Dielectric oil Preferred for The circuit breaking Used for metal
circuit 3.6 kV to 145 chamber is separate enclosed switchgear
breaker kV from supporting up to
chamber, small size, 36 kV, outdoors type
arc control device between
used. 36 and 245 kV. Now
supersede by SF6
circuit breaker.
4. Air blast Compressed 245 kV, Unit type Suitable for all EHV
circuit air (20-30) 35,000 MVA construction several applications, fast
breaker kg/cm2 up to 1100 units per pole, opening closing. Also
kV, 50,000 auxiliary for arc furnace duty.
MVA compressed air Now superseded by
system required SF6 C.B. for 145 kV,
and above.
5. SF6 circuit SF6 gas 145 kV, One interrupter pole Suitable for SF6
breaker 2 7500 MVA up to 245 kV switchgear and
single (5 kg/cm )
SF6 gas 245 kV, medium voltage
pressure
10,000 MVA, switchgear. EHV
puffer type (3 kg/cm2)
12 kV, 1000 circuit breaker.
SF6 GIS
MVA, Maintenance free
36 kV, 2000
MVA
420 kV, 40 kA
6. Vacuum Vacuum Preferred for Variety of designs, Suitable for a variety
circuit indoor long life, modest of application from
breaker switchgear maintenance 3.6 kV to 36 kV
rated up to 36
kV, 750 MVA
7. H.V.D.C. Oil or air 33 kV, 2 kA Artificial current Used for metallic
circuit blast zero by switching in return transfer
breaker capacitors breaker.
• Table 2.15.1 shows the summary of various types of circuit breakers, their voltage range,
quenching medium and design features.
• Table 2.15.2 shows the choice of circuit breakers for various voltage ranges.
Table 2.15.2 : Selection of circuit breakers
• Earlier oil circuit breakers were preferred in the voltage range of 3.3 kV-66 kV.
• Between 132 kV and 220 kV, either oil circuit breakers or air blast circuit breakers were
recommended.
• For voltages 400 kV and above, air blast circuit breakers were preferred.
• The present trend is to recommended vacuum or SF6 circuit breakers in the voltage range
3.3 kV-33 kV
• For 132 kV and above SF6 circuit breakers are preferred.
• Up to 1 kV air break circuit breakers are used.
• Air blast circuit breakers are becoming obsolets and oil circuit breakers are being
superseded by SF6 and vacuum circuit breakers.
The major duties under fault conditions, a circuit breakers is required to perform are :
1. It must be capable of opening the faulty circuit and breaking the fault current.
2. It must be capable of being closed on to a fault.
3. It must be capable of carrying fault current for a short time while another circuit breaker
( in series) is clearing the fault.
Corresponding to above-mentioned duties, the circuit breaker has three rating viz.
(1) Breaking capacity (2) Making capacity (3) Short time capacity.
• The peak value of the current (including D.C. component) during the first cycle of current
wave after the closer of circuit breaker is known as making capacity.
• There is always a possibility of closing or making circuits under short circuit conditions due
to auto recloser. The capacity of a breaker to “make” current depends upon its ability to
withstand and close successfully against the effect of electromagnetic forces.
• These forces are proportional to the square of maximum instantaneous current on closing.
Therefore making capacity is stated in terms of peak value of current instead of r.m.s. value.
• Making current is equal to the maximum value of a symmetrical current.
• To find this value we must multiply symmetrical breaking current by 2 to convert this
from r.m.s. to peak and then by 1.8 to include the “doubling effect” of maximum asymmetry.
Total multiplication factor becomes 2 1.8 = 2.55
• Therefore making capacity = 2.55 symmetrical breaking capacity.
It is the r.m.s. value of the current which the circuit breaker is capable of carrying
continuously at its rated frequency under specified conditions. The only limitation in this case is
the temperature rise of current carrying parts.
• Refer Fig. 2.17.1 in which circuit breaker is opened under fault condition.
Where, L = Inductance of system
C = System capacitance formed by cable insulation line separation etc.
• When the fault occurs circuit breaker contacts starts separating. Within this period i.e
before current interruption, the capacitance C is short circuited by the fault.
• Inductance L of the system is the only parameter by which the short circuit current through
the breaker is limited.
• Therefore the short circuit current will lag the voltage by 90 as shown in Fig. 2.17.2.
• Under this condition, the entire generator voltage appears across inductance L.
• When the contacts are opened and the arc finally extinguishes at some current zero, the
generator voltage e is suddenly applied to the inductance and capacitance in series.
• This L-C combination forms an oscillatory circuit and produces a transient of frequency.
1
fn =
2 LC
Which appears across the capacitor C and hence across the contacts of the circuit breaker.
• This transient voltage is known as restriking voltage and may reach an instantaneous peak
value twice the peak phase neutral voltage i.e. 2 Em.
ea = Arc voltage
• It is the rate of rise of restriking voltage (R.R.R.V.) which decides whether the arc will
restrike or not.
• If R.R.R.V. is greater than that of rise of dielectric strength between the contacts, the arc
will restrike.
• If R.R.R.V. is less than rate of increase of dielectric strength between the contacts of the
breaker the arc will fail to restrike.
Fig. 2.17.4 : Current and voltage wave form during current chopping
• This induces a lower prospective voltage to reignite the arc.
• Infact several chops may occur until a low enough current is interrupted which produces
insufficient voltage to restrike across the breaker gap. Consequently, the final interruption
of current takes place.
• When the fault occurs, the contacts of the circuit breaker are opened and an arc is struck
between the contacts.
• Since the contacts are shunted by resistance ‘R’, a part of the current flows through this
resistance.
• This results in decrease of arc current and an increase in the rate of deionisation of the arc
path.
• Consequently, the arc resistance is increased, this increase in arc resistance leads to a
further, increase in current through shunt resistance.
• This process continues until the arc current becomes so small that it fails to maintain the
arc. Now the arc is extinguished and circuit current is interrupted.
• The effect of shunt resistance R is to prevent the oscillatory growth of restriking voltage and
cause it to grow exponentially up to recovery voltage.
• This is being most effective when the value of R is so chosen (R = 0.5 L/C ) that the circuit
is critically damped.