Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 68

PROJECT

SUBJECT
Date

SN

1a

1b

1c

1.0

1.1

1.1.1
1.1.1a

2
2.1

2.1.1
2.1.2

2.1.1a
2.1.1b
2.1.2c

2.1.5

3.1.1
3.1.2

3.1.1
3.1.2

4
4.1

4.1

4.1a

3.1.11

4.1
4.1a

4.2
4.2a

5.1

5.1.1

7
7.1.7

7.1.7a

7.1.8

7.1.9

7.1.10.

7.1.10a

7.1.11

8.2

8.2.1
8.2.1a

8.3
8.3.1

8.6

8.6.2

8.6.3

8.6.4

9.1

10

10.1

10.2

10.3

10.4

10.5

12.0

12.1

12.1a

12.2b
12.3

12.4

12.5

12.6

12.7
: UDAAN @ LL ELE SERVICES BOQ OF LUDHIANA BTS NAHAR
: LT ELECTRICAL WORKS SUMMARY
15-Dec-21
1 - Vendor should visit site before sharing quote for this works,
2 - Only Supply item will be delivered after Project Manager Confirmation.
3 - Vendor Should Work on Site with Proper Safety, Like Safety Shoes, Helmet, Reflector & Safety Harness Etc. Else will not be allowed insid
for Execution.
4 - All the Material will be Installed as per approved make given in list of make sheet.
5 - Vendor will install the Reused Material first whihc the Project Team will provide from Store.*

Item Description

Supply, Installation and Commissioning of Wall mounted Panel of following MCCB capacity as incomer with Thermal Magnetic Trip Units with Shee
Box.

Should have Multi Function Digital Energy Meter.

1. With adjustable overload (Range 0.6 to 1.0) & fixed short-circuit setting) with phase indication & ON/OFF/ TRIP indication complete installation.
2. Should have Phase failure / reversal Protection/OV/UV/OC with GEC/Minilec/Siemens/ABB Controller.
3. With suitable size Spreader Bus Bar suitable to connect the cables at both Input & Output Terminals
4. Should have Type 1+ 2 SPD (TVSS) along with MPCB &
5. Should have 4 Nos of Bus Bars of suitable current ratings with terminal point for connecting the cables.
Breaker Make : Siemens / Schneider/ L & T/ Hager /Legrand & ABB
For other Accessories pls refer: Approved "List of Makes"- Tab

Supply, Installation and Commissioning of MCCB Breaker in Sheet Steal enclosure Box.

Approved Make : Siemens / Schneider/ L & T/ Hager /Legrand & ABB

Supply & Installation of 125 A 4P MCCB Breaker With Metal Enclosure

LT PANELS :

Supply, Installation and Commissioning of Wall mounted Panel of following MCCB capacity as incomer with Thermal Magnetic Trip U
Steel enclosure Box.

Should have Multi Function Digital Energy Meter.

1. With adjustable overload (Range 0.6 to 1.0) & fixed short-circuit setting) with phase indication & ON/OFF/ TRIP indication complete
2. Should have Phase failure / reversal Protection/OV/UV/OC with GEC/Minilec/Siemens/ABB Controller.
3. With suitable size Spreader Bus Bar suitable to connect the cables at both Input & Output Terminals
4. Should have Type 1+ 2 SPD (TVSS) along with MPCB &
5. Should have 4 Nos of Bus Bars of suitable current ratings with terminal point for connecting the cables.
Breaker Make : Siemens / Schneider/ L & T/ Hager /Legrand & ABB
For other Accessories pls refer: Approved "List of Makes"- Tab

Only Installation of 125 A 4P MCCB with Metal Enclosure


Repairing of 125 A 4P MCCB with Metal Enclosure, (Need to change Nob to operate the MCCB for ON n Off Purpose)
TOTAL FO

LT CABLES & ENDTERMINATIONS


Supply, Laying, Testing and Commissioning of stranded XLPE/PVC insulated, Armoured/Unarmoured/Flexible, Aluminium / Coppe
in tray / Hume pipe / in ready made trenches, with nylon cable ties / MS Clamps @ 600mm interval etc., as required. The cost of th
overlapping GI strip shall be included in the cost of installation.
Cable identification labels at both ends clearly mentioning the cable specs.
Supply, Installation, Testing and Commissioning of Compression type cable gland, aluminium lugs for aluminium cables / copper
cables, insulation tape, anti corrosive paste, brass clamps for gland earthing with 14 SWG copper wire to connect to nearest earth flat.
Insulation: XLPE 25Sqmm and above and Class A PVC below 25Sqmm
Inner sheath: Extruded PVC only for Multicore
Outer sheath: Extruded Type ST2 PVC with FLAME RETARDANT
Voltage grade:1100Volts
Armoured: Galvanized Steel strip/Wire for multicore
Non Magnetic Aluminium Wire/Strip for Single core
Gland type : Brass with nickel plated
Compression : Double compression 35 Sq.mm and above
Sealing Ring : Natural rubber for indoor, Neoprene for Outdoor
Only heavy duty cable ties should be used for cable dressing.
Only approved List of Makes should be used for all the line items given

XLPE Insulated & Steel Armoured Aluminium Conductor Cables

Supply & Installtion of 4 Core X 16 Sqmm (For LL Lighting DB 01 & 02 from LT Panel)
End terminations,

Supply & Installtion of 4 Core X 25 Sqmm (For 12 WAY TPN DB-01 (RP-01) WHICH WILL FEED TO HIGH BAY LIGHTHS
Only Installtion of 3.5 Core X 35 Sqmm (For Main Incoming Cable)
End terminations,

Supply & Installtion of 3 Core X 2.5 Sqmm Al Ar Cable, (Notes- For External Lighting Circuiting which is coming on boundary W
be fed from Cu Cable)

FRLS PVC Insulated & Flexible Copper Conductor cables (YY Type)

Supply & Installation of 3 Core x 10 Sq. mm, Cu cable (For Emg Ltg for LL DB-02)
End terminations

Supply & Installation of 3 Core x 6 Sq. mm, Cu Cable(For Emg Ltg for LL DB-01)
End terminations

Total for LT Cables and E


MCB DISTRIBUTION BOARDS (DB)

Supply, Installation, Testing and Commissioning of MCB Distribution board as per approved installation dwgs.
Wall mounted MCB DBs with MS wire way box on top / bottom & on sides. MCBs shall be rated for 10kA with current limiting featur
to be covered with blank plates. All out going ways shall be labelled & laminated.
Enclosure:1.2mm CRCA Sheet Steel, Powder Coated
Door : Single / Double Door
Protection : IP 42
Cable Entry : Top & Bottom
Bus bar : Shall be tinned Copper and 200% rating for UPS DB Neutral Link
MCB's : 10kA 'C' Curve for Lighting/Raw power & for UPS Distribution
Note:
1) Separate Earth bus/Neutral bus for each phase
2) Each Circuit shall have yellow ferrules with circuit number.
3) Accessories required for installation of DB's on Wall/Column/Gyp Board shall be considered
4) DB's shall be covered with powder coated (paint should match with DB Colour) wire ways all around and up to ceiling to receive inco

5) Laminated A3 OR A4 size DB. Sch. / SLD copy shall be pasted inside DB door (if not, should be displayed near the DB)
6) Safe shroud for Neutral link shall be provided
7) All the RCBO, MCB should fit in the DB, consider accordingly ETPN/7 segment or Flexi DBs
8) All DB marking to be done by vendor
9) Cables should be neatly routed in the DB knock outs using conduits/Glands/flexibles and should neatly tied/dressed.
10) All open knock outs should be closed using rubber grommets. No knockout should be left Open
11) A gap of 75mm to 100mm shall be maintained between the Wall and DBs (Suitable supports should be extended from Wall u
angles).

TPN RAW & UPS DB SET.


Supply & Installation of 8 Way - 4 Row Flexi MCB DB (Incomer+ Sub Incomer & Outgoing Modules) Set.
Incomer : 1No. 63A, 4P,MCB.
& 3Nos 32 A DP RCBO with 100mA with SI series.
Outgoing : 18 Nos 6-32A -10kA SP MCB of 'C' curve
(For LL Lighting DB 01-02)

Supply & Installation of 6 Way - 4 Row Flexi MCB DB (Incomer+ Sub Incomer & Outgoing Modules) Set.
Incomer : 1No. 63A, 4P,MCB.
& 3Nos 32 A DP RCBO with 100mA with SI series.
Outgoing : 12 Nos 6-32A -10kA SP MCB of 'C' curve
((For LL Lighting DB 03 & Emg Light - 01 & 02)

SPN RAW & UPS DB SET.


Supply Installation of 12Way SPN MCB DB (Incomer + Outgoing Modules) Set.
Incomer : 1No. 32A DP RCBO with 30mA sensitivity
Outgoing : 8 Nos of 10-32A -10kA SP MCB of C curve.

Total for MCB Dist


CIRCUIT MAINS

Circuit mains using 1.1kV grade PVC insulated PVC sheathed three core cables drawn in existing 2mm thick PVC conduit or in exi
Rates quoted shall include supply of cable and exclude conduits & other conduiting accessories. Circuit mains shall be measured from
the nearest point. All circuit terminations shall be provided with solder less crimping type copper sockets / lugs, ferrules indicating sou
side & load code on source side. There shall not be any joints in the circuits, only looping is allowed in terminal blocks & at points.
NOTE:
1) Costing of conduits & cable trays are excluded.
2) The number of wires drawn in each conduit shall be as per IS 694 code.
3) No different phases shall be drawn in same conduit
4) Conduit joints shall be done with threading proper accessories only
5) Cable looping should be by connectors only. NO CABLE JOINT ALLOWED
6) Use proper colour coded cables (Red, Yellow & Blue) for 3 core flex cables, If Easily Available else Update to Project M
Availibility.

Lighting Circuit RAW & Emg: (For Internal & External WH Highbay & Flood Light Wiring)
Supply & Installation of 3 C x 1.5 Sqmm FRLSH 1100V unarmoured double insulated flexible multicore cable for Lighting/Emergen
circuit. (FOR LIGHTING RAW CIRCUIT)

Lighting Circuit RAW & Emg: (For Internal WH Office, Hub, Canteen, Toilet etc Light Wiring)
Supply & Installation of 3 C x 2.5 Sqmm FRLSH 1100V unarmoured double insulated flexible multicore cable for Lighting/Emergen
circuit. (FOR LIGHTING UPS CIRCUIT)

Total fo
Switch Control

Switch Control
Supply, installation, Testing and Commissioning of switch installation . (This excludes the costing of conduits & cable tray)

Supply & fixing of 1x6A switch with 1 Module faceplate & Base box

Total fo
LIGHT FIXTURES (Supply in the Scope of Udaan or by Vendor)
Installation, Testing and Commissioning of Light fixtures and lamps with all accessories, fixing on the wall / ceiling/ false ceiling / susp
purlin with wooden blocks, screws, hardwares, suspended chain hooks, purlin clamps for high bay & midbay, supporting clamps fo
fixture, nuts, washers as required as per the site conditions (including the earthing of fixture). Cost includes all the supporting accessorie
for the complete Installations.
Light fixtures complete with accessories like driver, fixing clamps etc, (PF shall be >0.85 lag. )
Note : The make & the catalogue no. should be strictly followed or else should be approved by Project Manager.)
The electronic / Digital ballast shall be with THD between 6-8 %. & low loss copper ballast.
Lamp colour to be Cool day white which is 860/865 in Philips
LED burning hours: 50,000 hours, Fixture & Driver warranty: 5Years
surge protection >2kV.

Supply & Installation of LED Batten Light fixture with cover – 1 x 18/20W (lamp output – 2000 lumens) 5700- 6500˚K, cool day white.
Supply & Installation of IP65 standard compliant LED batten Light water proof fixture - 1 x20W ( Lamp output of 2000 lumens/ 6500˚K co
Waterproof for outside of fire door
Preferred Model : Havells Lumiline 18W- 2000 Lumens (polycarbonate body preferred) or Approved by Project Manager.

Supply & Installation of High bay 100W with lamp output of 14000 to 16000 Lumens, IP65 suitable fixture, 5700 to 6500 ˚K cool day
Models Preferred: Havells Baybrite Flare 100W, or Approved by Project Manager.

Supply & Installation of LED Flood Light 70/80W (lamp output - 8000-10000 lumens) Weather proof- suitable for outdoor type. (IP65)
Models Preferred: Havells JETA Compacto 30W, or Approved by Project Manager.

Supply & Installation of LED Flood Light 50W (lamp output - 6000-8000 lumens) Weather proof- suitable for outdoor type. (IP65)

Supply & Installation of LED Flood Light 70/80W (lamp output - 8500-10000 lumens) Weather proof- suitable for outdoor type. (IP65
Models Preferred: Havells JETA Compacto 70/80W, or Approved by Project Manager.

Supply & Installation of LED Flood Light 80W (lamp output - 8000-10000 lumens) Weather proof- suitable for outdoor type. (IP65)
Models Preferred: Havells JETA Compacto 50W, or Approved by Project Manager.

Total fo

Supply & Laying of following size 2mm thick rigid FRLS PVC conduits. Rate shall include necessary Bends, Collars, junction bo
saddles, screws, Flexibles, clamping / fixing arrangement.
NOTE:
1) Conduits running above false ceiling in multiples shall be supported by Slotted GI 'C' channel at distance not more than 0.5mtrs in
with spacers & saddles at an intervals of 0.5mtrs
2) Accessories shall includes Bends, Collars, junction boxes, Spacers, saddles, screws, Flexibles & clamps
3) Conduits shall be ISI marked.
4) The number of cables drawn in each conduit shall be as per IS 694 code.
5) No different phases shall be drawn in same conduit
6) Conduit joints shall be done with threading proper accessories only
7) Raw power & UPS power cable should not be drawn in same Conduit / Casing & capping.
8) All ways of Junction box should be closed with dummy cap if not used.

Supply & Installation of 20 mm dia PVC Conduit (White) FRLS


Only Installation of 25mm dia PVC Conduit (White)

Supply & Laying of following size 1.2mm thick rigid MS conduits. Rate shall include necessary Bends, Collars, junction boxes, S
saddles, screws, Flexibles, clamping / fixing arrangement.
NOTE:
1) Conduits running above false ceiling in multiples shall be supported by Slotted GI 'C' channel at distance not more than 0.5mtrs in
with spacers & saddles at an intervals of 0.5mtrs
2) Accessories shall includes Bends, Collars, junction boxes, Spacers, saddles, screws, Flexibles & clamps
3) Conduits shall be ISI marked.
4) The number of cables drawn in each conduit shall be as per IS 694 code.
5) No different phases shall be drawn in same conduit
6) Conduit joints shall be done with threading proper accessories only
7) Raw power & UPS power cable should not be drawn in same Conduit / Casing & capping.
8) All ways of Junction box should be closed with dummy cap if not used.

Supply & Instalation of MS conduit of 50mm dia.

Gripple support with fixing accessories with necessary clamps/ corner protection sheet to support from purlin/ MS Angles, (Mak
Indo Grip) (For All Services)

Only Installation of Loop end fixing No. 2 mm Gripple (Capable of taking 10 to 45 kg maximum) of 4 mtrs. Length including anchor
& complete requirement, (For Dock Flood & Highbay Light Hanging Support)
Supply & Installation of Loop end fixing No. 2 Gripple (Capable of taking 10 to 45 kg maximum) of 4 mtrs. Length including anchor
& complete requirement, (For High Bay Light Hanging Support)

MS WORK -Providing, Fabricating and Erecting, MS Fabricated Staircase/Foundatios/MS DOOR, ceiling support and other Misc wor
and drawings made available at All Heights inside the ware house . Includes one coat of red oxide primer + 2 Coats of Enamel Paint

Total for C

EARTHING

Supply & Installation of 1 Core x 6 Sq. mm FR copper flexible Green / Green+ Yellow colour Earthing Cable

Total f
MISCELLANEOUS ITEMS

Providing and fixing L.V. danger notice plate of 200 mm X 150 mm, made of mild steel, 2 mm thick, and vitreous enamelled white o
with inscription in single red Colour on front side as required.

Supply of movable Aluminium Scaffolding on rental basis usable upto 15 Meter working height- 1 month perion (31 days basis)
unloading at site in good usable condition (Project work)

Supply & Laying of 200 mm RCC Hume Pipe for Main Cable Laying, (If LL does not provide)

Supply & Installation of 12" H/D Ex. Fan with Louvar or Bird Nest Protection, (Installation includes Wall Opening with complete
with metal framing if required for Fan installation as per site condition))

Supply & Installation of 3 blade 1200mm ceiling Fan with electronic regulator Havells/CG/ Orient/Usha

Total for MISC


Lightening Protection System.

TECHNICAL SPECIFICATION-

Supply, Installation & commissioning of ESE type Lightning Protection - complete with the Lightning Air Terminal - Configured
material used to electrically isolate the panels shall be comprised of a base polymer which provides high Ozone & UV resistance w
strength of 24-38 kv/mm & ESE terminal shall withstand a minimum Switching Impulse Voltage of 500 KV tested as per NFC 17-10
EN 50164-1, EN 62305& IEC 16-1:1989 to be installed at the roof of and the centre of the building with the protection

Std. Protection Radius of 107 Mtr for 5mtrs mast

Std. Protection Radius of 65 Mtr for 5mtrs mast


L type Mast (G.I. 4 mtr minimum) for mounting the terminal & adaptor to mount the Air Terminal with Coupler/reducer, stray wires, C

Test Link Joint Kit in a IP 55 weather proof enclosure of suitable dimension and approved make & design.

Neutral Earthing: 'Supply, installation, testing & commissioning of MAINTENANCE FREE earthing system as per IS 3043:198
Electrode dual pipe consist of 3mtr long 77 mm dia outer pipe, 47 mm dia inner pipe, Terminal flat of 200mm x 50 x 10 mm, the en
processed with Hot Dip Galvanization, outer surface up to 100 microns and all inner surface Upto 300 microns, all inner annular space f
conductive and non-corrosive nature crystalline material, along with electrode Moisture Booster compound of 2 x 25 kg bags to fill sur
the time of installation. (Moisture Booster having its property of moisture retention, conduction and non – corrosive nature) . Also inclu
or PVC Chamber with top cover with lifting handle, complete .
Earth pit numbering to be done in black letters on yellow back ground inside the masonry chamber or PVC Chamber.
(LA - 2 Nos)
Distance between 2 Earth pit should be 6 Mtrs as per IS 3043:1987 standard

Lightning Strike Recorder / counter (6 digits display) of not resistible type in an IP 67 enclosure with the minimum sensitivity of 1500A
capacity of 220KA (8/20 micro second wave form) tested - Make Ellipse – LPS -France

Down Conductor 1C x 50sq.mm insulated copper flexible cable complete with end-termination & rigid PVC/ GI pipe as required at site,
withstand high impulse current of 110 KA make – Polycab / Havells /KEI

Total Fire & Light

G
Supply Install Supply Install
UOM Qty Remarks
Rate Rate Amt Amt

No

No
No
Mts 160
Nos. 4

Mts
Mts
Nos.

Mts 450

Mts 170
Nos. 2

Mts 55
Nos. 2
Set 2

Set 3

Set

2200
Mts.

1800
Mts.

Nos 38
Nos. 30

Nos. 15

Nos. 165

Nos. 46

Nos.

Nos.

Nos.

Mts. 3000
Mts.
Mts.

Nos.

Nos. 165

Kgs 250

Mts 250

Nos. 4

month 1

month 50

Nos 17

Nos

Nos.

Nos.
Set

Nos

Nos.

Nos

Mtrs
SN Item Description UOM Qty Supply Install Supply Install Remarks
Rate Rate Amt Amt

1.0 LT PANELS :
All Panels Should be as per Technical specifications & Power distribution scheme

Supply, installation, testing & commissioning of 3 Phase, 4 wire, 415 V, 50 Hz panels. The fabrication
shall be made with cold rolled annealed sheet with Machine pressing. The surface shall be rigorously
treated for derusting in 8 tank process with powder coating. The panel shall be totally enclosed metal
clad type with double gasketing with rubber / foam gasketing. The panel shall be off- white painted inside
and shall be having control directory pasted on the inside surface of the panel door. The panel shall be
suitable for mounting on existing trench and shall have cable entry provision from the top and bottom with
suitable alley as the case may be. The panel shall be tested for the same KA rating of the relevant highest
rating of breaker. All components shall be of approved make and shall have relevant IS/IEC approvals
(Fabrication, drawing, list of components and panel detail shall be got approved before fabrication). The
panel shall include base frame channel support. All complete as per relevant standard, technical
specification, SLD, data sheets and direction of Engineer-in-charge. The cost shall include factory
acceptance test & Site acceptance test

Indoor type LT Switchboards, Floor mounting type, Bottom/Top entry. Refer enclosed SLD for
component details.
Doors:2mm Body:2mm Gland Plate :3mm covers and partitions:1.6mm
IP class:IP55 for Indoor/IP65 with weather proof enclosure with top cover for outdoor
Bus bars: Electrolytic grade conductivity as per standard IS 5082
Bus bar Material: As per SLD
Bus bar supports: DMC/FRP/SMC
Bus bar joints: Shrouded/Tinned
Protection releases: As per SLD (Adjustable over current & short circuit unless otherwise specified)
Shade: Epoxy powder coated RAL 7032
Design: Modular type & Form 4B Construction
Cable entry: As per site condition

Bus bar insulation: Aluminium bus bars shall be bare with colour coding at the ends/Copper shall be bare
with colour coding at the ends/For Humidified areas the copper bus bars shall be coated with tin.

Note:
1. The Panel shall be fully as per the requirement of CEIG/Electrical Inspectorate/ EB authorities.

2. Auxiliary contactor to be provided along with auto-manual switch where ever required.

3. All Breakers both Incoming & Outgoing shall have LED 'ON / OFF / TRIP' indications without fail.
All MCB's should be with Indicating lamps
4. CTs shall be of cast resin /polycarbonate split core type only.
5. All doors to have double rubber/foam gasket with shutter assembly & door seating frame.
6. All AC feeders will have time delays of 0-60 Seconds.
7. All MCCBs of 250A and above for non-ups loads will be microprocessor based only and all UPS
Related panels shall be with thermal Magnetic releases only
8. All DLMs to be of dual source meters unless otherwise specified.
9. The current density for Aluminium busbars shall be 0.8 only.
10. The current density for Copper busbars shall be 1.6 only. Tinned copper

11. All UPS outgoing panels shall have neutral busbars double the size of phase & gland plates should be
of alluminium.Hooter to be provided in Main LT panel & same will be operated in case EB & DG Failure

12. All MCCB's shall have plug setting from (70 -100%) for < 250A & (40 - 100%) for > 250A

13. All ACB, MCCB's shall have 2 nos. NO + 2nos of NC Auxiliary contacts for BMS integration. All
Breakers should be monitored through BMS communication & necessary provision to be made at panel
level with terminal block provisions

14. All Lighting / RP and Lift panels shall have ELR with Rectangular CBCTfor incomer.
15. All test certificates must be provided immediately after commissioning.
16. SAFETY CERTIFICATE FOR THE PANELS SHALL BE PRODUCED FROM CEIG.Safety
Certificate for the panels shall be produced from CEIG
17. All meters shall be Digital type only.
18. ZHLS PVC copper wires shall be used for control wiring
19. Louvers shall be provided for all the bus bars chambers (Horizontal & Vertical) with mesh to meet IP
Requirement& Provision to be made to run fire suppression tube inside the panel & same needs to be
closed with rubber gasket
20. All ACBs shall confirm IS 13947-1/IEC 947-1 for general rules & IS 13947 rules & IS 13947-2/IEC
947-2 for Circuit breakers.
21.All breakers shall have spreaders of same make as make of breaker.
23. All vertical bus bars in bus bar alley shall have bottom supports.
24. Panel earthing strip should come out vertically on top/bottom of the panel to suit the site condition.
Double side earthing to be considered
25. Earthing bus shall be with green colour coding.
26. All MCCB should have RHOM(Rotary handle operating mechanism)
27. Door earthing's shall be provided for all doors with double side provision
28. Base frame shall be with each panel. The size shall be equal to each section.
29. Bi-metallic tape / washers to be used where ever copper & Aluminium are joined.
30. All breakers shall have flag indication for tripping.
31. The material of construction shall be CRCA sheet.

32. Live parts shall not be accessible after opening the door, Transparent acrylic sheet to be provided to
cover the same & busbar joints section shall be covered with PVC shrouds.

33. In any case Aluminium bus bars should not be connected directly to the breaker without spreaders.
34. Panel should be as per IEC-60439-2
35. All UPS panels should be with copper bus bar.
36. Panels should be provided with Lifting lugs/ Eye bolts for lifting the panel.
37. All the busbar bolts of 8.8 Grade should be tightened for Torque of 23N-m for 8mm, 45N-m for
10mm, 80N-m for 12mm bolt/nuts using Torque wrench.

38. 3 Point Locks (Front Single Door) and Cam Locks are Provided (Compartments) for Front Doors.

39. Special Retaining washers are provided for busbar chambers to avoid the falling of the bolts from door.
40. Panel Costing shall include base frame also wherever false floor is proposed.
41. 45 Deg bending construction to achieve the IP.
42. For viewing MCB Chambers Polycarbonate (Unbreakable & High Temperature withstanding) sheets
with glass frames to be used.

43. All PVC heat shrinkable sleeves should have temperature withstanding capacity of 105 degree Celsius.

44. All ACB & MCCB Power feeders should be connected with Busbars.LOTO System to be part of all
the panels & All panels shall be compatible with BMS integration for monitoring

45. Only resin cast C.T of suitable burden, class of accuracy, ratio and voltage shall be used as per the
SLD & Main LT panel should have simulation based display to indicate the distribution scheme

46. Space heater & thermostat to be provided in all the panels. LED lamps to be provided inside the lamps

1.1 Supply & Installation of MAIN LT PANEL (Ref to SLD) No.


1.1a Only Installation of MAIN LT PANEL (Ref to SLD) (Will use the old Pataudi LT Panel) No. 1 Will get it from Project WH
3 Nos of phase indicating lamps (LED type) each backed up with MCB and switch shall be provided for
a
Indication of R-Y-B
b ON/OFF/TRIP indicating lamps (LED type) each backed up with MCB

Phase Reversal Relay (Incoming Feeder): Incomer should have protection against phase reversal on
incoming side. This is to be achieved through Minilec/GEC Phase Reversal Relay with U/V and O/V
c
feature (HLV/D2) to be operated through Auxiliary Contactor (2NO+2NC); Hooter with Cancellation
(Accept/Reject) Push Buttons, Indication Lamps, Protective Fuses etc.

TVSS TPN Surge Suppressor Class B+C VAL MS320/3h Phoenix (Transformer Incoming Feeder Only)-
d
OBO/ Siemens/ABB/ GE/Hager
e ELR with CBCT of appropriate ratio and of Provok make (Each Incoming Feeder)
f CT operated Digital Multifunctional meter EM 6400 with RS 485 port intelligent panel meter.

The cost includes Transportation, unloading at site and shifting of panel to Electrical room using suitable
g
equipment/ Machine and installing at Electrical room as per Site Project Engineer/Manager's instruction

Pls Ref the SLD shared for details.

1.1 MAIN LT PANEL

A MAIN LT PANEL - Type #01 No.

B MAIN LT PANEL - Type #02 No.

C MAIN LT PANEL - Type #03 No.

D MAIN LT PANEL - Type #04 No.

1.2 UPS OUTPUT MCCB DB -Wall mounted panel

A UPS OUTPUT PANEL- Type 1 No.

B UPS OUTPUT PANEL- Type 2 No.

C UPS OUTPUT PANEL- Type 3 No.

D UPS OUTPUT PANEL- Type 4 No.

1.3 APFCR PANEL- STAND ALONE No.

1.4 Lighting & Raw power MCCB DB -Wall mounted panel

A Incomer : 1No. 125A, 4P,18kA MCCB- with RYB Indication with suitable Al Bus Bar
Outgoing : 12Nos. 63A 4P MCB of 'C' curve No.

B Incomer : 1No. 80A/ 100A, 4P,18kA MCCB- with RYB Indication with suitable Al Bus Bar
Outgoing : 12Nos. 40A/63A 4P MCB of 'C' curve No.

Supply, Installation and Commissioning of Wall mounted Panel of following MCCB capacity as incomer
with Thermal Magnetic Trip Units with Sheet Steel enclosure Box.

Should have Multi Function Digital Energy Meter.

1. With adjustable overload (Range 0.6 to 1.0) & fixed short-circuit setting) with phase indication &
ON/OFF/ TRIP indication complete installation.

2. Should have Phase failure / reversal Protection/OV/UV/OC with GEC/Minilec/Siemens/ABB


Controller.
1.5
3. With suitable size Spreader Bus Bar suitable to connect the cables at both Input & Output Terminals

4. Should have Type 1+ 2 SPD (TVSS) along with MPCB &

5. Should have 4 Nos of Bus Bars of suitable current ratings with terminal point for connecting the cables.

Breaker Make : Siemens / Schneider/ L & T/ Hager /Legrand & ABB

For other Accessories pls refer: Approved "List of Makes"- Tab

a 250 A 4P MCCB with 18kA No


b 160 A 4P MCCB with 18kA No
c 125 A 4P MCCB with 18kA No
d 100/63 A 4P MCCB with 18kA No

Supply, Installation and Commissioning of Manual operated 4 Pole Change Over switch in Sheet Steal
enclosure Box.
1.6
Approved Make : Siemens / Schneider/ L & T/ Hager /Legrand & ABB
a 250 A 4P No
b Only Installation of 160 A 4P COS No
c Supply & Installation of 125 A 4P COS No
d 100 A 4P COS No
e 63 A 4P COS No

Supply, Installation and Commissioning of MCCB Breaker in Sheet Steal enclosure Box.
1.7
Approved Make : Siemens / Schneider/ L & T/ Hager /Legrand & ABB

a 250 A - MCCB Breaker No


b Only Installation of 200 A - MCCB Breaker No
c 125 A - MCCB Breaker No
d 100 A - MCCB Breaker No
e 63 A - MCCB Breaker No
TOTAL FOR LT PANELS

2 LT CABLES & END TERMINATIONS

Supply, Laying, Testing and Commissioning of stranded XLPE/PVC insulated,


Armoured/Unarmoured/Flexible, Aluminium / Copper conductor, laid in tray / Hume pipe / in ready made
trenches, with nylon cable ties / MS Clamps @ 600mm interval etc., as required. The cost of the nylon tie
and overlapping GI strip shall be included in the cost of installation.

Cable identification labels at both ends clearly mentioning the cable specs.

Supply, Installation, Testing and Commissioning of Compression type cable gland, aluminium lugs for
aluminium cables / copper lugs for copper cables, insulation tape, anti corrosive paste, brass clamps for
gland earthing with 14 SWG copper wire to connect to nearest earth flat.

Insulation: XLPE 25Sqmm and above and Class A PVC below 25Sqmm
Inner sheath: Extruded PVC only for Multicore
Outer sheath: Extruded Type ST2 PVC with FLAME RETARDANT
Voltage grade:1100Volts
Armoured: Galvanized Steel strip/Wire for multicore
Non Magnetic Aluminium Wire/Strip for Single core
Gland type : Brass with nickel plated
Compression : Double compression 35 Sq.mm and above
Sealing Ring : Natural rubber for indoor, Neoprene for Outdoor
Only heavy duty cable ties should be used for cable dressing.
Only approved List of Makes should be used for all the line items given

2.1 XLPE Insulated & Steel Armoured Aluminium Conductor Cables

2.1.1 3.5 Core X 240 Sqmm. Mts


2.1.2 End terminations Nos.

2.1.3 Only Installtion of 3.5 Core X 185 Sqmm, (From DG to Udaan LT Panel) Mts 120 Will get it from Project WH
2.1.4 End terminations, (With Double Compression Gland) Nos. 2

2.1.5 3.5 Core X 150 Sqmm Mts


2.1.6 End terminations Nos.

Supply & Installtion of 3.5 Core X 120 Sqmm ( 120+20+30), (The Cable will be ordered after the
2.1.7 Mts 170
confirmation form Project Manager)
2.1.8 End terminations, (With Double Compression Gland) Nos. 6

2.1.9 3.5 Core X 95 Sqmm Mts


2.1.10 End terminations, (With Double Compression Gland) Nos.

2.1.11 Supply & Installtion of 3.5 Core X 70 Sqmm, (75), For 12 Way VTPN DB for Dock Leveller Mts 75
2.1.12 End terminations, (With Double Compression Gland) Nos. 2

2.1.13 Supply & Installtion of 3.5 Core X 50 Sqmm (20), For 8 Way VTPN DB for MHE Mts 20
2.1.13 Only Installtion of 3.5 Core X 50 Sqmm (20+25=45) Mts
2.1.14 End terminations, (With Double Compression Gland) Nos. 2

2.1.15 Supply & Installtion of 3.5 Core X 35 Sqmm (For MHE VTPN) Mts
2.1.16 End terminations, (With Double Compression Gland) Nos.

2.1.17 Supply & Installtion of 4 Core X 25 Sqmm (15+130+160=305) Mts 175


2.1.17a Only Installtion of 4 Core X 25 Sqmm (120) Mts
2.1.18 End terminations, (With Double Compression Gland toward LT Panel) Mts 6

Supply & Installtion of 4 Core X 16 Sqmm (150 (The Cable will be ordered after the confirmation
2.1.19 Mts 150
form Project Manager)

Only Installtion of 4 Core X 16 Sqmm (65+15+25+30+30+30=) (Use these Cable described below)
2.1.19 1 - 65 Meter for 8 WAY TPN RP DB SET - RPDB-02 Mts 195 Will get it from Project WH
2 - 15+ 25+30+30+30 for MHE from VTPN

2.1.20 End terminations Nos. 16

2.1.21 Supply & Installtion of 4 Core X 10 Sqmm (165) For MHE & TC Conveyor from VTPN Mts 165
2.1.21a Only Installtion of 4 Core X 10 Sqmm (10+18) (For MHE from VTPN) Mts
2.1.22 End terminations Nos. 4

2.1.23 Supply & Installtion of 4 Core X 6 Sqmm, Mts


2.1.24 End terminations Nos.

2.2 FRLS PVC Insulated & Flexible Copper Conductor cables (YY Type)

2.2.1 Only Installation of 4 Core x 16 Sq. mm, Cu Cable(20+20=40), For 20 KVA UPS I/O Mts 40 Will get it from Project WH
2.2.2 End terminations Nos. 8

2.2.3 Supply & Installation of 4 Core x 10 Sq. mm, Cu Cable, For 12 Way TPN DB Set of UPS DB - 02 Mts 180
2.2.4 End terminations Nos. 2

2.2.5 Only Installation of 4 Core x 6 Sq. mm, For 8 Way TPN DB Set of UPS DB - 01 Mts 20 Will get it from Project WH
2.2.6 End terminations Nos. 2

2.2.7 5 Core x 4 Sq. mm Mts


2.2.8 End terminations Nos.

2.2.9 5 Core x 2.5 Sq. mm Mts


2.2.10 End terminations Nos.

2.2.11 4 Core x 35 Sq. mm Mts


2.2.12 End terminations Nos.

2.2.13 4 Core x 25 Sq. mm Mts


2.2.14 End terminations Nos.

2.2.15 4 Core x 16 Sq. mm Mts


2.2.16 End terminations Nos.

2.2.17 Only Installation of 4 Core x 10 Sq. mm, Cu Cable Mts


2.2.18 End terminations Nos.

2.2.19 Supply & Installation of 4 Core x 6 Sq. mm (125) Mts


2.2.19 Only Installation of 4 Core x 6 Sq. mm, (15+15), Cu Cable Mts
2.2.20 End terminations Nos.

2.2.21 4 Core x 4 Sq. mm Mts


2.2.22 End terminations Nos.

2.2.23 3 Core x 16 Sq. mm Mts


2.2.24 End terminations Nos.

2.2.25 Supply & Installation of 3 Core x 10 Sq. mm, (170) For LL Emg Ltg DB-02 & 10 KVA Ups I/O Mts 170
2.2.25a Only Installation of 3 Core x 10 Sq. mm, (30+16=40) For 10 KVA Ups I/O Mts 46 Will get it from Project WH
2.2.26 End terminations Nos. 12

2.2.27 Supply & Installation of 3 Core x 6 Sq. mm, (70) For LL Emg Ltg DB-01 Mts 55
2.2.28 End terminations Nos. 2

2.2.28a Only Installation of 3 Core x 6 Sq. mm, (25) Mts

2.2.29 Supply & Installation of 3 Core x 4 Sq. mm, Mts


2.2.30 End terminations Nos.

2.2.31 1 Core x 16 Sq. mm Mts


2.2.32 End terminations Nos.

2.2.33 1 Core x 10 Sq. mm Mts


2.2.34 End terminations Nos.

2.2.35 1 Core x 6 Sq. mm Mts


2.2.36 End terminations Nos.

2.2.37 Supply & Installation of 6 Core x 2.5 Sq. mm (For DG Control) Mts 120
2.2.38 End terminations Nos. 2

2.2.39 Supply & Installation of 5 Core x 1.5 Sq. mm (For DG Control) Mts 250
2.2.40 End terminations Nos. 16

Total for LT Cables and End terminations

3 MCB DISTRIBUTION BOARDS (DB)

Supply, Installation, Testing and Commissioning of MCB Distribution board as per approved installation
dwgs.
Wall mounted MCB DBs with MS wire way box on top / bottom & on sides. MCBs shall be rated for
10kA with current limiting feature. Dummy ways to be covered with blank plates. All out going ways shall
be labelled & laminated.
Enclosure:1.2mm CRCA Sheet Steel, Powder Coated
Door : Single / Double Door
Protection : IP 42
Cable Entry : Top & Bottom
Bus bar : Shall be tinned Copper and 200% rating for UPS DB Neutral Link
MCB's : 10kA 'C' Curve for Lighting/Raw power & for UPS Distribution
Note:

1) Separate Earth bus/Neutral bus for each phase


2) Each Circuit shall have yellow ferrules with circuit number.
3) Accessories required for installation of DB's on Wall/Column/Gyp Board shall be considered

4) DB's shall be covered with powder coated (paint should match with DB Colour) wire ways all around
and up to ceiling to receive incoming circuits
5) Laminated A3 OR A4 size DB. Sch. / SLD copy shall be pasted inside DB door (if not, should be
displayed near the DB)
6) Safe shroud for Neutral link shall be provided
7) All the RCBO, MCB should fit in the DB, consider accordingly ETPN/7 segment or Flexi DBs
8) All DB marking to be done by vendor
9) Cables should be neatly routed in the DB knock outs using conduits/Glands/flexibles and should neatly
tied/dressed.

10) All open knock outs should be closed using rubber grommets. No knockout should be left Open

11) A gap of 75mm to 100mm shall be maintained between the Wall and DBs (Suitable supports
should be extended from Wall using C/ I MS angles).

3.1 MCCB/ VTPN DB (IP-43-) SET.


Supply & Installation of 12 Way VTPN MCCB DB. (For Dock Leveller 7 DB's)
3.1.1 Incomer : 1No. 125A, 4P,18kA MCCB, Set 1
Outgoing : 4Nos. 63A 10kA TP MCB of 'C' curve & 8Nos. 32A 10kA TP MCB of 'C' curve
Only Installation of 12Way VTPN MCCB DB.
3.1.1a Set
Incomer : 1No. 160A,
Supply & Installation of 8 Way VTPN MCCB DB. (For MHE)
3.1.2 Incomer : 1No. 160A, 4P,18kA MCCB, Set 1
Outgoing : 8Nos. 63A 10kA TP MCB of 'C' curve
3.1.2a Dismentalling of 8Way VTPN MCCB DB. Set

Supply & Installation of 6Way VTPN MCCB DB.


3.1.3 Incomer : 1No. 125A, 4P,18kA MCCB, Set
(Outgoing : 5Nos. 63A 10kA TP MCB of 'C' curve & Outgoing : 3Nos. 63A 10kA SP MCB of 'C' curve

Supply & Installation of 4 Way VTPN MCCB DB. (For 20 KVA & 10 KVA UPS)
3.1.4 Incomer : 1No. 100A, 4P,18kA MCCB, Set 2
Outgoing : 4Nos. 63A 10kA TP MCB of 'C' curve

TPN Lighting DB SET.


12Way - 4 Row Flexi MCB DB (Incomer+ Sub Incomer & Outgoing Modules) Set.
3.1.5 Incomer : 1No. 63A, 4P,MCB. Set
& 3Nos 32 A DP RCBO with 100mA with SI series.
Outgoing : 30 Nos 6-32A -10kA SP MCB of 'C' curve

8Way - 4 Row Flexi MCB DB (Incomer+ Sub Incomer & Outgoing Modules) Set.
3.1.6 Incomer : 1No. 63A, 4P,MCB. Set
& 3Nos 32 A DP RCBO with 100mA with SI series.
Outgoing : 18 Nos 6-32A -10kA SP MCB of 'C' curve

6Way - 4 Row Flexi MCB DB (Incomer+ Sub Incomer & Outgoing Modules) Set.
3.1.7 Incomer : 1No. 63A, 4P,MCB. Set
& 3Nos 32 A DP RCBO with 100mA with SI series.
Outgoing : 12 Nos 6-32A -10kA SP MCB of 'C' curve

TPN RAW & UPS DB SET.


Supply & Installation of 12Way - 4 Row Flexi MCB DB (Incomer+ Sub Incomer & Outgoing Modules)
Set.(For UPS DB-02)
3.1.8 Incomer : 1No. 63A, 4P,MCB. Set
& 3Nos 32 A DP MCB with 'C' Curve
Outgoing : 30 Nos 6-32A -10kA SP MCB of 'C' curve

3.1.8A Only Installation of 12 Way - 4 Row Flexi MCB DB (Incomer+ Sub Incomer & Outgoing Modules) Set. Set 1 Will get it from Project WH
Incomer : 1No. 63A, 4P,MCB

Supply & Installation of 8Way - 4 Row Flexi MCB DB


(Incomer+ Sub Incomer & Outgoing Modules) Set.
3.1.9 Incomer : 1No. 63A, 4P,MCB. Set
& 3Nos 32 A DP RCBO with 100mA with SI series.
Outgoing : 18 Nos 6-32A -10kA SP MCB of 'C' curve

3.1.9A Only Installation of 10 Way - 4 Row Flexi MCB DB (Incomer+ Sub Incomer & Outgoing Modules) Set. Set 4 Will get it from Project WH
Incomer : 1No. 63A, 4P,MCB,

6Way - 4 Row Flexi MCB DB (Incomer+ Sub Incomer & Outgoing Modules) Set.
Incomer : 1No. 63A, 4P,MCB.
3.1.10 Set
& 3Nos 32 A DP MCB with 'C' Curve
Outgoing : 12 Nos 6-32A -10kA SP MCB of 'C' curve

3.1.10a Only Installation of 6Way - 4 Row Flexi MCB DB (Incomer+ Sub Incomer & Outgoing Modules) Set. Set
Incomer : 1No. 63A, 4P,MCB.

Only Installation of 4Way - 4 Row Flexi MCB DB (Incomer+ Sub Incomer & Outgoing Modules) Set.
3.1.10b Set 1 Will get it from Project WH
Incomer : 1No. 63A, 4P,MCB.

SPN RAW & UPS DB SET.


18Way SPN MCB DB (Incomer + Outgoing Modules) Set.
3.1.11 Incomer : 1No. 63A, DP,MCB - 10kA of C- Curve. Set
Outgoing : 16 Nos of 10-32A -10kA SP MCB of C curve.
Supply Installation of 12Way SPN MCB DB (Incomer + Outgoing Modules) Set.
3.1.12 Incomer : 1No. 63A DP RCBO with 30mA sensitivity Set
Outgoing : 10 Nos of 10-32A -10kA SP MCB of C curve.
3.1.12A Only Installation of 12 Way SPN MCB DB (Incomer + Outgoing Modules) Set. Set
Supply Installation of 8Way SPN MCB DB (Incomer + Outgoing Modules) Set.
3.1.13 Incomer : 1No. 32A DP RCBO with 30mA sensitivity Set
Outgoing : 6 Nos of 10-32A -10kA SP MCB of C curve.
Only Installation of 6 Way SPN MCB DB (Incomer + Outgoing Modules) Set.
3.1.13a Set
Incomer : 1No. 32A DP RCBO with 30mA sensitivity
6Way SPN MCB DB (Incomer + Outgoing Modules) Set.
3.1.14 Incomer : 1No. 32A, DP,MCB - 10kA of C- Curve. Set
Outgoing : 4 Nos of 10-32A -10kA SP MCB of C curve.
3.1.14A Only Installation of 6 Way SPN MCB DB (Incomer + Outgoing Modules) Set. Set
4Way SPN MCB DB (Incomer + Outgoing Modules) Set.
3.1.15 Incomer : 1No. 32A, DP,MCB - 10kA of C- Curve. Set
Outgoing : 2 Nos of 10-32A -10kA SP MCB of C curve.
DP & TPN MCB WITH METAL ENCLOSURE SET.

3.1.16 Only Installation of 63A, DP,MCB - 10kA of C- Curve. With Metal Enclosure for UPS I/P. Set 3
3.1.17 Only Installation of 32A, SP/DP,MCB - 10kA of C- Curve. With Metal Enclosure for A/c Set 8
3.1.18 Only Installation of 25A, DP,MCB - 10kA of C- Curve. With Metal Enclosure for A/C Unit Etc. Set

3.1.19 Only Installation of 20A, DP,MCB - 10kA of C- Curve. With Metal Enclosure for UPS I/P, A/C Unit Set
Etc.

3.1.20. Supply & Installation of 63A, 4P,MCB - 10kA of C- Curve. With Metal Enclosure Set 9
for MHE.
Supply & Installation of 32A, 4P,MCB - 10kA of C- Curve. With Metal Enclosure
3.1.21 Set 8
for Dock Leveller

3.2 MCCBs / MCBs / RCBO ( Only supply to be considered.)

3.2.1 160A, 4P,18kA MCCB - TMD type with 0.6 to 1.0 Over load setting No.
3.2.2 125A, 4P,18kA MCCB - TMD type with 0.6 to 1.0 Over load setting No.
Only Supply of 100A, 4P,18kA MCCB - TMD type with 0.6 to 1.0 Over load setting, (For VTPN
3.2.3 No.
Incomer)
3.2.4 80A, 4P,18kA MCCB - TMD type with 0.6 to 1.0 Over load setting No.
3.2.5 63A, 4P,18kA MCCB - TMD type with 0.6 to 1.0 Over load setting No.

Only Supply of 63A 10kA 4P MCB of 'C' curve, (The Breaker will be ordered after the confirmation
3.2.6 No. 6
form Project Manager)
3.2.7 32/40A 10kA 4P MCB of 'C' curve No.
3.2.8 16/25A 10kA 4P MCB of 'C' curve No.

3.2.9 Only Supply of 63A 10kA TP MCB of 'C' curve No.


3.2.10 Only Supply of 32A 10kA TP MCB of 'C' curve No.
3.2.11 25/16A 10kA TP MCB of 'C' curve No.

Only Supply of 63A 10kA DP MCB of 'C' curve, (The Breaker will be ordered after the confirmation
3.2.12 No. 3
form Project Manager)
Only Supply of 32 A 10kA DP MCB of 'C' curve, (The Breaker will be ordered after the confirmation
3.2.13 No. 8
form Project Manager)
3.2.14 Only Supply of 20 / 25 A 10kA DP MCB of 'C' curve No.

3.2.15 32/25A 10kA SP MCB of 'C' curve No.


3.2.16 Only Supply of 32/25/20/16/10A 10kA SP MCB of 'C' curve No. 20
3.2.17 6A 10kA SP MCB of 'C' curve No.

3.2.18 63/40A 4P RCBO with 30mA sensitivity No.


3.2.19 32A 4P RCBO with 100mA sensitivity No.
3.2.20 20/16A 4P RCBO with 30mA sensitivity No.

3.2.21 Only Supply of 63/40A DP RCBO with 30mA sensitivity No.


3.2.22 Only Supply of 32A DP RCBO with 100mA sensitivity, No. 18
3.2.23 20/16A DP RCBO with 30mA sensitivity No.

Total for MCB Distribution Boards

4 CIRCUIT MAINS

Circuit mains using 1.1kV grade PVC insulated PVC sheathed three core cables drawn in existing 2mm
thick PVC conduit or in existing cable tray. Rates quoted shall include supply of cable and exclude
conduits & other conduiting accessories. Circuit mains shall be measured from respective DB to the
nearest point. All circuit terminations shall be provided with solder less
crimping type copper sockets / lugs, ferrules indicating source code on load
side & load code on source side. There shall not be any joints in the circuits,
only looping is allowed in terminal blocks & at points.

NOTE:

1) Costing of conduits & cable trays are excluded.


2) The number of wires drawn in each conduit shall be as per IS 694 code.
3) No different phases shall be drawn in same conduit
4) Conduit joints shall be done with threading proper accessories only
5) Cable looping should be by connectors only. NO CABLE JOINT ALLOWED
6) Use proper colour coded cables (Red, Yellow & Blue) for 3 core flex cables, If Easily Available
else Update to Project Manager of the Availibility.

4.1 Lighting Circuit: (For High Bay & Flood Light, Internal & External)
Supply & Installation of 3 C x 1.5 Sqmm FRLSH 1100V unarmoured double insulated flexible
4.1a multicore Copper cable. (The circuit terminations shall be provided with solder less crimping Mts.
type copper sockets / lugs, ferrules indicating source code on load side & load code on
source side.)

4.2 Lighting Circuit: (For Internal WH Office, Hub, Canteen, Toilet etc Light Wiring)
Supply & Installation of 3 C x 1.5 Sqmm FRLSH 1100V unarmoured double insulated flexible
4.2a multicore Copper cable. (The circuit terminations shall be provided with solder less crimping Mts. 650
type copper sockets / lugs, ferrules indicating source code on load side & load code on
source side.)

Only Installation of 3 C x 1.5 Sqmm FRLSH 1100V unarmoured double insulated flexible
multicore Copper cable. (The circuit terminations shall be provided with solder less crimping
4.2b type copper sockets / lugs, ferrules indicating source code on load side & load code on Mts. 400 Will get it from Project WH
source side.)

4.3 Emergency Lighting Circuit: (For Dock Flood Light, Internal)


Supply & Installation of 3 C x 1.5 Sqmm FRLSH 1100V unarmoured double insulated flexible
multicore Copper cable. (The circuit terminations shall be provided with solder less crimping
type copper sockets / lugs, ferrules indicating source code on load side & load code on Mts. 400
source side.)

4.4 Emergency Lighting Circuit: (For Internal WH Office, Hub, Canteen, Toilet etc Light Wiring)

Supply & Installation of 3 C x 1.5 Sqmm FRLSH 1100V unarmoured double insulated flexible
multicore Copper cable. (The circuit terminations shall be provided with solder less crimping Mts. 1200
type copper sockets / lugs, ferrules indicating source code on load side & load code on
source side.)

4.5 UPS POWER Circuit: for UPS -


Supply & Installation of 3 C x 1.5 Sqmm FRLSH 1100V unarmoured double insulated flexible
multicore Copper cable. (The circuit terminations shall be provided with solder less crimping
type copper sockets / lugs, ferrules indicating source code on load side & load code on Mts. 975
source side.)

4.6 RAW POWER Circuit: for Raw Power -


Supply & Installation of 3 C x 1.5 Sqmm FRLSH 1100V unarmoured double insulated flexible
multicore Copper cable. (The circuit terminations shall be provided with solder less crimping
type copper sockets / lugs, ferrules indicating source code on load side & load code on Mts. 850
source side.)

4.7 Circuit for HVAC units


Supply & Installation of 3 C x 2.5 Sqmm FRLSH 1100V unarmoured double insulated flexible
multicore Copper cable. (The circuit terminations shall be provided with solder less crimping Mts. 350
type copper sockets / lugs, ferrules indicating source code on load side & load code on
source side.)

4.8 Circuit for HVLS FAN.


Supply & Installation of 3 C x 4.0 Sqmm FRLSH 1100V unarmoured double insulated flexible
multicore Copper cable. (The circuit terminations shall be provided with solder less crimping Mts.
type copper sockets / lugs, ferrules indicating source code on load side & load code on
source side.)

4.9 Circuit for DG Battery Charging units


Supply & Installation of 3 C x 2.5 Sqmm FRLSH 1100V unarmoured double insulated flexible
multicore Copper cable. (The circuit terminations shall be provided with solder less crimping Mts. 120
type copper sockets / lugs, ferrules indicating source code on load side & load code on
source side.)

4.10. Circuit for HHD Charging Station


Supply & Installation of 3 C x 2.5 Sqmm FRLSH 1100V unarmoured double insulated flexible
multicore Copper cable. (The circuit terminations shall be provided with solder less crimping
type copper sockets / lugs, ferrules indicating source code on load side & load code on Mts. 75
source side.)

4.11 Circuit for EHPT & BOPT


Supply & Installation of 3 C x 2.5 Sqmm FRLSH 1100V unarmoured double insulated flexible
multicore Copper cable. (The circuit terminations shall be provided with solder less crimping Mts. 350
type copper sockets / lugs, ferrules indicating source code on load side & load code on
source side.)

4.12 Circuit for 16AMP. SOCKET FOR MAINTENANCE POINTS/ COOLER/ SHUTTER/ COFFEE
MACHINE/ OVEN ETC.
Supply & Installation of 3 C x 2.5 Sqmm FRLSH 1100V unarmoured double insulated flexible
4.12a multicore Copper cable. (The circuit terminations shall be provided with solder less crimping Mts. 1175
type copper sockets / lugs, ferrules indicating source code on load side & load code on
source side.)

Dismantling & Reinstallation of 3 C x 2.5 Sqmm FRLSH 1100V unarmoured double insulated
4.12b flexible multicore Copper cable. (The circuit terminations shall be provided with solder less Mts.
crimping type copper sockets / lugs, ferrules indicating source code on load side & load code
on source side.)

4.13 Circuit for 16AMP. SOCKET CCTV & IT RACKS.


Supply & Installation of 3 C x 2.5 Sqmm FRLSH 1100V unarmoured double insulated flexible
multicore Copper cable. (The circuit terminations shall be provided with solder less crimping Mts. 375
type copper sockets / lugs, ferrules indicating source code on load side & load code on
source side.)

4.14 Circuit for MHE/ CONVEYOR BELT 3 PHASE


Supply & Installation of 3 C x 6.0 Sqmm FRLSH 1100V unarmoured double insulated flexible
multicore Copper cable. (The circuit terminations shall be provided with solder less crimping Mts.
type copper sockets / lugs, ferrules indicating source code on load side & load code on
source side.)
4.14a End Termination Nos.

Total for Circuit Mains


5 Switch Control

5.1 Switch Control


Supply, installation, Testing and Commissioning of switch installation . (This excludes the costing of
conduits & cable tray)

5.1.1 Supply & fixing of 1x6A switch with 1 Module faceplate & Base box Nos 70
5.1.2 Supply & fixing of 2x6A switch with 2 Module faceplate & Base box Nos 15
5.1.3 Supply & fixing of 3x6A switch with 3 Module faceplate & Base box Nos 2
5.1.4 Supply & fixing of 4x6A switch with 4 Module faceplate & Base box Nos
5.1.5 Supply & fixing of 6x6A switch with 6 Module faceplate & Base box Nos
5.1.6 Supply & fixing of 8x6A switch with 8 Module faceplate & Base box Nos
Total for switch control

6 POWER RECEPTACLES

Supply, Installation, Testing and Commissioning of the following Modular/Industrial Switch, sockets with
modular front plate, and accessories as per the site conditions.
The quoted rate for power socket outlets shall include
a. Socket outlets - 5pin combi/intel sockets
b. Switches
c. 14SWG metal / PVC base boxes of same make with knockout on all sides
d. Front plate of required colours with accessories

Industrial type sockets shall be of Polycarbonate body with plug top. All switch / sockets shall be
provided with printed labels / stickers indicating source code. Colour code for UPS socket plates : Black or
Grey / Colour code for RP socket plates : White. All switch / sockets including front plate & frame which
will be mounted on the metal boxes shall have removable film coat to protect from scratches & paint
during installation. - Including Cabling with 3C x 1.5 Sqmm FRLS 1100V unarmoured double insulated
flexible multicore cable.

Note: Safety shutters to prevent accidental contact with live parts shall be provided. No indicator shall be
provided for switches
UPS Socket Face Plate Colour : Black/Grey
Raw Power Socket Face Plate Colour : White

6.1 With box

6.1.1 Supply & Installation of 1 No of 6/16A Combined Universal socket controlled by a 16A switch on RAW Nos. 110

6.1.1a Only Installation of 1 No of 6/16A Combined Universal socket controlled by a 16A switch on RAW Nos. 22 Will get it from Project WH

6.1.2 Supply & Installation of 1 No of 6/16A Combined Universal socket controlled by a 16A switch on UPS Nos. 20

6.1.2a Only Installation of 1 No of 6/16A Combined Universal socket controlled by a 16A switch on UPS Nos. 20 Will get it from Project WH

Supply & Installation of 2 Nos of 6/16A Combined Universal socket controlled by a 2x16A switch-RAW
6.1.3 Nos. 8
Power. 6 or 8 module Face plate & Base Box
Only Installation of 2 Nos of 6/16A Combined Universal socket controlled by a 2x16A switch - RAW
6.1.3a Nos. 30 Will get it from Project WH
Power. 6 or 8 module Face plate & Base Box

Supply & Installation of 2 Nos of 6/16A Combined Universal socket controlled by a 2x16A switch -
6.1.4 Nos. 39
UPS Power. 6 or 8 module Face plate & Base Box
Only Installation of 2 Nos of 6/16A Combined Universal socket controlled by a 2x16A switch - UPS
6.1.4a Nos. 9 Will get it from Project WH
Power. 6 module Face plate & Base Box

Only Installation of 3 Nos of 6/16A Combined Universal socket controlled by a 2x16A switch - 8
6.1.4 Nos. 2 Will get it from Project WH
module Face plate & Base Box on UPS

1x6/16A Combined Universal socket with 16A switch- 3 module Face plate & Base Box. (Weather
6.1.5 Nos.
Proof) For Crate Wash Area

6.1.6 Supply & Installation of 1x6/16A Combined Universal Internation socket with 16A SP MCB, of C Nos. 8
Curve - 3 module Face plate & Base Box. (For EHPT Charging Points).

Supply & Installation of 1x6/16A Combined Universal socket with 16A SP MCB, of C Curve - 3
6.1.7 Nos. 2
module Face plate & Base Box. (For HHD Charging Points).

Supply & Installation of 1x6/16A Combined Universal socket with 16A SP MCB, of C Curve - 3
6.1.8 Nos. 4
module Face plate & Base Box. (For 1.0 Tr. A/c).

Total of Power Receptacles

7 LIGHT FIXTURES (Supply in the Scope of Udaan or by Vendor)

Installation, Testing and Commissioning of Light fixtures and lamps with all accessories, fixing on the
wall / ceiling/ false ceiling / suspension from the purlin with wooden blocks, screws, hardwares, suspended
chain hooks, purlin clamps for high bay & midbay, supporting clamps for rack area light fixture, nuts,
washers as required as per the site conditions (including the earthing of fixture). Cost includes all the
supporting accessories which required for the complete Installations.

Light fixtures complete with accessories like driver, fixing clamps etc, (PF shall be >0.85 lag. )

Note : The make & the catalogue no. should be strictly followed or else should be approved by Project
Manager.)

The electronic / Digital ballast shall be with THD between 6-8 %. & low loss copper ballast.
Lamp colour to be Cool day white which is 860/865 in Philips
LED burning hours: 50,000 hours, Fixture & Driver warranty: 5Years
surge protection >2kV.

7.1.1 Supply & Installation of LED Batten Light fixture with cover – 1 x 18/20W (lamp output – 2000 Nos. 100
lumens) 5700- 6500˚K, cool day white.

7.1.1a Only Installation of LED Batten Light fixture with cover – 1 x 18/20W (lamp output – 2000 lumens) Nos.
5700- 6500˚K, cool day white.
Preferred Model : Havells Lumiline 18W- 2000 Lumens (polycarbonate body preferred) or Approved by
Project Manager.

7.1.2 Installation of LED fixture with cover – 1 x 18/20W with Occupancy Sensor (lamp output – 2000 lumens) Nos.
5700- 6500˚K, cool day white.
Preferred Model : Havells to confirm the model & type (polycarbonate body preferred), or Approved by
Project Manager.

7.1.3 Supply & Installation of IP65 standard compliant LED batten Light water proof fixture - 1 Nos. 25
x20W ( Lamp output of 2000 lumens/ 6500˚K cool day light) Waterproof for outside of fire door

Preferred Model : Havells Magnum Retro with 18W photon ultra tube (polycarbonate body preferred) or
Approved by Project Manager.

Only Installation of 36/40W Recess Mounted 2ftx2ft LED Light Fixture. (lamp output - 4200
7.1.4 Nos.
lumens/6500 K cool day light),
Models Preferred: Havells Venus Neo 42W, or Approved by Project Manager.

Installation of 36/40W Recess Mounted 2ftx2ft LED Light Fixture with Occupancy Sensor. (lamp output -
7.1.5 Nos.
4200 lumens/6500 K cool day light)
Models Preferred: Havells Venus Neo PIR 34W, or Approved by Project Manager.

7.1.6 Installation of 12W DLED Mini Downlighter. 1200 lumens/6500˚K cool day light Recess mounted fixture Nos.
Models Preferred: Havells INTEGRA 12W, or Approved by Project Manager.

Supply & Installation of High bay 100W with lamp output of 14000 to 16000 Lumens, IP65 suitable
7.1.7 Nos.
fixture, 5700 to 6500 ˚K cool day white.

Dismantling & Reinstallation of Landlord High bay 100W with lamp output of 14000 to 16000
7.1.7a Lumens, IP65 suitable fixture, 5700 to 6500 ˚K cool day white. (The Existing LL Lights are out of Nos.
Order approx 7 Nos which will replaced with good one of LL, Interchange will take place)

Models Preferred: Havells Baybrite Flare 100W, or Approved by Project Manager.

Installation of LED Flood Light 30W (lamp output - 4000 lumens) Weather proof- suitable for outdoor
7.1.8 Nos.
type. (IP65)
Models Preferred: Havells JETA Compacto 30W, or Approved by Project Manager.

Supply & Installation of LED Flood Light 50W (lamp output - 6000 lumens) Weather proof- suitable for
7.1.9 Nos.
outdoor type. (IP65)
Only Installation of LED Flood Light 50W (lamp output - 6000 lumens) Weather proof- suitable for
7.1.9a Nos. 14 Will get it from Project WH
outdoor type. (IP65)
Only Installation of LED Flood Light 70W (lamp output - 6000 lumens) Weather proof- suitable for
7.1.9a Nos. 25 Will get it from Project WH
outdoor type. (IP65)
Dismentaling & Installation of LED Flood Light 50W (lamp output - 6000 lumens) Weather proof-
7.1.9b Nos.
suitable for outdoor type. (IP65)
Models Preferred: Havells JETA Compacto 50W, or Approved by Project Manager.

Installation of LED STREET Light 15/20/25W (lamp output - 1600 TO 3000 lumens) Weather proof-
7.1.10 Nos.
suitable for outdoor type. (IP65)
Models Preferred: Havells ENDURA PEARL, or Approved by Project Manager.

7.1.11 Installation of LED B22 type 9W Lamp(lamp output - 900 to 1100 lumens) Nos.
Models Preferred: Havells, or Approved by Project Manager.

7.1.12 Supply of Rechargeable BEEMER 50 Rechargeable LED Torch LHEXAOPFUN1G005 (5W Nos.
Rechargeable -Li-Ion 3000mA )

Models Preferred: Havells BEEMER 50 - LHEXAOPFUN1G005, LED B22 type 9W Lamp

Total for Light fixtures

8 CABLE TRAYS for HV, MV & LV, Electrical Services.

Vendor should arrange the Ladders, speciallised machineries if required to perform the given job,
Udaan will not provide any costing additionally.

Supply and installation of following sizes of Ladder type PreGalvanized cable trays of 1.6 mm thickness
and 50mm high for supporting cables including bends, tees & reducers and including all labour and
materials, as per approved drawings, specifications of this tender and directions of Engineer-in-charge.
Supports Shall be provided at every 1500mm or as per Site Condition confirmed by Project
Manager.

The cost of 8mm SWG to be included in the cost of the cable tray. Trays shall be With one run of
(8mm SWG GI Wire) GI Wire to the cable tray sides. The cost of supports (bottom supports,
Threaded rod ) are inclusive.

For 50mm Cable tray GI strip not required, instead 2Runs of 8mm GI wires to be used for the Cable
tray and earthed at regular intervals.

Need to do the Tapping with Blue Colour for Electrical Services at the interval of 3 Meter.

8.1 Perforated Type

8.1.1 750 x 50mm Size Mts.

8.1.2 600 x 50mm Size Mts.

8.1.3 450 x 50mm Size with Cover Mts.


8.1.4 450 x 50mm Size without Cover Mts.

8.1.5 Supply & Installation fo 300 x 50mm Size Cable Tray with Cover, (Installation cost includes Mts. 10
necessary Support except Gripple for Cable Tray)
8.1.6 300 x 50mm Size without Cover Mts.

8.1.7 Supply & Installation fo 200 x 50mm Size Cable Tray Cover Only Mts.
Only Installation of 200 x 50mm Size Cable Tray, (For Ele. Services) , (Installation cost includes
8.1.8 Mts. 280 Will get it from Project WH
necessary Support except Gripple for Cable Tray)

8.1.9 Supply & Installation of 100 x 50mm Size with Cover Mts.
Only Installation of 100 x 50mm Size Cable Tray, (Installation cost includes all necessary Support
8.1.9a Mts. 160 Will get it from Project WH
except Gripple for Cable Tray)

Supply & Installation of 50 x 50mm Size Cable Tray, (Installation cost includes all necessary Support
8.1.11 Mts. 20
except Gripple for Cable Tray)
Dismantling & Reinstallation of 50 x 50mm Size Cable Tray, (Installation cost includes necessary
8.1.11a Mts.
Support except Gripple for Cable Tray)

8.1.13 Supply & Installation of 50 x 25mm Size Cable Tray, (For Ele. Services) Mts.
8.1.13a Only Installation of 50mm x 10mmx 2mm size GI C- Channel with all accesseries. Mts.

Supply & Laying of following size 2mm thick rigid FRLS PVC conduits. Rate shall include
8.2 necessary Bends, Collars, junction boxes, Spacers, saddles, screws, Flexibles, clamping / fixing
arrangement.
NOTE:

1) Conduits running above false ceiling in multiples shall be supported by Slotted GI 'C' channel at
distance not more than 0.5mtrs intervals. OR else with spacers & saddles at an intervals of 0.5mtrs

2) Accessories shall includes Bends, Collars, junction boxes, Spacers, saddles, screws, Flexibles & clamps

3) Conduits shall be ISI marked.


4) The number of cables drawn in each conduit shall be as per IS 694 code.
5) No different phases shall be drawn in same conduit
6) Conduit joints shall be done with threading proper accessories only
7) Raw power & UPS power cable should not be drawn in same Conduit / Casing & capping.
8) All ways of Junction box should be closed with dummy cap if not used.

8.2.1 Supply & Installation of 25mm dia FRLS PVC Conduit (White) FRLS Mts. 1200
8.2.1A Dismantling & Installation of 25mm dia FRLS PVC Conduit (White) FRLS Mts.

8.2.2 Supply & Installation of 20mm dia PVC Conduit (White) FRLS Mts.
8.2.2a Only Installation of 25mm dia (White) Mts.

8.2.3 25mm dia (Black/Grey) Mts.

8.2.4 Supply & Installation of 25mm dia (Ivory colour) Casing & Capping Mts. 200
as per ISI Marked as per IS 14927

Supply & Installation of 50mm dia (Ivory colour) Casing & Capping
8.2.5 Mts. 50
as per ISI Marked as per IS 14927

Supply & Laying of following size 1.2mm thick rigid MS conduits. Rate shall include necessary
8.3
Bends, Collars, junction boxes, Spacers, saddles, screws, Flexibles, clamping / fixing arrangement.
NOTE:

1) Conduits running above false ceiling in multiples shall be supported by Slotted GI 'C' channel at
distance not more than 0.5mtrs intervals. OR else with spacers & saddles at an intervals of 0.5mtrs

2) Accessories shall includes Bends, Collars, junction boxes, Spacers, saddles, screws, Flexibles & clamps

3) Conduits shall be ISI marked.


4) The number of cables drawn in each conduit shall be as per IS 694 code.
5) No different phases shall be drawn in same conduit
6) Conduit joints shall be done with threading proper accessories only
7) Raw power & UPS power cable should not be drawn in same Conduit / Casing & capping.
8) All ways of Junction box should be closed with dummy cap if not used.

8.3.1 Supply & Instalation of MS conduit of 50mm dia. Mts.

8.3.2 Supply & Instalation of MS conduit of 25mm dia. Mts. 20

8.4 Cable tray for Networking & FSS, (for Low Current)

Supply and installation of following sizes of PreGalvanized -perforated cable trays of 1.6mm thickness
and 50mm high for supporting cables including bends, tees & reducers and including all labour and
materials, as per approved drawings, specifications of this tender and directions of Engineer-in-charge.

1. Gripple Supports Shall be provided at every 1500mm or as per Site Condition confirmed by
Project Manager.
2. The cost of supports like MS angles/ C- Channels/ Hi-Tech Threaded to be included except
Gripple Hanging wire robes which is considered as separate line item.
3. If installation done under the RCC roof, then tray support with hi-tech threaded rods/ MS plates
& anchor fasteners (cost is inclusive of the cable tray).

Need to do the Tapping with Orange Colour for ELV Services at the interval of 3 Meter.

8.4.1 300 x 50mm Size with Cover Mts.


8.4.2 300 x 50mm Size without Cover Mts.

8.4.3 Supply & Installation of 200 x 50mm Size Cable Tray Cover Only Mts.
8.4.4 Only Installation of 200 x 50mm Cable Tray Mts.

8.4.5 Supply & Installation of 100 x 50mm Size Cable Tray Cover Only Mts.
Only Installation of 100 x 50mm Cable Tray , (Installation cost includes necessary Support except
8.4.6 Mts. 425 Will get it from Project WH
Gripple for Cable Tray)

8.4.7 Supply & Installation of 50 x 50mm Size with Cover Mts.


Supply & Installation of 50 x 50mm Size Cable Tray, (Installation cost includes necessary Support
8.4.7 Mts. 450
except Gripple for Cable Tray)
8.4.8 Only Installation of 50 x 50mm Size Cable Tray Mts.

8.4.9 Supply & Installation of 50 x 25mm Size Cable Tray Mts.


8.4.9a Only installation of 50mm x 10mmx 2mm size GI C- Channel with all accesseries. Mts.
8.4.10 25mm x 10mmx 1.6mm size GI C- Channel (AP points fixing) Mts.

8.5 Supply & Laying of following size 2mm thick rigid FRLS PVC conduits. Rate shall include necessary
Bends, Collars, junction boxes, Spacers, saddles, screws, Flexibles, clamping / fixing arrangement.
NOTE:

1) Conduits running above false ceiling in multiples shall be supported by Slotted GI 'C' channel at
distance not more than 0.5mtrs intervals. OR else with spacers & saddles at an intervals of 0.5mtrs

2) Accessories shall includes Bends, Collars, junction boxes, Spacers, saddles, screws, Flexibles & clamps

3) Conduits shall be ISI marked


4) The number of cables drawn in each conduit shall be as per IS 694 code.
5) Raw power & UPS power cable should not be drawn in same Conduit / Casing & capping.
6) All ways of Junction box should be closed with dummy cap if not used.

8.5.1 100mmx50mm Wiring Ducts Slotted Rectangular without Cover Screw PVC- Light Gray Mts.

8.5.2 50mmx50mm Wiring Ducts Slotted Rectangular without Cover Screw PVC- Light Gray Mts.

8.5.3 100mm dia 2mm thick Heavy duty GI pipe. Mts.

Gripple support with fixing accessories with necessary clamps/ corner protection sheet to support
8.6
from purlin/ MS Angles, (Make - Gripple, Indo Grip) (For All Services)

8.6.1 Supply & Installation of Loop end fixing No. 1.5 mm Gripple (Capable of taking 10 to 30 kg Nos.
maximum) of 15 mtrs. Length including anchor fasteners, studs & complete requirement

Supply & Installation of Loop end fixing No. 1.5 mm Gripple (Capable of taking 10 to 30 kg
8.6.2 Nos. 940
maximum) of 13 mtrs. Length including anchor fasteners, studs & complete requirement

Supply & Installation of Loop end fixing No. 1.5 mm Gripple (Capable of taking 10 to 30 kg
8.6.3 Nos.
maximum) of 10 mtrs. Length including anchor fasteners, studs & complete requirement

Supply & Installation of Loop end fixing No. 1.5 mm Gripple (Capable of taking 10 to 30 kg
8.6.4 Nos.
maximum) of 8 mtrs. Length including anchor fasteners, studs & complete requirement

Only Installation of Loop end fixing No. 1.5 mm Gripple (Capable of taking 10 to 30 kg maximum)
8.6.4a Nos.
of 8 mtrs. Length including anchor fasteners, studs & complete requirement

Dismenalling & Reinstallation of Loop end fixing No. 2 Gripple (Capable of taking 10 to 30 kg
8.6.4b Nos.
maximum) of 8 mtrs. Length including anchor fasteners, studs & complete requirement

Loop end fixing No. 1.5 mm Gripple (Capable of taking 10 to 30 kg maximum) of 6 mtrs. Length
8.6.5 Nos.
including anchor fasteners, studs & complete requirement

Supply & Installation of Loop end fixing No. 1.5 mm Gripple (Capable of taking 10 to 30 kg
8.6.6a Nos. 100
maximum) of 4 mtrs. Length including anchor fasteners, studs & complete requirement

Only Installation of Loop end fixing No. 1.5 mm Gripple (Capable of taking 10 to 30 kg maximum)
8.6.6b Nos. 300 Will get it from Project WH
of 4/6/8/10/13 mtrs. Length including anchor fasteners, studs & complete requirement

Only Installation of Loop end fixing No. 1.0 or 2.00 mm Gripple (Capable of taking 10 to 25 kg
8.6.6c maximum) of 4 mtrs. Length including anchor fasteners, studs & complete requirement. (For High Bay Nos.
Ligh Hanging)

18 SWG/1.2mm GI hanging wire to be used for CCTV/AP points C-channels supports with U clamps.
8.6.7 Kgs
Cost includes U-clamps. Ref the image given herewith.

Supply & Installation of 8mm dia Hitech threaded rod / 1.2mm thick 25mm C- channel /
25mmx25mmx1.2mm thick MS square Tube - MS epoxy painted support with 2 coats of anti rusting
8.6.8 Kgs 100
primer with fixing accessories like nuts & washer.(Only for additional work apart from Cable tray/CCTV
supports/ Drop down supports if any)

Total for CABLE TRAYS

9 EARTHING

Body Earthing: Supply, installation, testing & commissioning of MAINTENANCE FREE earthing system
as per IS 3043:1988 with with Earthing Electrode dual pipe consist of 3mtr long 48 mm dia outer pipe, 25
mm dia inner pipe, Terminal flat of 30 x 10/ 12 x 12mm, the entire construction processed with Hot Dip
Galvanization, outer surface up to 100 microns, and all inner surface 300 microns, all inner annular space
filled with highly conductive and non-corrosive nature crystalline material, along with electrode Moisture
Booster compound of 2 x 25 Kg bags to fill surround the pipe at the time of installation. (Moisture Booster
having its property of moisture retention, conduction and non-corrosive nature). Also include PVC
Chamber or brick masonry chamber with concrete Slab or Checkers Plate for top cover and lifting handle,
9.1 Nos. 7
complete.

Earth pit details to be displayed near earthpit using a Post mount Earth pit Label Board...
Earthpit NO/Connected To/Tested Date/Ohmic Value/Due Date should be displayed as per the
sample image attached. Size of the board : 150mmx300mm
(For DG /Servo/UPS & Panel Common Electrical Body Earthing)
Distance between 2 Earth pit should be 6 Mtrs as per IS 3043:1988 standard or as per Site Condition with
Project Manager Approval.
Neutral Earthing: 'Supply, installation, testing & commissioning of MAINTENANCE FREE earthing
system as per IS 3043:1988 with Earthing Electrode dual pipe consist of 3mtr long 88 mm dia outer pipe,
48 mm dia inner pipe, Terminal flat of 200mm x 50 x 10 mm, the entire construction processed with Hot
Dip Galvanization, outer surface up to 100 microns and all inner surface Upto 300 microns, all inner
annular space filled with highly conductive and non-corrosive nature crystalline material, along with
electrode Moisture Booster compound of 2 x 25 kg bags to fill surround the pipe at the time of installation.
(Moisture Booster having its property of moisture retention, conduction and non – corrosive nature) . Also
9.2 include PVC Chamber or brick masonry chamber with concrete Slab or Checkers Plate for top cover and Nos. 7
lifting handle, complete.

Earth pit details to be displayed near earthpit using a Post mount Earth pit Label Board...
Earthpit NO/Connected To/Tested Date/Ohmic Value/Due Date should be displayed as per the
sample image attached.
(DG / Servo Neutral Earthing)
Distance between 2 Earth pit should be 6 Mtrs as per IS 3043:1988 standard or as per Site Condition with
Project Manager Approval.

9.3 Supply & Installation of 1 Core x 35 Sq. mm FR copper flexible Green / Green+ Yellow colour Earthing Mtrs 50
Cable

9.4 Supply & Installation of 1 Core x 16 Sq. mm FR copper flexible Green / Green+ Yellow colour Earthing Mts 100
Cable

9.5 Supply & Installation of 1 Core x 10 Sq. mm FR copper flexible Green / Green+ Yellow colour Earthing Mts 200
Cable

Supply & Installation of 1 Core x 6 Sq. mm FR copper flexible Green / Green+ Yellow colour Earthing
9.6 Mts 600
Cable

9.7 1 Core x 4 Sq. mm FR copper flexible Green / Green+ Yellow colour Earthing Cable Mts

9.8 EARTH STRIPS

GI/Cu earth strips on cable tray or below ground as per site condition. All Cu. Strips shall be run in pvc
heat shrinkable sleeve & mounted on insulation mounts. Cost of civil works shall be included for strips
laid below ground. Including connection/ terminating with nut, bolt, spring, washer etc. as required.
Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm.
Joints to be welded for GI and brazing for copper strips.
9.8.1 Supply & Installation of 8 SWG GI Wire (Will be running 2 Run on Ele. Services Cable Tray) Mts. 500
9.8.1A Only Installation of 8 SWG GI Wire (for DB earthing's) Mts.

9.8.2 Supply & Installation of 25 x 3mm GI Earth flat Body Earthing (Elec DB Body Earthing) Mts. 50
9.8.2a Only Installation of 25 x 3mm GI Earth flat Body Earthing (Elec DB Body Earthing) Mts. 50 Will get it fro Project WH.

9.8.3 25 x 6mm GI Earth flat Body Earthing Mts.

9.8.4 25 x 3mm Cu Earth flat with shrink-wrapped sleeve Neutral Earthing Mts.

9.8.5 40 x 6mm Cu Earth flat with shrink-wrapped sleeve Neutral Earthing Mts.

Supply & Installation of Busbar of 300mm length made out of 25 x 3 mm GI. strip with drill holes of M8
9.8.6 at 25mm interval mounted on insulators along with Test Link option with Enclosure- Color- Nos. 6
Siemens Grey

Supply & Installation of Busbar of 300mm length made out of 25 x 3 mm GI. strip with drill holes of M8
9.8.7 Nos.
at 25mm interval mounted on insulators along with Test Link option with Enclosure- Color- Siemens Grey

Supply & Installation of Earthing Test Link Joint Kit in a IP 55 weather proof enclosure of suitable
9.8.8 Nos 10
dimension and approved make & design.

Total for EARTHING

10 MISCELLANEOUS ITEMS

Only Supply of 1.1 KV grade nominal 2.0 mm +/- 10% thick insulated Synthetic Mat of 2x1 Meter,
conforming to IS 15652: 2006 and meeting the requirements of IS 5216 (Part1,2&3), IS 8437, IEC-479
10.1 Nos 4
Pub-1, along-with suitable adhesive/ chemibound, Pu resin, waterproofing compound and sealing material
as per in service recommendation.

Only fixing of shock treatment chart duly framed required both in English/ Hindi & Local Language in the
10.2 Nos. 1 Will get it from Project WH
region for treating person suffering due to electric shock suitable to mount on wall.

Supply Installation of FLY CATCHER: Std - Model-POINEER (Product Dimensions: 61 x 16 x 36 cm ;


10.3 Nos. 18
4.6 Kg Item part number: FL-02) or Wellberg. (Old Material whichever is available in stock.)

Only Installation of FLY CATCHER: Std - Model-POINEER (Product Dimensions: 61 x 16 x 36 cm ;


10.3a Nos. 4 Will get it from Project WH
4.6 Kg Item part number: FL-02) or Wellberg.

Providing and fixing L.V. danger notice plate of 200 mm X 150 mm, made of mild steel, 2 mm thick, and
10.4 Nos. 10
vitreous enamelled white on both sides, and with inscription in single red Colour on front side as required.

10.5 Supply of Rubber hand gloves suitable for below voltage


a 11KV Pairs
b 1.1KV Pairs

Supply and Erection of Micro controller based technology Sequential Controller with LCD digital
display in Metal Enclosure continue to show run ac status, set time, run time, ac manual or auto mode,
10.6 Nos.
should controls 2 to 6 AC units. Automatic changeover timer for 2/3/4/ 6AC (Single & three phase) Can
set 1 hr to 12 hrs program. Make: Dynamic Microtech.

10.7 As built drawings:


Supply and fixing of Single line diagram chart & As Built Drawing whose Soft Copy will be provided
by us needs to be inside double layer of transparent acrylic sheet with ss studs - A1/ A0 size suitable to LS
mount on wall.

Supply of movable Aluminium Scaffolding on rental basis usable upto 15 Meter working height- 1 month
10.8 Month 1
perion (31 days basis) with loading & unloading at site in good usable condition (Project work)

Supply of movable Aluminium Scaffolding on rental basis usable upto 10Meter working height- 1 month
10.90 Month
perion (31 days basis) with loading & unloading at site in good usable condition (IT/CCTV requirement)

Supply of Boom/Scissor lift/Cherry picker with Operator on rental basis usable upto 15Meter working
10.10. Month
height- 1 month perion (31 days basis) with loading & unloading at site in good usable condition

Supply of Silent DG set with all safety breakers on wheel (S1 category- usabel for 24/7 for Project
10.11 purpose) on rental basis 1 month period (31 days basis) with loading & unloading at site in good usable Month 1
condition

Diesel For DG Set as per Site Consumption while Execution, (Need to Submit the Diesel Bill.)
10.12 Litre 250
(Considering Approx Consumtion)

Total for MISCELLANEOUS

11 Fire Protection & Lightening Protection


Supply & installation Fire Retardant seals & Supply & coating of Fire retardant paints as per the site
11.1 requirement meeting the safety IS / IEC standard.
Vertical Fire seal should have the load bearing capacity.
11.1.1 Supply & Installation of Sealing of Cables as per the identified detail below:-
HT /LT Cables sealing with approved Fire seal at identified places as per site condition (Product
11.1.2 description Hilti CP-620/ Birla 3M product) : Nos 1
LT Panel room cable Entry point opening / Compressor Room cable Entry opening at Wall/ DG panel
room Out going cable exit point/ (with 300x200 size)

11.1.3 MDP Panel /DB Cables entry sealing with approved Fire seal at identified places (Product description Nos
Hilti CP-620 or Birla 3M product):

11.2 Supply & coating of Fire retardant paint for External & internal cables at identified places.

11.2.1 Cable Coating Internal Area top/Bottom cable entry with quoting for 2 Mtrs length at identified area Bucket 1
(Product description Hilti CP-678/ Birla 3M product)

11.2.2 Cable Coating (exterior, near DG, Panel room, and cable entries) at identified areas (Product description Bucket
Hilti CP-679A/ Birla 3M product)

12.0 Lightening Protection

TECHNICAL SPECIFICATION-

Supply, Installation & commissioning of ESE type Lightning Protection - complete with the Lightning Air
Terminal - Configured as an Insulation material used to electrically isolate the panels shall be comprised of
a base polymer which provides high Ozone & UV resistance with a di-electric strength of 24-38 kv/mm &
12.1
ESE terminal shall withstand a minimum Switching Impulse Voltage of 500 KV tested as per NFC 17-102
, UNE 21-186, EN 50164-1, EN 62305& IEC 16-1:1989 to be installed at the roof of and the centre of the
building with the protection

12.1a Std. Protection Radius of 107 Mtr for 5mtrs mast Nos.

12.2b Std. Protection Radius of 65 Mtr for 5mtrs mast Nos.

L type Mast (G.I. 4 mtr minimum) for mounting the terminal & adaptor to mount the Air Terminal with
12.3 Set
Coupler/reducer, stray wires, Clamps etc

12.4 Test Link Joint Kit in a IP 55 weather proof enclosure of suitable dimension and approved make & design. Nos

Neutral Earthing: 'Supply, installation, testing & commissioning of MAINTENANCE FREE earthing
system as per IS 3043:1987 with Earthing Electrode dual pipe consist of 3mtr long 77 mm dia outer pipe,
47 mm dia inner pipe, Terminal flat of 200mm x 50 x 10 mm, the entire construction processed with Hot
Dip Galvanization, outer surface up to 100 microns and all inner surface Upto 300 microns, all inner
annular space filled with highly conductive and non-corrosive nature crystalline material, along with
electrode Moisture Booster compound of 2 x 25 kg bags to fill surround the pipe at the time of installation.
12.5 Nos.
(Moisture Booster having its property of moisture retention, conduction and non – corrosive nature) . Also
include concrete Slab or PVC Chamber with top cover with lifting handle, complete .
Earth pit numbering to be done in black letters on yellow back ground inside the masonry chamber or PVC
Chamber.
(LA - 2 Nos)
Distance between 2 Earth pit should be 6 Mtrs as per IS 3043:1987 standard

Lightning Strike Recorder / counter (6 digits display) of not resistible type in an IP 67 enclosure with the
12.6 minimum sensitivity of 1500A & maximum capacity of 220KA (8/20 micro second wave form) tested - Nos
Make Ellipse – LPS -France

Down Conductor 1C x 50sq.mm insulated copper flexible cable complete with end-termination & rigid
12.7 PVC/ GI pipe as required at site, suitable to withstand high impulse current of 110 KA make – Polycab / Mtrs
Havells /KEI

Total Fire & Lightning Protection

13 Supply & Installation of FANS with necessary Plug tops & Chicken Mesh

Supply & installation of Almonard/Crompton/Havells 18 Inch Air Circulator Wall Fan Green ( 450 mm
13.1 Nos
) Industrial Fan Heavy Duty with necessary supports and fittings & including MS support work.

Only installation of Almonard/Crompton/Havells 18 Inch Air Circulator Wall Fan Green ( 450 mm )
13.1a Nos 10 Will get it from Project WH
Industrial Fan Heavy Duty with necessary supports and fittings & including MS support work.

Complete Repairing of Almonard/Crompton/Havells 18/24 Inch Air Circulator Wall Fan Green
13.1b ( 450/600 mm ) Industrial Fan Heavy Duty with necessary supports and fittings & including MS support Nos
work.

Supply and installation of Almonard/Crompton/Havells 24 Inch Air Circulator Wall Fan Green ( 600
13.2 mm ) Industrial Fan Heavy Duty with necessary supports and fittings & chicken mesh jali on front & back Nos
including MS support work.

Supply & installation of Almonard/Crompton/Havells 18 Inch Air Circulator Pedestal Fan Green ( 450
13.3 mm ) Industrial Fan Heavy Duty with necessary supports and fittings & chicken mesh jali on front & back Nos
including MS support work.

Only installation of Almonard/Crompton/Havells 18 Inch Air Circulator Pedestal Fan Green ( 450
13.3a mm ) Industrial Fan Heavy Duty with necessary supports and fittings & chicken mesh jali on front & back Nos 4 Will get it from Project WH
including MS support work. (If it is in dismatled condition)

Supply & installation of Almonard/Crompton/Havells 24 Inch Air Circulator Pedestal Fan Green ( 600
13.4 mm ) Industrial Fan Heavy Duty with necessary supports and fittings & chicken mesh jali on front & back Nos 10
including MS support work. (If it is in dismatled condition)

Supply and installation of Almonard/Crompton/Havells 18" Heavy Duty Exhaust Fan 1400 RPM 230 V
13.5 Nos
with wall opening, Finishing & necessary supports and fittings & louvers /Bird nest protection.

Only installation of Almonard/Crompton/Havells 12" Heavy Duty Exhaust Fan, 230V (Installtion
13.6 includes wall opening, Finishing & necessary Metal supports and fittings & louvers /Bird nest Nos 6 Will get it from Project WH
protection.

13.7 Supply & installation of Exhaust Fan 300mm for Toilet with Louvers. Havells/CG/ Orient/Usha Nos 4
13.7a Only installation of Exhaust Fan 300mm for Toilet with Louvers. Nos 4 Will get it from Project WH

13.8 Only installation of 3 blade 1200mm ceiling Fan with electronic regulator Havells/CG/ Orient/Usha Nos 2 Will get it from Project WH

Supply & installation of 400mm wall mounted fan with swipe option ( 400 mm ) with required
13.9 Nos 6
Havells/CG/ Orient/Usha
Only installation of 300/400mm wall mounted fan with swipe option ( 400 mm ) with required
13.9a Nos 22 Will get it from Project WH
Havells/CG/ Orient/Usha

Total FANS

14 Transportation

32 feet closed Truck with Lock & Key facility - Loading & unloading of material as per the site
14.1 requirement (From New Project WH to Gorakhpur), (in Vendor Scope) LS

22 feet closed Truck with Lock & Key facility - Loading & unloading of material as per the site
14.2 LS
requirement (From New Project WH to Gorakhpur), (in Vendor Scope)

14.3 Packing of old Material in Store in Bubble wrap for all Material before transportation. Lot

14.4 Un-Skilled Man power Support (Loading/ unloading/ HK) days 6

Repairing & Maintenance work of Main LT Panel, (The Vendor will share the Bifurcation of expences,
15 Nos 1 0 150000
which he will be charging for Repairing & maintenance of existing Panel)

16 Safety Supervisor with Safety PPE Kit as per site requirement, Month 1

Miscellaneous Electrical Work. (By Default) The Vendor will Share the details for Extra Material/ Work
17 Lot 1 0 75000
which he will be done in maintenance & repairing on the instruction of the project Manager. (OPTIONAL)

18 Only Installation of 10 KVA UPS by OffCom Lot

19 Only Installation of 6 KVA UPS by OffCom Lot

20 Black or White Spray Paint by Berger iPaint - 400ml (Or any Make which is Easy Available) Lot 2

21 Supply & Laying of 200mm Hume Pipe. (For DG Cable Pulling) Mtr
Servo Stablizer BOQ of Ludhiana BTS Nahar
Sl.No
A

Vendor-Gravity/
Payment terms-30 days
Leadtime-4-5 weeks
Freight-Inclusive
GST Extra
Servo Stablizer BOQ of Ludhiana BTS Nahar
DESCRIPTION
Servo Stabilizer
3 phase Oil cooled
Supply, Installation, Testing and Commissioning of Oil Cooled Servo Stabilizer of:3phase, 415V , 50 Hz
output with suitable switch gears. It should have O/L, S/C, U/V, OV, single Phase Prevention &  TVSS/Surge
protection, phase failure indication &tripping with inbuilt Manual bypass option.  Input range from 295V to
500V
Transformer Oil Inclusive
125 KVA (Rate as per ARC)
Packing cost
Total

Vendor-Gravity/
Payment terms-30 days
Leadtime-4-5 weeks
Freight-Inclusive
GST Extra
Unit Qty Cost Installation Total

No 1
Project
Subject
Date

SL no

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.8

1.9
1.10

1.11

1.12

1.13

1.14

1.15

1.16

1.17

Vendor should adhere with all the points applicable. If any deviation, should be clarified at the initial stage itself

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19

1
2
3
4

General Notes
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
: UDAAN @ HVCA SERVICES BOQ OF PANIPAT 30K OF MITTAL
: HVAC WORKS SUMMARY
13-Aug-21
Vendor should visit site before sharing quote for this works
Description

HVAC UNITS

Supply & Installation, testing & commissioning of split air-conditioning with indoor unit comprising evaporator coil, fan and
motor, controls and insulated drain pan enclosed in a powder coated sheet metal enclosure, outdoor unit comprising of Scroll /
rotary type compressor, condenser coil, corded remote , pre-filter, fan and motor, controls, enclosed in powder coated sheet
metal cabinet. Pressure testing and commissioning of the air-conditioning system with topping up of R410a Refrigerant is part
of the scope. Unit shall be suitable for operation on 230 V+/- 10%, 50 Hz AC supply.
Required Refrigerant Supply & top up is part of Vendor scope. Vendor should consider as part of his costing.
Capacities shall be as follows:

Supply , Installation, Testing & Commissioning of 3 star rated of 0.75 TR split AC Unit which includes gas charging, Voltage
Stablizer, 3 Mtr copper piping, 5mtr of control cable, with indoor Stand & Condenser platform.

Supply , Installation, Testing & Commissioning of 3 star rated of 1.0 TR split AC Unit which includes gas charging, Voltage
Stablizer, 3 Mtr copper piping, 5mtr of control cable, with indoor Stand & Condenser platform.

Supply , Installation, Testing & Commissioning of 3 star rated of 1.5 TR split AC Unit which includes gas charging, Voltage
Stablizer, 3 Mtr copper piping, 5mtr of control cable, with indoor Stand & Condenser platform.

Supply , Installation, Testing & Commissioning of 3 star rated of 2.0 TR split AC Unit which includes gas charging, Voltage
Stablizer, 3 Mtr copper piping, 5mtr of control cable, with indoor Stand & Condenser platform.
(Place an order of this A/C after Confirmation from Saquib)

Supply , Installation, Testing & Commissioning of 3 star rated of 3.0 TR split AC Unit which includes gas charging, Voltage
Stablizer, 3 Mtr copper piping, 5mtr of control cable, with indoor Stand & Condenser platform.

Servicing, installation, Gas Charging with nitrogen Testing, commissioning along with indoor & out door Stand of existing
split AC units of 0.75 TR including Refrigerent R134a/410a supply & gas charging)

Servicing, installation, Gas Charging with nitrogen Testing, commissioning along with indoor & out door Stand of existing
split AC units of 1.0 TR including Refrigerent R134a/410a supply & gas charging)

Servicing, installation, Gas Charging with nitrogen Testing, commissioning along with indoor & out door Stand of existing
split AC units of 1.5 TR including Refrigerent R134a/410a supply & gas charging)

Servicing, installation, Gas Charging with nitrogen Testing, commissioning along with indoor & out door Stand of existing
split AC units of 2.0 TR including Refrigerent R134a/410a supply & gas charging)
Servicing, installation, Gas Charging with nitrogen Testing, commissioning along with indoor & out door Stand of existing
Cassette AC units of 1.5 TR including Refrigerent R134a/410a supply & gas charging)

Supply and Erection of Micro controller based technology Sequential Controller with LCD digital display in Metal Enclosure continue to
show run ac status, set time, run time, ac manual or auto mode, should controls 2 to 6 AC units. Automatic changeover timer for 2/3/4/ 6AC
(Single Phase) Can set 1 hr to 12 hrs program.
(Make: Dynamic Microtech.)

Additional Copper Piping for Split AC units (3/4" & 3/8")

Auto Drain pump with necessary wiring & support. (Electrical points shall be Electrical Vendor scope)
Make: Aspen Pumps Max Hi-Flow

Supply of Common A/c Remote of Bluestar/Carrier/Voltas/LG Etc. (Need to confirm with Project Manager before purchase)

Supply of Indoor unit clamps & installation

Supply of Outdoor unit stand & installation

Repairing & Maintenance work of HVAC, (The Vendor will share the Bifurcation of expences, which he will be charging for
Repairing & maintenance of Old A/c)

Supply, Installation and testing of UPVC - blue piping complete with fittings, supports as per specifications and
insulated with 9 mm thick xlpe insulation with protective coating etc., complete

19 mm dia

25 mm dia

32 mm dia

Very Important Notes-


Vendor should adhere with all the points applicable. If any deviation, should be clarified at the initial stage itself in
written communication.
Failure to communicate any in written, considered as points accepted
Time limit for completion 2/3 weeks from LOI/PO (Basis site area & Business requirement- weeks will change)
Penalty @ 2% per week on Total Project value will be applicable for delay from project timelines
Billing shall be done as per actual measurement/usage at site. Vendor should visit the site & should take concurrence from P
Works shall be carried out as per instructions of site in Charge
All Free issue items shall be provided from HLPL (Udaan) store available in the same site
Electricity will be provided free of cost at 01 point for the usage, further extn if any should be taken care by Vendor.
Water for working purpose shall be provided free of cost if available at site. Else vendor to arrange.
Site Existing toilets can be utilized by Vendor & should avoid frequent movement between the floor & toilet.
Labours shall not be allowed to stay at site/ Should adhere with HLPL (Udaan) security norms & should cooperate with the
Vendor should follow the Work permit/Entry permit system as per the Project In charge .
Vendor has to deploy a safety supervisor at all times while working at site and is fully responsible for safety of the workers
Vendor has to ensure that their workers n staff use PPEs while at site
All samples to be approve from Site in charge in line with BOQ
HLPL (Udaan) will not provide any dedicated storage room at site. Vendor should arrange their own.
Vendor should take care of his inventory / Tools in lock & key in their own possession. HLPL (Udaan) will not be responsi
Vendor only responsible for all his inventory till Handing over to Projects / FM team. HLPL will not be responsible for any
Vendor should complete the snag points/Documentation with 2 weeks time from the date of Snag list.
Failing to close the snag list & documentation within the Time Line will attract deviation penalty.
The snag points will be closed by HLPL (Udaan) with other competent Vendor & Double the cost for same shall be recovered from Ven

Safety Deviations & Penalty clause


1st Time Safety Deviation/Violation: Memo I & Rs. 10000 as Penalty
2nd Time Safety Deviation/Violation: Memo II & 10 % Penalty of the project cost
3rd Time Safety Deviation/Violation: Stoppage of Project by the Vendor & block listing
All works should be covered under ESI or Group insurance & details should be displayed at site & copy of the same to given to the Proje

General Notes
Billing shall be done as per actual measurement/usage at site
Vendor should arrange 75% of BOQ material at site within 03 days from the date of Kick off at site.
Electrical Supervision should be valid Supervisor Licence issued by EB authorities & Wiremen Licence for workers.
Vendor should deploy qualified and experience Supervisors for their respective work.
Ferruling, tagging & labelling shall be carried out wherever applicable
Test certificate shall be provided for cables & wires
Only heavy duty PVC cable tie should be used
Vendor should follow all the security/safety requirement at site. Proper PPE & Safety shoes must be worn at all time inside
Vendor must bring his own fire extinguisher and should be kept near by during execution of any hot work.
Vendor must always use proper extension board with adequate size /rating MCB n ELCB/ with proper plug tops
All machines, tools and extension board should be with proper 3 Pin Top
All Wires should be connected with connectors, no tapping allowed
Each Vendor should arrange their ladders, scaffolding and any support required for carrying out the work.
Vendor shall supply and install only approved makes
Vendor should visit site before sharing quote for this works
Temp lights if required anywhere will be arranged by vendor only
Dedicated Safety supervisor to be deployed at site to monitor the safety in each shift. Only Safety supervisor can approach H
Site debris cleaning will be vendor responsibility & daily cleaning should be done post completion of the day work before l
Invoice should be along with necessary supporting documents with necessary Security seals/ inward register data.
DC copies should be in print format or in the CAPITAL LETTERS.
Installation
UOM QTY. Supply Installation Supply Rate
Rate
Remarks

No's

No's 1

No's 4

No's 4

No's

No's

No's 3 Will get it from Project WH

No's

No's 2 Will get it from Project WH


No's

No's 3

Rmt 80

No's

No's 5

No's

No's

No's 1 1 40000

Rmt 150

Rmt

Rmt

concurrence from Project Manager before ordering the materials.

by Vendor.

cooperate with them.

fety of the workers n staff


will not be responsible for any loss / damage to the Vendors materials / Inventory.
responsible for any loss/Theft in the premises if any.

e recovered from Vendor.

e to given to the Project In-charge via mail/ file.

for workers.

rn at all time inside the premises

visor can approach HLPL (Udaan) Project team for Work permits.
e day work before leaving the site.
Project : UDAAN @ UPS SERVICES BOQ OF Ludhiana BTS Nahar
Subject : Priced Bill of Quantities - UPS & ASSOCIATED WORKS
Date 15-Dec-21

Sl.No. Description Qty


VERTIV(Emerson): ITA 2 20 KVA Online UPS system with 3 Phase input & 3
1 1
Phase output WITH Dry Contact Card and Modbus Card

1b Hooter 1

1c Ram Cable 30 Mts with conduit 1

Quanta/Exide make SMF batteries to provide 30 mins backup


2 (12V-42AH-32 No's) 1

3 MS powder coated Rack to accommodate 42AH-32 No's batteries 1

4 Interlinks for 42AH-32No's batteries 1

5 Freight Charges (per UPS & battery set) 1

Only Installation of 10 KVA UPS Set 1 Phase along with New Interlinks for
6 1
42AH-16No's batteries

TOTAL (BASIC)
Units Unit Price Total Price HSN code
No - 85044090

Nos -

Set -

With Parallel Kit, RAM Panel, Dry


Contact Card, modbus card and 3
Set - 85072000 year warranty

set - 73012010

No - 85443000

No - 996519

Set 7,000 7,000 996519 Will get it from Project WH

-
Transportation
SL ITEM DESCRIPTION UNIT QTY Total
32 feet closed Truck with Lock & Key facility - Loading & unloading of material as per the site
1 requirement (From Faruk Nagar Haryana Store to Ludhiana BTS Nahar), LS 1
(in Vendor Scope)
22 feet closed Truck with Lock & Key facility - Loading & unloading of material as per the site
2 requirement (From Faruk Nagar Haryana Store to Ludhiana BTS Nahar), LS 1
(in Vendor Scope)

Packing of old Material in New Project WH Store in bubble wrap for all Material before
3 Lot 1
transportation. (UPS & A/C Out Door will be packed in wodden boxes after bubble wrap)

4 Un-Skilled Man power Support (Loading/ unloading/ HK) days 30


: UDAAN @ LOAD CALCULATION OF LUDHIANA BTS NAHAR Dated: 10-12-2021

Connected Load in Utilization Total Utilization


Sl. No Load Description FINAL QTY. Watts kW
Watts Factor Load in Watts

LOADS ON RAW
1 No. 6/16 Amp. Socket with 6/16 Amp.Switch
1 2 100 200 0.25 50 0.1
for W/M Fan Etc. (In Ele. Room & Dock, Etc)
2 1 No. 6/16 Amp. Socket with 6/16 Amp.Switch for Digital Clock 3 25 75 0.5 37.5 0.0
3 1 No. 6/16 Amp. Socket with 6/16 Amp.Switch for 400mm W/M Fan 29 70 2030 0.4 812 0.8
1 No. 6/16 Amp. Socket with 6/16 Amp.Switch for Fly Catcher,
4 22 35 770 0.5 385 0.4
( 10 Nos Fly Catcher)
1 No. 6/16 Amp. Socket with 6/16 Amp.Switch
5 25 75 1875 0.3 562.5 0.6
for Office Room / Work station with Laptop Etc.
6 1 No. 6/16 Amp. Socket with 16 Amp.Switch for Printer 900 Watts 2 900 1800 0.3 540 0.5
1 No. 6/16 Amp. Socket with 16 Amp.Switch
7 10 125 1250 0.15 187.5 0.2
for Maintenanc Points in Warehouse.
8 1 No. 6/16 Amp. Socket with 16 Amp.Switch for Micro Oven 2500 Watts 1 2500 2500 0.5 1250 1.3
9 1 No. 6/16 Amp. Socket with 16 Amp.Switch for Coffee Machine 2500 Watts 1 2500 2500 0.5 1250 1.3
10 1 No. 6/16 Amp. Socket with 16 Amp.Switch for Fridge 1 100 100 0.5 50 0.1
11 1 No. 6/16 Amp. Socket wit h 16 Amp.Switch for Weigning Scale 6 50 300 0.3 90 0.1
12 1 No. 6/16 Amp. Socket wit h 16 Amp.Switch for Sewing Machine 6 100 600 0.3 180 0.2
13 1 No. 6/16 Amp. Socket wit h 16 Amp.Switch for Water Dispencer 9 300 2700 0.5 1350 1.4
14 1 No. 6/16 Amp. Socket wit h 16 Amp.Switch for Visi Coller/ Deep Freezer 0 500 0 1 0 0.0
15 1 No. 6/16 Amp. Socket with 16 Amp.SP MCB for BOPT/ EHPT 8 1000 8000 0.7 5600 5.6
16 1 No. 6/16 Amp. Socket with 16 Amp.SP MCB for HHD/ Mobile Charging Box 2 200 400 0.5 200 0.2
1 No. 6/16 Amp. Socket with 16 Amp.SP MCB for 1.0 Tr Split A/c Etc.
17 4 0 0 0.8 0 0.0
(Load has been cosidered below)
1 No. 6/16 Amp. Socket with 16 Amp.SP MCB
18 0 2150 0 0.4 0 0.0
for Pressure Pump Bosch Aquatek 140, (Weather Proof)
19 2 No. 6/16 Amp. Socket with 6/16 Amp.Switch for Conf/ Meeting Room Table. 2 150 300 0.3 90 0.1
2 No. 6/16 Amp. Socket with 6/16 Amp.Switch
20 15 200 3000 0.4 1200 1.2
for Work station with Desktop
2 No. 6/16 Amp. Socket with 6/16 Amp.Switch
21 13 975 12675 0.45 5703.75 5.7
for Work station with Desktop along with H/d Printer Point
2 No. 6/16 Amp. Socket with 16 Amp.Switch
22 5 150 750 0.25 187.5 0.2
for SS Table/ Packing/ Sorting Table/ Mist Fan's Etc.
23 High Bay Light 50 Watts (Or LED Bulb 50 Watts) 0 50 0 1 0 0.0
24 High Bay Light 80 Watts. 0 80 0 1 0 0.0
25 High Bay Light 100 Watts.(By LL 00 Nos & Udaan 24 Nos) 0 100 0 1 0 0.0
26 High Bay Light 120 Watts.(BY LL) 109 120 13080 1 13080 13.1
27 Flood Lights 50 Watts. (For External) by LL 0 50 0 0.8 0 0.0
28 Flood Lights 80 Watts. (For External) by LL 46 80 3680 1 3680 3.7
29 Flood Lights 100 Watts. (For External Light BY LL) 0 100 0 1 0 0.0
30 50 Watts Street Light by LL. 0 50 0 1 0 0.0
2 / 2 Recess Down Light, 36/40 Watts.
31 0 40 0 0.7 0 0.0
(Need to consider the Repairing, Like change of Lower Acrylic sheet.)
32 Led Batten Lights 20 Watts. ( Nos. for Toilet, Etc by LL & 20 Nos by Udaan) 20 20 400 0.7 280 0.3
33 Led Batten Lights 20 Watts. (Weather Proof for External SIde) 0 20 0 1 0 0.0
34 Led Batten Lights 36 Watts. (Weather Proof for External SIde) 0 36 0 1 0 0.0
W/M 400mm Fan, 70 Watts,
35 27 0 0 1 0 0.0
(Load Has been Considered above)
W/M Almonard Fan 18" or 24"
36 3 0 0 0.5 0 0.0
(Load has been Considered Above) (For Dock & WH)
Pedestal Almonard Fan 18" or 24".
37 20 0 0 0.5 0 0.0
(Load has been Considered Above) (For Dock & WH)
38 Ceiling Fan 600/900/1200 mm 70 Watts. (By LL ) 2 70 140 0.7 98 0.1
Exhaust Fan Plastic with louvar 300mm.
39 8 70 560 0.25 140 0.1
(0 Nos by LL for Toilet Etc, & 8 Nos by Udaan)
40 Exhaust Fan Heavy duty 1400 RPM. 18", 3 Nos By LL 3 250 750 0.8 600 0.6
Exhaust Fan Heavy duty 1400 RPM. 12" (For Ele. Room)
41 26 80 2080 0.5 1040 1.0
(By LL 20 Nos & By Uddan 6 Nos)
42 HVAC - 1.0 Tr. 1200 Watts. (For DVR & IT) 4 1200 4800 0.8 3840 3.8
43 HVAC - 1.5 Tr. 1800 Watts. (For office, cash, ele, meeting) 4 1800 7200 0.8 5760 5.8
44 HVAC - 2.0 Tr. 2400 Watts. (For Ele. Room), Cassate Unit of Pataudi 4 2400 9600 0.8 7680 7.7
45 HVLS Fan Single Phase 0 1000 0 1 0 0.0
46 MHE 3 Phase 7000 Watts. 5 7000 35000 0.8 28000 28.0
47 Conveyour Belt 3 Phase 1 2500 2500 1 2500 2.5
48 LIFT 10 KW 1 NO. 0 10000 0 1 0 0.0
Total Load on RAW in KW 121615 86423.75 86.42375
Total Load of RAW in KVA 152018.75 108029.688 108.02969

LOADS ON UPS
1 No. 6/16 Amp. Socket with 6/16 Amp.Switch
1 12 50 600 1 600 0.6
for Bio Metric, UPS room Indicator, Fire Alarm Panel, Etc. 50 Watts
1 No. 6/16 Amp. Socket with 6/16 Amp.Switch
2 26 75 1950 0.5 975 1.0
for Office/Conf Room Work station with Laptop
3 2 No. 6/16 Amp. Socket with 2x6/16 Amp.Switch for CCTV & IT Racks 0 150 0 1 0 0.0
2 No. 6/16 Amp. Socket with 6/16 Amp.Switch for Conf/ Meeting Room, Fire Panel & UPS
4 6 150 900 0.5 450 0.5
Hooter Table.
2 No. 6/16 Amp. Socket with 6/16 Amp.Switch
5 24 250 6000 0.6 3600 3.6
for Office/ Cash/ Inward / Outward Etc. Work station with Desktop.
6 2 No. 6/16 Amp. Socket with 6/16 Amp.Switch for CCTV & IT Racks in DVR Room 16 200 3200 1 3200 3.2
7 3 Nos. 6/16 Amp. Socket with 6/16 Amp.Switch for TV Points. 2 300 600 1 600 0.6
8 High Bay Light 50 Watts (Or LED Bulb 50 Watts) 0 50 0 0.8 0 0.0
9 High Bay Light 80 Watts. 0 80 0 1 0 0.0
10 High Bay Light 100 Watts.(By LL ? Nos & Udaan 14 Nos) 0 100 0 1 0 0.0
11 High Bay Light 130 Watts.(BY LL) 66 130 8580 1 8580 8.6
12 Flood Lights 50 Watts. (For Dock & WH Area Light) (BY Udaan 42 Nos) 38 50 1900 0.8 1520 1.5
13 Flood Lights 80 Watts. (For Internal Light) 0 80 0 1 0 0.0
14 Flood Lights 80 Watts. (For External Light) 0 80 0 1 0 0.0
15 50 Watts Street Light by LL. 0 50 0 1 0 0.0
16 2 / 2 Recess Down Light, 36/40 Watts 0 40 0 1 0 0.0
17 Led Batten Lights 20 Watts. (28 Nos. for Toilet, Etc by LL & 75 Nos by Udaan) 103 20 2060 1 2060 2.1
Led Batten Lights 20 Watts. (Weather Proof for External SIde)
18 25 20 500 1 500 0.5
(15 Nos from LL & from Udaan 15)
19 12W DLED Recess Mini Downlighter 0 12 0 1 0 0.0

Total Load of UPS in KW 26290 22085 22.085


Total Load of UPS in KVA 32862.5 27606.25 27.60625
Total Load of Raw + UPS in KW. 147905 108509 109
Total Load of Raw + UPS in KVA. 184881 135636 136

Calculation for DG.


Total Utiliation Factor KVA Load / .8 169.54 KVA 1 No 160 KVA & 1 No 125 KVA

So the Suggested DG would be 160.00 KVA

Calculation for UPS


Total Utiliation Factor KVA Load of UPS / .8 34.51 KVA 2 Nos 3 Phase of 20 KVA
So the Suggested UPS would be of 20.00 KVA 2 Nos 3 Phase

Calculation for Servo Stablizer.


Total Utiliation Factor KVA Load / 1 135.64 KVA
So the Suggested Servo Stablizer would be 125.00 KVA
ELECTRICAL SERVICES LIST OF APPROVED MAK

Sl.No Description
1.1 TRANSFORMER VOLTAMP VOLTECH

1.2 DIESEL GENERATORS KIRLOSKAR CUMMINS

1.3 UPS UNITS VERTIV (EMERSON) SCHNIEDER (APC)

1.4 SERVO STABILIZERS GRAVITY/EMERSON Consul Neowatt

1.5 HVAC BLUE STAR VOLTAS

1.6 BATTERIES FOR UPS AMARARJA QUANTA HBL NIFE

1.7 BATTERIES FOR AUTOMOBILES EXIDE HBL NIFE

2 ACB ABB L&T

a Incomer SCHNEIDER (Masterpact NW SIEMENS (3WL with ETU76B Release)


with Micrologic 6H  Release)

b Outgoings SCHNEIDER (Masterpact NW SIEMENS (3WL with ETU45B+EF Release)


with Micrologic 6A Release) SIEMENS (3WL with ETU45B+EF Release)
SIEMENS (3WL with ETU45B+EF Release)
3 MCCB SCHNEIDER (COMPACT SIEMENS (3VL)
NS SERIES)
4 MPCB SCHNEIDER SIEMENS

5 MCB/ELCB/RCCB/RCBO/MPCB LEGRAND SCHNEIDER

6 MCCB/MCB DB LEGRAND SCHNEIDER

7 POWER CONTACTORS, TIMER, HRC SCHNEIDER SIEMENS


FUSES & FUSE FITTINGS
8 Instrument Transformers KAPPA ABB

9 Protection relays SCHNEIDER SIEMENS

10 Earth leakage relay PROK DV'S ELMEASURE

11 LED indication lamps L&T SCHNEIDER

12 Selector switches L&T KAYCHEE

13 TVSS OBO SIEMENS

14 Isolators ABB SCHNEIDER

15 HEAVY DUTY POWER CAPACITOR WITH EPCOS NEPTUNE


SERIES REACTORS WITH HARMONIC
FILTERS AND THYRISTOR SWITCH

16 APFC RELAY EPCOS NEPTUNE

17 DIGITAL VOLTMETER, AMMETER, KWH SCHNEIDER L&T


METER, MULTIFUNCTION METER

18 AL BUS BAR HINDALCO JINDAL

19 PANEL ACCESSORIES , TERMINAL ELMAX PHOENIX


BLOCK
20 LT Panel Builders. (ISI Mark)
21 PVC-FR/FRLS Insulated copper POLYCAB Finolex / KEI / Havells
wires
22 HT/LT cables POLYCAB Finolex / KEI / Havells

23 LT single-multicore copper cables POLYCAB Finolex / KEI / Havells

24 Control cables POLYCAB Finolex / KEI / Havells

25 End termination materials DOWELS COMET

26 Perforated Cable tray, (ISI Marked)

27 Raceway / DB CABINET (ISI Marked)

28 Modular type sockets & switches ANCHOR - ROMA CLIPSAL

29 U-PVC RACEWAY, (ISI Marked)

30 Industrial plug & socket NEPTUNE SCHNEIDER

31 FRLS PVC Conduits VIP NELCO

32 MS Conduits BHARATH GB

33 Light fixtures Havells PHILIPS

34 Lighting Management system SCHNEIDER HONEYWELL

35 Maintenance free earth pits/ Lightening ELLIPS ASHLOK


Arresters
36
Instrumentation cable
37 Lightning Protection ELLIPS ALTEC Terrastreamer

38 FAN/EXHAUST FAN CROMPTON


USHA
39 FIRE SEALENT / FIRE STOP BOARDS 3M OBO

40 PA System Ahuja

NOTE: 1. SAMPLES OF ALL MATERIALS THAT WILL BE USED HAVE TO BE SUBMITTED FOR APPROVAL BEFORE PROCUREMENT / SUPPL
NOTE: 2. TECHNICAL SUBMITTALS OF ALL MATERIALS THAT WILL BE USED HAVE TO BE SUBMITTED FOR APPROVAL BEFORE PROCUR
6Way VTPN MCB DB (7 segment)
(Incomer+ Sub Incomer + Outgoing
Modules) Ref: Hager Cat No: VYG06DL)
RICAL SERVICES LIST OF APPROVED MAKES (2021)

Makes
GE/ ABB MAHINDRA & MAHINDRA ISI MARKED OR EQUIVALENT

MAHINDRA & MAHINDRA STERLING & WILSON

NEUMARIC CONSUL NEOWATT

POWERGUNN

CARRIER/LG/SAMSUNG DAIKEN

AMRON/ EXIDE

CUMMINS PERSOLITE

SCHNIEDER HAVELLS

L&T (Upower Omega with MTX3.5H  Release) ABB (Emax with PR123 Release
with PR120D/M & PR120V module)

L&T (Upower Omega with MTX1.5G Release) ABB (Emax with PR122 LSIG
Release)

L&T (D-SINE)/ HAVELLS ABB (T-MAX) HAGER

L&T ABB

SIEMENS HAGER L&T

SIEMENS HAGER L&T

L&T ABB

SIEMENS KALPA

SEGC L&T ABB

SCHNEIDER L&T
GIC
TECHNIC VAISHNO ESSBEE

GEPC SCHNEIDER ABB

ABB ASCO SOCOMEC

SIEMENS L&T

ABB DUCATI L&T

DUCATI L&T

ELMEASURE ABB SOCOMEC

DIRAK WAGO

MAXWELL ELECTRICAL & CONTROLS


GEMSCAB Havells POWER-FLEX

NICCO/POWER-FLEX GEMSCAB CCI

NICCO/POWER-FLEX GEMSCAB CCI/BONTON

NICCO/POWER-FLEX GEMSCAB CCI/BONTON

JOINTWELL

MK SCHNEIDER LEGRAND

HENSEL JJ/ Siemens LEGRAND

POLYCAB UNIVERSAL FINOLEX

SUPREME VIP

WIPRO Lumens OSRAM / BAJAJ /

PHILIPS SIEMENS

GLOBAL GALAXY EARTHING

ALUTECH ASHLOK THOR OBO

HAVELLS ALMAONRD BAJAJ

HILTI

ROVAL BEFORE PROCUREMENT / SUPPLY OF ANY MATERIAL.


TTED FOR APPROVAL BEFORE PROCUREMENT / SUPPLY OF ANY MATERIAL.
0
0
0
Makes
ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT


ISI MARKED OR EQUIVALENT

UNIVERSAL ISI MARKED OR EQUIVALENT

UNIVERSAL ISI MARKED OR EQUIVALENT

UNIVERSAL ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT


HAGER
ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT

ISI MARKED OR EQUIVALENT


0
0
0
If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.
If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.

If the Specified Make is not Available then kindly take the prior Approval from Commercial/ Procurement to go ahead with other makes.
0
0
0

You might also like