Feed-Through Terminal Block - UK 6 N - 3004524: Key Commercial Data
Feed-Through Terminal Block - UK 6 N - 3004524: Key Commercial Data
Feed-Through Terminal Block - UK 6 N - 3004524: Key Commercial Data
com/gb/products/3004524
Feed-through terminal block, nom. voltage: 800 V, nominal current: 41 A, connection method: Screw
connection, number of connections: 2, cross section: 0.2 mm² - 10 mm², AWG: 24 - 8, width: 8.2 mm, color:
gray, mounting type: NS 35/7,5, NS 35/15, NS 32
Your advantages
All universal terminal blocks in the UK... series can also be used in the Ex e area according to IEC/EN 60079 as standard
The corresponding EC-type examination numbers for Ex approval can be found in the technical connection data
GTIN
GTIN 4017918090821
Weight per Piece (excluding packing) 13.014 g
Custom tariff number 85369010
Country of origin China
Sales Key BE1211
Technical data
General
Number of rows 1
Number of connections 2
Potentials 1
Nominal cross section 6 mm²
Color gray
Insulating material PA
Flammability rating according to UL 94 V0
Mounting type NS 35/7,5
Rated surge voltage 8 kV
07/26/2021 Page 1 / 5
https://www.phoenixcontact.com/gb/products/3004524
Dimensions
Width 8.2 mm
End cover width 1.8 mm
Length 42.5 mm
Height NS 35/7,5 47 mm
Height NS 35/15 54.5 mm
Height NS 32 52 mm
Connection data
Connection method Screw connection
Screw thread M4
Stripping length 10 mm
Tightening torque, min 1.5 Nm
Tightening torque max 1.8 Nm
Connection in acc. with standard IEC 60947-7-1
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 10 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 8
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 6 mm²
Min. AWG conductor cross section, flexible 24
Max. AWG conductor cross section, flexible 12
07/26/2021 Page 3 / 5
https://www.phoenixcontact.com/gb/products/3004524
Ambient conditions
Operating temperature -60 °C ... 105 °C (max. short-term operating temperature 130°C)
Ambient temperature (storage/transport) -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport) 30 % ... 70 %
Ambient temperature (assembly) -5 °C ... 70 °C
Ambient temperature (actuation) -5 °C ... 70 °C
Drawings
Circuit diagram
07/26/2021 Page 4 / 5
https://www.phoenixcontact.com/gb/products/3004524