-CNHHS/Q Routine Test Report 2022.3.10 CNHHS/FQC Luke

Three phase metal enclosed switchgear Type Page/Pages Rev.


Report No. ELK-04 G
1/1
1HZC 259 801/T1008262
Device Shipping unit
Order No. 502855105 Rated voltage 170 kV

Location Bangladesh Rated power frequency withstand voltage 325 kV

Substation CNTIC Bangladesh Ashuganj 132kV kV


Rated lightning im pulse withstand voltage 750

Bay designation E23 Rated frequency 50 Hz

Shipping unit SD10623 Rated short tim e withstand current


50 kA

Single line diagram 1HZC2 3 20150-02 Rated duration of short-circuit sec


3
Layout drawing Rated peak withstand current kA
1HZC2 3 20150-01 125
Gas compartment
1HZC2 3 20150-02 Rated current busbar 3150 A

Tests carried out acc. to IEC 62271-203 (Last edition)


1. Resistance of the main circuits ( I = 200 ADC ) Measurement at room temperature

measured from ... to ... Desired value R Phase Y Phase B Phase

50F2-F3 15  9  12  10 
- -  -  -  - 
- -  -  -  - 
2. Design and visual checks X All right

3. Power frequency voltage dry test


Min. gas density = min. gas pressure at 20°C, (abs)
According Gas-compartment drawing: 1HZC2 3 20150-02
325 kV, 1min X All right

4. Partial discharge measurement


Partial discharge level at 1.2xUn
< 2 pC , 1.5 min X All right

5. Gas tightness test


≤0.1% per year
Test acc. to internal instruction X All right

Shipping Unit

CNHHS/Q Prepared by Approved by For the client

Date 2022-06-08 2022-06-08