Hydrocarbon Fire Protection – ISOLATEK® Type M-II / TG

T
H
E
R
M
O
L
I
N
U
L
I
T
E
W
O
ISOLATEK® Type M-II / TG
Industrial - Hydrocarbon Fire Resistive Material
T O
E L

access to innovation

ISOLATEK Type M-II is a single package factory


controlled Spray-Applied Fire Resistive Material
(SFRM) based on vermiculite and portland
cement. It is the most widely used fireproofing
product for use in the landbase oil, gas and
petrochemical related industries. The material is
used to achieve hydrocarbon fire ratings on
structures, pressurised vessels, sphere, bullets,
skirts and equipment in exterior environments
and interior situations where higher levels of
abrasion resistance and hardness are
necessary.

Although ISOLATEK Type M-II is lightweight, thus


significantly reducing dead load, it is also highly
durable and resistant to cracking or spalling ISOLATEK Type M-II along with Topcoat applied on 3 LPG vessels
under mechanical impact. Its excellent fire
performance offers the client an economical,
durable and effective fire protection solution. Spheres and Vessels

Our long term association with the petrochemical


ISOLATEK Type TG and chemical process industries has enabled
Isolatek and Newkem to design and develop
When application of the fire protection is systems engineered to provide long term passive
required on a live plant, there are occasions fire protection to storage vessels and spheres.
when it is considered that application by spray
may prove too high a risk in terms of spark ISOLATEK Type MII will limit the unwetted surface of
ignition. ISOLATEK Type TG has been developed vessel to below their critical temperature for the
for application by trowel in areas where required period (usually two hours) for any of the
spraying is impractical or not permitted and has following fire types:
the same technical capabilities to perform as
the spray grade material. i. Intense torching fires
ii. Enveloping fires
Fire Performance iii. Radiant heat from adjacent fires

ISOLATEK Type M-II and ISOLATEK Type TG are The ISOLATEK Type MII system applied to vessels
classified by Underwriters Laboratories(UL) for incorporates a self supporting mesh retention
up to 4 hours protection in accordance with system which does not rely on mechanical fixing
the Rapid Rise Fire Test (UL 1709) & RWS Fire to vessel surfaces.
Curve. With UL 1709, the furnace temperature
rises from ambient to 2000°F (1093°C) within five
minutes. Only materials tested and classified in GASAFE
accordance with UL 1709 can be used where
the risk of a hydrocarbon fire exists. GASAFE was a project undertaken by several
UL 1709 Rapid Fire Test Results Classified Under UL Design sponsors in Europe to investigate the behavior of
XR 729 & XR 730 on a W10 X 49 column (Thickness in mm) pressurized LPG tanks and liquefied hydro-carbon
products in pressure vessels under fire conditions.
Fire Thickness Thickness Thickness
The project investigated the performance of fire
Rating Profile Profile Boxed
protection materials under various conditions
(Lath) (Mesh) (Lath)
(e.g. Jet fire, Pool fire, Accelerated weathering
45 min 17.5 17.5 17.5 and Hose Stream tests).
60 min 20.7 20.7 20.7
90 min 27.0 27.0 23.9 The GASAFE results were excellent and
120 min 31.8 32.5 23.9 independently confirmed that ISOLATEK Type M-II
150 min 36.6 36.8 30.2 consistently exceeded the design requirements.
180 min 39.7 41.2 36.6
240 min 47.6 50 47.6
ISOLATEK® Type M-II / TG
Technical Data

General Single Package. Approximate Curing Time @20˚C 50% RH


Water added on site Initial Set 2-6 hours
Finish Monolithic spray texture or Subsequent Coats After Initial Set
floated 50% Strength 5 days
Colour Off White 75% Strength 12 days
Cure By Hydraulic Set 98% Strength 28 days
Flash Point None
Minimum Density 704- 768 kg/ m3 Substrates Unprimed Steel
Number of Coats One or more as required Primed Steel
Galvanized Steel
Minimum Practical 8 mm (Unreinforced) Concrete
Thickness 15mm (Reinforced)

pH value 12 - 12.5 Storage Off the ground; and keep


Cohesion/ Adhesion 500 kPa dry until ready for use
Thermal Conductivity 0.19 W/mK @24˚C
Bond Impact No cracking or delamination Corrosion Resistance 0.00 gms/ m3
Shelf Life 24 months Packaging 22.7 kgs (50 lbs)
The physical property results given in this data sheet are based on laboratory tests under controlled conditions.

ISOLATEK Type M-II System Components

Mesh Retention System Top Coating Corrosion Protection System

For long term service durability or where A top coating system may Whilst the ISOLATEK Type MII
vibration of a structure may be be considered to protect system is non corrosive, a
anticipated a mesh retention system from long term chemical substrate priming system is
comprising of weld attachment and spills, the ingress of recommended for long term
plastic coated reverse twist galvanised hydrocarbons or frequent corrosion resistance, particularly
hexagonal mesh 1.0 (1.4) x 50 mm is washdown. when the structure is to be fully
recommended. exposed to the elements.

For advice on thickness calculations for structural steel sections (I, H, Hollow or Castellated) consult
Newkem’s Technical Team
Email: info@newkem.com, Phone: +91-22-24144261
Newkem® Products Corporation, Harganga Mahal, Khodadad Circle, Dadar TT, Mumbai 400014, India

ISOLATEK INTERNATIONAL provides passive fireproofing materials under the CAFCO® and FENDOLITE®
trade names throughout the Americas and under the ISOLATEK® brand worldwide, including India.

Worldwide: Licensee Applicator (India):

In the United States: Isolatek International, Stanhope, New Jersey Tel: 1.973.347.1200
In México & Central America: Cafco México S.A. de C.V., México D.F. Tel: 52.55.5254.6683
In Andean Countries: Cafco Andina S.A., Santiago, Chile Tel: 562.719.0394
In Canada: Cafco Industries, Toronto (Ontario) Tel: 1.416.679.2830
In Indian Subcontinent: Newkem Products Corporation, Mumbai, India Tel: +91-22-24144261 In
Asia: Tel: 60.3.5121.3886

The performance data herein reflect our expectations based on tests conducted in accordance with recognized standard methods under T N

controlled conditions. The applicator, general contractor, property owner and/or user MUST read, understand and follow the directions, H
E
U
L

specifications and/or recommendations set forth in Isolatek International's/Newkem’s publications concerning use and application of these
R I
M T
O E

products, and should not rely merely on the information contained in this product data sheet. Isolatek International/Newkem is not responsible for L
I
T
W
O
O

property damage, bodily injuries, consequential damages, or losses of any kind that arise from or are related to the applicator's, general E L

contractor's, or property owner's failure to follow the recommendations set forth in Isolatek International's/Newkem publications. The sale of these
© ISOLATEK International All Rights Reserved products shall be subject to the Terms and Conditions of Sale set forth in the Company's invoices.

F 4.4 Mar15