SRB301

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Emergency-Stop and guard door monitoring

SRB 301 LC Technical data


Standards: IEC/EN 60204-1, EN 954-1, BG-GS-ET-20
Stop category 3x Stop 0
Control category: 4
Start conditions: Reset button, autostart
Enclosure: glass-fibre reinforced thermoplastic, ventilated
Termination: screw terminals
Cable section: max. 2.5 mm2 solid or multi-strand lead
(incl. conductor ferrules)
Ue: 24 VDC –15%/+20%, residual ripple max. 10%
24 VAC –15%/+10%
Frequency range: 50/60 Hz (on AC operational voltage)
Ie: max. 0.08 A
• Signal evaluation of potential-free contacts, Protection class: terminals IP 20
e.g. emergency stop command devices, enclosure IP 40 to EN 60529
position switches with safety function and Power consumption: max. 1.9 VA, 1.7 W
solenoid interlocks Max. fuse rating: Glass fuse F1, tripping current 1.25 A
• Signal evaluation of potential outputs, Monitored inputs 1 or 2 channels
for instance safety light curtains and grids Feedback circuit: yes
• 1 or 2 channel control Drive circuits: S11/S12, S21/S22: max. 28 VDC
• 3 enabling paths, Stop 0 Enabling contacts: 3 enabling paths
• 1 indication contact (NC) Utilisation category: AC-15, DC-13
• optionally cross-wire detection Switching capacity: enabling paths: 6 A/230 VAC, 6 A/24 VDC
• Reset without edge detection Fuse rating: enabling paths: 6 A slow blow
or automatic start Signalling contacts: 1 NC contact
• 4 LEDs to show operating conditions Switching capacity: Indicating contact: 2 A/24 VDC
• Control Category 4 to EN 954-1 Contact material: AgSnO, self-cleaning, positive action
Contact resistance: max. 100 mΩ in new condition
Pull-in delay: ≤ 30 ms
Drop-out delay: ≤ 50 ms
Air clearances and creepage distances: DIN VDE 0110-1 (04.97), 4 kV/2
Overvoltage category: III to DIN VDE 0110
Degree of pollution: 2 to DIN VDE 0110
Ambient temperature: – 25 °C … + 45 °C
(Derating curve on request)
Mechanical life: 10 million operations
Function display: 4 LEDs
Weight: 230 g
Dimensions: 22.5 x 100 x 121 mm

Approvals

H C D
Ordering details
SRB 301 LC ➀
No. Replace Description

➀ 24 VAC/DC

5-2
Emergency-Stop and guard door monitoring

Note Wiring diagram


• Input level: the example shows a 2-channel
control of a guard door monitoring with two
position switches, wherof one with positive A L1
break, external reset button J cross-wire
monitoring and feedback circuit S
• The control recognises cross-wire shorts,
cable breakage and earth leakages in the
monitoring circuit. A1 S12 S11 S21 S22 X1 X2 13 23 33 41
• Duties: Suitable for 2 channel control, for
increase in capacity or number of contacts
by means of contactors or relays with
positive-guided contacts. Control logic K1
AC/ F1
DC
• For 1-channel control, connect NC contact S
to S11/S12 and bridge S12/S22 UB Ui K2
• Connect potential p-type outputs of safety K1 K2
light grids/curtains to S12/S22. The devices
must have the same reference potential. A2 14 24 34 42
• Automatic start: the automatic start is
programmed by connecting the feedback SRB 301LC
circuit to terminals X1/X2. If no feedback KB
circuit is required, establish a bridge.
KA
N
3
M

LED Note
Function display: The wiring diagram is shown with guard doors closed and in de-energised condition.
The integrated LEDs indicate
the following operational states.
• Position relay K1
• Position relay K2
• Supply voltage UB
• Internal operating voltage Ui