Substations: OPTIONS
> Transformer lockout (86). > Reset Inhibitor available upon request
> Sequencer in tap changers. > Manual reset pushbutton available upon request
> Security loops. > LDL contacts available
> Alarm signaling with recognition.
Construction Characteristics
Applications Power source independent lockout
Contacts 8 Changeover contacts
Connections
Electrical Characteristics
Standard voltages 24, 48, 72, 110, 125, 220 Vdc / 63,5, 110, 127, 230 Vac (50-60 Hz)
Voltage range -20% +10% Un
Coil characteristics Pick-up / release voltage See pick-up/release voltage-temperature curves
Average consumptions in the
<25.2 W dc
changeover
Operating times Pick-up time <10 ms Vdc / <20 ms. Vac
Contact material AgNi
≤ 30 mΩ
Contacts resistance
(15 mΩ LDL range)
Distance between contacts 1,8 mm
Permanent current 10 A
Contacts
Instantaneous current 30 A 1s. 80 A 200 ms 200 A 10 ms.
Max. making capacity 40A, 0,5s, 110Vdc | 30A, 1s, 36Vdc, | 30.000 operations (1op/15s)
Breaking capacity *See figures
Max. breaking capacity 100.000 operations
Umax opened contact 250 Vdc / 400 Vac
Dielectric strength 2 kV. 50Hz. 1 min
Impulse voltage 5 kV. 0,5 J. 1,2/50 µs
Insulation resistance 500 Vdc.; > 100MW
Endurance characteristics
Mechanical endurance 1*107 operations
48 Vdc 125Vdc
Resistive load:
L/R = 0 ms
Inductive load:
L/R = 20 ms
Highly inductive load:
L/R = 40 ms
RELAY DIMENSIONS
Sockets
JN DE IP 10
JN DE 2C IP10
JN DE IP 20
JN DE 2C IP20
JN TR OP
JN TR2C OP
J DE CL IP
J-EMP OP
Clips
Metal 45/DE
-
Metal E46/TR