Repeater / Power Supply
Repeater / Power Supply
Repeater / Power Supply
5104A
– 1- or 2-channel version
– 3- / 5-port 3.75 kVAC galvanic isolation
– Loop supply > 17.1 V
– 20 programmable measurement ranges
– Universal supply by AC or DC
Application
Applications
• Power supply and signal isolator for 2-wire transmitters.
• Signal isolator for analog current / voltage signals.
• 1 : 1 or signal conversion of analog current / voltage signals.
Technical characteristics
• The 20 factory-calibrated measurement ranges in the 5104A
can be selected by the internal DIP-switches without the need
for recalibration. Special measurement ranges can be
delivered.
• PR5104A is based on microprocessor technology for gain and
offset. The analog signal is transmitted at a response time of
less than 25 ms.
• Inputs, outputs, and supply are floating and galvanically
separated.
• The output can be connected either as an active current /
voltage transmitter or as a 2-wire transmitter.
Mounting / installation
• Mounted vertically or horizontally on a DIN rail. By way of the
2-channel version up to 84 channels per meter can be
mounted.
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions Output specifications
Operating temperature................................... -20°C to +60°C Current output
Calibration temperature................................. 20...28°C Signal range................................................... 0...20 mA
Relative humidity............................................ < 95% RH (non-cond.) Min. signal range............................................ 16 mA
Protection degree........................................... IP20 Load (@ current output)................................. ≤ 600 Ω
Load stability.................................................. ≤ 0.01% of span / 100 Ω
Mechanical specifications Current limit.................................................... ≤ 28 mA
Dimensions (HxWxD)..................................... 109 x 23.5 x 130 mm
Passive 2-wire mA output
Weight approx................................................ 225 g
Max. external 2-wire supply........................... 29 VDC
DIN rail type................................................... DIN 46277
Effect of external 2-wire
Wire size........................................................ 1 x 2.5 mm2 stranded wire supply voltage variation................................. < 0.005% of span / V
Screw terminal torque.................................... 0.5 Nm
Voltage output
Common specifications Signal range................................................... 0...1 VDC / 0...10 VDC
Supply Min. signal range............................................ 0.8 VDC / 8 VDC
Supply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or Load (@ voltage output)................................ ≥ 500 kΩ
19.2...300 VDC of span........................................................... = of the presently selected
Fuse............................................................... 400 mA SB / 250 VAC range
Max. required power...................................... ≤ 3 W (2 channels)
Internal power dissipation.............................. ≤ 2 W (2 channels) Observed authority requirements
Isolation voltage EMC............................................................... 2014/30/EU
Isolation voltage, test / LVD................................................................ 2014/35/EU
working........................................................... 3.75 kVAC / 250 VAC EAC................................................................ TR-CU 020/2011
PELV/SELV.................................................... IEC 61140
Approvals
Response time
Response time (0...90%, 100...10%)............. < 25 ms c UL us, UL 508............................................. E231911
DNV Marine.................................................... TAA0000101
Auxiliary supplies
2-wire supply (pin 44...42
and 54...52).................................................... 28...17.1 VDC / 0...20 mA
Signal / noise ratio......................................... Min. 60 dB (0...100 kHz)
EMC immunity influence................................ < ±0.5% of span
Extended EMC immunity: NAMUR
NE21, A criterion, burst.................................. < ±1% of span
Input specifications
Common input specifications
Max. offset...................................................... 20% of max. value
Current input
Measurement range....................................... 0...20 mA
Min. measurement range (span).................... 16 mA
Input resistance.............................................. Nom. 10 Ω + PTC 10 Ω
Voltage input
Measurement range....................................... 0...10 VDC
Min. measurement range (span).................... 8 VDC
Input resistance.............................................. > 2 MΩ
5104A-101122