Close Coupled Pumps Operating and Maintenance Manual
Close Coupled Pumps Operating and Maintenance Manual
Close Coupled Pumps Operating and Maintenance Manual
A N E M P LOY E E O W N E D CO M PA N Y
INTRODUCTION .................................................................................................................................................. 3
HEALTH & SAFETY ............................................................................................................................................ 4
LIMITS OF USE ................................................................................................................................................................ 4
NOISE ............................................................................................................................................................................. 4
PUMP INSTALLATION / MAINTENANCE ........................................................................................................................ 5
WORK ON ELECTRICAL EQUIPMENT .............................................................................................................................. 6
WORKING ON PRESSURISED SYSTEMS .......................................................................................................................... 6
COSHH ............................................................................................................................................................................ 6
INFORMATION ON ALBANY PUMPS ............................................................................................................... 7
TECHNICAL / DESCRIPTION ............................................................................................................................................ 7
OPERATING PRINCIPLE .................................................................................................................................................. 7
RECIEVING THE PUMP ................................................................................................................................................... 8
LIFTING OF GEAR PUMPS ................................................................................................................................ 9
INSTALLATION ................................................................................................................................................. 10
DIRECTION OF ROTATION ............................................................................................................................................ 10
BUILD CONFIGURATION .............................................................................................................................................. 10
REVERSING YOUR PUMP ROTATION ........................................................................................................................... 10
DUPLEX PUMPS ................................................................................................................................................. 11
DUPLEX PUMP SET OPERATING INSRUCTIONS ........................................................................................................... 11
VP PUMP SEAL REPLACEMENT ..................................................................................................................... 12
25 & 40 SERIES SEAL REPLACEMENT ........................................................................................................... 13
SPARES ............................................................................................................................................................... 14
VP PUMPS .................................................................................................................................................................... 14
25 & 40 SERIES PUMPS ................................................................................................................................................ 15
56 SERIES PUMPS ......................................................................................................................................................... 16
CONTACTS ......................................................................................................................................................... 17
Albany Engineering Co. Ltd Operating & Maintenance Manual (OMM-CCP:1.0) Page: 2
INTRODUCTION
This manual is a supplement to the standard Albany operating and maintenance manual
and contains general instructions for the storage, installation, operation and maintenance
of the following Albany gear pumps.
To get the best from the pump, carefully read and understand the Albany operating & maintenance
manuals before installation and start-up. Albany cannot anticipate all of the situations a user may
encounter while installing and using Albany products. Therefore, the user of an Albany product
MUST know and follow all applicable industry specifications on the safe installation and use of
these products.
Albany Engineering Company Limited will not be held responsible for any consequence due to the
improper use of the pump.
• If pump maintenance is necessary use this manual for safety and technical
information.
• For safe working observe the operating and maintenance instructions for associated
motors, engines, couplings and relief valves.
Albany Engineering Co. Ltd Operating & Maintenance Manual (OMM-CCP:1.0) Page: 3
HEALTH & SAFETY
The following are general safety precautions not related to any specific procedure, however, the
United Kingdom Health and Safety At Work Act 1974 Section 6(a) requires manufacturers to
advise their customers on the safety and the handling precautions to be observed when installing,
operating, maintaining and servicing their products.
Personnel must understand and apply these precautions during both operating and maintenance of
the pump. The user's attention is therefore drawn to the following:
1. The appropriate sections of this manual must be read before working on the equipment.
2. Installation and servicing must only be carried out by suitably trained or qualified personnel.
3. Normal safety precautions must be taken and appropriate procedures observed to avoid
accidents
The following symbols are used throughout this manual to draw attention
LIMITS OF USE
The pump/pump sets must not be subjected to pressures and temperatures in
excess of those for which it was originally quoted and supplied. It must not be
subjected to extremes of temperature and/or humidity for which it was not designed.
• Never use heat to disassemble the pumps due to risk of explosion from trapped liquid.
• Never operate the pump beyond the rated conditions for which the pump was originally
sold.
• Always lock out and post a permit on the power to the driver before performing any pump
maintenance.
NOISE
On certain installations, pump models and at certain operation points shown on the pump curves a
noise level of 80 dB, can be exceeded.
PUMP INSTALLATION / MAINTENANCE
Please install your pump in accordance with the latest National Safety Regulations.
It is hazardous to:
1) Run the pump without the coupling guard fitted
2) Change the use of the pump or modify it without Albany approval
3) Fail to maintain the pump, as this can cause injury or fire
The pump user is responsible for the safe use of the pump.
Lock off the electric starter; post a permit to prevent unauthorised starting.
Switch off and isolate any electrical heating system.
Assume that the pump is hot, check; allow to cool before starting work.
In the case of pumps for hot liquids allow to cool. Shut off all oil or steam heating
systems, vent them when cool.
Consider whether the pump or its parts may topple over. Take care to avoid injury
from falling parts, especially if the pump is large or heavy.
Albany Engineering Co. Ltd Operating & Maintenance Manual (OMM-CCP:1.0) Page: 5
HEALTH & SAFETY
WORK ON ELECTRICAL EQUIPMENT
Take extra care when working with any electrical equipment associated with the operation of the
pump; check that the motor terminals are not live even after switching off the supply. Earthing -
ensure the pump has a proper ground connection.
Do not attempt any inspection or repair before disconnecting the pump set from the
electric supply.
Where possible lock off the switch gear and post a permit on it, yourself.
Test that the motor terminals are not live before starting work.
WORKING ON PRESSURISED SYSTEMS
Liquids under pressure can cause injury, wear goggles and PPE
Vent all pressure containing parts to atmosphere, taking care in case the system is
under pressure.
Bleed the pump and system; this includes any thermal oil heating system.
COSHH
Albany Engineering Co. Ltd Operating & Maintenance Manual (OMM-CCP:1.0) Page: 6
INFORMATION ON ALBANY PUMPS
TECHNICAL / DESCRIPTION
The Albany gear pump is an external gear positive displacement pump which consists of two
counter-rotating shafts. The gears (rotors) which are attached to these shafts mesh together
retaining a limited clearance and rotating freely inside the pump casing bores.
The pumping rotors are contained within a rigid housing which is securely fixed together with
mating faces being sealed by the use of a gasket or O-ring to prevent leakage of fluid under
pressure.
The driving shaft of the pump (VP pumps the shaft protrudes from the motor into the pump casing)
is sealed to prevent leakage of the pumped fluid by means of mechanical seal or lipseal.
Note: Drive to the pump is achieved via the motor shaft entering the pump casing.
OPERATING PRINCIPLE
BEFORE STARTING UP. Make sure the pump rotates freely. To check this, the fan cowl can be removed
and the shaft rotated by turning the fan. Replace the fan cowl before switching on.
Before commencing on any work on the pump, ensure that the motor is isolated and any pressure is relieved
from the pump casing.
Albany Engineering Co. Ltd Operating & Maintenance Manual (OMM-CCP:1.0) Page: 7
INFORMATION ON ALBANY PUMPS
RECIEVING THE PUMP
Before reaching you, Albany will have run in, tested and recorded the pump performance in
accordance with your enquiry and order.
This means that the design, materials, and workmanship incorporated in the construction of Albany
pumps make them capable of giving, trouble-free service. The life and reliability of any pump,
however, is enhanced by:
• correct application
• proper installation
• periodic inspection, condition monitoring
• careful maintenance/servicing
These pumps can transfer a wide range of light, medium and heavy viscosity liquids, depending on
design and components, however they are not intended for use with water.
Inspect the pump as soon as it is received. Carefully check that everything is in good order. Make
notes of damage or missing items on the receipt and freight bill.
Should any problems occur with the pump in its lifetime we have a spares and repair service. The
use of genuine Albany parts will provide the safest and most reliable operation of your pump. ISO
certification and quality control procedures ensure the parts are manufactured to the highest quality
and safety levels. Please contact Albany for details on genuine pump parts.
To help us identify the pump Albany will need to know the pump serial No. which is stamped into
the pump casing. Typical positions for serial number are shown below.
Albany Engineering Co. Ltd Operating & Maintenance Manual (OMM-CCP:1.0) Page: 8
LIFTING OF GEAR PUMPS
Take care when moving the pump. Rough treatment or lifting in an unsuitable way may cause
permanent damage.
Use the lifting points provided. Do not lift pump sets using the motor lifting lug. Recommended
hand lift is 21 kg (44 lbs) below shoulder, but above ground level. The pump should never be lifted
by the shaft end.
Before lifting the pump set, check the weight of the delivery from the delivery note.
Be careful when moving pumps. Lifting equipment must be able to adequately support the entire
assembly.
Lifting Points
Most pumps below size VP5 are under the safe hand lift weight of 21kg.
Albany Engineering Co. Ltd Operating & Maintenance Manual (OMM-CCP:1.0) Page: 9
INSTALLATION
DIRECTION OF ROTATION
Pumps can be run in either direction and when reversed the direction of flow is reversed. It is
advisable to keep the original rotation as a pressure relief system is provided in the covers to
prevent hydraulic noise. Some pumps have internal relief passages between suction areas and
the gland or seal. These are used to reduce gland pressures and become inoperative in reverse
rotation. The Relief Valve becomes inoperative in reverse. In most pumps the valve can be
moved to operate with the new rotation (see drawing of Build Configurations)
BUILD CONFIGURATION
The handing of a pump indicates the direction of flow through the pump looking on the motor drive
shaft.
All views below are looking on the pump back cover and show a relief valve pump (these views will
apply equally to a non relief valve pump).
Top Drive/
Anti Clockwise
Rotation
(Left hand pump – SUCTION DELIVERY
SUCTION DELIVERY
Flow from right to left)
Top Drive/
Clockwise Rotation
(Right hand pump – DELIVERY SUCTION
DELIVERY SUCTION
Flow from left to right)
REVERSING YOUR PUMP ROTATION
To preserve your warranty, please phone us first before making any changes, have the serial
number to hand.
It maybe that to reverse the direction of rotation on your build of pump could create a hazardous
situation.
If you have a pump fitted with a pressure relieved seal / gland this will not work in reverse rotation.
Albany Engineering Co. Ltd Operating & Maintenance Manual (OMM-CCP:1.0) Page: 10
DUPLEX PUMPS
Duplex Pump sets are based on the 25, 40, 56 or VP series of pumps. For spares follow the
relevant pages in this manual.
DUPLEX PUMP SET OPERATING INSRUCTIONS
Ensure motors are wired for correct rotation, the left hand pump runs clockwise and the right hand
pumps runs anti-clockwise (viewed from pump end of the set).
See motor manufactures instructions inside terminal box for wiring instructions.
Open every gate valve fully, on suction and delivery pipe work to both pumps.
Select filter basket to be used by moving the lever on top of the filter unit.
Start the motor on the left hand pump check for flow and stop the motor.
Start the motor on the right hand pump check for flow and stop the motor.
Stop the motor and start the right hand pump run for three months.
After six months move the lever on top of the filter unit through 180 degrees. The filter basket not
covered by the handle should be removed and cleaned.
Replace the filter basket and repeat this cycle every six months.
Should a problem be experienced with either pump, stop the motor, start the motor of the other
pump. Close the suction and delivery gate valves on the pumps giving problems. Loosen the
swivel union joint next the pump and remove for examination.
Rectify the problem replace the pump and open the gate valves.
Albany Engineering Co. Ltd Operating & Maintenance Manual (OMM-CCP:1.0) Page: 11
VP PUMP SEAL REPLACEMENT
The shaft seal is often the most sensitive component in a pump as it must seal between a rotating
shaft and the stationary pump housing on VP pumps Albany use a mechanical seal.
Seal faces are lapped to high standards of flatness. Mating materials are chosen for long life
operation in the pumped liquid by Albany’s seal supplier.
A bleed hole has been drilled in the bottom of the pump front cover (item 13), so that if the
mechanical seal fails oil will be seen to come from this hole. The pump should be disconnected
from the main supply and the mechanical seal replaced or returned to Albany for repairs.
6
5 12 13
9 10 11
4 7 8
2 3
1
First unscrew the setscrews (item 1) from the back cover (item 2).
With the smaller size of pump the screws pass through the body (item 3) and engage in the front
cover so that the body, following shaft and rotors (items 4,5,6) can be removed along with the back
cover.
With the larger size of pump the setscrews between the body and front cover must be unscrewed.
The driving rotor (item 4) is a sliding fit on the motor shaft key (item 11) and when this and the seal
cover plate (item 7) are removed the grubscrew locating the seal collar (item 8) can be unscrewed
and the seal rotating member (item 9) withdrawn. To replace the seal seat it is necessary to
remove the front cover (item 11) from the motor by removing the holding screws (item 12). It is
advisable to renew gaskets when re-assembling the pump. Alternative methods may be used to
retain the seal. If in doubt check details with Albany.
Sizes VP5 & under are re-assembled with gasket cement. This material must be used very
sparingly. After assembly hand rotate the unit adding oil to clean any traces of cement from the
gear teeth.
Albany Engineering Co. Ltd Operating & Maintenance Manual (OMM-CCP:1.0) Page: 12
25 & 40 SERIES SEAL REPLACEMENT
Remove the pump head from the motor, and remove coupling hub from the drive shaft.
Gland Packing
Remove gland follower and extract old packing rings (4 off). Check gland area of shaft for wear.
Refit new packing pieces around shaft and press into chamber ensuring the joints of each piece
are staggered at 90º angles. Refit gland follower and tighten screws until resistance is felt. Ensure
shaft rotates and further tighten each screw by 1/6th of a turn.
Lip Seals
Remove old lip seals (1 or 2 fitted). Tape over keyway in drive shaft and push seal down shaft,
ensuring it is the right way round, to locate in the seal chamber. Tap ‘squarely’ into chamber to
shoulder stop with clean-ended dolly. If pump was fitted with 2 seals fit the second in the same
way.
Note! Pumps fitted with lip seals must not be subjected to a static pressure exceeding 0.3 Bar.
Mechanical Seals
Remove 4 screws securing the collar containing the seal face and remove the static face from the
collar. Remove the rotating element of the seal. Tape over keyway in drive shaft and apply a light
coating of silicone grease. Slide the rotating section down the shaft and position against step on
shaft. Fit new static face to collar and fit collar back in pump using a new gasket (ensure all faces
the gasket mates with are thoroughly cleaned).
Albany Engineering Co. Ltd Operating & Maintenance Manual (OMM-CCP:1.0) Page: 13
SPARES
To ensure the correct spares are supplied we need to know the pump serial number which is
stamped into the metal of the pump body, or cover, in a prominent position on the top area of the
pump (not motor).
Make sure that the correct spares are to hand before starting work on the pump.
Contact our works if you need assistance before starting the job.
VP PUMPS
19
18
10
17
8 9
16 6 7
3 5 15
2
1
11
12
13
14 4
Albany Engineering Co. Ltd Operating & Maintenance Manual (OMM-CCP:1.0) Page: 14
SPARES
25 & 40 SERIES PUMPS
11
10
9
8
7
6
5
4
3
2
1
13
12
14
15
16
17
18
Albany Engineering Co. Ltd Operating & Maintenance Manual (OMM-CCP:1.0) Page: 15
SPARES
56 SERIES PUMPS
16
17 12
10 11
18 8 9
7
19 6
4 5 20
2 3
1