DH Series: Air Circuit Breakers

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

08/80

Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog


Information subject to change without notice
Air Circuit Breakers
DH series
I Wiring diagram (with AGR-11 OCR or without OCR)
X X X X X X X
PB
Main circuit
CT for
neutral line
Control
power
Operation
Motor charging/
Operation circuit
For single-contact indication only 05 and 15
(+) (+) (+) (+)
Terminal description
Check OCR voltage before connecting
Over-current release
(type AGR-11 OCR)
15 25 06 16 26 17 27 22
MHT
Ry LRC
SHT
CT for
neutral line
S1
CT1 CT3
S3
S2
CT2
05 01 02 12 11 03
M
10
20 19 29 21
k K
L
X
CT1 - CT3 : Power CTs
M : Charging motor
LRC : Latch release coil
MHT : Magnetic Hold Trigger
Isolating terminal connector
(for draw-out type)
Manual connector
User wiring
Relay or indicator lamp
Symbols for accessories
S1 - S3 : Current sensors
ON switch
Continuous rating
shunt trip
i
: Do not connected NC contact of auxiliary switch to ON switch
in series, otherwise, pumping may occur.
: Wiring diagrams changes for capacitor trip.
: Use NO contact of auxiliary switch of ACB.
: For motor split circuit, terminals 02 , 22 and 03 , 04 are used for charging
operation respectively.
01 21 Control power supply AC200 - 240V,DC200 - 250V,DC48V 01 11 Control power supply AC100 - 120V
11 21 Control power supply DC100 -125V,DC24V
02 22 Control power supply AC10 - 240V,DC100 - 220V,DC24V,DC48V 12 Operation switch,common 03 ON switch
05 Operation indication terminal,common 15 LT trip indication or single-contact indication 25 St/INST trip indication 06 PTA indication
16 GF trip indication 26 System alarm indication 17 trip indication 27 Spring charge indication 10 20 Cotinuously-rated shun trip
19 Separate CT for neutral line (k) 29 Separate CT for neutral line ( ) 08 ,18 , 28 UVT power supply 09 UVT power supply common
100V 200V 380V
110V 220V 415V
120V 240V 440V
Terminal
No.
100V AC
coil
200V AC
coil
400V AC
coil
UVT power supply
08 - 09
18 - 09
28 - 09
( ) ( ) ( )
1
1
2
2
3
4
4
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice 08/81
08
Air Circuit Breakers
DH series
PB
Common
(
Position switches Auxiliary switches
UVT control circuit
111 121 131 141 151 211 311 411 511 611 711 811 911 011
UVT
09 08 18 28 24 30
122 124 132 134 142 144 152 154 114 112 214 212 314 312 414 412 514 512 614 612 714 712 814 812 914 912 014 012
Designation of terminals for
auxiliary and position switches
1: Auxiliary switch
CONNECTED position : 121124 ON
121122 OFF
TEST position : 131134 ON
131132 OFF
ISOLATED position : 141144 ON
141142 OFF
INSERT position : 151154 ON
151152 OFF
1: Common, 2: NC contact, 4: NO contact
2: Position switch (for CONNECTED)
3: Position switch (for TEST)
4: Position switch (for ISOLATED)
5: Position switch (for INSERT)
1 0: Switch numbers
A, B, C: Auxiliary switches for low level circuit
Top 151
Position switches
Middle
Bottom
Top 131
141 131 121
121
154
134
144 134 124
124
152
132
142 132 122
111
Auxiliary switches
211 311 411
112 212 312 412
114 214 314 414
511 611 711 811
512 612 712 812
514 614 714 814
911 011
912 012
914 014
122
Middle
Bottom
(Standard 4PDT arrangement)
(4PDT arrangement)
(2PDT arrangement)
(Standard 4PDT + optional 6PDT arrangement)
111 211
112 212
114 214
311 411
312 412
314 414
01 02 03 04 05 06 07 08 09 10
11 12 13 14 15 16 17 18 19 20
21 22 23 24 25 26 27 28 29 30
Operation/control circuits
Fixed type UVT
4PDT 3PDT 3PDT
Standard equipment Optional Optional
AUX.
SW
3
08/82
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
Air Circuit Breakers
DH series
I Wiring diagram (with AGR-21 OCR)
X X X X X X X
R-phase S-phase T-phase
X
Main circuit Operation circuit
CT for
neutral line
Control
power
Operation
For single-contact indication only 05 and 15
(+) (+)
(+)
Terminal description
Check OCR voltage before connecting
Over-current release
(type AGR-21 OCR)
15 25 06 16 26 07 27
M
CT for
neutral line
S1
CT1 CT3
S3
S2
CT2
05 01 02 12 11 08 18 28
19 29 21
k K
L
X
CT1-CT3 : Power CTs
M : Charging motor
LRC : Latch release coil
TC : Tripping coil
Isolating terminal connector
(for draw-out type)
Manual connector
User wiring
Relay or indicator lamp
Symbols for accessories
S1-S3 : Current sensors
ON
switch
OFF
switch
OCR
reset
switch
UVT/RPT power
i
: Operation input signal is rated at DC40V 5mA.
: Used for separation of operation input signals.
: Can be used for trip indicator in place of UVT indication.
: See page 08/57 for the circuit diagram of the continuous rating
shunt trip device with capacitor trip device.
01 21 Control power supply AC200 - 240V, DC200 - 250V, DC48V 01 11 Control power supply AC100 - 120V
11 21 Control power supply DC100 -125V, DC24V
02 22 Operation power supply AC100- 240V, DC100 - 250V, DC24V, DC48V 12 Operation switch, common 03 ON switch 1 13 OFF switch 1
23 OCR reset switch 1 04 Operation switch for signal separation 2 14 Operation switch for signal separation 2 24
05 Operation indication terminal, common 15 LT trip indication or single-contact indication 25 ST/ INST trip indication 06 PTA indication
16 GF,RPT or ELT trip indication 26 System alarm indication 07 HEAT indication 17 UVT indication 3 27 Spring charge indicator or PTA2
08 18 28 UVT/RPT power supply R.S.T (Max. AC460V) 09 N-phase voltage detection 19 Separate CT for neutral line (k)
29 Separate CT for neutral line ( ) 10 20 Continuously-rated shunt trip 30
100V 200V 380V
110V 220V 415V
120V 240V 440V
Terminal
No.
100V AC
coil
200V AC
coil
400V AC
coil
UVT power supply
08 - 09
18 - 09
28 - 09
( )
09
Detection of
N-phase voltage
1
2
3
4
LRC TC
22
( )
PB
03
PB
13
PB
23 04 14
17
Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice 08/83
08
Air Circuit Breakers
DH series
(
Position switches Auxiliary switches
(+)
111 121 131 141 151 211 311 411 511 611 711 811 911 011
SHT
122 124 132 134 142 144 152 154 114 112 214 212 314 312 414 412 514 512 614 612 714 712 814 812 914 912 014 012
10
20
Designation of terminals for auxiliary and position switches
1: Auxiliary switch
CONNECTED position : 121124 ON
121122 OFF
TEST position : 131134 ON
131132 OFF
ISOLATED position : 141144 ON
141142 OFF
INSERT position : 151154 ON
151152 OFF
1: Common, 2: NC contact, 4: NO contact
2: Position switch (for CONNECTED)
3: Position switch (for TEST)
4: Position switch (for ISOLATED)
5: Position switch (for INSERT)
1 0: Switch numbers
A, B, C: Auxiliary switches for low level circuit
Top 151
Position switches
Middle
Bottom
Top 131
141 131 121
121
154
134
144 134 124
124
152
132
142 132 122
111
Auxiliary switches
211 311 411
112 212 312 412
114 214 314 414
511 611 711 811
512 612 712 812
514 614 714 814
911 011
912 012
914 014
122
Middle
Bottom
(Standard 4PDT arrangement)
( 4PDT arrangement)
( 2PDT arrangement)
(Standard 4PDT + optional 6PDT arrangement)
111 211
112 212
114 214
311 411
312 412
314 414
01 02 03 04 05 06 07 08 09 10
11 12 13 14 15 16 17 18 19 20
21 22 23 24 25 26 27 28 29 30
Operation/control circuits
Continuous rating
shunt trip
4PDT 3PDT 3PDT
Standard equipment Optional Optional
( )