Professional Documents
Culture Documents
Adl Ap4g3
Adl Ap4g3
INSTRUCTION MANUAL
GENERAL-PURPOSE INVERTER
AP2G3-137~AP2G3-1185 AP2G3-337~AP2G3-3220 AP4G3-337~AP4G3-3220
THANK YOU VERY MUCH FOR YOUR PURCHASE OF ADLEE INVERTER APxG3 SERIES. PLEASE READ THIS INSTRUCTION MANUAL BEFORE INSTALLATION OF THE INVERTER.
CONTENTS
1. RECEIVING 2. SPECIFICATIONS 3. DIMENSION DRAWINGS 4. INSTALLATION 5. DESCRIPTION OF TERMINALS 6. DIGITAL OPERATION PANEL 7. FUNCTIONS DESCRIPTION 8. PROTECTIVE FUNCTIION 9. PRECAUTIONS 10. TROUBLESHOOTING 11. APPLICATION 12. INVERTER SELECTION 13. APPENDIX A. Optional braking resistor B. Terminal wiring diagram C. Remote operator 1 2 4 6 8 18 19 73 77 78 79 85 89 89 90 91
1. RECEIVING
Befor installation and wiring, check to see : (1) No damage is found on each product after shipping. (2) The product is as ordered (check the nameplate, voltage and frequency). (3) A set of inverter unit and instruction manual is contained in the package. For any irregularity, contact the sales shop where you purchased immediately. (4) Description of name plate VER A 01 SOFTWARE HARDWARE VERSION MODEL : AP 4 G3 - 3 37 AP series Voltage class : 2 : 200/220V 4 : 380/440V IPM AC drive
Max Applicable motor(4 pole) 37 : 3.7KW 55 : 5.5KW 75 : 7.5KW 110 : 11KW 150 : 15KW 185 : 18.5KW 220 : 22KW 1 : 1 3 : 3
2. SPECIFICATIONS
Model AP2G3
Voltage
1p 220VAC 10%
3p 220VAC 10%
Model No
137
155
175
1110
1150
1185
337
355
375
3110
3150
3185
3220
Input Frequency
50HZ/60HZ 5%
Output Voltage
3p 220VAC
Output Frequency
0.5 ~ 400HZ
Capacity (KVA)
6.1
8.8
11.4
16.4
21.3
26.7
6.5
9.2
12.6
17.6
23.3
29
34
Largest motor 3.7 KW ( 2.4.6 poles ) 5.5 7.5 11 15 18.5 3.7 5.5 7.5 11 15 18.5 22
Control
Braking
Acceleration time
Deceleration time
Use keyboard
PROG
Output signal
Cooling Method
Air-cooled
Dimension drawing
Fig 1
Fig 2
Fig 1
Fig 2
Weight ( KG )
5.5
6.2
6.6
17
18
18.5
5.5
6.2
6.6
17
18
18.5
19
Model Voltage Model No Input Frequency Output Voltage Output Frequency Output 8.5 Rated current (A) Capacity (KVA) 6.5 Largest motor 3.7 KW ( 2.4.6 poles ) Control Braking Over current Capacity Acceleration time Deceleration time 12 9.2 5.5 16.5 12.6 7.5 337 355 375
AP4G3 3p 380/440VAC 10% 3110 3150 3185 3220 50HZ/60HZ 5% 3p 380/440VAC 0.5 ~ 400HZ 23 17.6 11 31 23.6 15 38 29 18.5 45 34 22
Sine wave pulse width modulation Regenerative discharge braking 150% of rated current ( 1 minute) 0.1 ~ 6000 SEC 0.1 ~ 6000 SEC
PROG
for setting and confirm by Frequency Digital Use keyboard setting Analog Analog signal input DC 0~5V, 0~10V, 4~20mA Output signal Cooling Method Dimension drawing Weight ( KG ) 5.5 6.2 Fig 1 6.6 6.8 18 Open collector output 50v 50mA Max Air-cooled Fig 2 18.5 19.5
3. DIMENSION DRAWINGS
Unit : mm ( AP2G3-137 AP2G3-155 AP2G3-175 ) ( AP2G3-337 AP2G3-355 AP2G3-375 ) ( AP4G3-337 AP4G3-355 AP4G3-375 AP4G3-3110 )
Fig 1
4
Unit : mm ( AP2G3-1110 AP2G3-1150 AP2G3-1185 ) ( AP2G3-3110 AP2G3-3150 AP2G3-3185 AP2G3-3220 ) ( AP4G3-3150 AP4G3-3185 AP4G3-3220 )
Fig 2
5
4. INSTALLATION
Inadequate environment around installation site and installation surface can result in damage to the inverter. Before operating the APxG3 series inverter, please check the following points : (1) Avoid high temperature, high humidity, easy-to-dew ambient environment. Don expose to dust or dirt, corrosive gas, and coolant t mist, and direct sunlight. Place the unit in a well-ventilated room. (2) Avoid a place subjected to substantial vibration. (3) When installing the unit within the cabinet. Please pay attention to ventilation and limit the ambient temperature in between -10 ~ J 45 . (14K 113K J ~ ). (4) Use a nonflammable material, such a steel sheet on the wall for installation. (The rear side will generate heat) (5) Install the unit always vertically with a marginal spacing around.
15 cm
15 cm
10 cm
10 cm
5 cm
AIR FLOW
AIR FLOW
5. DESCRIPTION OF TERMINALS
(1) Main circuit connection diagram
R S T U V W P P R
IM
R S T P P U 2 1 V W
IM
Main circuit terminal Symbol R / L1 S / L2 T / L3 U V W P / P1 DC voltage terminal PR / P2 Regenerative braking resistor connecting terminal Inverter output terminal Terminal connecting with motor Inverter power source Terminal name Description Terminal connecting with power source Single phase input : L1/R, L2/S
Note : Release the internal braking resistor when connect external braking resistor.
RS485
ARR/RUN
MET
MA MB MC
SW1
RS485
J4
SIGNAL
ON
FA1
FA2
ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4
0 - 10V
1 2 3 4 ON
0 - 5V
1 2 3 4 ON 1 2 3 4 ON
4 - 20mA (Note 1)
Error setting
1 2 3 4
10
Keypad VR/F306
ON
F306
1 2 3 4 5 6 ON
Error setting
1 2 3 4 5 6 ON
Error setting
1 2 3 4 5 6
SIGNAL
ON
FA1
ON
FA2
0 - 10V
1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 1 2 3 4 5 6
0 - 5V
1 2 3 4 5 6 ON 1 2 3 4 5 6 ON
4 - 20mA ( Note 1)
Error setting
1 2 3 4 5 6
11
(4) Jumper setting 1. JP1 : FT2 over temperature selection 1 and 2 short circuit : PTC temperature switch. 1 2 and 3 short circuit : NTC temperature switch. 2 3 2. JP2 : MET output selection 1 and 2 short circuit : Connect to meter. 1 2 and 3 short circuit : Analog output. 2 (0~10VDC refer to 0~CD14) 3 3. JP3 : Pannel VR and F306 VR selection AP2G3-137~AP2G3-175, AP2G3-337~AP2G3-375, AP4G3-337~AP4G3-3110 1 and 2 short circuit : Pannel VR. 1 2 and 3 short circuit : F306 VR. 2 3 4. J3 : RUN/ARR Relay selection AP2G3-137~AP2G3-175, AP2G3-337~AP2G3-375, AP4G3-337~AP4G3-3110 Left : ARR Relay. Right : RUN Relay. 5. J4 : RUN/ARR Relay selection AP2G3-1110~AP2G3-1185, AP2G3-3110~AP2G3-3220, AP4G3-3150~AP4G3-3220 Up : RUN Relay. Down : ARR Relay. Note : When J3 or J4 select ARR, ARR/RUN terminal is RUN open collector output and MA/MB/MC Relay is ARR. When J3 or J4 select RUN, ARR/RUN terminal is ARR open collector output and MA/MB/MC Relay is RUN.
12
HZ
Ground VR5KB
FAN
Relay ARR/RUN
AP2G3-137~175BAP2G3-337~375BAP4G3-337~3110
6 H
10
11
12
13
14
15
ARR/RUN
16
17
18 MB
19 MC
20 A
21 B
22 C
FT2 RST
MET MA
HZ
Ground VR5KB
Relay ARR/RUN
AP2G3-1110~1185BAP2G3-3110~3220BAP4G3-3150~3220
13
Control circuit terminal Symbol Terminal FG1 10V GND FA1 FA2 H COM FWD REV CF1 Multistage speed terminal CF2 Ground terminal 1 Analog source Analog common terminal Free analog terminal 1 Free analog terminal 2 Ref. voltage Common terminal Forward operation Reverse operation Description Grounding Power source +10V of analog terminals Common terminal of free analog terminals See functions description (CD44) See functions description (CD45) Basic source (+10V) terminal for frequency Common terminal of control board Forward operation / stop terminal Reverse operation / stop terminal
CF1 OFF ON OFF ON CF2 OFF OFF ON ON SPEED SPEED - 1 SPEED - 2 SPEED - 3 SPEED - 4
Multi function terminal 1 Multi function terminal 2 Reset Operation output terminal Frequency arrival signal Frequency meter terminal Alarm output A Alarm output C Alarm output B
See functions description (CD42) See functions description (CD43) Reset Open collector output 50Vdc 50mA Max. 0~100% duty open collector output or 0~10VDC output (0~CD14) Fault alarm contact (normal open) Fault alarm contact (common) Fault alarm contact (normal close) Relay output contact (normal open)
14
(6) WIRING 6-1 Wiring of main circuit 1.AP2G3 1 power source terminal connect L1/R and L2/S. 2.AP2G3 3 and AP4G3 3 POWER SOURCE power source terminal connect L1/R, L2/S and L3/T.
APxG3-Series
THRY U V W E
IM
6-2 Wiring equipments Select the wiring equipment and wiring size, refer to the table below. 1. On the input power side, a molded case circuit breaker (MCCB) to protect inverter primary wiring should be installed. 2. A leakage current breaker threshold of 200mA and above, or of inverter use is recommended. 3. Use of input side magnetic contactor. An input MC can be used to prevent an automatic restart after recovery from an external power loss during remote control operation. However, do not use the MC frequently for start/stop operation, or will lead to a reduced reliability. 4. In general, magnetic contactors on the output of the inverter, Should not be used for motor control. Starting a motor with the inverter running will cause large surge currents and the inverter overcurrent protector to trigger.
Model Model No Capacity (KVA) Current (A) AP2G3 AP4G3 137 155 175 1110 1150 1185 337 355 375 3110 3150 3185 3220 337 355 375 3110 3150 3185 3220 6.1 16 20 18 8.8 11.4 16.4 21.3 26.7 6.5 23 30 35 30 50 50 43 75 65 56 100 80 70 125 93 17 20 18 9.2 12.6 17.6 23.3 24 30 35 33 50 50 46 75 65 61 100 80 29 76 125 93 34 90 150 93 6.5 9 15 12 9.2 12.6 17.6 23.6 12 20 18 17 30 18 23 50 35 31 50 48 29 38 75 50 34 45 75 50
Circuit Breaker (MCCB) (A) Electro-Magnetic Contactor (A) Thermal relay RC value (A)
15
20
28
40
55
67
15
20
28
40
55
67
80
6.8
15
20
28
40
40
15
6-3 Surge absorber In order to prevent malfunction, provide the surge absorber on the coils of the electromagnetic contactors, relays and other devices which are to be used adjacent of the inverter. 6-4 Cable size and length If the inverter is connected to a distant motor (especially when low frequency is output), motor torque decreases because of voltage drop in the cable. Use sufficiently heavy wire. Changing the carrier frequency reduce RF1 noise and leakage current. (Refere to the table below)
Distance under INVERTER MOTOR 25M APxG3 SERIES under 50M under 100M above 100M
16
6-5 Wiring and cautionary points A. Main circuit 1. Dont connect the cables of the power supply side (L1/R,L2/S,L3/ T) to the U, V and W output terminals for the motor. 2. Dont connect any electromagnetic contactor between the inverter and motor. If it is inevitable, turn on the contactor when both the inverter and motor are both at stand still. 3. Dont put the advance phase capacitor between the inverter and motor. 4. Put MCCB in the input power supply. B. Control signal circuit 1. Separate the power cables of main circuit etc. from the control cables of the sequence and analog signals by passing the cables through the different ducts. 2. Use twisted pair shielded wire for control signal and connect the shield to earth terminal at on end, COMMON terminal of control board. Leave the other end of shielding open. 3. Avoid common Ground leads between high and low level voltage equipment. C. Grounding 1. Be sure ground both the inverter and motor. 2. Keep grounded leads as short as possible. 3. Shield cables used to protect low-level signal leads should grounded at one end point. 4. Provide class 3 grounding (100 or less) for a terminal. [ 5. When grounding several inverters, make connections as shown below, no loop is produced as shown in FIG a , FIG b .
(a)
(b)
17
(c)
Model Indication
Digital Indication
SMART INVERTER
REV
FWD
FUNC
PROG
STOP
AP
LED Operating Indication
FW D REV
G3 DSP
Model Indication
VR
FREQ. SET
Key
Key function Forward run Reverse run Cursor movement Down Up Memory storage Function Stop
Description Commands forward run Commands reverse run Select the digit Decrease the parameter value Increase the parameter value Saves the setting vaule Press once to select function CDxx and press again to change its content Stop operation / Escape to standby mode
FUNC
STOP
18
7. FUNCTIONS DESCRIPTION
DISPLAY CODE CD00 CD01 CD02 CD03 CD04 CD05 CD06 CD07 CD08 CD09 CD10 CD11 CD12 CD13 CD14 CD15 CD16 FUNCTION DEFAULT VALUE 60.00HZ First speed setting 50.00HZ Parameter lock Acceleration time 1 Deceleration time 1 Jogging frequency Start frequency Jog mode Analog output gain 100.00HZ CW or CCW or CW / CCW Search speed function Analog / digital frequency Dynamic brake / Free running Terminal / Keypad command 1 Source operation command Maximum frequency limit 50.00HZ Minimum frequency limit Frequency display Scale 30.00 0.00HZ 1.00 0 120.00HZ 0 0 1 0 0 0 10.0Sec 10.0Sec 5.00HZ 0.50HZ 0 120.00HZ
19
DISPLAY CODE CD17 CD18 CD19 CD20 CD21 CD22 CD23 CD24 CD25 CD26 CD27 CD28 CD29 CD30 CD31 CD32 CD33 CD34 CD35 CD36 CD37
FUNCTION
1st Maximum voltage frequency 50.00HZ V/F pattern setting DC braking time DC braking power Torque boost Second speed setting Third speed setting Fourth speed setting Acceleration time 2 Deceleration time 2 Carrier frequency Output voltage gain Frequency jump 1 Frequency jump 2 Freuqency jump 3 Jump range Frequency reference bias Frequency reference bias direction Frequency gain The latest errors record Errors record 1 0 1.0Sec 10 0.0% 20.00HZ 30.00HZ 40.00HZ 10.0Sec 10.0Sec 16.0K 100.0% 0.00 0.00 0.00 0.50HZ 0.00 0 100.0 % NONE NONE
20
DISPLAY CODE CD38 CD39 CD40 CD41 CD42 CD43 CD44 CD45 CD46 CD47 CD48 CD49 CD50 CD51 CD52 CD53 CD54 CD55 CD56 CD57 CD58 CD59
FUNCTION Errors record 2 Errors record 3 Clear errors record HZ / RPM / AMP Display FT1 Multi-Function Terminal 1 FT2 Multi-Function Terminal 2 FA1 Free Analog Terminal 1 FA2 Free Analog Terminal 2 Reserved 5th speed setting 6th speed setting 7th speed setting 8th speed setting Dynamic Braking Energy Limit Version selector S curve 4 ~ 20mA speed command Frequency arrive signal range 2nd Maximum voltage frequency Reserved Auto running mode 1st step timer
0 0.01
21
DISPLAY CODE CD60 CD61 CD62 CD63 CD64 CD65 CD66 CD67 CD68 CD69 CD70 CD71 CD72 CD73 CD74 CD75 CD76 CD77 CD78 CD79~ CD99
FUNCTION 2st step timer 3st step timer 4st step timer 5st step timer Timer unit selector Stall prevention Overload current stall prevention Overload detect Overload setting Overload time setting 2nd stage overload time setting Reserved Communication loss time Communication error counter Address setting Transmission speed Transmission fault treatment Reserved Communicator protocol Reserved
DEFAULT VALUE 0.00 0.00 0.00 0.00 0 0 170.0% 0 150.0% 60.0SEC 20.0SEC
0.5SEC 3 1 0 3
22
Different initial set value for F50.0 : 50HZ power region and F60.0 : 60HZ power region. To change version see description of CD52. This function provides different standard setting values for 50/60HZ power region. F60.0 : 60HZ region for USA, CANADA etc. F50.0 : 50HZ region for Europe, Australia, Singapore etc. CD13 after finished parameter setting, please repower ON.
23
7-1. Function setting Before starting test run, check carefully the following points : (1) Be sure to connect the power supply to L1/R, L2/S, L3/T (input terminals) and the motor to U.V.W. (output terminals). (Wrong connections will damage the inverter.) (2) Check that the input power supply is 220VAC 10%, 50/60HZ 5% for AP2G3 and 380~440VAC 10%, 50/60HZ for AP4G3 series. 5% (3) Check the signal lines for wrong wiring. (4) Be sure to ground an earth terminal for personnel safety. (5) Check that other terminals than earth terminal are not grounded. (6) Check that the inverter is mounted on the wall. Also check that non-flammable material, U. V. W.(output terminals). (Wrong connection will damage the inverter.) (7) For operation start and stop, use
STOP
24
Operation 1-1. Pannel Action : (a) Press Speed : (a) Using increment step. or setting and confirm by Standby : (a) Press
STOP
for forward / reverse operation. to change motor speed with 1HZ to select the digit for quick
PROG
setting mode. 1-2. F306 Set CD13=1 and repower ON, operation same as 1-1 pannel. 1-3. RS485 communication control Set CD13=2 and set CD74~CD78. (Refer to CD74~CD78). Using 06H function write command to address 100(64H). 1 : CW, 2 : CCW, 3 : Stop, 4 : Clear fault. 1-4. Terminal control Set CD12=1, writing refer to 5-5 control circuit terminal wiring digaram.
25
key for increase or decrease the speed with 1HZ key to select the digit for quick setting. to save the setting value.
0 or 1 0
Function to prevent inadequate setting. To change the contents data of CD , set CD01=1 and press To lock the data set CD01=0 and press
PROG
PROG
first.
CD02 value corresponds to the time of acceleration from 0 to 50/ 60HZ.(For 120Hz. setting, the arrival time to 120Hz is double.)
0.1
26
6000 TIME(Sec)
0.1
6000 TIME(Sec)
Use terminal control refer to CD12 and CD42 setting, keyboard control refer to CD06.
0HZ
Time(Sec) Time(Sec)
Jog command
30HZ 0.5HZ
Time(Sec) Time(Sec)
Run command
27
0 or 1 0
0 : Normal 1 : Jog Mode 1. Set jogging operation from key panel 2. LED blinking in JOG mode.
&
The specification of the output meter is 10V(i.e. 1mA) full scale rating . Set by CD07 the value will be correspond to maximum correspond of MET terminal output signal.
30
400HZ(F)
0~2 0
0 : CW/CCW operation 1 : CW only 2 : CCW only If inadequate operation, the OPE2 warning message would be indicated.
28
0 or 1 1
CD09=0
CD09=1
0 or 1 1
0 : Operation frequency change by using or key and confirm by PROG . 1 : Operation frequency depends on the angle of the knob. Note : Using key to change motor speed when CD01=0, then OPE3 warning message would be indicated.
29
0 or 1 0
0 : Activates dynamic brake function when deceleration. 1 : Output cut off when accept a stop command to be free running.
0 or 1 0 1
0 : RUN/STOP Command from operation panel. 1 : RUN/STOP Command from control terminal. Note : If inadequate operation, the OPE4 warning message would be indicated.
0~2 0
0 : Normal 1 : F306 2 : RS485 communication Note : After finished this parameter setting, please repower ON.
30
Use the following equation to calculate the mechanical shaft speed in rpm. RPM = HZ Scale setting
31
When RPM > 9999 display for over range warning. On this condition. Setting CD41=1 for display shown RPM. Scale for various motors
Pole 2 4 6 8 10 12 Synchronous speed 50HZ 3000 1500 1000 750 600 500 60HZ 3600 1800 1200 900 720 600 Scale setting 60 30 20 15 12 10
Use 2nd V/F to setCD42(43)=7 and terminal FT1(2) close. 2nd V/F setting is at CD56. Constant power V V 100% setting range
F Constant torque
25HZ
400HZ
32
0~2 0
400(Hz)
25sec
0 ~ 250 10
250
DC Voltage
25sec
33
Torque boosting is used to compensate the torque lost due to stator resistance. Over boosting will cause over current and high acoustic noise. V 100% 25% 0%
0.5(CD17) (CD17)
34
Terminal order
ON
CF1 CF2
CD42 or CD43 setting FT1 or FT2=3, then CD25 or CD26 can be setted.
Acceleration OFF time 2 Deceleration time 2 Deceleration time 1 2CH=ON 2CH=ON Acceleration time 1 Acceleration time 2 2CH=OFF ON Deceleration time 2 Time(Sec)
To operate inverter with 2CH function, check to see CD42 or CD43=3. 2CH command inputs from FT1 or FT2 terminal.
35
Increase the carrier frequency would reduce motor noise but efficiency might be decreased. Reduce the carrier frequency would increase noise and reduce motor current, than gain better efficiency.
Reduce output voltage for energy saving operation. Setting CD44(45)=12 for FA1 (FA2) terminal control. V 100% 50% (HZ)
36
Speed command
37
Analog input
0 or 1 0
Analog input
38
0 or 1 0
Set CD40=1 and PROG clear CD36 ~ CD39 Error record the contents in CD36 ~ CD39 are NONE
39
0~2 0
0 = HZ Display 1 = RPM Display 2 = Current Display Setting corrent scale CD16 for R.P.M. display shown.
0 ~ 15 0
Function description -------Jog operation FWD command Jog operation REV command ACC/DEC time 2 command Free running command 3 - wire sequence mode 5 - 8 Speed Setting Terminal 2nd V/F curve setting (CD56) Reserved
OH
CD42=5
CD12=1
40
Application circuit 8
R
12
12
STOP
FWD STOP R R
Control power
R and CONTROL POWER not necessary Remark: STOP command entry from control terminal 5 FT1 or 6 FT2, and set CD42(FT1)=5 or CD43(FT2)=5 before operation.
Non-latch trip protect and display OH when switch ON. (2) FT2=9 (Thermistor) 7 R NTC/PTC 13 JP1(FT2) L Free run when R is less than 1K[ H Free run when R is higher than 1K[
0 ~ 15 0
41
0 ~ 15 0
0 ~ 15 0
42
5th speed setting CD47 6th speed setting CD48 7th speed setting CD49 8th speed setting CD50
SPEED
CF3 CF2
CF1
1th speed setting OFF OFF OFF 2th speed setting OFF OFF 3th speed setting OFF 4th speed setting OFF 5th speed setting 6th speed setting 7th speed setting 8th speed setting ON ON ON ON ON ON ON OFF ON
For example, set 8th speed as follows : 1. CD12=1 (Terminal function) 2. CD42 or CD43=6 (Function command) (FT1 or FT2 CF3)
0 ~ 300% 100
The higher the percentage, the more braking energy. The lower the percentage, the lower braking energy. Description of regenerative discharge braking active period. 1. 0 ~ 100% Deceleration period 2. 101 ~ 200% Braking active period of (Decel/accel/constant frequency) 3. 201 ~ 300% Braking active period of (Decel/accel/constant frequency/stand-by) Remark : NO.1,2,3 are different working situations, but their braking energy ranges are 0 ~ 100%.
43
Select function CD52, then use UP/Down key to select F50.0/F60.0 Version. Press PROG to save it. System will return to the factory setting and go into waiting mode..
S curve CD53
0 ~ 10 0
Setting S curve non-Linear Accel/Decel Operation from 1 to 10. Setting 0 is normal operation without S curve.
F CD53=0 (Hz) CD53=3
CD53=7
TIME
Output Frequency
S Curve period
44
0~3 0
This function only effects in CD44(CD45)=8,9,10,13. Set FA1(FA2) for current signal (4-20mA). F 0 : No current signal application Fmax 1 : Current signal in terminal FA1 2 : Current signal in terminal FA2 3 : FA1 & FA2 current signal terminal Note : referenct to FA1(FA2) terminal Fmin 4mA setting for 4-20mA signal.
1.Signal output at running F. setting F.x(1-CD55%) for acceleration. 2.Signal output at running F. setting F.x(1+CD55%) for deceleration.
10%
Setting Frequency 1 Setting Frequency 2 10% 10% 10%
45
Set CD42(CD43)=7 define FT1(FT2) terminal for hardware V/F curve switcher. Open : select the 1st V/F curve preset in CD17 Close : select the 2nd V/F curve preset in CD56 V 100% 1 V/F CD17 (1st) CD56 (f) (2nd)
FT1 2 V/F
COM
0~5 0
System can operate at digital panel control only when set at auto-running mode. CD10=1 and CD12=1 are inactive.
SPEED SPEED SETTING TIMER SETTING 1th CD47 CD59 2th CD48 CD60 3th CD49 CD61 4th CD50 CD62 Master / suspend CD00 CD63 VALUE RANGE 0 ~ 400 UNIT Hz
0 ~ 15.00 hr.min
46
CD58 0 1 2 3 4 5 6
Auto running mode Speed with timing control disable Sequence running then constant speed running Sequence running then stop and repeat from 1st step for cycling Sequence running then stop and repeat from 1st step in reversed direction for cycling Sequence running, and repeat for cycling Sequence running then perform reverse direction and repeat for cycling Sequence running then stop
START 1th SPEED 1st step 2th SPEED 2nd step 3th SPEED 3rd step 4th SPEED 4th step Master speed / suspend 5th step
CD58=1
(S)
CD00 CD48 CD49 CD50 CD47
(T)
CD58=2
(S)
CD48 CD49 CD50 CD47 CD00
CD59 CD60 CD61 CD62 CD63 CD59 CD60 CD61 CD62 CD63 CD59
(T)
47
CD58=3
(S)
CD48 CD49 CD50 CD47 CD00 CD59 CD60 CD61 CD62 CD63 CD59 CD60 CD61 CD62 CD63 CD59 CD47 CD50 CD49 CD48
(T)
CD58=4
(S)
CD48 CD49 CD50 CD47 CD00
CD63 CD59
(T)
CD58=5
(S)
CD00 CD48 CD49 CD50 CD47
CD59
CD59 CD60 CD61 CD62 CD63 CD59 CD47 CD50 CD49 CD48 CD00
(T)
CD58=6
RPM
CD00
48
0 ~ 15Hr 0.01Hr.min
0 ~ 15Hr 0.00Hr.min
0 ~ 15Hr 0.00Hr.min
0 ~ 15Hr 0.00Hr.min
0 ~ 15Hr 0.00Hr.min
49
0~1 0
0 : hr.min 1 : min.sec Note 1 : CD64 cannot be reset to default value by CD52. Set CD64 as needs separately. Note 2 : In RS485 communication input, CD59~CD63 need to tranfer minimum unit. Ex CD64=0, CD59=2.3 CD59 contant for RS485 communication is 2 60+30=150(0096H).
0~1 0
0 : Disable 1 : Enable When enable CD65, if any overload over CD66 setting value during DEC period, inverter will increase DEC time to prevent inverter to go into fail safe mode.
20 ~ 250% 170%
Current
During ACC, if ACC time is too short or load is too heavy, the current will reach CD66 value, inverter will stop to ACC until current is lower than CD66 value.
Actual stall current limit=rate current CD66 percentage. Rate current number refers to section 2 table.
50
0~2 0
0 : Normal 1 : Overload detection and stop Motor stops operation if load condition is reached CD68 and CD69 setting. 2 : Two stages overload detection and stop (CD68<100% only). AC drive will limit output current at CD68 setting if load condition is reached CD68 and CD69 setting. And motor will stop operation if timing of limited output current is reached CD70 setting.
51
Set communication loss time. When communication loss time over CD72 setting, Inverter will active as CD76 selected. Note : This function does not effect in standby condition.
0 ~ 10 3
When communication error continuous time more than CD73 setting. Inverter will active as CD76 selected.
1 ~ 255 1
Each drive must have unique identified addrss if they are controlled by RS485 communication. Each address connot be duplicated. 0 : broadcast to all inverter.
0~3 0
Setting the transmission speed between computer and drive. 0 : 2400 bits/second. 1 : 4800 bits/second. 2 : 9600 bits/second. 3 : 19200 bits/second.
52
0~3 3
0 : Alarm and keep operation. 1 : Alarm and decelerate to stop. 2 : Alarm and free to stop. 3 : No alarm and keep operation. Use panel or write address 100=4 to clear the transmission fault. Note : Warning means Fault Relay active.
STOP
0~7 0
A. Date format 0 : 8,N,1 RTU (1 start bit+8 data bits+1 stop bit) 8,N,1 RTU (10-bit)(character frame in hexadecimal)
Start bit 0 1 2 3 4 5 6 7 Stop bit
1 : 8,N,2 RTU (1 start bit+8 data bits+2 stop bit) 8,N,2 RTU (11-bit)(character frame in hexadecimal)
Start bit 0 1 2 3 4 5 6 7 Stop bit Stop bit
2 : 8,E,1 RTU (1 start bit+8data bits+1 Even bit+1 stop bit) 8,E,1 RTU (11-bit)(character frame in hexadecimal)
Start bit 0 1 2 3 4 5 6 7 Even Stop Parity bit
53
3 : 8,O,1 RTU (1 start bit+8data bits+1 Odd bit+1 stop bit) 8,O,1 RTU (11-bit)(character frame in hexadecimal)
Start bit 0 1 2 3 4 5 6 7 Odd Stop Parity bit
4 : 8,N,1 ASCII (1 start bit+8data bits+1 stop bit) 8,N,1 ASCII (10-bit)(character frame in hexadecimal)
Start bit 0 1 2 3 4 5 6 7 Stop bit
5 : 8,N,2 ASCII (1 start bit+8data bits+2 stop bit) 8,N,2 ASCII (11-bit)(character frame in hexadecimal)
Start bit 0 1 2 3 4 5 6 7 Stop bit Stop bit
6 : 8,E,1 ASCII (1 start bit+8data bits+1 Eveb bit+1 stop bit) 8,E,1 ASCII (11-bit)(character frame in hexadecimal)
Start bit 0 1 2 3 4 5 6 7 Even Stop Parity bit
7 : 8,O,1 ASCII (1 start bit+8data bits+1 Odd bit+1 stop bit) 8,O,1 ASCII (11-bit)(character frame in hexadecimal)
Start bit 0 1 2 3 4 5 6 7 Odd Stop Parity bit
54
B. Communication protocol Data contents are in hexadecimal with postive and negative format. 1. RTU
Start Address Function Data (n-1) ... Data 0 CRC CHK Low CRC CHK High End Check sum (CRCL) Check sum (CRCH) A silent interval of more than 10ms Contents of data : n*8-bit data, n30 A silent interval of more than 10ms 8-bit address 8-bit command
2. ASCII
STX Address Hi Address Lo Function Hi Function Lo Data (n-1) ... Data 0 LRC CHK High LRC CHK Low END Hi END Lo LRC check sum : 8-bit check sum consists of 2 ASCII codes. End characters : END Hi=CR(0DH) END Lo=LF(0AH) Contents of data : n*8-bit data consist of 2n ASCII codes. Start character=' : ' (3AH) Communication address : 8-bit address consists of 2 ASCII codes. Command code : 8-bit command consists of 2 ASCII codes.
55
CRC(Cyclical Redundancy Check) is calculated by the following steps: Step 1. Load a 16-bit register (called CRC register) with FFFFH. Step 2. Exclusive OR the first 8-bit byte of the command message with the low order byte of the 16-bit CRC register, putting the result in the CRC register. Step 3. Shift the CRC registers one bit to the right with MSB zero filling. Extract and examine the LSB. Step 4. If the LSB of CRC register is 0, repeat step 3, else Exclusive OR the CRC register with the polynomial value A001H. Step 5. Repeat step 3 and 4 until eight shifts have been performed. When this is done, a complete 8-bit byte will have been processed. Step 6. Repeat steps 2 to 5 for the next 8-bit byte of the command message. Continue doing this until all bytes have been processed. The final contents of the CRC register are the CRC value. LRC (Longitudinal Redundancy Check) is calculated by summing up, module 256, the values of the bytes from Address to last data character then calculating the hexadecimal representation of the 2 s-complement negation of the sum. For example, refer to 06H at CD00=60.00HZ 34+06+00+00+17+70=C1H the 2 s-complement negation of C1H is 3FH C. ASCII code description
Character ASCII code Character ASCII code "0" 30H "8" 38H "1" 31H "9" "2" 32H "A" "3" "4" "5" "6" "7" 33H 34H 35H 36H 37H "B" "C" "D" "E" "F"
D. Function code 1. 03H : Read AC drives setting 2. 06H : Write parameter setting into AC drive 3. 08H : Communication loop detection
56
(1) 03H : Read AC drive's setting Computer command message D1 : Communication address D2 : Function code D3 : Parameter number (H) D4 : Parameter number (L) D5 : Quantity of parameter (H) (word count) D6 : Quantity of parameter (L) (word count) D7 : CRCL D8 : CRCH Drive response message D1 : Communication address D2 : Function code D3 : Quantity of parameter (byte count) D4 : Content of data (H) D5 : Content of data (L) ... Dn-1 : CRCL Dn : CRCH (00~FFh) (03h) (00h) (0~67h) (00h) (00~10h) (0~FFh) (0~FFh) (01~FFh) (03h) (00~20h) (0~FFh) (0~FFh) (0~FFh) (0~FFh)
Example : Read two parameters of AC drive address52(34H) from CD22. CD22=20.00(07D0H) CD23=30.00(0BB8H). 1. RTU
Computer command message D1 Address D2 Function D3 Start address (H) D4 Start address (L) D5 # of data (H) D6 # of data (L) D7 CRCL D8 CRCH 34H 03H 00H 16H 00H 02H CRCL CRCH AC drive response message D1 Address D2 Function D3 Quantity of data (count by byte) 34H 03H 04H 07H D0H 0BH B8H CRCL CRCH
D4 CD22 content (H) D5 CD22 content (L) D6 CD23 content (H) D7 CD23 content (L) D8 CRCL D9 CRCH
57
2. ASCII
Computer command message STX D1 Address '3' Address '4' Function '0' Function '3' Start address '0' Start address '0' Start address '1' Start address '6' # of data '0' # of data '0' # of data '0' # of data '2' count by word '2' D7 D7 LRC HI D8 LRC LO END HI END LO LRC HI LRC LO 0D 0A 3A 33 D1 34 30 D2 33 30 D3 30 31 D4 36 30 D5 30 30 D6 32 AC drive response message STX Address '3' Address '4' Function '0' Function '3' # of data '0' count by byte '4' CD22 content '0' CD22 content '7' CD22 content 'D' CD22 content '0' CD23 content '0' CD23 content 'B' CD23 content 'B' CD23 content '8' 3A 33 34 30 33 30 34 30 37 44 30 30 42 42 38 LRC HI LRC LO 0D 0A
D2
D3
D4
D5
D6
58
Note 1 : The parameter values can be in integer and decimal. Each value has different process to read and write. Refer to 8-1 lists to find out the minimum unit and value range for each parameter. The following value processing description (Note 2~3), each hexadecimal value has 4 numbers. First two numbers are D4, last two numbers are D5. Note 2 : Processing integer number Transfer value into hexadecimal value. The first two numbers is D4 and the last two numbers is D5. Ex. Speed=1710 rpm 1710(decimal)=06AE(hexadecimal) D4=06H D5=AEH Note 3 : Processing decimal number Using following methods to process if the minimum parameter value is decimal number. Minimum unit by 1st decimal number : The original value times 10 to be a new number. Minimum unit by 2nd decimal number : The original value times 100 to be a new number. Then, Use this new number to tansfer value into hexadecimal value. Returning numbers to original value, the numbers need to divide by 10 or 100 if they have been timed by 10 or 100. The first two numbers is D4 and the last two numbers is D5. Ex. Acc. time 1 CD02=60.0 sec 60.0 10=600(decimal)=0258(hexadecimal) D4=02H D5=58H The value needs to divide by 10 when it returns to original shape.
59
(2) 06H : Write parameter setting into AC drive Computer command message D1 : Communication address D2 : Function code D3 : Parameter number (H) D4 : Parameter number (L) D5 : Content of data (H) D6 : Content of data (L) D7 : CRCL D8 : CRCH AC drive response message D1 : Communication address D2 : Function code D3 : Parameter number (H) D4 : Parameter number (L) D5 : Content of data (H) D6 : Content of data (L) D7 : CRCL D8 : CRCH (00~FFh) (06h) (00h) (0~4Eh) (0~FFh) (0~FFh) (0~FFh) (0~FFh) (01~FFh) (06h) (00h) (0~4Eh) (0~FFh) (0~FFh) (0~FFh) (0~FFh)
Computer write CD00 content (60.00HZ) to inverter address=52 1. RTU Computer command message
D1 D2 D3 D4 D5 D6 D7 D8 34H 06H 00H 00H 17H 70H CRCL CRCH
60
2. ASCII
Computer command message STX D1 Address '3' Address '4' Function '0' Function '6' Number of parameter '0' Number of parameter '0' Number of parameter '0' Number of parameter '0' CD00 content '1' CD00 content '7' CD00 content '7' CD00 content '0' 3A 33 D1 34 30 D2 36 30 D3 30 30 D4 30 31 D5 37 37 D6 30 LRC HI LRC LO 0D 0A AC drive response message STX Address '3' Address '4' Function '0' Function '6' Number of parameter '0' Number of parameter '0' Number of parameter '0' Number of parameter '0' CD00 content '1' CD00 content '7' CD00 content '7' CD00 content '0' 3A 33 34 30 36 30 30 30 30 31 37 37 30 LRC HI LRC LO 0D 0A
D2
D3
D4
D5
D6
61
Computer command message inverter address=52, foward run at 60.00HZ 1. RTU Step 1. Write CD00=60.00HZ(6000=1770H) to AC drive address=52 Computer command message
D1 D2 D3 D4 D5 D6 D7 D8 34H 06H 00H 00H 17H 70H CRCL CRCH
Note : When address 100=1, speed is depended on terminal setting (CF1, CF2, CF3) 2. ASCII Step 1. Write CD00(60.00HZ) to inverter address=52
Computer command message STX D1 Address '3' Address '4' Function '0' Function '6' 3A 33 D1 34 30 D2 36 AC drive response message STX Address '3' Address '4' Function '0' Function '6' 3A 33 34 30 36
D2
62
Computer command message D3 Number of parameter '0' Number of parameter '0' Number of parameter '0' Number of parameter '0' CD79 content '1' CD79 content '7' CD79 content '7' CD79 content '0' 30 D3 30 30 D4 30 31 D5 37 37 D6 30 LRC HI LRC LO 0D 0A
AC drive response message Number of parameter '0' Number of parameter '0' Number of parameter '0' Number of parameter '0' CD79 content '1' CD79 content '7' CD79 content '7' CD79 content '0' 30 30 30 30 31 37 37 30 LRC HI LRC LO 0D 0A
D4
D5
D6
D2
D3
D4
D5
63
Computer command message D6 CD31 content '0' CD31 content '1' 30 D6 31 LRC HI LRC LO 0D 0A
AC drive response message CD31 content '0' CD31 content '1' 30 31 LRC HI LRC LO 0D 0A
(3) 08H : Communication loop detection Computer command message D1 : Communication address D2 : Function code D3 : Data 1 D4 : Data 2 D5 : Data 3 D6 : Data 4 D7 : CRCL D8 : CRCH AC drive response message D1 : Communication address D2 : Function code D3 : Data 1 D4 : Data 2 D5 : Data 3 D6 : Data 4 D7 : CRCL D8 : CRCH (0~FFh) (08h) (0~FFh) (0~FFh) (0~FFh) (0~FFh) (0~FFh) (0~FFh) (0~FFh) (08h) (0~FFh) (0~FFh) (0~FFh) (0~FFh) (0~FFh) (0~FFh)
AC drive response messages need to be same as command message when do communication loop detection.
64
Ex. Write data 1=11, data 2=22, data 3=33 and data 4=44 to AC drive address 52(34H) 1. RTU
Computer command message D1 Address D2 Function D3 Data 1 D4 Data 2 D5 Data 3 D6 Data 4 D7 CRCL D8 CRCH 34H 08H 11H 22H 33H 44H CRCL CRCH AC drive response message D1 Address D2 Function D3 Data 1 D4 Data 2 D5 Data 3 D6 Data 4 D7 CRCL D8 CRCH 34H 08H 11H 22H 33H 44H CRCL CRCH
2. ASCII
Computer command message STX D1 Address '3' Address '4' Function '0' Function '8' Content1 '1' Content1 '1' Content2 '2' Content2 '2' Content3 '3' Content3 '3' Content4 '4' Content4 '4' 3A 33 D1 34 30 D2 38 31 D3 31 32 D4 32 33 D5 33 34 D6 34 AC drive response message STX Address '3' Address '4' Function '0' Function '8' Content1 '1' Content1 '1' Content2 '2' Content2 '2' Content3 '3' Content3 '3' Content4 '4' Content4 '4' 3A 33 34 30 38 31 31 32 32 33 33 34 34
D2
D3
D4
D5
D6
65
E. Communication error respond Once communication error happened, inverter will respond Function code and 80H and communication error code to master system. Communication error code definition
Error code 01H 03H 04H 05H 31~39H Description Function code error, only 03/06/08 available Illegal data address (data address is not available) Illegal operation command Check sum error Data error
66
2. ASCII
Start code Address (01) Function code & 80H (86) Error code (02) LRC (77) End code H End code L 3A 30 31 38 36 30 32 37 37 0D 0A
Ex. Write CD00=500HZ(C350H), but maximum value of CD00 is 400HZ. 1. RTU Computer command message
D1 D2 D3 D4 D5 D6 D7 D8 01H 06H 00H 00H C3H 50H CRCL CRCH
67
2. ASCII
Computer command message STX D1 Address '0' Address '1' Function '0' Function '6' Address content '0' Address content '0' Address content '0' Address content '0' CD00 content 'C' CD00 content '3' CD00 content '5' CD00 content '0' 3A 30 D1 31 30 D2 36 30 D3 30 30 D4 30 43 33 35 30 LRC HI LRC LO 0D 0A AC drive response message STX Address '0' Address '1' Function '8' Function '6' Error code '0' Error code '2' LRC HI '7' LRC LO '7' END HI END LO 3A 30 31 38 36 30 32 37 37 0D 0A
D2
D3
D4
D5
D6
68
0~4 3
0 : Normal 1 : Forward run 2 : Reverse run 3 : Stop 4 : Fail mode reset Note : 1. Fail mode reset by writting address 100 content=4. 2. Speed command is CD00, or using CF1/CF2/CF3 terminal to select 2 nd~8th speed(CD22~CD24, CD47~CD50)
Unit
0.01HZ
To know output frequency, using function 03H to read address 101 content.
Unit
0.1A
To know motor current, using function 03H to read address 102 content.
69
70
Setting sequence
Display indicator
FUNC
FUNC
Press "FUNC" again to change the parameter value Enable to change parameter
PROG
Press "PROG" to save the parameter and back to waiting mode Enter function mode Select function number 2 (acceleration time)
FUNC
FUNC
Press "FUNC" again to change the parameter value Select the first digit Increase the value to 3 Select the second digit Increase the value to 2
PROG
71
Setting sequence
FUNC
Description
Increase the value to 4 Select the second digit Increase the value to 1
FUNC
Press "FUNC" again to change the Maximum frequency limit Select the second digit Decrease the value to 90HZ
PROG
72
8. PROTECTIVE FUNCTION
A. Inverter self-checking errors
Program check sum error EP0 EEPROM access error EEP1 EEPROM check-sum error EEP2 Power device failure 1 PF01
Power device failure during acceleration
first
74
75
Over heat OH
Over temperature for external indicator. Refer to CD42 (FT1) or CD43 (FT2)
Over load OL
Load is over rating.
76
9. PRECAUTIONS
9-1 Prior to maintenance, check the following : (1) Before maintenance, be sure to turn the power off and wait until the LED digits vanish in the display. However, approx. 50 VDC still remains immediately after the display disappears, so wait a little bit longer. (2) When removing or re-installing a connector, do not pull the cable. (3) Take special care not to misplace the connector. Carefully note any disconnecting or poor contact. Be sure to tighten the terminals and connectors securely. (4) It should be noted that electronic equipment is not resistant to moisture and oil mist, and intrusion of dust or iron powder will damage the insulation, leading to an unexpencted accident. 9-2 Application precautions (1) Before you start operation, thoroughly check for erroneous wiring or short circuits in the motor or in the wiring between your motor and the inverter. Do not ground the neutral point of the motor with a star connection. (2) An inverter-driven run generates a certain amount of electromagnetic noise, as compared with that of driven directly by a commercial power supply. Thus you should be aware of such limitation when using an inverter-driven motor at a noise-sensitive site. (3) Before setting the maximum frequency at 60HZ or higher, confirm that this operation range is acceptable with that of your motor. (4) When you determine an appropriate inverter capacity, ensure that the rated current of the motor does not exceed , the inverter s rated current. (5) Install a mold-case circuit breaker (MCCB) at the , inverter s power supply end to protect the wiring.
77
10. TROUBLESHOOTING
Display symbol Cause of fault message contents Check point Suggested remedy
Review the power system. Turned on or Check that MCCB has been Replace MCCB turned on or no poor contact. The acceleration time is too short. Boost voltage too high Increase the acceleration time Reduce CD21 contents
PF01
Power device failure Check the motor is locked or Reduce the load during acceleration the load is too heavy factor Disconnecting the output wiring U.V.W. Restart (Run) the inverter check for the same message Check for sudden change in Power device failure load during constant frequency operation Check that the ambient temperature is too high The load GD is excessive Power supply voltage is too high Check around the noise Power device failure source. during stand-by Power supply voltage is too high. EEPROM access error EEPROM checksum error Rework with previous process. Check for the same message.
2
Repair
Eliminate sudden change in load Reduce the ambient temperature Set the deceleration time suitable for load GD2 Reduce th voltage within specified range Remove the cause Reduce the voltage
PF02
PF03
PF04
EEP1 EEP2
Repair
78
11. APPLICATION
EXAMPLE 01 : Use 2 external variable resistor for multistage speed command input. DESCRIPTION : CD10 = 1 ( Use frequency knob for 1st speed setting) CD12 = 1 ( External command) CD44 = 8 ( 2nd speed signal enter from FA1) SW1 = RUN / STOP SW2 = 1st / 2nd speed
RUN/STOP
79
EXAMPLE 02 : Normal DESCRIPTION : CD00 = Normal speed CD04 = Jog speed CD12 = 1 CD42 = 1 CD43 = 2
/ Jog operation ; User setting ; User setting ; Terminal command (For External) ; Define FT1 Terminal = JOGF function ; Define FT2 Terminal = JOGR function
7 S3 8 9 S1
12 FT1(JOGF) S2 13 FT2(JOGR)
80
EXAMPLE 03 : Master/slave driver system DESCRIPTION : Set FA1=13 for 1st (Master) speed signal input terminal. Set FA2=11 for maximum speed setting
A
0 - 100%
B
0 - 200%
C
0 - 50%
10V
FA1
FA2
GND rate A
10V
FA1
FA2
GND rate B
10V
FA1
FA2
GND rate C
10k
10k
10k
5KB Master
Function setting
Fmax (SPEED)
rate C
rate A
rate B
81
EXAMPLE 04 : Using VR for 3 stages DESCRIPTION : CD10 = 1 ; 1st speed single enter from terminal CD12 = 1 ; Terminal command (For External) CD44 = 8 ; 2nd speed single enter from FA1 CD45 = 9 ; 3nd speed signal enter from FA2
SPEED 1 2 3
FG1 10V GND FA1 FA2 H COMFWDREV CF1 CF2 FT1 FT2 RST ARR/RUN MET
MA MB MC
VR2
82
EXAMPLE 05 : Basic external control setup DESCRIPTION : CD07 = 120HZ ; See maximum value on the meter CD10 = 1 ; External analog(Pannel VR or F306 VR) CD12 = 1 ; External command
START
Full scale
83
ALARM
22(A)
START 30Vdc RY
STOP
RY
24(C)
23(B)
7(COM) RY 8(FWD)
84
Load type
Load characteristics
Load charcteristics
Operastion
Continuous operation Long-time operation at medium or low speeds Short-time operation Maximum required output(instantaneous) Constant output(continuous) Maximum rpm Rated rpm Power supply transformer capacity percentage impednace Voltage fluctuations Number of phases, singla phase protection Frequency
Power supply
Deterioration of Mechanical friction, losses in wiring load capacity Duty cycle modification due to age
85
Time Ratings
Overload Capacity
Starting torque
86
[ nT + nS ( kS - 1 ) ]
+ ( nS / nT )( ks - 1 )
= Pc1
[1
nT lm [ 1 + ( nS / nT )( kS - 1) ]
b 973 COS
tL
87
Description
b COS r
Pc1
1 + ( nS / nT )( ks - 1 )
Pc1 : Continuous capacity[KVA] kS : Motor starting current/motor rated current nT : Number of motors in parallel nS : Number of simultaneously started motors GD2 : Total (GD2) converted into motor shaft (kg-m2) tL : Load torque(kg-m) tA : Motor acceleration time
88
13. APPENDIX
A. Optional braking resistor
150
390 395
10
Remove build-in dynamic brake resistor. Connect a larger capacity resistor, the value bigger than the table below: Unit : Ohm
Model No AP2 AP4 37 40 160 55 20 80 75 15 60 110 11 30 150 8 30 185 8 22 220 8 22
20.5
89
MCCB Input power Forward run/stop Reverse run/stop Multistage speed 1 Multistage speed 2 Multi function 1 Multi function 2 Reset Motor
Grounding
90
C. Remote operator
UNIT : M/M
A-0000-F306G3 E-092A-010200 E-092A-030200 E-092A-050200 F306 Remote operator 1 meter extension cable 3 meter extension cable 5 meter extension cable
91
MEMO
MEMO
MEMO
MEMO
MEMO
MEMO
ADLEEPOWER
Taiwan
Tel No : 886-4-25622651 Fax No : 886-4-25628289 E-mail : webmaster@adlee.com URL : http://www.adlee.com
SERVICE OFFICE
Wu Han (China)
Tel No : 86-27-59322991 Fax No : 86-27-59322992
Hong Kong
Tel No : 852-24081937 Fax No : 852-24071036
Shanghai (China)
Tel No : 86-21-64843529 Fax No : 86-21-64837594