MAM6080M
MAM6080M
MAM6080M
MAM6080M
USER
MANUAL
Shenzhen Plot Electronic Co., Ltd specializes on the manufacture and R&D of air
compressor controller. We are devoted to win customer trust through our high quality
We try our best to ensure the completeness and correctness of the manual, but
PLOT Company shall reserve the rights for continuous research and improvement on
its products and assume no obligation for the modification and improvement on the
without notice.
Please feel free to contact our after-sale service center if you encounter any
Page 2 Total 35
NOTICE
Please read all the operation manual before operating the set and keep this manual for further
reference.
Installation position shall be considered carefully in order to ensure good ventilation and reduce
electromagnetic interference.
Wiring shall be performed respectively according to regulations for heavy and weak current to reduce
electromagnetic interference.
RC snubber must be connected to the two terminals of coil (such as AC contactor ,valve, etc),which
are controlled by relay output.
Correct ground connection (the third ground)can help increase product capacity of resisting signal
interference.
Features:
● Support motor frequency conversion; motor and fan frequency conversion.
● 7 inch color screen ,with button and touch penal.
● Support real time power consumption and accumulative power consumption measurement.
● More accurate in writing frequency to control inverter through 485 communication
● Free to control all inverter supporting MODBUS RTU protocol.
● High integration, high reliability, high cost performance
Page 3 Total 35
Contents
1 Basic operation ........................................................................................................................................................5
1.1 Button explanation........................................................................................................................................5
1.2 Indicator explanation ....................................................................................................................................6
1.3 Status Display and Operation .......................................................................................................................6
1.4 Run parameter...............................................................................................................................................7
1.5 User parameter..............................................................................................................................................9
1.6 Factory parameter .......................................................................................................................................12
1.7 Calibration parameter .................................................................................................................................13
1.8 Block Parameter..........................................................................................................................................13
1.9 Hardware parameter....................................................................................................................................14
1.10 Maintenance parameter.............................................................................................................................14
1.11 Inverter Set................................................................................................................................................15
1.12 Touch Calibration .....................................................................................................................................17
1.13 History Record..........................................................................................................................................17
1.14 Motor VSD ...............................................................................................................................................17
1.15 Fan VSD ...................................................................................................................................................20
1.16 Operation Authorization and Password ....................................................................................................22
2 Controller Function and Technical Parameter .......................................................................................................22
3 Model and Specifixation........................................................................................................................................23
3.1 Model explanation ......................................................................................................................................23
3.2 Power specification sheet for corresponding fan motor..............................................................................23
4 Installation .............................................................................................................................................................24
4.1 Mechanical Installation...............................................................................................................................24
4.2 Controller installation .................................................................................................................................24
5 Alarm function.......................................................................................................................................................27
5.1 Air Filter Alarm...........................................................................................................................................27
5.2 Oil Filter Alarm...........................................................................................................................................27
5.3 O/A Separator Alarm ..................................................................................................................................27
5.4 Lubricant Alarm..........................................................................................................................................27
5.5 Grease Alarm ..............................................................................................................................................27
5.6 Discharge High Temperature Alarm ...........................................................................................................27
6 Controller Protection .............................................................................................................................................27
6.1 Fan motor Protection ..................................................................................................................................27
6.2,Protection of Discharge Temperature High.................................................................................................28
6.3 Protection of fan motor anti-reversal ..........................................................................................................28
6.4 Protection of Air Pressure High ..................................................................................................................28
6.5,Protection of Sensor Fault ..........................................................................................................................28
6.6 Protection of low temperature.....................................................................................................................28
7 Trouble Shooting ...................................................................................................................................................28
8 Block control and network communication...........................................................................................................29
8.1 Block Control .............................................................................................................................................29
8.2 Network Communication............................................................................................................................30
9 Inverter Control .....................................................................................................................................................30
10 Schematic Diagram..............................................................................................................................................33
Appendix:Output Mode Introduction: ...................................................................................................................34
Page 4 Total 35
1 Basic operation
1.1 Button explanation
图 1.1.1
——Start Button:
When compressor is at stop status, press this button to start the compressor.
When compressor is set as master ( No.1 ) in block status ,press this button to start the compressor and activate
block mode function at the same time.
——Stop Button:
When the compressor is at running status, press this button to stop the compressor;
When compressor is set as master (No.1 ) in block status, press this button to stop compressor and block function
as well;
——Power:
Indicator is alight when controller is powered on
——Run:
Indicator is alight when motor is running
——Alarm:
Indicator is blinking when controller is alarming;
Indicator is alight when compressor is alarm and stop;
Indicator is off after error is cleared and reset.
Page 6 Total 35
After 5 seconds, the menu will switch as below:
User can enter the below menu through clicking MENU icons on the screen or press button” ”
Page 7 Total 35
Menu Preset Data Function
Page 8 Total 35
FAN OUTPUT
000.0 Kw Display the real time output power based on the current fan inverter.
POWER
FAN THIS
000000.00K Display the accumulative this power consumption based on the fan
POWER
w.H inverter real time output power
CONSUMPTION
FAN TOTAL
000000.00K Display the accumulative total power consumption based on the fan
POWER
w.H inverter real time output power
CONSUMPTION
FAN STATE Display in the controller fan status area based on the running status
0000
DISCRIPTION register data reads from fan inverter
ERROR Display in the controller error area based on the running error register
0000
DISCRIPTION data read from fan inverter
WRITE
000.0 Display the frequency based on the PID calculation
FREQUENCY
FAN OUTPUT
000.0 Hz Display the output frequency of current fan inverter
FREQUENCY
FAN OUTPUT
000.0 A Display the output current of current fan inverter
CURRENT
PROD DATE 0000-00-00 Display the production date
THIS RUN TIME 0000:00:00 Record compressor this run time
THIS LOAD
0000:00:00 Record compressor this load time
TIME
VERSION CK0000M0000
CHECK1 0000 3FFF
CHECK2 7FFFFFFF_1
5 6 7 8
● ● ● ●
5:In accordance with No.5 digital input state;
6:In accordance with No.6 digital input state;
INPUT STATE
7:In accordance with No.7 digital input state;
8:In accordance with No.8 digital input state;
Red circle of input state means terminal is connected; Orange circle of input state means
terminal is disconnected
14 13 12
● ● ●
14: In accordance with No.14 digital output state;
OUTPUT STATE 13: In accordance with No.13 digital output state;
12: In accordance with No.12 digital output state;
Red circle of input state means terminal is connected; Orange circle of input state means
terminal is disconnected
Page 9 Total 35
Touch operation:(base is yellow)
1, When the cursor is fixed here ,you
can revise the parameter by clicking
the data box directly if the password
has been verified already
2, If the password is not verified yet, a
password verification box will prompt.
Button operation shows as below:
1, In data checking mode, press left or
right button to enter data modification
mode;
2, In data checking mode, press up or
down button to move the cursor to next
Page 10 Total 35
SLEEP Set the backlight brightness of the controller in the case of no
0000
BACKLIGHT operation for a long time
WORK During manual operation, the backlight brightness, the higher the
0007
BACKLIGHT : data, the brighter the display(from level 1 to level 4)
Set the communication address in COMPUTER or BLOCK mode.
COM ADD: 0001
This address is unique for every controller in net
Set AIR P in VSD mode to keep running stable. When pressure is
fluctuated around this data, controller will adjust operating
MOTOR VSD P
00.70 frequency of inverter to control the pressure close to this data( This
(MPa)
data is only available in MOTOR VSD or MOTOR/FAN VSD
mode)
In VSD mode, set DISC T to keep running stable. When DISC T is
fluctuated around this data, controller will adjust operating
FAN VSD T(℃) 0078℃
frequency of fan inverter to control DISC T close to this data( This
data is only available in MOTOR/FAN VSD mode)
MANUAL : only when the pressure is above UNLD P, compressor
will unload automatically .For any other case ,the Load/Unload
MANUAL/A
LOAD MODE: function can only be executed by pressing “load/unload” key.
UTOMATIC
AUTOMATICAL: the load/unload function can be executed by the
fluctuation of AIR P automatically
LOCAL :only the button on the controller can turn on and turn off
the machine.
REMOTE: both the button on the controller and the remote control
LOCAL/RE button can turn on and turn off the machine;
START MODE:
MOTE Note: When one input terminal is set as REMOTE START
ENABLE, start mode is controlled by hardware status. It is remote
when terminal is close, it is local when terminal is open.
In this case, the set here is not available.
MOTOR Choose the corresponding compressor run mode according to
RUN MODE VSD/MOTO customer requirement and choose the corresponding schematic
R FAN VSD diagram for reference.
DISABLE: communication function is not activated.
COMPUTER COMPUTER: compressor can communicate with computer or DCS
COM MODE: /BLOCK/DIS as slave according to MODBUS-RTU. Baud rate:9600;Data
ABLE format:8N1;Parity bit: even parity check
BLOCK: compressors can work in a net
MPa: pressure unit displays as MPa
MPa/PSI/BA
PRESSURE UNIT: PSI: pressure unit displays as PSI
R
BAR: pressure unit displays as BAR
TEMPERATURE ℃:temperature unit displays as ℃
℃/℉
UNIT: ℉:temperature unit is displays as ℉
CHINESE/E ENGLISH: Displays in English
LANGUAGE:
NGLISH CHINESE: Displays in Chinese
USER User could modify the user password by old user password or
****
PASSWORD: factory password
Page 11 Total 35
1.6 Factory parameter
Factory parameter is used to store relative data. Factory password is required for check and
modification.
Page 12 Total 35
After turn on, if the detected temperature is lower than this value,
the controller will display low temperature and the compressor is
LOW TEMP PROT not allowed to start;
-0050
(℃): Two seconds after the controller turns on, if the detected
temperature is lower than this value, controller makes temperature
sensor fault and stop
SERIAL NO.: 12345678 The serial number from the manufacturer
PROD DATE: 2016-02-20 The production date
OIL FILTER RUN Record total running time of oil filter. If changing new oil filter,
0000
TIME(H) the data should be reset by manual operation.
O/A SEPERATOR Record total running time of O/A separator. If changing new
0000
RUN TIME(H) O/A separator, the data should be reset by manual operation
Page 14 Total 35
AIR FILTER RUN Record total running time of air filter .If changing new air filter,
0000
TIME(H) the data should be reset by manual operation
LUBRICANT RUN Record total running time of lubricant. If changing new
0000
TIME(H) lubricant, the data should be reset by manual operation
GREASE RUN TIME Record total running time of grease. If changing new grease, the
0000
(H) data should be reset by manual operation
1, Alarm prompt when total running time of oil filter is above
OIL FILTER MAX the set data .
2000
RUN TIME(H) 2,Set this data to “0000” , alarm function for oil filter running
time is not activated
1, Alarm prompt when total running time of O/A separator is
O/A SEPERATOR
above the set data.
MAX RUN 2000
2,Set this data to “0000” ,alarm function for O/A separator
TIME(H)
running time is not activated
1, Alarm prompt when total running time of air filter is above
AIR FILTER MAX the set data.
2000
RUN TIME(H) 2,Set this data to “0000” , alarm function for air filter running
time is not activated
1, Alarm prompt when total running time of lubricant is above
LUBRICANT MAX the set data.
2000
RUN TIME(H) 2, Set this data to “0000”, alarm function for lubricant running
time is not activated.
1, Alarm prompt when total running time of grease is above the
GREASE MAX set data.
2000
RUN TIME(H) 2,Set this data to “0” , alarm function for grease running time is
not activated
Page 16 Total 35
1.12 Touch Calibration
Touch calibration is used to adjust touch accuracy. Touch calibration password is required for adjustment.
After entering touch calibration menu, use fingertip or other tool with sharp head to click the "+" icon that
appears on the screen, Press “FINISH” button to restart and save the modification ; If user wants to calibrate
again, press “CALBR” button to re-operate..
Page 17 Total 35
When motor run time under min frequency reach the value set
here, stop running automatically and display LOW FREQ STOP.
LOW FREQ STOP
0000 After pressure is lower than the loading pressure, start
DELAY (S)
automatically.
When it set to 0, the function is invalid.
MOTOR PROP Track speed of PID TARGET P , the bigger the data, the faster
0010
GAIN the track; the smaller the data, the slower the track
Track the speed of PID TARGET P and STEADY STATE
ERROR, the bigger the data ,the faster the track and smaller the
MOTOR INT GAIN 0012
STEADY-STATE ERRORS; the smaller the data ,the slower
the track and bigger the STEADY-STATE ERRORS
Track the hysteresis system(such as temperature) ,it is not used
MOTOR DIFF GAIN 0000
very often and normally set as “0000”
MOTOR MAX FREQ
180.0HZ The maximum operating frequency in loading status
(HZ)
In the process of adjustment, The minimum operating frequency
MOTOR MIN FREQ
040.0HZ when pressure is over the LOAD P pressure and not reach the
(HZ)
UNLD P
MOTOR UNLD
025.0HZ Permitted operating frequency in UNLD MODE
FREQ(HZ)
MOTOR INVERTER Set the MOTOR VSD ADD and keep it consistent with VSD
001
ADD COM ADD
Use for constant pressure control.
SPEED ADJUST Range: 0~1.0
01.00
COEF The larger this value is, the more significant the down-clocking
effect is at a constant pressure point.
Controller can prestore at most 10 different inverter
MOTOR INVERTER
ATV61 communication address ( Inverter should support MODBUS
MODEL
RTU protocol for communication )
Page 18 Total 35
1、INVERTER START MODE to COM ON-OFF:
SLOW :When controller receives stop command, INLET
VALVE terminals will open。Controller sends stop
command to inverter to slow stop inverter
FREE : When controller receives stop command, INLET
VALVE terminals will open。Controller sends write
frequency through RS485.Controller frequency will
decrease and send stop command to inverter 1S
MOTOR STOP before stop delay finished.
SLOW/FREE
MODE 2、INVERTER START MODE to TERMINAL ON-OFF:
SLOW: When compressor receives stop command, INLET
VALVE terminals will open and MOTOR
INVERTER RUN terminal will open. The compressor
will stop according to STOP DELAY set.
FREE: When compressor receives stop command, Inlet valve
will open. MOTOR INVERTER RUN terminal will
keep closed to control inverter frequency decreasing
and it will open until 1 S before STOP DELAY finishes
COM ON-OFF : Start or stop inverter through RS485
COM TERMINAL ON-OFF:Start or stop inverter through digital
INVERTER START ON-OFF/ input
MODE TERMINAL Note:
ON-OFF 1 : Controller set should be accordance with INVERTER
START MODE
INVERTER START Maximum allowable time Controller sends start command to
06
NO. inverter with no response.
INVERTER STOP Maximum allowable time Controller sends stop command to
06
NO. inverter with no response.
VSD MOTOR
POWER
0000000.0 Set the accumulative motor VSD running power consumption.
CONSUMPTION
Kw.H
MOTOR INVERTER Press start button, motor sends start command to inverter after
001.0
DELAY(S) this set time.
ENABLE/DI is used to enable and disable the air supply mode function. See
DISCH AIR MODE
SABLE the appendix for related introduction.
In constant power running mode, when pressure is above the
CONSTANT POWER
0.60 data set here, Max output frequency is set as CONSTANT
PRESSURE 1(MPa)
POWER FREQUENCY1
CONSTANT POWER In constant power running mode, when pressure is above the
PRESSURE 2(MPa) 0.70 data set here, Max output frequency is set as CONSTANT
POWER FREQUENCY2
CONSTANT POWER In constant power running mode, when pressure is above the
PRESSURE 3(MPa) 0.80 data set here, Max output frequency is set as CONSTANT
POWER FREQUENCY3
Page 19 Total 35
In constant power running mode, when pressure is above the
CONSTANT POWER
0.90 data set here, Max output frequency is set as CONSTANT
PRESSURE 4(MPa)
POWER FREQUENCY4
CONSTANT POWER In constant power running mode, when pressure is above the
PRESSURE 5(MPa) 1.00 data set here, Max output frequency is set as CONSTANT
POWER FREQUENCY5
CONSTANT POWER In constant power running mode, when pressure is above the
PRESSURE 6(MPa) 1.10 data set here, Max output frequency is set as CONSTANT
POWER FREQUENCY6
CONSTANT POWER In constant power running mode,when pressure is above the data
PRESSURE 7 (MPa) 1.20 set here, Max output frequency is set as CONSTANT POWER
FREQUENCY7
CONSTANT POWER
180.0 See Note1:
FREQUENCY 1(HZ)
In constant power running mode, when pressure is above the
CONSTANT POWER
0.60 data set here, Max output frequency is set as CONSTANT
PRESSURE 1(MPa)
POWER FREQUENCY1
CONSTANT POWER In constant power running mode, when pressure is above the
PRESSURE 2(MPa) 0.70 data set here, Max output frequency is set as CONSTANT
POWER FREQUENCY2
CONSTANT POWER In constant power running mode, when pressure is above the
PRESSURE 3(MPa) 0.80 data set here, Max output frequency is set as CONSTANT
POWER FREQUENCY3
In constant power running mode, when pressure is above the
CONSTANT POWER
0.90 data set here, Max output frequency is set as CONSTANT
PRESSURE 4(MPa)
POWER FREQUENCY4
CONSTANT POWER In constant power running mode, when pressure is above the
PRESSURE 5(MPa) 1.00 data set here, Max output frequency is set as CONSTANT
POWER FREQUENCY5
CONSTANT POWER In constant power running mode, when pressure is above the
PRESSURE 6(MPa) 1.10 data set here, Max output frequency is set as CONSTANT
POWER FREQUENCY6
Note 1:In constant power running mode
CONSTANT POWER PRESSURE 1<= CONSTANT POWER PRESSURE 2<= CONSTANT POWER
PRESSURE 3<= CONSTANT POWER PRESSURE 4<= CONSTANT POWER PRESSURE 5<=
CONSTANT POWER PRESSURE 6<= CONSTANT POWER PRESSURE 7
Note 2:CONSTANT POWER FREQUENCY 1>= CONSTANT POWER FREQUENCY 2>= CONSTANT
POWER FREQUENCY3>= CONSTANT POWER FREQUENCY 4>= CONSTANT POWER
FREQUENCY 5>= CONSTANT POWER FREQUENCY 6>= CONSTANT POWER FREQUENCY 7
Note 3:Suppose M>N,When CONSTANT POWER PRESSURE N set to 00.00,CONSTANT POWER
PRESSURE M and CONSTANT POWER FREQUENCY M,the set is invalid.
Note 4: When constant power function is not required,set CONSTANT POWER PRESSURE to 00.00MPa
Page 21 Total 35
COM/
FAN INVERTER START
TERMIN Set fan inverter start mode
MODE
AL
VSD FAN ELEC(Kw.H) 000000.00 VSD fan power consumption
Page 22 Total 35
2.8 Temperature protection: when actual temperature measured is higher than temperature set; response
time≤2s;
2.9 Contact capacity of output relay: 250V,5A;Contact endurance: 500000 times;
2.10 Current error is less than 1.0%;
2.11 points of RS485communication port. 1 point is for block mode or computer communication;
The other point is for inverter communication like reading inverter run parameter, controlling inverter
on-off or adjusting inverter frequency;
2.12 Remote control compressor: When set as REMOTE, user can remotely control the compressor.
6080M controller
Model
Page 23 Total 35
4 Installation
The CT shall be installed at a place where the current of fan cable can be measured, thus, controller can
be set according to instructions on fan motor nameplate, and the detailed dimension is shown as below:
A
B
Page 24 Total 35
Page 25 Total 35
4. 2.1 Controller structure dimension
Note:Though rear cabinet is 190.93mm,the hole size should be at least 206mm.After connect the cable in the
rear cabinet, there will be about 10-15mm more space requested. You can save the step of dispatch cable when
install controller.
Page 26 Total 35
5 Alarm function
6 Controller Protection
7 Trouble Shooting
High discharge Bad vent condition, Oil shortage Check the vent condition and lubricant
temperature etc. amount etc.
Temperature
Cable broken or PT100 failure Check the wiring and PT100
Sensor Failure
Pressure too high or the pressure
High Pressure Check the pressure and the pressure sensor
sensor failure
Pressure Sensor Cable broken, Sensor failure or
Check the wiring and pressure transmitter
Failure the cables connect reversely
Voltage too low, tubes block,
bearing wear off or other Check the set data, voltage, bearings, tubes
Fan overload
mechanical failure or wrong set and other mechanical system.
data etc.
Wrong Phase Phase sequence reversal or open
Check the wiring
Sequence phase
The controller detects that Check whether the inverter reports a
Inverter fault IO
the inverter fault output fault; check whether the fault output
Page 28 Total 35
terminal is disconnected. terminal of the inverter is
disconnected.
Inverter Wrong set of relatively parameter Check the set data ;Check the cable
communication of controller and inverter;
fault Communication cable loose
Pitcure8.1.1.1
Compressor with COM ADD 0001 is master, others are slave. Any one MAM series compressor can be set
as master or slave.
8.1.1 Block Control Set:
8.1.2.1 Set as Master:
Set rhe COM ADD in USER PARAMTER to 001
According to user requirement, set COM MODE, BLOCK NUMBER, TURN TIME, BLOCK LOAD P,
BLOCK UNLD P, BLOCK DELAY , BLOCK MODE .After set, controller needs to be powered off and restart
to save setting.
Page 29 Total 35
8.1.2.2 Set as Slave:
When MAM6080 controller serves as slave, it is only necessary to set COM MODE as BLOCK, COM
ADD can be set from2-16 in sequence according to the quantity of compressors, .BLOCK STATUS set as
SLAVE.
8.1.2 Start, Stop Block mode:
Make sure block cables connect correctly, also the parameter of compressor in block mode is set correctly.
Activate master, master controls the compressor in net automatically according to the AIR P detected. When
manually stop the master, block control stops at the same time, thus, master will no longer send command to
compressors in net.
9 Inverter Control
There is one spare port for RS485 to communicate with inverter. User can start or stop controller through
RS485,it transfers the output frequency based on PID calculation to inverter through 485 port. This is how to
adjust inverter output frequency and realize constant pressure and temperature. The baud rate is fixed as 9600BPS
when RS485 control inverter. Different inverter data format can be set in INVERTER SET in FACTORY
PARAMETER. MOTOR INVERTER is suggested to be set as 0001, FAN INVERTER is suggested to be set as
0002.
In order to be compatible with different inverter, set the item such as CURR(R) ADD, VOLT(R) ADD,
FREQ(R) ADD , POWE(R) ADD, RUN (W) ADD, ERR STATE(R) ADD, FREQ(W) , RESET(W) ADD. For
different inverter, amplification of current, voltage, frequency, power is different. Write a formula to every
parameter to transfer current, voltage, frequency, power of inverter to one digit data.
Relative parameter introduction is as below, please take the Schneider 67,71 inverter as example.
INVERT
0ATV61 Set inverter name
ER NAME:
RUN(W)
2135 Corresponding address 1 of inverter start command
ADD1:
RUN This data is inverter start data (please refer to communication
0001
VALUE: chapter in inverter manual for different inverter.)
RUN(W)
2135 Corresponding address 2 of inverter start command
ADD2:
RUN This data is inverter start data (please refer to communication
0001
VALUE: chapter in inverter manual for different inverter.)
STOP(W)
2135 Corresponding address of inverter stop command
ADD:
RUN This data is inverter start data (please refer to communication
0001
VALUE: chapter in inverter manual for different inverter.)
Page 30 Total 35
RESET(
2135 Corresponding address of inverter reset command
W) ADD:
RUN This data is inverter start data (please refer to communication
0001
VALUE: chapter in inverter manual for different inverter.)
FREQ(W) Corresponding register address of inverter running frequency
2136
ADD: source
The REC value is frequency value with one decimal. Use
formula to transfer to corresponding value based on different
inverter and send it to inverter.
Example: 50HZ running frequency,REC value:500
FREQ(R) REC*0001÷ For inverter with write frequency of 2 decimals, formula:
= 0001 REC**0001÷0010
For inverter with write frequency of 1 decimal, formula:
REC**0001÷0001
For the inverter whose max output frequency is in
corresponding with 10000,the formula :REC*0020÷0001
STATE(R
2135 Read inverter running status address
) ADD:
R AND Check if inverter has run the formula(please refer to
RUN S =
0001=0001 communication chapter in inverter manual)
Set the data format of controller and inverter communication.
This set should be consistent with inverter communication format
8N1-N: 1start bit,8 data bits,1 stop bit, no parity bit
COM
8N1-N 8N1-E: 1start bit,8 data bits,1 stop bit, even parity bit
FORM
8N1-O: 1start bit,8 data bits,1 stop bit, odd parity bit
8N2-N: 1start bit,8 data bits,2 stop bit, no parity bit
Note: Communicate with inverter, the baud rate is fixed:9600
FREQ(R)
0C82 Read inverter frequency address(refer to inverter manual )
ADD
FREQ(R) REC*0001÷ Calculate inverter frequency formula. Controller will transfer
= 0001 the frequency to one decimal.
VOLT(R)
0C88 Read inverter voltage address
ADD
VOLT(R) REC*0001÷ Calculate inverter voltage formula. Controller will transfer the
= 0001 voltage to one decimal
CURR(R)
0C84 Read inverter current address
ADD
CURR(R) REC*0001÷ Calculate inverter current formula. Controller will transfer the
= 0001 current to one decimal
POWE(R)
0C8B Read inverter power address
ADD
REC*1*001
POWE= Calculate inverter power
÷0001
ERR
8000 Read inverter error address
ADD
Page 31 Total 35
R AND
ERR S = Inverter reports error formula or not
0000≠0000
EMERGE
2135 Corresponding add of inverter emergency stop command
NCY ADD
RUN This data is inverter free stop data (please refer to
0001
VALUE communication chapter in inverter manual for different inverter.)
Firstly,controller sends 0 to corresponding register of“STATE(R) ADD” through inverter. After delay for a
while, sends 1 to corresponding register of“RUN1(W) ADD”. After another delay, reads“ RUN S”register, and
judges if the inverter is running based on the set formula. Calculate the output frequency based on the comparison
of pressure detected and pressure set and send this value to corresponding address of“FREQ(R) ADD” through
formula operation.
Schneidel inverter parameter set:
1、CON |AD2-
|AD1-|ADD :1
|EBr :96
|EFO :8N1
|EEO :15
CTL- | Fr1 :ndb
|rln
|PST
|CHCF :IO
|CD1 :ndb
Flt- | PTC-
|rST- | rSF :C107
Page 32 Total 35
10 Schematic Diagram
Page 33 Total 35
Appendix:Output Mode Introduction:
We add 4 control mode options to controller 6080、6090、6070. User can choose to
open or close this function. The introduction is shown as below:
Turn on “output option” in motor VSD parameter, than menu selection interface will
increase “output option”. Shown as below:
Click “output option” and enter the interface as shown in the below. Users can choose the proper speed
Mode A: In this mode, the motor is speeded up to motor rated frequency according to inverter
maximum acceleration performance after start. After running for some time, pressure is close to
constant pressure, then to judge whether brake intelligently according to pressure rise speed, and
stabilize pressure to a constant pressure point in one time. ( the old version software adopts the
model)
Mode B: (Overclocking operation) In this mode, the motor is speeded up to the corresponding
frequency value according to constant power pressure point set by users after start. After running
for some time, pressure is close to constant pressure, then to judge whether brake intelligently
according to pressure rise speed, and stabilize pressure to a constant pressure point in one time.
Page 34 Total 35
(New mode 1)
Mode C :( Overclocking and high speed operation). In this mode, the motor is speeded up to the
corresponding frequency value according to constant power pressure point set by users after start.
Make fastest air output. This mode will take full advantage of the air compressor. (New mode 2)
Mode L: This mode, based on the mode A, to reduces the running time in low frequency and to
Page 35 Total 35