NR 428 DTO R01 E - Electrical Systems On Board Offshore Unit
NR 428 DTO R01 E - Electrical Systems On Board Offshore Unit
NR 428 DTO R01 E - Electrical Systems On Board Offshore Unit
Rule Note
Note: this document is a complement to Rules for Classification and is intended to be used
in cases and conditions specified within these Rules; the requirements of this document are
applicable, in these conditions, to units or installations for which the contract of
construction is signed 3 months after the publication date of this Rule Note; however, the
Society may refer to the contents hereof, as and when necessary or appropriate.
Outside the scope of Classification, contents of this document, unless otherwise
specified, will be considered as requirements for Certification by Bureau Veritas.
Bureau Veritas decline any responsibilities or liabilities for consequences which may
result from the application of this document outside above mentioned cases and
conditions.
MARINE DIVISION GENERAL CONDITIONS
ARTICLE 1 4.1. The Rules, Guidance Notes and other documents
1.1. BUREAU VERITAS is a Society, the purpose of published by the Society endeavour to meet the state of
whose Marine Division is the classification of vessels, sea currently available technology at the time they are published.
and river units, offshore structures and craft of all kinds, Committees, consisting of personalities from the
collectively hereinafter referred to as "ships". International Maritime Industry, contribute to the development
The Society : of these documents.
- sets forth and develops Rules, Guidance Notes and The Society is not responsible for any inadequacy or
other documents; failure of such Rules, Guidance Notes or other documents as
- publishes Registers; a result of future development of techniques which could not
- issues Certificates, Attestations and Reports reasonably have been foreseen at the time of their
following its interventions. publications.
1.2. BUREAU VERITAS also participates in the application 4.2. BUREAU VERITAS is sole qualified to decide upon the
of National or International Regulations or Standards, in meaning, the interpretation and application of the documents
particular, by delegation from different Governments. mentioned above. Any reference to them is of no value if it
does not involve, accompany or follow a Society's
1.3. BUREAU VERITAS can also carry out Technical intervention.
Assistance missions and provide special services exceeding
the scope of classification, to which Particular Conditions will 4.3. The Society exercises due care and skill and acts in
then apply. a professional and workmanlike manner :
- in the selection of its surveyors,
1.4. BUREAU VERITAS is neither, and may not be - in the performance of its services, considering the
considered as, an underwriter, Consulting Engineer, Naval state of currently available technology at the time the
Architect, Shipbuilder or a Shipowner, and cannot assume services are being performed.
the obligations incumbent on such functions, even through its
experience enables it to answer enquiries concerning 4.4. Surveys conducted by the Society include, but are
matters not covered by its Rules, Guidance Notes or other not limited to, visual inspections, non-destructive testing,
documents. laboratory testing and underwater inspection by divers.
Survey practices and procedures are selected by the Society
ARTICLE 2 in its sole and absolute discretion based on its experience
2.1. Classification is the expression of confidence given and knowledge and according to generally accepted
by the Society to a ship, for a particular use or service and professional standards in the Industry.
for a certain period of time, by reference to its Rules,
Guidance Notes and other documents: this opinion expresses ARTICLE 5
only the strict personal view of the Society. It is represented 5.1. No report, statement, notation on a plan,
by a class published in the Register. review, certificate of class or any document or
information issued or given as part of the services
2.2. The documents issued pursuant to surveys carried provided by the Society shall be given any legal effect
out by the Society's surveyors according to the methods and of implication other than a representation that the
modalities mentioned in Articles 3 and 4 reflect the condition ship, structure, item of material, equipment or
of the ship at the time of the survey. It is the Owner's or his machinery or any other item covered by such
Agent's responsibility to maintain that condition until the next document or information has met one or more of the
survey required by the Rules. Society's Rules. Any such representation is issued
solely for the use of the Society, its committees and
ARTICLE 3 clients or other duly authorized entities and for no
BUREAU VERITAS other purpose.
- appraises specifications and drawings for the
construction of ships by reference to its Rules, 5.2. The classing of a ship, or the issuance of certificate
- inspects materials, machinery, equipment, fittings and with relation to, or in furtherance of the classification of a
other items used in the construction of ships, by ship or the performance of services by the Society, is not a
reference to its Rules, representation, statement or warranty of seaworthiness,
- surveys the construction of ships to ensure that they structural integrity, quality or fitness for a particular purpose
are built in accordance with the Society's published or service of any ship, structure, material, equipment or
Rules, machinery surveyed by the Society, beyond any
- classes ships in accordance with its Rules and representation set forth in the Rules of the Society.
publishes the ship's names in its Register,
- carries out periodic surveys of ships in service in 5.3. Nothing contained herein, or in any
order to ensure that the requirements for the information, report, certificate or like document
specified class are met. It is the owner's duty to issued in connection with or pursuant to the
report to the Society any incident or event affecting performance by the Society of its services, shall be
the condition of the ship or the need for repairs, deemed to relieve any designer, naval architect or
whatever their nature or extent. engineer, builder, manufacturer, shipyard, seller,
supplier, contractor or subcontractor, repairer, or
ARTICLE 4 owner, operator or other entity from any warranty or
other contractual obligations express or implied or
from any fault whatsoever, nor to create any right, ARTICLE 8
claim or benefit in any third party. 8.1. Any intervention of BUREAU VERITAS, whatever its
In particular, the Society does not declare the nature, whether completed or interrupted for any cause
acceptance or commissioning of a ship; that being the whatsoever, shall involve the payment of fees upon receipt
exclusive responsibility of the owner. of the invoice and the reimbursement of the expenses
The validity, application, meaning and interpretation of a incurred. Interests may be demanded in case of late payment.
Classification Certificate or any similar document or
information issued by the Society in connection with, or in 8.2. The class of a ship may be withheld or, if granted,
furtherance of the performance of its services, is governed suspended or withdrawn, in the event of non-payment of
by Rules of the Society which shall be the sole judge thereon, fees.
in its absolute discretion.
ARTICLE 9
ARTICLE 6 9.1. All plans, drawings, specifications and information
6.1. In providing services, information or advice, provided to the Society, or of which the Society may become
neither the Society nor any of its servants or agents reasonably aware in connection with the performance of its
warrants the accuracy of any information or advice services, shall be treated as confidential by the Society and
supplied. Furthermore, all express and implied shall not, without the prior consent of the party furnishing
warranties are specifically disclaimed. Except as set such document, be used for any purpose other than that for
out herein, and also in the case of the surveys which they are furnished.
mentioned in Article 1.2., neither the Society, nor any
of its servants or agents, shall be liable for any loss, 9.2. Records and other documents whatsoever relating to
damage or expense of whatever nature sustained by ships classed with the Society shall not be disclosed or
any person, in tort or in contract, due to any act or communicated by the Society to any third party but with the
omission or error of whatever nature, whether or not prior approval of the owner, unless it is in pursuance of an
negligent, and howsoever caused in any information order of the flag authorities or an injunction of a Court having
or advice given in any way whatsoever by or on behalf jurisdiction.
of the Society.
ARTICLE 10
6.2. Nevertheless, if any person uses the Society's Should a technical disagreement arise between the
services, and suffers loss, damage or expense requesting party and the BUREAU VERITAS surveyor, the
thereby, which is proved to have been due to any Society may, at the request of that party, designate another
negligent act, omission or error of the Society, its of its surveyors.
servants or agents, or any negligent inaccuracy in
information or advice given by or on behalf of the ARTICLE 11
Society, then the Society will pay compensation to 11.1. Any dispute over the interpretation, or the
such person for his proved loss, up to, but not enforcement of these General Conditions except as
exceeding, five times the amount of the fee - if any - regards article 8, or the performance of BUREAU
charged by the Society for the particular service, VERITAS' services, shall be submitted to arbitration in
information or advice and, if no fee is charged, London. Arbitration proceedings will be conducted
FRF 50,000. according to the English law on arbitration. The
Where the fees are related to a number of arbitrator shall be selected by the parties and, in case
services, the amount of fees shall be apportioned for they could not reach an agreement, he would then be
the purpose of the calculation of the maximum nominated by the President of the Law Society of
compensation, by reference to the estimated time England and Wales upon request of any party.
involved in the performance of each service.
Any liability for consequential damages is 11.2 Disputes arising out of the enforcement of
specifically excluded. the provisions of the article 8 shall be submitted to
In any case, whatever the amount of the fees, the the Court of Nanterre - France.
maximum damages payable by the Society shall be
not more than FRF 5,000,000.
ARTICLE 7
Requests for interventions shall, in principle, be submitted
in writing. They entail the acceptance without reservation, of
the present General Conditions and of Particular Conditions
which may be attached thereto.
CONTENTS
SECTION 1. GENERAL ...............................................................................................................1
1.1. Scope - classification requirements............................................................................................ 1
1.2. National Authorities requirements .............................................................................................. 1
1.3. Units............................................................................................................................................ 1
1.4. General requirements................................................................................................................. 2
1.5. Conditions of operation............................................................................................................... 2
1.6. Protection index ......................................................................................................................... 4
1.7. Maximum voltage ....................................................................................................................... 6
1.8. Essential services........................................................................................................................ 6
SECTION 4. CABLES................................................................................................................16
4.1. Choice of cables........................................................................................................................16
4.2. Current ratings...........................................................................................................................17
4.3. Cables installation .....................................................................................................................19
4.4. Type testing ...............................................................................................................................22
4.5. Routine testing...........................................................................................................................22
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
i
SECTION 6. ROTATING ELECTRICAL MACHINES ..........................................................32
6.1. General ..................................................................................................................................... 32
6.2. Generating sets - Prime movers ................................................................................................ 32
6.3. Permissible maximum temperature rise for electrical rotating machines................................. 33
6.4. Characteristics of d.c. generators.............................................................................................. 35
6.5. Characteristics of a.c. generators.............................................................................................. 36
6.6. Control gear of electrical rotating machines............................................................................. 37
6.7. Protection of the electrical rotating machines........................................................................... 37
6.8. Testing of electrical rotating machines..................................................................................... 37
6.9. Tests after construction.............................................................................................................. 39
SECTION 7. TRANSFORMERS..............................................................................................40
7.1. General ..................................................................................................................................... 40
7.2. Temperature rise of transformers.............................................................................................. 40
7.3. Service characteristics of transformers...................................................................................... 41
7.4. Protection of transformers......................................................................................................... 41
7.5. Testing of transformers.............................................................................................................. 41
SECTION 8. ACCESSORIES...................................................................................................43
8.1. General ..................................................................................................................................... 43
8.2. Connection boxes...................................................................................................................... 43
8.3. Socket-outlets............................................................................................................................ 43
8.4. Control gears and starters ......................................................................................................... 43
8.5. Requirements applicable to interrupting and protective devices.............................................. 43
8.6. Lighting fittings.......................................................................................................................... 44
8.7. Heaters...................................................................................................................................... 44
8.8. Electronic equipment ................................................................................................................ 45
8.9. Electrical equipment in paint stores and in the enclosed spaces leading to paint stores.......... 45
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
ii
SECTION 11. HIGH VOLTAGE INSTALLATIONS ...............................................................50
11.1. Scope .......................................................................................................................................50
11.2. General ....................................................................................................................................50
11.3. Rotating electrical machines....................................................................................................50
11.4. Transformers............................................................................................................................50
11.5. Switchboards ...........................................................................................................................51
11.6. Cables and cabling wires.........................................................................................................52
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
iii
SECTION 1. GENERAL
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
1
• power: kilowatts (kW); 1.4.3.3.
1.4.2. Low voltage or low power Where large equipment sets are concerned, the
vibration tests may be carried out separately on all
installations sub-sets; these sub-sets are to be connected to
the other parts of the equipment and be under
The installations not exceeding either 50 V or normal supply conditions.
20 kW (d.c. or a.c.), are specially considered;
some of the requirements of the present Rule Note During the test, equipment is to be under normal
may be dispensed with. power supply conditions; tripping point of pressure
and temperature switches is to be adjusted at 50 %
1.4.3. Spare parts of the measuring range.
1.4.3.1. 1.5.2.3.
The test is to be repeated with the equipment
In pursuance of Chapter 1 of Rules for
mounted successively in three mutually
Classification, spare parts listed in the present Rule
perpendicular directions, one of them being vertical.
Note are given for information only.
1.4.3.2. 1.5.2.4.
Within the frequency range considered, a
Spares will be carefully labelled and wrapped.
sweeping is carried out (maximum frequency
variation: 1 octave per min) to search possible
resonance frequencies.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
2
1.5.2.5. • in all cases, from the upright condition to the
Equipment is to operate satisfactorily under the values of inclination specified, if any, in the
following vibration conditions: Society's Rules for Classification applicable
to the unit or installation considered.
• from 2 Hz to 13,2 Hz, with a displacement
amplitude of ± 1,0 mm; 1.5.4. Marine environment
• from 13,2 Hz to 100 Hz, with an acceleration
equal to 0,7 g. 1.5.4.1.
Electrical equipment is are to operate
1.5.2.6.
satisfactorily under the following temperature and
Equipment fitted on diesel engines and humidity conditions:
compressors or in steering gear room (solenoid
valves, pressure, temperature, level, speed and flow • as a general rule, standard ambient
switches, etc.) as well as fire detectors, is to temperature of the air is 45°C with an
operate satisfactorily under the following vibration average relative humidity of 70 %;
conditions: temperature of the sea cooling water is to be
30°C;
• from 2 Hz to 25 Hz, with a displacement
amplitude of ± 1,6 mm; • on board units not liable to operate in tropical
waters, the standard ambient temperature is
• from 25 Hz to 100 Hz, with an acceleration to be 40°C and the sea cooling water
equal to 4 g. temperature 25°C;
Note: very special condition may exist, for instance on • on board permanent or fixed installations, to
exhaust manifold of Diesel engines and especially for medium most severe temperature and humidity
and high speed engines. Values may be obtained from the conditions liable to be encountered on site.
concerned engine manufacturer. Otherwise, the following
Note: other conditions may be applicable to some equipment,
values are to be applied: 25 Hz to 200 Hz, acceleration 5 g.
e.g. rotating machines (refer to 6.3.).
1.5.2.7.
1.5.4.2.
In case of no resonance condition, a vibration
test is to be carried out 90 minutes at 30 Hz. Electrical equipment is to operate satisfactorily
when exposed to saline air or sea-water mist, in
If a resonance frequency at which Q ≥ 2 is found particular at weather exposed location.
during vibration tests, an endurance test is to be
carried out for not less than 90 min at this 1.5.5. Voltage and frequency
frequency and according to the direction where this
resonance has been found. In no case is Q to
variations
exceed 5.
1.5.5.1.
1.5.2.8. Electrical equipment is to operate satisfactorily
During the vibration test, the working when voltage and frequency variations in transient
characteristics of the equipment tested are to condition reach the following values:
remain within the limits specified by the
Manufacturer. Voltage: ± 0,2 U n (1,5 s)
Frequency: ± 0,1 Fn (5 s)
1.5.3. Inclination requirements
Where U n and Fn are respectively the rated
Electrical equipment is to be so arranged as to
voltage and frequency of the network.
operate satisfactorily under the following conditions:
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
3
1.5.5.2. 1.5.5.3.
Electrical equipment is to operate satisfactorily Contactors and similar electromagnetic
when voltage and frequency variations in steady equipment are to operate at 0,85 U n , U n being
condition reach the following values from the rated the rated voltage of the network, under the
values: conditions of 1.5.3.
Voltage: + 0,06 U n and - 0,10 Fn Note: in case the contactor coil is supplied by a separate
source, the corresponding voltage is to be taken into account
Frequency: ± 0,05 Fn instead of Un.
TABLE 1.6.
PROTECTION INDEX OF EQUIPMENT
Note 1: the case of immersed equipment will be specially considered by the Society.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
4
Note 2: higher protection index IP may be required in some cases (accessories for instance); refer to the IEC Publication 92-201.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
5
• domestic appliances not less than 3 kW
1.7. Maximum voltage permanently connected to fixed wiring:
• three phase systems: 1000 V
• motors:
1.8. Essential services
• three phase systems: 1000 V
• single phase systems: 500 V Essential services are those rendered by
• heating appliances permanently connected
servitude auxiliaries and complementary auxiliaries,
as they are defined in the Society's Rules for
to fixed wiring:
Classification applicable to the unit or installation
• three phase systems: 1000 V considered.
• single phase systems: 500 V
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
6
SECTION 2. DISTRIBUTION
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
7
• or supplied at a voltage not exceeding 250 V switchboard in relation to the main source of
by isolating transformers supplying only one electrical power, associated transforming
consuming device; equipment, if any and the main switchboard
are to be such as to ensure to the
• or constructed in accordance with the satisfaction of the Society that a fire or other
principle of double insulation. casualty in the space containing the main
source of electrical power, associated
transforming equipment, if any, and the main
2.4.2. Earthing connection switchboard, or in any machinery space of
category A will not interfere with the supply,
Earthing connections are to be made of copper control and distribution of emergency
or other corrosion-resistant conductive material; electrical power.
they are to be protected where necessary against
mechanical damage and electrolytic corrosion. As far as practicable, the space containing
the emergency source of electrical power,
2.4.3. Cross sectional area of associated transforming equipment, if any,
the transitional source of emergency
earthing conductor electrical power and the emergency
switchboard are not to be continuous to the
Unless justification, the earthing conductor cross boundaries of machinery spaces of category
sectional area is to be at least: A or those spaces containing the main
• if section of the main conductors is less than
source of electrical power, associated
transforming equipment, if any, and the main
16 mm2, this section of the main
switchboard. Where this is impracticable,
conductors, with a minimum of 3 mm2;
alternative arrangement of space boundaries
• if section of the main conductors is equal to may be considered.
or greater than 16 mm2, half this section of
the main conductors, with a minimum of d) Provided that suitable measures are taken
16 mm2. for safeguarding independent emergency
operation under all circumstances, the
emergency generator may be used,
2.5. Emergency power exceptionally, and for short periods, to
supply non-emergency circuits.
sources and circuits
Note: exceptionally is understood to mean conditions such
2.5.1. Emergency power source as:
• blackout condition;
• dead-ship condition i.e. the propulsion plant, boilers and
2.5.1.1.
auxiliaries stopped due to the absence of power.
The following is to be fulfilled:
2.5.1.2.
a) A self-contained emergency source of
electrical power is to be provided. For units and installations where the main
source of electrical power is located in two or more
b) On floating units, the emergency source of spaces which have their own systems, including
electrical power, associated transforming power distribution and control systems, completely
equipment, if any, transitional source of independent of the systems in other spaces and so
emergency power, emergency switchboard arranged that a fire or other casualty in any one of
and emergency lighting switchboard are to the spaces will not affect the power distribution
be located above the uppermost continuous from the others, or the services required in 2.5.2.
deck and to be readily accessible from the and other services that may be required by the
open deck. They are not to be located Society's Rules for Classification applicable to the
forward of the collision bulkhead, if any. unit or installation considered, the
requirement 2.5.1.1. a) may be considered satisfied
c) The location of the emergency source of without an additional emergency source of
electrical power, associated transforming electrical power, provided that:
equipment, if any, the transitional source of
emergency power, the emergency
switchboard and the emergency lighting
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
8
a) there are at least two generating sets, depletion by the automatic starting
meeting operational requirements stated by system;
the Society's Rules for Classification • provided with a transitional source of
applicable to the unit or installation emergency electrical power as specified
considered concerning inclinations, in each in 2.5.3. unless an emergency generator
of at least two spaces; is provided capable both of supplying the
services mentioned in that paragraph and
b) in the opinion of the Society, arrangements of being automatically started and
of these generating sets and of switchboards supplying the required load as quickly as
make a source of electrical power available is safe and practicable subject to a
at all times to the services required in 2.5.2. maximum of 45 s.
and other services that may be required by
the Society's Rules for Classification b) Where the emergency source of electrical
applicable to the unit or installation power is an accumulator battery it is to be
considered; capable of:
c) the location of each of the spaces referred to • carrying the emergency electrical load
in a) is in compliance, for floating units, without recharging while maintaining the
with 2.5.1.1. b); voltage of the battery throughout the
discharge period within 12 % above or
d) the boundaries of the spaces referred to in a) below its rated voltage;
meet the requirement 2.5.1.1. c), except that • automatically connecting to the
contiguous boundaries consist of an "A-60" emergency switchboard in the event of
bulkhead and a cofferdam, or a steel failure of the main source of electrical
bulkhead insulated to class "A-60" on both power, and
sides. • immediately supplying at least those
services specified in 2.5.3.
2.5.1.3.
2.5.1.4.
The emergency source of electrical power may
be either a generator or an accumulator battery. The following is to be fulfilled:
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
9
c) The emergency generator set and the • at the fire pump mentioned in item e), at
emergency battery are to be so designed the sprinkler pump, if any, at the
and arranged as to ensure that they will emergency bilge pump, if any, and at the
function under inclinations prescribed by the starting positions of their motors;
Society's Rules for Classification applicable • on helideck, including landing area
to the unit or installation considered. perimeter and obstacle lighting.
d) Provision is to be made to maintain the c) For a period of 18 h, the navigation lights and
stored energy at all times. other lights required by the International
Regulations for the Prevention of Collisions
e) All starting, charging and energy storing at Sea in force.
devices are to be located in the emergency
generator room and are not to be used for d) For a period of 18 h:
any purpose other than the operation of the
emergency generator set. This does not • all internal communication equipment as
preclude the supply to the air receiver of the required in an emergency, i.e. between
emergency generator set from the main or the navigating bridge and the steering
auxiliary compressed air system through a gear room, the machinery control room or
non-return valve fitted in the emergency equivalent engine control position, and
generator room. the telecommunication station(s);
• for self-propelled units, the navigation aids
as required by Regulation V/12 of
2.5.2. Services carried out Amendments to the SOLAS 1974
Convention as amended; where such a
The available electrical power is to be sufficient provision is unreasonable or
to supply all emergency services, i.e. services impracticable, special consideration will
which are essential for safety in an emergency, due be given by the Society for units of less
regard being paid to the services that may have to than 5000 tons gross tonnage, where
be operated simultaneously. applicable;
• the fire and gas detection and their alarm
The emergency source of electrical power is to
systems and;
be capable, having regard to starting currents and
to the transitory nature of certain loads, of • intermittent operation of the daylight
supplying simultaneously at least the following signalling lamp, the ship's whistle, the
emergency services for the periods specified below, manually operated call points, and all
if they need electrical power for their operation: internal signals that are required in an
emergency;
a) For a period of 18 h, emergency lighting at • where applicable, the capability of closing
every muster and embarkation station on the blow-out preventer and of
deck and over sides. disconnecting the unit from the wellhead
arrangement, if electrically controlled,
b) For a period of 18 h, emergency lighting: unless they have an independent
• in all service and accommodation emergency supply from an accumulator
alleyways, stairways and exits, personnel battery suitably located and sufficient for
lift cars and personnel lift trunks; a period of 18 h.
• in the machinery spaces and main e) for a period of 18 h one of the fire pumps
generating stations including their control required by the Society's Rules for
positions; Classification applicable to the unit or
• in all control stations, machinery control installation considered if dependent upon the
rooms, and at each main and emergency emergency generator for its source of power.
switchboard;
f) for a period of 4 days any signalling lights or
• at the stowage positions for firemen's
sound signals which may be required for
outfits;
marking of offshore structures.
• at the steering gear, as applicable;
g) for a period of 18 h, permanently installed
diving equipment, if dependent upon
electrical power of the unit or installation.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
10
h) on semi-submersible units, for a period of 2.5.4. Emergency switchboard
18 h:
• ballast control and indicating systems The following is to be fulfilled:
required by the Society's Rules for
Classification applicable to the unit or a) The emergency switchboard is to be
installation considered; installed as near as practicable to the
emergency source of electrical power.
• any of the ballast pumps required by the
Society's Rules for Classification
b) Where the emergency source of electrical
applicable to the unit or installation
power is a generator, the emergency
considered.
switchboard is to be located in the same
i) on floating units, for a period of 0,5 h, the space unless the operation of the emergency
power to operate watertight doors, remote switchboard would thereby be impaired.
controlled doors and hatch covers, together
with corresponding alarms and controls, but c) No accumulator battery fitted as emergency
not necessarily all of them simultaneously, or transitional source of power is to be
unless an independent temporary source of installed in the same space as the
stored energy is provided. emergency switchboard. An indicator is to
be mounted in a suitable place on the main
j) in addition, for production installations, and switchboard or in the machinery control room
for a period of 18 h: to indicate when the batteries constituting
either the emergency source of electrical
• the alarm and public address system; power or the transitional source of electrical
• the emergency shutdown system. power referred to in 2.5.1.3. b) or 2.5.3. are
being discharged.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
11
2.5.6. Particular provisions is to consist either of a multi-pole switch and a set
of fuses, or of a circuit breaker. These devices are
applicable to fixed
to be permanently connected to the main
installations switchboard or to the emergency switchboard by
suitable cables; this circuit is to be provided, at the
2.5.6.1. main or emergency switchboard, as applicable,
Electrical power is to be provided, in case of with a multi-pole switch or a circuit breaker.
particular conditions causing loss of both main and
emergency power, so that enough of the luminaries Where the external source of supply is of the
and communications listed in 2.5.2. are available to earthed system type, a terminal is to be provided
permit communication and lighting to allow the for suitable hull connection to earth.
personnel on board to escape safely from the
installation and to maintain contact with the A suitable device is to be fitted to the main
external emergency services. The requirement is for switchboard before the switchgear to indicate that
personnel to be mustered and either safely held on the external source feeder is under voltage.
board or evacuated by helicopter or sea.
A polarity checking device (d.c. supply) or a
phase sequence indicator (a.c. supply) is to be
2.5.6.2.
fitted for comparing the external service with the
Electrical equipment to meet requirement ship distribution network.
2.5.6.1. is to be suitable for use in Zone 1
hazardous area. The sources of power are to be A notice is to be provided in the connection box
integral accumulator batteries arranged to supply giving full information as to the nature of supply,
the service for an appropriate operating duration. rated voltage, frequency, as well as the instructions
This duration is to be evaluated for each to make the connection.
installation, taking account of the maximum
number of persons on board and the estimated time
to evacuate the installation, without being less than 2.7. Particular provisions
60 min.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
12
2.7.2. Navigation light circuits corresponding to their distance below the bulkhead
deck.
Electric navigation lights are to be connected
separately to a switchboard reserved for this It is to be possible to start the motor of a
purpose and supplied, directly of through submersible permanently installed bilge pump from
transformers, from the main or emergency an appropriate point above the bulkhead deck.
switchboard. If the navigation light switchboard is
installed on the bridge, it may be supplied by a
2.7.6. Fire pumps
distribution board located in the same part of the
ship and connected to the main switchboard by
means of two cables each one being capable of
2.7.6.1.
supporting the full load; this switchboard will then Arrangements and location of the power sources
be considered as an extension of the main and supply cables for fire pumps are to be in
switchboard. accordance with requirements of the Society's
Rules for Classification applicable to the unit or
It is to be possible to connect the navigation light installation considered.
switchboard from the bridge, to a second circuit.
2.7.6.2.
Each navigation light is to be protected by a fuse
in each insulated pole and provided with a double- Where an emergency fire pump is required, this
pole switch or by a double-pole circuit breaker fitted pump and its starting equipment are to be arranged
on the board referred to above. in compliance with requirements of the Society's
Rules for Classification applicable to the unit or
Each navigation light is to be provided with an installation considered.
automatic indicator which gives audible or visual
warning in the event of unexpected extinction of the 2.7.6.3.
light. If only an audible device is used, it is to be Cables connecting fire pumps to the emergency
connected to a separate source of supply, for switchboard are to be of a fire resistant type where
example dry cell or accumulator battery. they pass through high fire risk areas.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
13
2.7.9. Automatic combined c) Power supplies and electric circuits
necessary for the operation of the system
sprinkler, fire detection and
are to be monitored for loss of power or fault
fire alarm systems conditions as appropriate.
There are not to be less than two sources of Occurrence of a fault condition is to be
power supply for the seawater pump and automatic indicated by a visual and audible fault signal
alarm and detection system. If the pump is at the control panel which is to be distinct
electrically driven it is to be connected to the main from a fire signal.
source of electrical power, which is to be capable of
being supplied by at least two generators. The
feeders are to be so arranged as to avoid galleys, 2.7.11. Magnetic compasses
machinery spaces and other enclosed spaces of
high fire risk except as far as necessary to reach Cables and equipment are to be placed
the appropriate switchboards. One of the power sufficiently far from magnetic compass.
supply sources for the alarm and detection system
is to be an emergency source.
2.7.12. Final sub-circuits
2.7.10. Fixed fire detection and fire Every final sub-circuit connected to a distribution
alarm systems panel is to be protected unless otherwise specified,
by a fuse or a maximum current circuit-breaker on
Where a fixed fire detection and fire alarm each insulated pole.
system with manually operated call points is
required, the following is applicable: These circuits can be controlled by single-pole
switches in dry spaces of the accommodations.
a) There are not to be less than two sources of
power supply for the electrical equipment A separate final sub-circuit is to be provided for
used in the operation of the fire detection and every apparatus assuming an essential service and
fire alarm system, one of which is to be an for each motor rated 1 kW or more.
emergency source.
b) Electrical wiring which forms part of the Diversity factors may be based on the
system is to be so arranged as to avoid indications of the Builders; alternatively, the values
galleys, machinery spaces of category A, mentioned in the IEC Publication 92-201 may be
and other enclosed spaces of high fire risk applied.
except where it is necessary to provide for
fire detection or fire alarm in such spaces or
to connect to the appropriate power supply.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
14
SECTION 3. INTERNAL COMMUNICATIONS
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
15
SECTION 4. CABLES
4.1.2.1.
4.1.1. General
Cables are to be provided with a protective
4.1.1.1. covering or sheath suitable for the service
conditions.
The present Section 4. is applicable to cables
used for low voltage power and lighting installations. 4.1.2.2.
They are applicable also to other circuits such as On open decks, in damp spaces, in cargo holds,
telecommunications, remote control or remote in refrigerated spaces, in machinery compartments
monitoring as far as they are appropriate. and, generally in all spaces where water or
detrimental vapours (including oil vapours) may
4.1.1.2. condensate, cables are to include an impervious
sheath. In permanently damp spaces, the
Cables, cores and wire are to be normally of a
imperviousness degree is to be suitable for the
type approved by the Society, on the basis of the
immersion conditions (nature of the liquid,
IEC standards 92-3 and 92-350 to 92-376. Using
pressure, time of immersion).
other cables is submitted to special consideration
and to appropriate and satisfactory testing.
4.1.2.3.
4.1.1.3. Protective sheaths or coverings are to be
suitable for the degree of the mechanical actions to
The rated voltage of cables is not to be less than
which the cables can be submitted in service;
the rated voltage of the circuits in which they are
where their resistance may be considered as
used. The risks of strong or frequent overvoltages
insufficient, an additional protection is to be
due to current switching effects (winches, static
provided by means of pipes, conduits or metallic
converters, etc.) are to be duly considered when
guards (particular case of the cables in cargo
selecting the cables.
holds).
Note: rated voltage of a cable is expressed by the ratio of 2
values Uo / U , where:
4.1.2.4.
Cables intended to supply movable equipment
Uo is the r.m.s. value between an insulated
under a voltage higher than 250 V are to be metal
conductor and "earth; braid armoured, earthed and covered with a non
U is the r.m.s. value between 2 phase metallic sheath, unless it may be considered that
conductors of a multi-core cable. their insulation and protective sheath are reinforced.
4.1.1.4.
4.1.3. Conductor cross sectional
Cables and cabling wires are to be at least of the
area
flame retardant type and are to be so installed as
not to impair their original flame retarding properties
as far as practicable, in particular where they are 4.1.3.1.
arranged in bunches (refer to 4.3.6.). The cross sectional area of cable cores is to be
such that the maximum permissible current as
per 4.2. be not less than the maximum load of the
considered circuit. The maximum load may be
calculated in using the diversity factors of 2.8.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
16
4.1.3.2. voltage for lighting circuits and 11 % for the other
circuits may be accepted.
The cross sectional areas of conductors is to be
so determined that the drop in voltage from the
main or emergency switchboard busbars to any
and every point on the installation when the
4.2. Current ratings
conductors are carrying the maximum current
under normal conditions of service, does not 4.2.1. General
exceed 6 % of the nominal voltage. For supplies
from batteries with a voltage not exceeding 50 V Tables 4.2.1.-I and -II give the maximum
this figure may be increased to 10 % temperatures permissible in the conductors of
single-core cables according to the nature of their
Under current surge conditions such as motor insulation: 6 classes of temperature are
starting, voltage drops up to 8 % of the nominal considered:
TABLE 4.2.1.-I
MAXIMUM PERMISSIBLE TEMPERATURES IN CONDUCTORS
(Material insulating compounds as per IEC publication 92-351)
a/ Thermoplastics:
- based upon polyvinyl chloride or PVC/A 60
copolymer of vinyl chloride and vinyl acetate
b/ Elastomeric or thermosetting:
- based upon ethylene propylene rubber or EPR 85
similar (EPM or EPDM)
- base upon chemically cross-linked XLPE 85
polyethylene
- based upon silicon rubber S 95 95
TABLE 4.2.1.-II
MAXIMUM PERMISSIBLE TEMPERATURES IN CONDUCTORS
(Other recognised material insulating compounds)
a/ Thermoplastics:
based upon polyvinyl chloride
PVC 75 T 75 75
PVC 85 T 85 85
PVC 90 T 90 90
b/ Elastomeric or thermosetting
- based upon synthetic rubber CS 80 80
- based upon ethylene propylene rubber or EPR 90 90
similar
- based upon chemically cross-linked PR 95 95
polyethylene XLPE
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
17
4.2.2. Currents permissible in service for an ambient temperature of 45°C and are
applicable to copper conductor cables fitted in
continuous service
groups so arranged as not to obstruct the air
circulation around cables. In the case of aluminium
The current ratings given in Table 4.2.2. are the
conductors, permissible currents are to be derated
maximum d.c. currents permissible in continuous
by 0,6.
TABLE 4.2.2.
MAXIMUM PERMISSIBLE D.C. CURRENTS FOR CONTINUOUS SERVICE (in A)
Cross Temperature class Temperature class Temperature class Temperature class Temperature class
section 60° C 75° C 80° C 85° C 95° C
in mm 2 1 2 3, 4 1 2 3, 4 1 2 3, 4 1 2 3, 4 1 2 3, 4
core core core core core core core core core core core core core core core
1 8 7 6 13 11 9 15 13 11 16 14 11 20 17 14
1,5 12 10 8 17 15 12 19 16 13 20 17 14 24 20 17
2,5 17 15 12 24 20 17 26 22 18 28 24 20 32 27 22
4 22 19 16 32 27 22 35 30 25 38 32 27 42 36 29
6 20 25 20 41 35 29 45 38 32 48 41 34 55 47 39
10 40 34 29 57 40 40 63 54 44 67 57 47 75 64 53
16 54 46 38 76 65 53 84 71 59 90 77 63 100 85 70
25 71 60 50 100 85 70 110 94 77 120 102 84 135 115 95
35 87 74 61 125 106 88 140 119 98 145 123 102 165 140 116
50 105 89 74 150 128 105 165 140 116 180 153 126 200 170 140
70 135 115 95 190 162 133 215 183 151 225 191 158 255 217 179
95 165 140 116 230 196 161 260 221 182 275 234 193 310 264 217
120 190 162 133 270 230 190 300 255 210 320 272 224 360 306 252
150 220 187 154 310 264 217 340 289 238 365 310 256 410 349 287
185 250 213 175 350 298 245 390 332 273 415 353 291 470 400 329
240 290 247 203 415 353 291 460 391 322 490 417 343 570 485 399
300 335 285 235 475 404 333 530 451 371 560 476 392 640 545 448
400 390 332 273 570 485 400 610 519 427 670 570 469 760 646 532
500 455 387 320 655 560 460 695 591 490 770 655 540
600 505 430 355 730 620 510 770 655 540 650 725 595
Where it is known that the ambient temperature CORRECTION FACTORS FOR CHANGE
will remain less than 45°C (in particular for mobile OF AMBIENT TEMPERATURE
units navigating in limited zones and for fixed
Correction factors for
installations), permissible currents higher than
Cable ambient temperature of
those indicated in Table 4.2.2. may be accepted,
class 35°C 40°C 45°C 50°C 55°C
but ambient temperature of less than 35°C will not Class 60 1,29 1,15 1,00 0,82 -
be considered. Class 75 1,15 1,08 1,00 0,91 0,82
Class 80 1,13 1,07 1,00 0,93 0,85
Class 85 1,12 1,06 1,00 0,94 0,87
Class 90 1,11 1,05 1,00 0,94 0,88
Class 95 1,10 1,05 1,00 0,95 0,89
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
18
4.2.4. Correction factors for T is thermal time constant of cable in min
grouping of cables The thermal time constant may be given by the
cable manufacturer, or by the formula:
Where more than six cables, which may be
expected to operate simultaneously at their full T = 0,245 d 1,35
rated capacity, are laid close together in cable
bunch in such a way that there is an absence of d is external cable diameter in mm;
free air circulation around them, a correction factor T is time constant in min.
of 0,85 is to be applied to the current ratings given
in 4.2.2. Intermittent time service correction is applicable
only if the expected resting time is longer than
three times the cables constant time.
4.2.5. Correction factors for a.c. 50
or 60 Hz For service times shorter than 0,75 of the time
constant, correction factors in excess of 1,5 are not
In a.c. systems, the conductor cross sectional applicable unless specially justified.
areas in excess of 300 mm2 are to be determined
in applying the reduction factors of Table 4.2.5. For service times longer than 3 times the time
constant, the cable is considered as permanently
loaded, whatever the resting time period may be.
TABLE 4.2.5.
CORRECTION FACTORS FOR 4.3. Cables installation
A.C. 50 OR 60 Hz
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
19
4.3.1.5. These connections are to be made at both cable
ends. However, the cables in final sub-circuits may
The cable runs are to be so designed that the be earthed at their supply end only; it may be also
internal radius of bend does not exceed, at any the case for the shieldings of particularly sensitive
point, the permissible value for the cable lines of remote monitoring or control systems.
concerned. In the absence of values specified by
the Manufacturer, the following values are to be
4.3.3.2.
adopted as minima for the internal radius of bend:
The electrical continuity of all metallic covering is
• 4 d for thermoplastic or rubber-like insulated to be ensured throughout the cable length,
cables without metallic covering (6 d if including at joints and tappings.
d > 25 mm);
4.3.1.6. 4.3.4.1.
Where two supplies are provided for the same With the exception of cables installed in pipes
service, the routes are to be different as far as conduits, trunkings or casings, cables are to be
possible. fixed by means of suitable elements. The use of
fastening parts made of flame-retardant synthetic
material may be accepted for cables laid on
4.3.2. Mechanical protection horizontal supporting surface; on non-horizontal
support, one metallic fastening elements is to be
4.3.2.1. fitted each five elements.
Cables exposed to the risk of mechanical The distance between fixing parts is generally
damage, if neither armoured nor enclosed in steel not to exceed 0,50 m, extended to 0,60 m for
conduits, are to be protected by a casing. Mineral armoured or copper-sheathed cables. This distance
insulated cables are, for the purpose of the present is 0,75 m over the vertical runs.
requirement, considered to be armoured cables.
4.3.4.2.
4.3.2.2.
The fixing arrangement of single-core cables is to
Where the risk of mechanical damage is high, be made with due consideration of the possible
cables are to be protected by suitable metallic electrodynamic forces induced in case of short-
casings, even when armoured, unless the structure circuit.
of the unit or installation, or its attached parts, do
afford sufficient protection.
4.3.5. Cable glands through
bulkheads and decks
4.3.3. Earthing of metallic sheaths
and coverings 4.3.5.1.
4.3.3.1. Cables penetration of watertight decks and
bulkheads may consist in either individual stuffing
Any exposed metallic coverings of cables glands or boxes containing several cables and filled
(copper sheath, armour, etc.) is to be electrically with flame-retarding compound.
earthed.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
20
4.3.5.2. 4.3.7.5.
Where fire-resistance (Type A) or fire-retardant For long distance runs, expansion joints may be
(Type B) bulkheads or decks are drilled for the provided.
passage of cables, all arrangements are to be
made so that their fire resistance degree is not
decreased. 4.3.8. Installation in non-metallic
ducts and conduits
4.3.5.3.
Non-metallic ducts and conduits are to be made
Where unarmoured cables are to pass through of flame retardant material.
non-watertight bulkheads or, more generally,
through holes drilled in steel plates, such holes are
to be bushed in order to protect the cables, by soft 4.3.9. Connections
metal or any other suitable material which will
prevent damage to the cable by abrasion. The 4.3.9.1. Cable ends
same process is recommended for armoured
cables. The ends of the conductors having a cross
section greater than 4 mm2 are to be provided with
crimped or soldered connectors or to be connected
4.3.6. Installation in bunches to fastening terminals. If the connected cable has
an insulating belt common to several conductors,
Where cables are bunched, provisions are to be an additional insulation is to be provided where the
made to limit fire propagation. This may be insulation of the conductors risk to come into
achieved by either of the following methods: contact directly with earth.
• use of cables successfully tested
according to the IEC Report 332.3 or to
4.3.9.2. Joints
an equivalent testing procedure; Cables runs are normally not to include joints. If
• fitting of suitable fire stop screens a joint is absolutely necessary, it is to be carried
arrangement; out in such a way that the conductors remain
properly insulated and protected. The joints are
• use of an appropriate protective coating.
normally to be made in suitable boxes.
The internal radius of bends is not to be less Tappings are to be made by means of
than those permitted for cables, nor less than twice connectors, terminals or bars, placed in appropriate
the external diameter of the conduit for conduits casing.
exceeding 63 mm external diameter.
4.3.10. Special provisions for a.c.
4.3.7.2.
cables
The filling factor (ratio of the sum of the cross
sectional areas corresponding to the external cross Where it is necessary to install single-core
section of the conduit) is not to be greater than 0,4. cables, the following special provisions are to be
made:
4.3.7.3.
a) Armouring, if any, is to be on non-magnetic
Conduits are to be so arranged that water cannot
material.
accumulate inside. If necessary, ventilating or
draining outlets are to be provided to allow
b) Where cables are installed in metallic
circulation of air.
conduits, the cables belonging to the same
circuits are to be contained within the same
4.3.7.4. conduit.
The conduits and their metallic fittings are to be
earthed.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
21
c) When installing 2, 3 or 4 conductors forming 4.4. Type testing
a circuit, these conductors are to be joined
close together or spaced less than one
The cables and insulated cabling wires for which
diameter.
an application of type approval has been made are
to be or to have been submitted to type testing on
Fastening straps are to encompass all the
both their constituent materials and on the
phases or to be made of non magnetic
completed cables.
material.
Type tests are carried out according to an
d) Where single-core cables, rated above
approved programme based on the IEC Standard
250 A, are fitted along steel bulkheads, they
92-350, Section three: Test Requirements, and
are either to be arranged in "trefoil" or to be
approved by the Society in accordance with note
sufficiently spaced from the bulkhead
767 ND DT2 (tests on the electric cables).
surface.
Other equivalent standards may be used with the
Cable glands used for penetration through
agreement of the Society, relevant type testing
bulkheads or decks are not to be made of
program being submitted beforehand to the Society
magnetic metal. Moreover, it may be
for review.
necessary to provide non magnetic metallic
plates, large enough to prevent bulkheads
from overheating.
4.5. Routine testing
4.3.11. requirements for hazardous
4.5.1. General
areas
Normally, routine tests are to be carried out on
Particular requirements are laid down in Section all lengths of cables. However, the number of
12. concerning cables installed in hazardous areas. lengths may be reduced in agreement with the
Surveyor and with due regard to be results of the
4.3.12. Requirements for quality inspection for instance.
4.3.12.3. Where:
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
22
4.5.3. Dielectric strength test 4.5.4. Insulation resistance
measurement
This test is to be carried out at ambient
temperature with an industrial frequency a.c. 4.5.4.1.
voltage; alternatively, d.c. voltage, suitable filtered
may be used. Measurement is to be carried out at ambient
temperature, under d.c. voltage within the 80 -
Each core of the cable is to sustain for 5min, 500 V range, after completion of the dielectric
without breakdown, the testing voltage specified in strength test. It is to be effected 1 min after the
Table 4.5.3. voltage application (5 min for thermoplastic
insulated cables).
Test voltage
• for single-core cables with metallic covering,
the insulation resistance measurement is
Rated voltage Alternating Direct performed between the conductor and the
of cables Uo / U current (a.c.) current (d.c.) metallic covering;
•
(kV) (kV) (kV)
for single-core cables without metallic
0,15/0,25 1,5 3,6 covering, the insulation resistance
0,6/1,0 3,5 8,4 measurement is performed between the
conductor and the water in which the cable
The test voltage is to be applied for 5 min in is to be immersed at least 1 h before the
succession between each insulated conductor and test;
all the other ones connected to each and to
metallic covering, if any. • for cables having two to five conductors, with
or without metallic covering, the insulation
Single core cables without metallic covering are resistance measurement is performed in turn
to be immersed in water at room temperature for between each conductor and all other
1 h and the test voltage then applied for 5 min conductors connected together and to the
between the conductor and the water. metallic covering, if any;
Alternatively for single-core cables without • for cables having more than five conductors,
sheath, at Manufacturer's option, a spark test may the insulation resistance measurement test
be carried out on the cable. The spark test is performed; first, between all conductors of
equipment is to detect a puncture in the insulation uneven number in all layers and all
having a diameter equal to or greater than half of conductors of even number in all layers;
the specified insulation thickness. second, between all conductors of even
layers and all conductors of uneven layers;
The test voltage is to be increased gradually to third, if necessary, between the first and the
the specified value and no breakdown of the last conductor of each layer having an
insulation is to occur. uneven number of conductors.
4.5.4.3.
The measurement values of the insulation
resistance is to be corrected to the reference
temperature of 20°C by using an appropriate
temperature correction factor based on
experimental results obtained on the insulation
material concerned.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
23
4.5.4.4. l is length of the cable, in m;
The insulation resistance constant Ki, in MΩ.km D is outer diameter of the insulation, in mm;
is to be calculated using the formula: d is inner diameter of the insulation, in mm.
Notes:
l R.10-9
Ki = • for the core of shaped conductors, the radio D / d is the
D ratio of the perimeter over the conductors;
log10
d • the calculated value of K is to be not less than the value
specified for the relevant insulating material in Table II of
where: IEC Publication 92-351.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
24
SECTION 5. SWITCHBOARDS
5.1.1.1. 5.1.2.3.
Easy access to switchboards is to be provided
The main and emergency switchboards are to be
for crew. In particular, when a space is provided for
provided with insulated handrail or handles on their
access at the rear of switchgear and control gear
front. If access is available on their rear, an
sets, it is to be not less than 0,6 m in the clear,
insulated handrail is also required on their rear side.
except that the width may be reduced to 0,5 m,
where there are stiffeners or frames.
5.1.1.2.
5.2. Design - Construction
Location of switchboards is not to give rise to
flammable gas or vapour accumulation, unless 5.2.1. General
equipment designed for use in explosive
atmosphere be selected. 5.2.1.1.
Live parts normally submitted to a voltage
5.1.1.3. exceeding 55 V, are not to be installed without
Switchgears are to be located in such a way that protection on the front of switchboard.
there is no pipe carrying liquids above, behind or
near the switchboards. 5.2.1.2.
Generally, switchboards or enclosures
Where this cannot be avoided, pipes are to be containing switchboards, are to be constructed of
built joint less or provided with double pipes or durable, flame-retardant and non-hygroscopic
shields in these spaces. materials. In addition, mechanical features of the
materials are to be suitable for the service
5.1.1.4. conditions.
For self-propelled units, storage units and mobile
drilling units, the main switchboard is to be so 5.2.2. Busbars
placed relative to one main generating station that,
as far as practicable, the integrity of the normal
5.2.2.1. Materials
supply may be affected only by a fire or other
casualty in one space. An environmental enclosure Busbars are to be made of cooper. Nevertheless,
for the main switchboard, such as may be provided the use of aluminium busbars may be specially
by a machinery control room situated within the considered.
main boundaries of the space, is not to be
considered as separating the switchboards from the 5.2.2.2. Temperature rise
generators.
The mean temperature rise of the busbars and
their connections is not to exceed 45°C when
5.1.2. Installation running continuously at the normal rating.
5.1.2.1.
The protection index IP of switchboards is to be
as per Table 1.6.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
25
5.2.2.3. Electrodynamic forces connection concerned is to be fitted in the vicinity
of all protective apparatus.
Busbars, together with their joints and supports,
are to be so designed as to withstand the
mechanical stresses which may arise from short- 5.2.5. Testing
circuits, without any deformation.
5.2.5.1. Dielectric test
Where maximum symmetrical short-circuit
currents are expected to exceed 50 kA, calculation The main circuit and the auxiliary circuits
is to be submitted to the Society. connected to it are to be tested within the range of
45-62 Hz with the a.c voltages given by
5.2.2.4. Air clearances Table 5.2.5.1.-I
TABLE 5.2.5.1.-II
5.2.3. Equaliser conductors and
bars TESTING VOLTAGE FOR SWITCHBOARD
DIELECTRIC TEST (AUXILIARY
Current rating of the equaliser conductors and of CIRCUITS)
the corresponding switches is to be not less than
half the rated current of the corresponding Insulation rated voltage A.c. test voltage
generator. (V) (r.m.s.) (V)
Ui ≤ 12 250
The current rating of equaliser bars is to be not
12 < Ui ≤ 60 500
less than half the rated current of the largest
60 < Ui 2 Ui + 1000
generator arranged to run in parallel. with minimum: 1500
All measuring apparatus and devices controlling During this test, all interrupting and protective
a circuit are to be indelibly marked. A plate devices are to be closed; measuring instruments
mentioning the rated current of the apparatus or and relays may how-ever be disconnected.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
26
For three-wire generators feeding a d.c. three-
wire circuit, an ammeter with a commutator is to be
5.2.5.2. Measurement of the insulation mounted on each pole of each generator and a
resistance voltmeter between each pole of the busbars and the
equalising conductor.
Immediately after completion of the high voltage
test, the insulation resistance between current 5.4.1.3.
carrying parts connected together and earth and
between current carrying parts of opposite polarity In the case of alternators not arranged to run in
is to be not less than 1 M Ω measured under 500 V parallel, every main or emergency switchboard is to
d.c. be provided with at least, for each alternator, one
voltmeter, one frequency meter, one ammeter per
phase or one ammeter with commutator permitting
5.3. Distribution boards and to measure the current in each phase and for
alternators of more than 50 kVA, one wattmeter.
panels
However in the case of emergency alternator the
5.3.1. General frequency meter may be not provided if a
tachometer is fitted on the generating set.
Distribution boards and panels are to comply
with requirements 5.1. and 5.2., as applicable. 5.4.1.4.
In the case of alternators arranged to run in
parallel, every main or emergency switchboard is to
5.3.2. Physical protection be provided with at least:
Distribution boards are normally to be placed • for each alternator, one wattmeter, one
within a protective casing; large ones are to be ammeter per phase or one ammeter with
placed in a special compartment. commutator permitting to measure the
current in each phase;
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
27
reverse currents of at least 15 % of the rated No independent interrupting device is to be
current. placed in an earthing conductor; this does not
preclude however the fitting of disconnecting links
5.4.2.3. for testing or surveying purposes.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
28
5.6.3. Protection against short- circuit-breaker on the generator side, having at
least the necessary short-circuit rating and not
circuit currents
being the generator circuit-breaker; the same fuse
or circuit-breaker may back-up more than one
5.6.3.1. circuit-breaker when essential services are not
Protection against high overcurrents, and involved.
essentially against short-circuit currents, is to be
provided on each conductor not directly earthed. The short-circuit performance of the arrangement
is at least to be equal to the ones of a single
5.6.3.2. circuit-breaker having the same short-circuit
Such a protection is to consist of circuit- performance category as the backed-up circuit-
breakers or fuses. breaker and rated for the maximum prospective
short circuit level at the supply terminals of the
P1 category circuit-breakers may be used on arrangements.
circuits other than generator circuits, where the
system arrangements are such, for example by
5.6.4. Protection of generators
duplication and separation of supplies, the failure
of the circuit-breakers may be accepted.
5.6.4.1. General
5.6.3.3. Generators are to be protected against overloads
and short-circuits by means of circuit-breakers of
The devices provided are to have a breaking
the category P2.
capacity at least equal to the maximum prospective
short-circuit current at the point of installation. At
The use of discontactors is allowed for the
first approximation, the value of this short-circuit
protection of emergency generators.
current may be determined on the following basis:
For d.c. compound generators the equaliser
a) D.c. networks:
conductor (connected to the negative pole) is to be
• 10 times the rated current of all interrupted at the same time as the main
generators arranged to run in parallel, conductors.
plus
• 6 times the rated current of motors 5.6.4.2. Protection against overloads
operating simultaneously. Breakers are to trip with a time-delay not
exceeding 15 s for an overload of 50 % unless the
b) A.c. networks:
generator is so designed as to withstand heavier
• 10 times the rated current of all overloads.
alternators arranged to run in parallel,
plus An additional protection against smaller
• 3 times the rated current of motors overloads may also be provided; it may consist of
operating simultaneously. an audible alarm activated by a time-delayed
overcurrent relay adjusted at approximately 110 %
5.6.3.4. of the rated current.
The closing capacity of any interrupting (even not 5.6.4.3. Load-shedding of non essential
intended to be used as circuit-breaker in case of
circuits
short-circuit) or protective device to be possibly
closed on short-circuit is to be at least equal to the For generators intended to run in parallel and to
highest value of the maximum prospective short- avoid that the tripping of one of them involves the
circuit current at the point of installation; in a.c. the tripping of another one by overload, automatic load-
value to be considered will be the maximum peak shedding of some circuits, others than those
value in asymmetrical conditions. supplying the servitude auxiliaries listed in 1.8. is to
be provided after a short time delay.
5.6.3.5.
Audible and visible alarm is to be provided in
The use of a circuit-breaker not having a short- case of load-shedding.
circuit breaking and/or making capacity at least
equal to the maximum prospective short-circuit
current at the point where it is installed is allowed,
provided that it is backed-up by a fuse or by a
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
29
5.6.4.4. Protection against short-circuits addition to the protection against short-circuit
currents, the following is to be provided:
The protection against heavy overloads or short-
circuits is to provide a quick tripping, either a) Protection against overload; this protection
instantaneous or slightly delayed so as to permit may be replaced, for those motors intended
selectivity. for essential services, by an aural and visual
alarm in case of overload.
5.6.4.5. Case of generators of power
lower than 50 kW b) Protection against single phase operation for
For generators of a rated power lower than three-phase induction motors the supply
50 kW and not intended to run in parallel, the system of which is provided with fuses.
protection may consist of:
c) An under voltage protection device causing
• either a circuit breaker with a single relay the the tripping of the corresponding circuit and
tripping of which intervenes in a time one of the following functions:
inversely proportional to the overload; • either to remain in the stop position until
• or fuses and a switch.
the auxiliary is put again on operation by
a voluntary action;
5.6.4.6. Protection against reverse power • or to restart automatically after
restoration of the voltage. In this case,
D.c. generators and alternators arranged for
arrangements are to be made to ensure
parallel operation are to be protected against
that the automatic restarting of motors
reverse power.
takes enough time to avoid excessive
voltage drop.
Such protection may be omitted in the case of
low power generators further to special The under voltage protection is to permit
consideration and justification. starting as soon as the voltage exceeds
85 % of the rated voltage and is to
For d.c. generators, this protection is to be operate when the voltage drops to
instantaneous and is to work at less than 15 % of approximately 20 % of the rated voltage
the rated current. at the rated frequency with time delay if
necessary.
For alternators the reverse power protection is to
be set between 2 and 15 % of the rated power 5.6.6. Protection of transformers
according to the characteristics of the prime mover
and it may be time-delayed. The reverse power 5.6.6.1.
protection provided on alternators can be replaced
by other devices ensuring adequate protection of Power transformers are to be protected against
the prime movers. short-circuit currents and overloads; the protection
against short-circuits is to be placed on the primary
5.6.4.7. Protection against under voltage side; the protection against overloads may be
placed on the secondary side; protection against
When generators are intended to run in parallel, overload is not required wherever the size of the
arrangements are to be made for preventing the transformer makes it impossible to be overloaded
generator circuit breakers from closing or from when supplying all the consumers connected to it.
remaining closed when there is no voltage.
5.6.6.2.
If a low voltage tripping relay is used, it is to
control the circuit breaker opening instantaneously, Where transformers can be connected in
while controlling the circuit breaker closing is to be parallel, arrangements are to be made to allow
delayed in order to achieve selectivity. isolation of their secondary windings.
5.6.6.3.
Transformers intended to supply control and
5.6.5. Protection of motors monitoring circuits are to be protected on the
primary and secondary sides against short circuit
Motors of more than 0,5 kW or assuming an currents, unless they are designed to sustain
essential service are to be individually protected; in permanent short circuit current. This does not
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
30
exempt from providing individual protection of the 5.6.8. Protection of measuring or
circuits supplied by the transformers where justified
monitoring instruments,
by their cross section area. This individual
protection may be achieved on one wire only if all surge suppressors,
the conductors have same cross section area. indicating lights, etc.
5.6.8.1.
5.6.7. Protection of final sub-
circuits supplying motors Each circuit supplying a monitoring or remote
control device such as voltmeter, indicating light,
Every final sub-circuit supplying only one motor etc. is to be protected on each phase or pole not
may be provided with only one short-circuit directly earthed by a suitable protective device; this
protection on the generator side and one overload one may be common to several devices, provided
protection either on the generator side or on the that, in case of operation, it can be considered that
load side. this does not decrease the availability of the
remaining plant.
5.6.8.2.
Surge suppressors connected to busbars,
generators and motors achieving essential services
are to be protected, on each phase or pole not
directly earthed, by means of fuses or equivalent
devices.
Bureau Veritas Rule Note for electrical systems on board offshore units and installations
31
SECTION 6. ROTATING ELECTRICAL
MACHINES
6.1.1. Approval
6.2. Generating sets - Prime
Rotating machines used for essential services as movers
defined in 1.8. and of a rated power over 50 kW are
normally to be type approved by the Society, on the
basis of the IEC Standards 92-301. Machines rated 6.2.1. Number of generating sets
above 1 kW and not type approved are subject to
tests specified in 6.8. 6.2.1.1.
The offshore units and installations where
6.1.2. Location, installation electrical energy is the only means for supplying
the services specified in 1.8. are to be provided with
Machines and their gear are to be located in at least 2 generating sets of adequate
spaces suitably ventilated where flammable dusts, characteristics, so that these services can still be
vapours or gases cannot accumulate. Where this maintained whichever the generating set is
condition, in the case of motors, cannot be fulfilled, stopped.
the Society is to be advised accordingly and
special consideration will be given, after 6.2.1.2.
examination, to the proposed arrangements.
The arrangement of the power sources is to be
such that the services referred to in 1.8. can be
6.1.3. Protection of the machines maintained regardless of the speed and direction of
against mechanical shocks, the propulsion machinery or shafting.
accidental contacts and 6.2.1.3.
external agents
For the application of 6.2.1.1. and 6.2.1.2.,
6.1.3.1. generators driven from the propulsion plant may be
accepted as generators forming the main source of
Machines and their gear are to be so arranged electrical power if in all sailing and manoeuvring
that their components are shielded from conditions, including the propeller being stopped,
mechanical damage and also from any damage the generating capacity of these generators is
likely to occur due to external agents such as sufficient to provide the required electrical power
water, oil and their vapour. and fulfil all further requirements, especially those
of the present 6.2.1.
6.1.3.2.
Live parts are to be efficiently sheathed from any
6.2.1.4.
accidental contact when the voltage exceeds 55 V. In addition, for self-propelled mobile units, the
generating plant is to be such as to ensure that
6.1.3.3. with any one generators or its prime mover out of
operation, the remaining generator(s) is (are)
Protection of the machines and their gear from
capable of providing the electrical services
external agents is to be in accordance with
necessary to start the main propulsion plant from a
Table 1.6.
dead ship condition. The emergency source of
electrical power may be used for the purpose of
6.1.4. Earthing starting from a dead ship condition if its capability
either alone or combined with that of any other
Bedplates and framework of the machines and source of electrical power is sufficient to provide at
generating sets are to be earthed; no insulating the time the required services.
material is to be placed between the prime movers
32
• momentary variations 10 % when the rated
electrical load of the set is suddenly thrown
6.2.1.5. off;
In addition, for fixed offshore installations, the
number and rating of the generator sets in service
• momentary variations 10 % when an
electrical load equal to 50 % of the rated
is to be sufficient to ensure the operation of
power of the set is suddenly thrown on
essential services even when one generating set or
whatever its initial load may be within 0 to
converting set has failed.
50 % of its rated power. In any case the
speed is to be restored in less than 5 s to
6.2.1.6. 1 % of the original speed;
In addition, the generating plant is to be such as
Note: other characteristics may be considered, such as
to ensure that with any one generator or its prime
by application of an electrical load below 50 % of the
mover out of operation, the remaining generator(s)
rated power.
is (are) capable of providing the electrical services
necessary to start the essential auxiliairies from
the dead ship / dead platform condition. The
• permanent deviation 5% for any load up to
the rated power.
emergency source of electrical power may be used
for the purpose of starting from the dead ship / dead 6.2.2.2.
platform condition if its capability either alone or
combined with that of any other source of electrical The governing characteristics of prime movers
power is sufficient to provide at the same time the driving a.c. generators arranged to run in parallel
required services. are to be such that, within the limits of 20 % and
100 % of total load at cos ϕ = 0,8, the load on any
6.2.1.7. generating set will not differ from its proportionate
share of the total load by more than 15 % of the
Where a.c. is used, the number of generators
rated output of the largest machine, or by more
and their characteristics are to be such that, in
than 25 % of the rated output of the smallest
dead ship / dead platform condition, the starting of
machine.
the motors, including the largest ones, does not
cause excessive voltage drop detrimental to the
good running of the equipment on duty. Unless
particular arrangements are made to ensure good 6.3. Permissible maximum
working of the installations, the voltage variations temperature rise for
are not to exceed 15 % under all service
circumstances.
electrical rotating
machines
This may be omitted for the circuits supplying
high power motors if their starting conditions and
the good operation of their associated control 6.3.1. Standard cases
circuits are not affected by voltage drop higher than
15 %. 6.3.1.1.
The permissible limits of temperature rise,
6.2.2. Speed automatic control particularly for windings, sliding contacts of air
cooled motors under continuous running and for air
cooled generators, are given in the Table 6.3.1.
6.2.2.1.
Prime movers are to be provided with a governor
capable of maintaining the speed variations within
the following limits:
33
TABLE 6.3.1.
MAXIMUM PERMISSIBLE TEMPERATURE RISES FOR ELECTRICAL ROTATING
MACHINES
on the basis of a cooling air temperature not exceeding 50°C
Class of insulation
6.3.1.2. 6.3.1.3.
Where a machine is designed to operate with a If air-to-water heat exchangers are used, the
coolant at an ambient temperature different from temperature rise is increased by 20°C, but only if
50°C, the permissible temperature rises may be the specified inlet water temperature does not
reduced or increased in accordance with the actual exceed 30°C. When commutators of these
ambient temperature. machines are not in the enclosed air circuit cooled
by the water cooler, but are cooled by the ambient
cooling air, the permissible temperature rise above
34
the ambient cooling air is to be as for ventilated the voltage obtained at nominal load does not
machines. exceed the nominal voltage by more than 1,5 %.
6.3.3. Tests
• or shunt excitation.
6.4.3.1.
In relation to the speed regulation of driving
machines, the inherent voltage regulation of d.c.
generators rated at 50 kW or more is to satisfy, at
service temperature, conditions given in 6.4.3.2.
and 6.4.3.3.
6.4.3.2.
Compound wound generators are to have such
an inherent voltage regulation that, when starting at
20 % load with a voltage within 1 % of rated load,
35
Furthermore, the average regulation curve when 6.5. Characteristics of a.c.
the load varies between 20 % and 100 % of rated
load, either by increase or decrease, is not to vary generators
by more than 3 % from the rated voltage.
6.5.1. Voltage automatic control
6.4.3.3.
For shunt wound generators arranged to run in A.c. generators, unless of the self-regulated
parallel, the inherent voltage regulation is to satisfy type, are to be fitted with automatic voltage
the following conditions: regulators.
6.5.2.3.
6.4.5. Parallel operation of d.c.
generators When the generator driven at its rated speed and
delivering the rated voltage, is submitted, from an
Generators arranged to run in parallel are to be initial specified load, to a sudden change of
stable in operation at all loads from no load to rated symmetrical load within the limits of specified
load. current and power factor, the voltage must not set
below 85 % of the rated voltage at loading, or above
120 % at deloading.
6.4.6. Equaliser conductors and
bars The voltage is to be restored within ± 3 % of the
final steady voltage in less than 1,5 s, and
The requirements concerning equaliser respectively ± 4 % and 5 s for emergency
connections and bars are given in 5.2.3. generators.
6.5.2.4.
In case of short circuit, generators whose rated
power is greater than 50 kW are to be at least
36
capable of withstanding a current equal to 3 times 6.8. Testing of electrical
their rated current during 2 s.
rotating machines
6.5.3. Parallel operation of a.c.
generators 6.8.1. General requirements
In addition to the requirements of 6.2.2., the Machines supplying an essential service such as
generators arranged to run in parallel are to be such those specified in 1.8. and rated above 1 kW and
that the wattless load on any generator does not not type-approved are to be submitted to the type
differ from the theoretical load (proportional to tests required by the present 6.8., carried out in the
rating) by more than 10 % of the rated wattless presence of the Surveyor, or in accordance with an
load of the last generator, or 25 % of the rated alternative procedure accepted by the Society.
wattless load of the smallest generator if this value
Note: by alternative procedure accepted by the Society, it is
is lower than the first one.
meant: this tests required in 6.8.2. to 6.8.5. may not be carried
out, totally or partly, if type test reports concerning identical
machines or other justifications acceptable by the Society are
6.6. Control gear of electrical submitted. The tests are carried out by an independent
rotating machines Laboratory or attended by authorised bodies.
37
TABLE 6.8.4.
HIGH VOLTAGE TEST
38
6.8.3. Performance tests 6.8.4. Dielectric tests
39
SECTION 7. TRANSFORMERS
TABLE 7.1.6.
7.1.3. Windings
TRANSFORMERS SHORT-CIRCUIT
Transformers are to be double-wound -two WITHSTANDING CAPACITY
separate windings). Starting transformers may be of
the autotransformer type. Short-circuit Symmetrical short- Duration in s
voltage circuit current to
Ucc be withstood
7.1.4. Location, installation ≤4% 25 In 2
>4 % 100 I n 3
7.1.4.1.
Ucc
The transformers are to be placed in accessible
Note: In is the rated current of the transformer
well ventilated spaces free from any gaseous or
Ucc is expressed in percentage of the
acid fumes. They are to be clear of non-protected
primary rated voltage
ignitable materials.
40
TABLE 7.2.
MAXIMUM PERMISSIBLE TEMPERATURE RISE FOR TRANSFORMERS AND SIMILAR
APPARATUS
Winding mean temperature rises measured by resistance variation of the windings between terminals (°C).
Class of insulation
Type Cooling A E B F H
dry air or 50 65 75 95 115
solid dielectri
c
immersed self 50 - - - -
in a liquid forced 55 - - - -
dielectric
Temperature rise of the liquid dielectric:
50°C when the liquid in the main tank is protected from contact with air.
45°C when the liquid in the main tank is in contact with air.
Temperature rise of the magnetic cores (for all types): the temperature rise measured by the thermometer on the
outer faces of the cores is not to exceed the maximum permissible temperature rise of the adjacent windings.
The voltage variations between no load and the Each type of transformer is normally subject to
rated current with a unity power factor are not to design approval and to type tests to be performed
exceed 5 % for transformers rated at up to 5 kVA according to a test programme approved by the
per phase, and 2,5 % for transformers rated at Society. Such programme comprises at least the
more than 5 kVA per phase. tests required in 7.5.3. to 7.5.5.
Note: this requirement is not applicable to starting Particular arrangement may be considered, for
transformers. instance in the case of transformers identical to a
transformer type, temperature rise type tests are
acceptable up to 100 kVA rated power.
41
An applied voltage test is to be carried out on
every new transformer. When applied voltage tests
are intended on machines or parts of machines
7.5.3. Temperature rise tests and having already been tested, the r.m.s. value of test
measurements of voltage voltage may be reduced by 25 %.
drop
7.5.5. Induced voltage test
Transformers are to be submitted to a test under
the rated load current. This test is to last long
Internal insulation is to be checked by applying
enough for temperature stabilising. The maximum
twice the rated voltage to the transformers.
permissible temperature rises for transformers and
other static electrical machines specified in 7.1.1.
In order not to exceed the usual induction, this
are not to exceed the limits given in Table 7.2.
test can be made with a voltage source having a
frequency of at least twice the rated frequency.
During this test, voltage drop in the secondary
winding is to be as per 7.3.
The normal duration of the test is 1 min.
42
SECTION 8. ACCESSORIES
8.1. General
8.4. Control gears and
8.1.1. Materials starters
Materials used are to be durable, non-
hygroscopic, flame retardant and corrosion proof.
8.4.1. Design requirements
8.4.1.1.
8.1.2. Protection indexes
Where necessary, depending on the capacity of
generators and of the distribution network, some
The protection indexes IP XX of the equipment or
motors are to be equipped with an appropriate
of their envelopes are to be in accordance with the
control device lowering the starting overcurrent to
requirements of 1.6.
an acceptable value.
43
excluding installation apparatus such as sockets- 8.6. Lighting fittings
outlets, cabin switches or equivalent.
8.6.1. Protection
8.5.2. Approval
Luminaries exposed to risks of mechanical
The devices are normally to be type approved by
damage are to be suitable protected or strongly
the Society on the basis of the following IEC
built.
Standards:
IEC 947-1 Low voltage switchgear and
control gear - Part 1: general 8.6.2. Luminous discharge
rules. equipment
IEC 947-2 Low voltage switchgear and
control gear - Part 2: circuit 8.6.2.1.
breakers. The necessary reactors, capacitors and other
IEC 947-3 Low voltage switchgear and auxiliaries are to be enclosed in an earthed metal
control gear - Part 3: switches, casing.
disconnectors, switch-
disconnectors and fuse 8.6.2.2.
combination.
Multiple switches are to be used on the primary
IEC 947-4.1 Low voltage switchgear and circuits of the equipment rated higher than 250 V,
control gear - Part 4: contactors to enable the installation to be totally isolated.
and motor-starters. Section 1:
electromechanical contactors
and motor-starters. 8.7. Heaters
IEC 947-5.1 Low voltage switchgear and
control gear - Part 5: control
circuit devices and switching 8.7.1. General
elements. Section 1:
electromechanical control circuit Heaters are to be built, installed or protected that
devices. one cannot easily cover them with clothes or
inflammable objects.
IEC 947-6.1 Low voltage switchgear and
control gear - Part 6: multiple
function equipment. Section 1: 8.7.2. Approval
automatic transfer switching
equipment. The following is applicable:
IEC 947-7.1 Low voltage switchgear and
control gear - Part 7: ancillary a) Visual inspection to evaluate in particular:
equipment. Section 1: terminal
• the protection index IP XX (refer to 1.6.),
blocks for copper conductors.
testing may be required;
IEC 269 Low voltage fuses
• the expected behaviour when submitted
Equipment in accordance with national to vibration; testing according to the
regulations and having at least equivalent requirements of 1.5.2. may be required;
characteristics may also be used; necessary • the protection against corrosion;
justification may be required. • the protection against covering by
inflammable objects (refer to 8.7.1.);
The Society may require, in addition, justification
• earthing arrangement;
of the characteristics of switchgears, by means of
tests for instance. • the arrangement of fuses, switches and
other built-in control devices; it is to be
such that these components are not
submitted to higher temperatures than
the ones for which they have been
designed.
44
b) High voltage test, using test voltage of • explosion group II B;
2U + 1000 V at industrial frequency,
minimum 2000 V during 1 min, phase-to- • temperature class T3.
phase and phase-to-earth.
45
SECTION 9. STORAGE BATTERIES
46
Other electrolyte-resistant coating may be Adequate openings, whether connected to ducts
accepted. or not, for air inlets are to be provided near the floor
of battery rooms of the bottom of lockers or boxes.
Alternatively, the floor of battery compartments
may be lined or coated with electrolyte-resistant The fan motor is to be placed external to the
material or casing spanning the entire floor. The duct; possible friction of blades on fixed parts is not
lining is to be watertight and carried up to at least to result in sparking.
150 mm on all sides.
The fan is to be of non sparking construction, as
9.2.2.3. defined in 9.2.4.2.
47
SECTION 10. SEMICONDUCTOR STATIC
CONVERTERS
Semiconductor converter equipment is to be Where forced cooling (air or water) is used, the
installed in such a manner that the circulation of air circuit is to be fitted with a protection device
to converter stacks or to their envelope (if any) is ensuring that voltages cannot be applied to
not impeded. rectifiers unless effective cooling is maintained.
48
• interference from high frequency noise; the 10.5. Testing
IEC publication 478-3 gives a method of
measurement of conducted electromagnetic
interference (EMI). 10.5.1. General
49
SECTION 11. HIGH VOLTAGE INSTALLATIONS
11.2.3. Identification
11.4.2. Location, installation
11.2.3.1.
Transformers are to be installed in places or
Each high voltage equipment is to be provided rooms set for this purpose.
with an identification plate specifying the voltage
and relating danger.
50
11.4.3. Protection 11.5.2.2.
Where maintenance tasks are expected, the
11.4.3.1. access to the cells is to be effected either by the
5.6.6. is applicable. opening of a door or of an element of the protective
envelope or by the disconnection of an element of
11.4.3.2. this envelope.
11.4.3.4. 11.5.2.5.
The secondary side of instrument transformers is The outgoing circuits supplying equipment
to be earthed. located near the switchboard may be provided with
disconnectors instead of interrupting devices.
11.4.4. Testing
11.5.3. Creepage distances and air
Dielectric test voltages at industrial frequency to clearance
be carried out are those indicated for switchboard
testing in Table 11.5.4. Creepage distances and air clearances between
live parts or between them and the earthed
conductive parts, are to be suitable for the service
11.5. Switchboards voltage, including the expected voltages surges and
for the environmental conditions.
11.5.2. Access and arrangement Highest voltage for R.m.s. test voltage, Impulse voltage
equipment 1 min at a rated test 1,2/50 peak
(kV) frequency voltage (kV)
11.5.2.1. (kV)
51
11.6. Cables and cabling wires TABLE 11.6.4.
VOLTAGES FOR DIELECTRIC AND
11.6.1. General ELECTRIC SHOCK TESTS OF CABLES
52
SECTION 12. ADDITIONAL RULES FOR UNITS
AND INSTALLATIONS INCLUDING HAZARDOUS
AREAS
• IEC Publication 79-1A (1975),.Amendment Note: the certification ratings specified by this requirement
N° 1 (1979), First supplement, Appendix D are valid only for gases emanating from hydrocarbon
"Method of test for ascertainment of products.
maximum experimental safe gap";
53
12.1.4.2. • neutral earthing systems of power
Any modification is to be the subject of a new distribution networks where the voltage is
certification by an independent competent 3 kV or over, provided that resulting current
institution (refer to 12.1.2.). It is to be reported with cannot flow through any hazardous area.
necessary documentation to the Society, in
accordance with the requirements of the IEC 12.2.3. Generators, switchboards
Publication 79-17 (1990), Part 17.
and batteries
12.2.2.1.
• copper sheath (for mineral insulated cables);
54
they are to be installed on cable runs and clearly 12.3.1.2.
separated from bulkheads and decks.
The Society is to be supplied, with a general
drawing showing the location of the electrical
12.2.4.6.
material with regard to the hazardous areas and
Supply cables to intrinsically safety type with the justification of the safety character of the
equipment are to be separated from the other electrical material to be used in these zones.
cables.
• through-runs of cables.
55
12.3.2.4. • equipment in an enclosure which is filled with
In zone 2 spaces are permitted the following a dielectric and which is to the satisfaction of
types of electrical equipment: the Society;
56
SECTION 13. SPARE GEARS
For each type of generator required by the For the starting gear of motors supplying one of
present Rule Note, including rotating exciters, the the essential services specified in 1.8., the
following is recommended: following is recommended:
13.1.3. Alternators:
• one of each type of coil used for contactors,
relays, low voltage releases.
• one set of roller bearings. Where several starters in which these parts
are interchangeable are fitted on board, it is
Note: this recommendation is not applicable to emergency sufficient to provide, for six or less starters,
generating sets. one set of spare parts for the starter
employing the greatest number of parts.
57
13.3. Miscellaneous 13.3.3. Electronic material
Where the supply voltage of emergency circuit For plants rated above 10 kW, it is
differs from that of the main circuit, one complete recommended to provide an insulation level
spare set of lamps is recommended. measuring instrument powered with 500 V d.c.
58
SECTION 14. TESTS
59
14.3.2. Motors In case of doubt, insulation level check may be
required.
Motors driving essential services,, together
with their control gear, are to be tested under
service conditions. 14.3.5. Lighting, heating and various
appliances (galley, pantry,
14.3.3. Protection gear etc.)
Switch gears are to be tested at a load as near Fixed appliances and corresponding electrical
as possible to the working load to check the circuits are to be tested under normal working
absence of overheating due to faulty connection or conditions as far as practicable.
incorrect rating. Circuit-breakers are to be tested,
as far as practicable at the rated load of the circuit
they control; checking is made on the working 14.3.6. Internal communication
condition of both the switch gears and their control systems
devices. Working condition of the other protection
devices (overcurrent, low voltage, back power, The alarm transmission system and the order
reverse current, load shedding relays) is also transmitters to the engines, steering gears and
checked. windlasses are to be checked in order.
60
61