Boletin Copeland Aplicación ZF y ZB
Boletin Copeland Aplicación ZF y ZB
Boletin Copeland Aplicación ZF y ZB
TABLE OF CONTENTS
Section Page Section Page
Safety Demand Wiring..................................................................13
Safety Instructions..............................................................2 Protection/Contactor Control Wiring.................................. 13
Safety Icon Explanation......................................................2 Discharge Temperature Protection with CoreSense
Instructions Pertaining to Risk of Electrical Shock, Diagnostics for K5 Compressors..................................... 13
Fire, or Injury to Persons.................................................3 Communication DIP switch Configuration......................... 13
Safety Statements..............................................................3 Cable Routing / Daisy Chain Configuration....................... 14
Terminations......................................................................14
Introduction COMMISSIONING.............................................................14
Nomenclature.....................................................................4 Stand Alone Mode.............................................................14
Approved Refrigerants.......................................................4 Modbus® Communication to CoreSense Diagnostics
Digital Compressor Operation............................................4 for K5 Compressors........................................................15
Operating Envelope............................................................5 CoreSense K5 Programming Instructions...................... 16-20
Extended ZF*K5E Operating Envelope.............................. 5 .
ZF*K5E Low Temperature K5 Compressors for Figures
Refrigeration...................................................................6 Modulation Troubleshooting..............................................21
Liquid Injection....................................................................6 Operating Maps.............................................................. 22-28
DTC Valve Specifications...................................................6 Typical Suction Tubing......................................................29
Installation of DTC Valve....................................................6 Liquid Injection Scroll with DTC Valve............................... 30
Suggested Application Techniques for All Liquid Injection .... EVI Scroll with DTC and T-fitting Adapter.......................... 30
Applications....................................................................6 EXV...................................................................................30
Vapor Injection....................................................................7. Circuit Diagram and Cycle for EVI.....................................31
Discharge Temperature Control with Vapor Injection......... 7 Downstream Extraction.....................................................31
System Configuration.........................................................7. Upstream Extraction..........................................................31
Downstream Extraction......................................................8. H/X Piping Arrangement....................................................32
Upstream Extraction...........................................................8. 8 - 17 HP Copeland Scroll Compressor Rack Mounting... 32
Heat Exchanger Piping Arrangements............................... 8 8 - 17 HP Condensing Unit Mounting................................ 32
Accumulator Requirements................................................8 CoreSense Module Wiring Schematics............................. 33
Superheat Requirements...................................................8 Discharge Thermistor Connector.......................................34
Crankcase Heater..............................................................8 Top Cap Thermistor...........................................................34
Pressure Controls...............................................................8 Discharge Line Thermistor................................................34
IPR Valve ...........................................................................8 CoreSense Terminal Box...................................................35
Motor Protection.................................................................9 K5 Communication Module DIP Switch Settings............... 35
PTC Motor Protection.........................................................9 Wiring Relay Example.......................................................35
Programmable Logic Controller Requirements.................. 9. E2 Jumpers.......................................................................35
Kriwan INT69 Module and Sensor Functional Check......... 9 RS485 Daisy Chain Connection........................................36
Motor Protector Module Voltage Supply Troubleshooting.. 9 Two Rack Daisy Chain Connection................................... 36
Sensor Troubleshooting.....................................................9 Old/New Model Comparison.............................................37
Compressor Voltage Supply Troubleshooting................... 10 Digital Compressor Cutaway View.................................... 38
Oil Management for Rack Applications............................. 10 20 Second Operating Cycle..............................................39
Discharge Mufflers.............................................................10 CoreSesne Diagnostics + EXV Operation......................... 40
Compressor Mounting.......................................................10 Digital Operation DIP Switch Settings............................... 40
Deep Vacuum Operation................................................... 11
Unbrazing System Components........................................ 11 Tables
HiPot Testing..................................................................... 11 Injection Accessories.........................................................41
Three Phase Scroll Compressors – Directional External Wrap-Around Crankcase Heaters....................... 41
Dependence.................................................................... 11 Kriwan INT69 Module Specifications................................. 41
Copeland Scroll Compressor Functional Check................ 11 K5 Compressor Additional Accessories............................. 42
K5 Compressor (8 to 17 HP) Fitting Sizes........................ 43
CoreSense™ Diagnostics Module for K5 Compressors... 12 High and Low Pressure Control Settings.......................... 43
CoreSense Module LED Overview....................................12 Digital Modulation Capacity(%) vs. Analog (V).................. 43
Product Specifications.......................................................12 CoreSense™ Diagnostics Fault Codes.............................. 44
Compressor Lead Wiring ..................................................13 CoreSense™ Diagnostics Module Troubleshooting........ 45-46
CoreSense Module Mounting............................................13 Demand Wiring..................................................................47
110-220VAC CoreSense Module Power Wiring................ 13 K5 DIP Switch Settings......................................................47
1
AE4-1383 R14
Safety Instructions
Copeland Scroll
Copeland Scroll™
™
compressors are
compressors CoreSense™ according
withmanufactured Diagnosticsto are
the manufactured
latest U.S. andaccording
EuropeantoSafety
the latest U.S. and
European Safety Standards. Particular emphasis has been placed on the user's safety.
Standards. Particular emphasis has been placed on the user's safety. Safey icons are explained Safey icons are explained
below
below and safety instructions applicable to the products in this bulletin are grouped
and safety instructions applicable to the products in this bulletin are grouped on Page 3. Theseon Page 3. These instructions
should be retained
instructions should throughout
be retained the lifetime of
throughout thethe compressor.
lifetime You are strongly
of the compessor. You areadvised
stronglytoadvised
follow these safety
instructions.
to follow these safety instructions.
2
AE4-1383 R14
BURN HAZARD
WARNING • Do not touch the compressor until it has cooled down.
• Ensure that materials and wiring do not touch high temperature areas of
the compressor.
• Use caution when brazing system components.
• Personal safety equipment must be used.
• Failure to follow these warnings could result in serious personal injury or
property damage.
COMPRESSOR HANDLING
CAUTION • Use the appropriate lifting devices to move compressors.
• Personal safety equipment must be used.
• Failure to follow these warnings could result in personal injury or
property damage.
Safety Statements
• Refrigerant compressors must be employed only for their intended use.
•
install, commission and maintain this equipment.
•
• All valid standards and codes for installing, servicing, and maintaining electrical and
refrigeration equipment must be observed.
3
AE4-1383 R14
4
AE4-1383 R14
10% which equates to 2 seconds of pumping during one state. By varying the time of the loaded state and the
20 second cycle. unloaded state, an average capacity is obtained. The
An example for the 20 second controller cycle: In any lowest achievable capacity is 30% which equates to 6
20 second cycle, if the loaded time is 10 seconds and seconds of pumping during one 20 second cycle.
the unloaded time is 10 seconds, the average capacity An example for the 20 second controller cycle: In any
is 50%, or if the loaded time is 5 seconds and the 20 second cycle, if the loaded time is 10 seconds and
unloaded time is 15 seconds the capacity during that the unloaded time is 10 seconds, the average capacity
20 second period is 25%. See Figure 20 for a graphical is 50%, or if the loaded time is 6 seconds and the
representation of the digital cycle, and Figure 21 for unloaded time is 14 seconds the capacity during that
a graph showing solenoid on-time vs. compressor 20 second period is 30%. See Figure 20 for a graphical
capacity. representation of the digital cycle, and Figure 21B
Medium Temperature Digital operation is controlled for a graph showing solenoid on-time vs. compressor
by the CoreSense Diagnostics module and has a capacity.
patented algorithm that allows the compressor to run
at 10%. If the compressor's discharge line temperature How it Works
rises at a high rate of change over time the CoreSense The digital scroll compressor unloads by taking
Diagnostics module will increase the compressor advantage of the Copeland Scroll compressor's
capacity until discharge line temperature is at a axial compliance. All Copeland Scroll compressors
safe operating temperature. To operate with a 10% are designed so that the compression elements can
minimum capacity please confirm that DIP switch separate axially. See Figure 20 for internal view.
1 (EXV) in the top left corner on the CoreSense
The digital solenoid can be controlled two ways with
Diagnostics module (See Figure 19) IS IN THE OFF
the CoreSense Diagnostics module:
POSITON. For correct DIP switch settings please see
Figure 23A. 1. Through a 1-5v signal. For tables of digital
capacity(%) vs. analog input (v) see Tables 7A
Low Temp Digital Compressor Operation and 7B
2. Via mod-bus communication
Due to lower mass flows the low temperature digital
compressor operation is restricted to 30%-100%. The 8.0 HP and larger digital scroll compressors
By restricting to 30% minimum capacity this ensures employ a solenoid valve that is mounted on the side
enough mass flow to the compressor for safe operation. of the compressor that vents the intermediate cavity
To operate with a 30% minimum capacity Please confirm to the low side of the compressor during the unloaded
that DIP switch 1 on the digital and EXV DIP switches state. During the loaded state the solenoid valve is de-
in the top left corner on the CoreSense Diagnostics energized and the intermediate cavity is pressurized to
Module(See Figure 19) IS IN THE ON POSITON. For load the floating seal and scrolls axially.
correct DIP switch settings please see Figure 23B.
Operating Envelope
A normally closed (de-energized) solenoid valve is a key Operating envelopes for the K5 compressors for
component for achieving modulation. When the solenoid refrigeration are depicted in Figures 2A through 2M.
valve is in its normally closed position, the compressor
operates at full capacity, or loaded state. When the Extended ZF*K5E Operating Envelope
solenoid valve is energized, the two scroll elements Figure 2I presents an extended envelope for the
move apart axially, or into the unloaded state. The ZF*K5E scroll. While this product is optimized for a low
Solenoid coil must be controlled by the same voltage temperature application, in some instances the ZF*K5E,
that is powering the CoreSense Diagnostic module. either with vapor injection or no injection at all, can be
During the unloaded state, the compressor motor applied in a medium temperature application. This may
continues running, but since the scrolls are separated, be done to use common model numbers in a system or
there is no compression. During the loaded state, the to apply vapor injection for additional cooling capacity.
compressor delivers 100% capacity and during the
unloaded state, the compressor delivers 0% capacity. When applying with vapor injection, it should be noted
A cycle consists of one loaded state and one unloaded that the total amount of internal subcooling is limited
5
AE4-1383 R14
6
AE4-1383 R14
7
AE4-1383 R14
Downstream Extraction suction line 6 inches (152mm) from the suction valve,
to prevent liquid refrigerant floodback.
The downstream extraction is the preferred method
employed in the United States. In downstream Another method to determine if liquid refrigerant is
extraction the TXV is placed between the liquid outlet returning to the compressor is to accurately measure
and vapor inlet of the heat exchanger. The advantage the temperature difference between the compressor
of downstream extraction is that subcooling is ensured oil crankcase and the suction line. During continuous
because the liquid is further subcooled as it flows operation we recommend that this difference be a
through the heat exchanger. Therefore, more subcooled minimum of 50°F (27°C). This “crankcase differential
liquid enters the TXV which increases the probability temperature” requirement supersedes the minimum
that the valve will not hunt. The disadvantage with this suction superheat requirement in the last paragraph. To
method is that it is not as efficient as the upstream measure oil temperature through the compressor shell,
method; however, the difference is too small for place a thermocouple on the bottom center (not the side)
practical purposes. See Figure 5. of the compressor shell and insulate from the ambient.
During rapid system changes, such as defrost or ice
Upstream Extraction
harvest cycles, this temperature difference may drop
In upstream extraction the TXV is placed between rapidly for a short period of time. When the crankcase
the condenser and the heat exchanger. The TXV temperature difference falls below the recommended
regulates the flow of subcooled refrigerant out of the 50°F (27°C), our recommendation is the duration should
condenser and into the heat exchanger. With this type not exceed a maximum (continuous) time period of two
of configuration there is a potential for flash gas which minutes and should not go lower than a 25°F (14°C)
would cause the valve to hunt. See Figure 6. difference.
Heat Exchanger Piping Arrangements Contact your Emerson Climate Technologies
representative regarding any exceptions to the above
Best subcooling effect is assured if counter flow of requirements.
gas and liquid is provided as shown (see Figure 7).
In order to guarantee optimum heat transfer, the plate Crankcase Heater
heat exchanger should be mounted vertically and
Crankcase heaters are required, on outdoor systems,
vapor should exit it at the top.
when the system charge exceeds 17 lbs.
For more information on applying ZF*K5E scrolls with
Table 2 includes crankcase heaters intended for use
an economized vapor injection (EVI) circuit refer to AE4-
only where there is limited access. The heaters are
1327, Economized Vapor Injection (EVI) Compressors.
not equipped for use with electrical conduit. Where
Accumulator Requirements applicable electrical safety codes require heater lead
protection, a crankcase heater terminal box should be
Due to the Copeland Scroll compressor's inherent used. Recommended crankcase heater terminal cover
ability to handle liquid refrigerant in flooded start and and box numbers are also listed in Table 2 If there
defrost operation conditions, accumulators may not are any questions concerning the application, contact
be required. An accumulator is required on single Application Engineering.
compressor systems with refrigerant charges over
17 lbs. On systems with defrost schemes or transient Pressure Controls
operations that allow prolonged, uncontrolled liquid
Both high and low pressure controls are required. The
return to the compressor, an accumulator is required
minimum and maximum pressure setpoints are shown
unless a suction header of sufficient volume is used to
in Table 4.
prevent liquid migration to the compressor.
IPR Valve
Superheat Requirements
There is no internal pressure relief valve in these larger
In order to assure that liquid refrigerant does not return
horsepower scrolls. Therefore a high pressure control
to the compressor during the running cycle, attention
located prior to any shut-off valves is mandatory. There
must be given to maintaining proper superheat at the
is an access port located on the compressor discharge
compressor suction inlet. Emerson recommends a
rotalock fitting to accommodate this control.
minimum of 20°F (11°C) superheat, measured on the
8
AE4-1383 R14
9
AE4-1383 R14
10
AE4-1383 R14
Connection Fittings, Service Valves, and Adapters lower the current leakage reading, the system should
The fitting sizes for 8 through 17 HP scroll compressors be operated for a brief period of time to redistribute the
are shown in Table 5. refrigerant to a more normal configuration and the system
hipot tested again. See bulletin AE4-1294 for megohm
Deep Vacuum Operation testing recommendations. Under no circumstances
should the Hipot or Megohm test be performed while the
WARNING compressor is under a vacuum.
Do not run a Copeland Scroll compressor in a deep NOTE: The solid state electronic module components
vacuum. Failure to heed this advice can result in and internal sensors are delicate and can be damaged
arcing of the Fusite pins and permanent damage by exposure to high voltage. Under no circumstances
to the compressor. should a high potential test be made at the sensor
A low pressure control is required for protection against terminals or sensor leads connected to the module.
deep vacuum operation. See Pressure Control section Damage to the sensors or module may result.
for proper set points. (Table 6)
Three Phase Scroll Compressors – Directional
Scroll compressors (as with any refrigerant compressor) Dependence
should never be used to evacuate a refrigeration or air
conditioning system. See AE-1105 for proper system Scroll compressors are directional dependent; i.e. they
evacuation procedures. will compress in one rotational direction only. Three
phase scrolls will rotate in either direction depending
Unbrazing System Components on power phasing. Since there is a 50/50 chance of
connected power being “backwards”, contractors should
WARNING be warned of this. Appropriate instructions or notices
If the refrigerant charge is removed from a scroll should be provided by the OEM.
unit by bleeding the high side only, it is sometimes Verification of proper rotation can be made by observing
possible for the scrolls to seal, preventing pressure that the suction pressure drops and the discharge
equalization through the compressor. This may pressure rises when the compressor is energized.
leave the low side shell and suction line tubing
pressurized. If a brazing torch is then applied to the No time delay is required on three phase models to
low side, the pressurized refrigerant and oil mixture prevent reverse rotation due to brief power interruptions.
could ignite as it escapes and contacts the brazing The CoreSense module will provide reverse rotation
flame. It is important to check both the high and low protection.
sides with manifold gauges before unbrazing or in
Copeland Scroll Compressor Functional Check
the case of assembly line repair, remove refrigerant
from both the high and low sides. Instructions Copeland Scroll compressors do not have internal
should be provided in appropriate product literature suction valves. It is not necessary to perform functional
and assembly (line repair) areas. compressor tests to check how the compressor will
pull suction pressure. This type of test may damage a
High Potential (Hipot) Testing
scroll compressor. The following diagnostic procedure
Many Copeland™ compressors are configured with the should be used to evaluate whether a Copeland Scroll
motor below the compressor. As a result, when liquid compressor is functioning properly.
refrigerant is within the compressor shell the motor can
1. Verify proper unit voltage.
be immersed in liquid refrigerant to a greater extent than
with compressors with the motor mounted above the 2. Normal motor winding continuity and short to
compressor. When Copeland compressors are hipot ground checks can be used to determine proper
tested and liquid refrigerant is in the shell, they can motor resistance or if an internal short to ground
show higher levels of leakage current than compressors has developed.
with the motor on top because of the higher electrical 3. With service gauges connected to the suction
conductivity of liquid refrigerant than refrigerant vapor and discharge pressure fittings, turn on the
and oil. This phenomenon can occur with any compressor compressor. If suction pressure falls below normal
when the motor is immersed in refrigerant. The level of levels the system is either low on charge or there
current leakage does not present any safety issue. To is a flow blockage.
11
AE4-1383 R14
4. If the suction pressure does not drop and the The LEDs will flash a number of times consecutively,
discharge pressure does not rise, reverse any two pause and then repeat the process. To identify an alert
of the compressor power leads and reapply power code number, count the number of consecutive flashes.
to verify the compressor was not wired to run in Detailed descriptions of specific alert codes are shown
the reverse direction. in Table 8.
The operational compressor current draw should The CoreSense module will continue to display the alert
be compared to published performance curves at code until the condition returns to normal or if module
the operating conditions (pressures and voltages). power is cycled to the device.
Significant deviation (± 15%) from published values Yellow LED:
may indicate a faulty compressor.
FLASHING: Alerts of an abnormal system condition
CoreSense Diagnostics™ Module for Refrigeration via Alert Codes
Compressors
SOLID: Demand is present but no current is
The CoreSense Diagnostics module (see Figure 19) detected. All protective shutdowns will auto reset in
for Copeland Scroll refrigeration compressors (referred their allotted time
to as “the CoreSense module” in this document) is a
breakthrough innovation for troubleshooting refrigeration Red LED:
system faults. The CoreSense module is installed in FLASHING: Indicates the CoreSense module is
the electrical box of all 8-17 HP K5 refrigeration scroll locked out on the flashing Alert Code. Manual power
compressors. By monitoring and analyzing data from cycle reset is required to restart the compressor
the Copeland compressors via module power, discharge
Green LED:
line thermistor, and the current transducer (referred to
as “CT” in this document), the CoreSense module can FLASHING: Alert Codes that do NOT have a
accurately detect the cause of electrical and system protective shutdown associated with them.
related issues. A flashing LED indicator communicates Blue LED:
the alert code and guides the service technician more
quickly and accurately to the root cause of a problem. Flashing indicates alert codes for Digital only. Alert
Codes that do NOT have a protective shutdown
The CoreSense module can provide both compressor associated with them. A solid Blue LED represents
protection and lockout capability. Compressor compressor unloaded.
protection means that the CoreSense module will trip
the compressor when any of the following severe alert Some troubleshooting tips for the CoreSense module
conditions (Codes 1, 2, 4, 6, 7 or 9) are detected. A trip are listed in Table 9 at the end of this document.
condition is when the protector on a compressor opens Product Specifications
and stops current flow into the compressor motor. As a
result, the compressor shuts down. A trip condition will Operating Temp: -40° to 150°F (-40° to 65°C)
reset after short cycle time and when trip condition is Storage Temp: -40° to 175°F (-40° to 80°C)
not present.
Power Supply Range: 85-265VAC, 50-60 Hz
If lockout is enabled and a preset number of alarm
Working amperage for CT module: 3-200A
events happen, the CoreSense module will not allow
the compressor to start (Codes 1, 4, 6 or 7) until the NOTE: The CoreSense module is not accurate below
situation is corrected and the module is manually 3 Amps. If the current drawn by the compressor during
reset. The module can be reset by cycling power to operation falls below 3 Amps, the module may indicate
the module. a nuisance fault condition and alarm.
In low current application it is applicable to loop the
CORESENSE MODULE LED OVERVIEW
power leads through the current sensor twice to double
CoreSense Diagnostics™ Module for Refrigeration the current value the sensor reads and eliminate the low
Compressors with Digital and EXV Capability current nuisance trips.
The CoreSense module has the ability to shut down the NOTE: The 2X current reading may need to be
compressor if the compressor contactor coil is wired addressed at the system or rack controller.
through the M1-M2 relay.
12
AE4-1383 R14
The CoreSense module connections are standard male Protection/Contactor Control Wiring for CoreSense
electrical flag terminals. Diagnostics Module (543-0174-**)
Maximum continuous contactor coil current is 2A with The M1-M2 relay on the CoreSense module is a normally
a max inrush current of 20A. open relay. When the module is powered and there are
no protective faults, the relay is energized and does not
Compressor Lead Wiring cycle on/off. On a detected protection condition, the
The compressor leads must be routed through the holes CoreSense module will de-energize the relay to stop the
in the CT module marked T1, T2, and T3. Only the motor from running. The relay is not used as a cycling
compressor lead wires should be placed through device for normal compressor operation. The cycling
the CT module. device must be supplied externally from the module.
Protection/Contactor Control Wiring for CoreSense
CoreSense Module Mounting
Diagnostics Module (543-0209-**)
The CoreSense module will come pre-mounted inside
The M1-M2 relay on the CoreSense module is a
the compressor terminal box. The module is mounted
normally open relay. M1-M2 relay cycles with demand of
so all LEDs are in front of the light pipes in the terminal
the compressor. This eliminates the need for The cycling
covers so codes are visible when the terminal box cover
device to be supplied externally from the module. On a
is installed on the terminal box. The CoreSense module
detected protection condition, the CoreSense module
should be installed inside the terminal box with a torque
will de-energizethe relay to stop the motor from running.
of 8 inch pounds.
Discharge Temperature Protection with CoreSense
110-230VAC CoreSense Module Power Wiring
Diagnostics for K5 Compressors
The CoreSense module requires 110-230VAC power
Copeland Scroll K5 compressors for refrigeration with
between to the L1 and L2 terminals. The module should
CoreSense Diagnostics come standard with discharge
remain powered through all states of compressor on/off
temperature protection. Depending on the application
operation. Refer to wiring schematic examples.
and refrigerant a certain mode of protection will be
NOTE: The physical Location of L1 and L2 have used whether it is a top cap thermistor or DTC valve
changed on 543-0209-**. Confirm correct location of with discharge line thermistor or an EXV valve with a
L1 and L2 wiring. Reference Figure 19. top cap thermistor. The CoreSense module identifies
the protection device based on the pin locations in the
Demand Wiring for (543-0174-**) connector. Figures 10 and 11 depict the installation of
The CoreSense module requires a demand signal to the top cap thermistor and discharge line thermistor,
operate properly. The demand signal input, labeled respectively.
D on the module, should always be connected to the Table 1 at the end of this bulletin identifies the discharge
compressor demand so that the demand signal input temperature protection device by application and
is 110 or 220VAC with respect to L2. See Figure 9A refrigerant. Table 4 identifies the service part numbers
for proper wiring diagrams. Choose the appropriate for those devices.
diagram depending on how the demand signal will be
fed to the module. Communication DIP Switch Configuration
The communication module on the CoreSense
Demand Wiring for (543-0209-**) Diagnostics module is equipped with a 10 switch DIP
For CoreSense Diagnostics module (543-0209-**) a switch used for selection of the Modbus® address, baud
demand relay is no longer needed. Control voltage rate, parity, and other operating conditions to simplify
(110/220V) is needed at the D terminal. For digital service and start-up procedures. See Figure 13. For
models the D terminal is used to monitor control more information on DIP switch settings, Table 11 lists
voltage only. The demand signal comes from the the purpose for each switch.
RS485 network OR the 1-5V analog input. For fixed NOTE: Cycle power after changing any of the DIP
capacity models the demand signal input comes from settings for changes to take effect.
the D terminal, and is 110 or 220VAC with respect to The following steps cover the DIP switch settings
L2. See Figure 9B for proper wiring diagram throughout the commissioning process for a multiple
13
AE4-1383 R14
compressor system with communications to the E2: in the plastic housing will help reduce abrasion to the
1. Switches 1 through 5 are used for setting the wiring. Appropriate strain relief is recommended.
address. Each CoreSense Diagnostics device that NOTE: The RS485 is polarity sensitive. “+” wires
is connected to a rack controller must have a unique must connect to other “+” terminals, and “-” wires
node address (as determined by the DIP switch must connect to other “-” terminals. The shield wire is
settings). connected to the center terminal, or “0 volt” position.
2. Switch 6 defines the communications baud rate for
Terminations
the CoreSense Diagnostics module. If the switch
is “off”, the baud rate is 19200. If the switch is “on” The last compressor in the daisy chain must be
the baud rate is 9600. The baud rate for each of the “terminated” by setting the DIP switch number 10 to the
CoreSense devices should be set to match the rack "on" (up) position. For all other compressors the number
controller. The default baud rate is 19200 (“off”) for 10 DIP switch should remain in the "off" (down) position.
the CoreSense Diagnostics module. To determine More information: The E2 jumpers on the Network
the baud rate in the E2, follow these steps: Interface Board should be set for “terminated”. Refer
• From the main menu select 7 (System to Figure 16.
Configuration)
COMMISSIONING
• Press 3 (System Information)
Modules using a communications network must be
• Press 1 (General Controller Info) commissioned as part of the E2 rack controller setup.
• Access the Serial Communications Tab by The commissioning process uploads compressor
pressing CTRL + 3 asset information (model and serial number) into
the rack controller for future reference. Once the
• Use the Page Down button or scroll down to
commissioning process is completed, the controller will
view the settings for COM4
supervise and communicate with the module unless
3. Switch 7 defines the communication parity. The the node is deleted. Refer to section titled Modbus®
default parity setting for the CoreSense Diagnostics Communication to CoreSense Diagnostics for K5
module is no parity. If the switch is set to “on” the Compressors for more details on commissioning the
module will communicate using even parity. The K5 scrolls in an Emerson Retail Solutions E2 rack
parity setting must match the parity setting of the controllers.
rack controller.
NOTE: For digital capacity using an E2 controller,
4. Switch 8 is used to set the network mode (on) an enhanced suction group must be enabled.
for the module. The default setting is stand
The CoreSense Diagnostics module does not
alone mode (off). Network mode will generate a
need to communicate to the rack controller in
communications error if the rack controller fails
order to provide compressor protection. Using
to communicate with the device. For standalone
the communication process is optional, but provides
mode, no communications are expected so the
for information flow to the controller for proofing,
communication error is blocked.
remote reset, asset information, and fault history and
Cable Routing / Daisy Chain Configuration compressor status. Skip to section titled Stand Alone
Mode if the communication feature will not be used.
A second set of DIP switches are used for compressor
operation. See Table 12 for default configuration and The commissioning process begins by assigning a
application guidelines for DIP switches. The CoreSense unique node address to each module. The address is
Diagnostics module can communicate with a rack established by the setting of a DIP switch in the module.
controller using Modbus® protocol. The communication
Stand Alone Mode
cable is wired from the rack controller to the first
compressor. Additional compressors are wired in a daisy If running a K5 with CoreSense Diagnostics without
chained configuration. Refer to Figures 16 and 17. communication to a rack controller, DIP switch 8 should
be set to "Off" (down).
A shielded, twisted pair cable such as Belden #8761
(22AWG) should be used for the communication wiring. Modbus® Communication to CoreSense Diagnostics
Passing the communications wire through the grommet
14
AE4-1383 R14
* These guidelines are based on E2 firmware version 3.0 and are subject to change. Contact your Emerson representative or refer to the
operation manual for more details on configuring an E2 module.
15
AE4-1383 R14
3. From the Network Setup Menu select 2. Connected I/O Boards and Controllers
4. From the Setup Screen go to the C3: ECT Tab (Press Ctrl + 3)
5. In Option #9, enter the number of K5 compressors being controlled by the E2.
16
AE4-1383 R14
8. Select the Modbus® that the CoreSense device is connected to. (If only Modbus® network is
connected, this step will automatically complete itself, skip to step 9)
9. From the Modbus® Device Menu select an unused space that matches the DIP switch
Address of the CoreSense device and press Enter..
10. Verify the address matches the address assigned by the CoreSense module’s DIP switch
settings and press Enter.
17
AE4-1383 R14
11. Press to return to the Network Summary screen. The device should now be
“Online”.
Repeat steps 8 -10 to address the remaining CoreSense K5 modules.
12. Once all the devices are addressed, press to save changes and exit the
Network Summary.
18
AE4-1383 R14
15. From the Network Setup Menu, select 4. Controller Associations . Then Select 4. Compressor
(Press Enter)
16. Highlight the Suction Group2 field, select F4: Look Up (Press F4) and select the appropriate
suction group for the device and press Enter.
19
AE4-1383 R14
2 For more information on setting up suction groups in the E2, consult your Emerson Retail
Solutions representative.
17. Scroll over to the Comp Stage and type in the compressor stage. (CoreSense Protection
provides proofing only on the compressor.)
Note! The compressor stage number should correspond to the stage numbers in the suction
group setup (Step 7)
20
AE4-1383 R14
Start
WARNING!
Is the compressor Is the compressor Disconnect and lockout
Allow time to cool
running? No overheated? Yes the power before
proceeding
Yes No
Perform troubleshooting
Observe the compressor
to determine why the Put the system back into Remove one wire from
suction & discharge
compressor isn’t operation and retest the modulation coil
pressures
running
Are pressures
changing with the Operation Measure the resistance
modulation Yes is normal of the coil
cycle?
No
Yes
Replace modulation
Is voltage present,
Troubleshoot the valve, follow valve Put the system back into
coinciding with the
No modulation control replacement operation and retest
modulation cycle?
instructions
Yes
21
AE4-1383 R14
140
Condensing Temperature (°F)
120
100
80
60
40
20
0
-50 -40 -30 -20 -10 0 10
Evaporating Temperature (°F)
Figure 2 (A)
140
Condensing Temperature (°F)
120
100
Maximum
80 40F
Superheat
60
40
20
** DTC/EXV Liquid Injection Required with EVI for R-407A /R-407C/ R-407F/R-448A/R-449A
0
-50 -40 -30 -20 -10 0 10
Evaporating Temperature (°F)
Figure 2 (B)
22
AE4-1383 R14
140
Condensing Temperature (°F)
120
100
DTC/EXV Liquid
Injection Required
80
60
40
20
0
-50 -40 -30 -20 -10 0 10
Evaporating Temperature (°F)
Figure 2 (C)
120
Condensing Temperature (°F)
100
DTC/EXV Liquid
80 Injection Required
60
40
20
0
-50 -40 -30 -20 -10 0 10
Evaporating Temperature (°F)
Figure 2 (D)
23
AE4-1383 R14
62
140
FS
20° SH
52
120 t to
i 0°F
Lim 2
4 07A i m it to
-
R /F L 42
07C
100 R-4
80
22
60
12
40
2
20 -8
0 -18
- 20 - 10 0 10 20 30 40 50
Figure 2 (E)
62
140
Condensing Temperature (°C)
Condensing Temperature (°F)
t
imi 52
tL
120
rhea
pe
Su
°F 42
20
100
32
80
22
60
12
40
2
20 -8
0 -18
-20 -10 0 10 20 30 40 50 60
Figure 2 (F)
Note: For operating maps at different return gas conditions, contact your Application Engineer.
24
AE4-1383 R14
150
Condensing Temperature (°F)
140
130
120
110
100
90
80
70
60
0 10 20 30 40 50 60
Evaporating Temperature (°F)
Figure 2 (G)
160
Condensing Temperature (°F)
140
120
100
80
60
0 10 20 30 40 50 60 70
Evaporating Temperature (°F)
Figure 2 (H)
25
AE4-1383 R14
120
Condensing Temperature (°F)
100
80
60
20
0
-15 -10 -5 0 5 10 15 20 25 30
Evaporating Temperature (°F) *R-22 Not Approved for Vapor Injection
26
AE4-1383 R14
62
140
52
120
100%-10%
42
100
100%-20%
32
80
22
60
12
40
2
20 -8
0 -18
- 20 - 10 0 10 20 30 40 50
Figure 2 (K)
62
140 Condensing Temperature (°C)
Condensing Temperature (°F)
52
120
42
100%-60%
100%-50%
100%-30%
100%-10%
100
32
80
22
60
12
40
2
20 -8
0 -18
- 20 - 10 0 10 20 30 40 50
NOTE: Minimum capacity is assumed running at a continuous minimum capacity. These Minimum capacity restrictions ONLY
apply when NOT using CoreSense™ Diagnostics
NOTE: Envelope restrictions will vary slightly between refrigerants.
27
AE4-1383 R14
62
140
52
120
42
100%-30%
100%-70%
100%-50%
100%-40%
100
32
80
22
60
12
40
2
20 -8
0 -18
- 20 - 10 0 10 20 30 40 50
Figure 2 (M)
62
140
Condensing Temperature (°C)
Condensing Temperature (°F)
52
120
100%-30%
42
100%-70%
100%-50%
100%-40%
100%-70%
100
32
80
22
60
12
40
2
20 -8
0 -18
- 20 - 10 0 10 20 30 40 50
NOTE: Minimum capacity is assumed running at a continuous minimum capacity. These Minimum capacity restrictions ONLY
apply when NOT using CoreSense™ Diagnostics
NOTE: Envelope restrictions will vary slightly between refrigerants.
28
AE4-1383 R14
FILTER
DRIER SUCTION
MANIFOLD
KEEP MIN
(SEE NOTE 6)
<12”
<12”
CONTINUOUS TUBING
(NO ELBOWS) <30”
Figure 3 (A)
Notes: Typical Suction Tubing
(1) The above tubing configurations are guidelines to minimize tube stress.
(2) Follow similar guidelines for discharge tubing and oil return tubing as needed.
(3) If a run over 30” is required, intermediate clamps may be necessary.
(4) Do not hang weights on tubing (e.g. filter drier on suction tubing) except after clamps or close to the header.
(5) This dimension should be made as short as possible but still insuring a proper braze joint.
(6) The above tubing recommendations are based on “no elbow joints”. The use of continuous tubing is preferred.
29
AE4-1383 R14
Figure 3 (D)
30
AE4-1383 R14
Condenser
LIT
Outlet
VOT
Vapor Outlet to
Compressor
SIT
Vapor Out Cond. Out
Heat
Exchanger
Liq. In
UT TXV
TXV SIT
LOT
Liq. Out
Vapor In
31
AE4-1383 R14
028-0188-22
SLEEVE
102-0283-00
WASHER
027-0115-00
RUBBER PAD
027-0400-00
RUBBER GROMMET
027-0383-00 KIT# 998-0178-00 KIT #527-0210-00
STEEL SPACER
Figure 8A Figure 8B
8 - 17 HP Copeland Scroll Compressor 8-13HP Condensing Unit Mounting for
Rack Mounting Models ZB95-ZB(D)114 and ZF49-54
028-0188-16
027-0186-00
527-0116-00
Figure 8C
13-17HP Condensing Unit Mounting for
Models ZB58/66, ZB(D)76 and ZF34-ZF(D)41
32
CoreSense Module With Pressure Safety Control
AE4-1383 R14
L1
L2
13 14
*Kriwan
M1
Module
M1 INJ
Sol
M2
M2
T1 L1
CC
T2 L2
OMB
Alarm
L1 L2
Kriwan CoreSense
Module Diagnostics
T1 L1
T2 L2
INJ
M2 M1 M2 SOL
M1
** The physical location of M1/M2 & L1/L2 have
changed on the CoreSense module ** CC
Current Transducer
Note: If Kriwan module is used, wire in series
D Discharge Top Cap
with CoreSense module, as indicated in diagram. Thermistor
Digital Solenoid
(Same as Control
If Kriwan module is not used, wire M1 directly Circuit Voltage)
from safety circuit to M1 on CoreSense & M2
1-5v Digital
from contactor coil to M2 on CoreSense module. System Capacity Input
6 Pin to EXV Coil
Control OMB 12VDC
** System control point only needed for fixed
capacity compressors.
LPCO HPCO
EXV Coil
Alarm
33
** The physical location of M1/M2 & L1/L2
have changed on the CoreSense module **
AE4-1383 R14
Top Cap
Thermistor
34
Communication Module DIP Switch Settings AE4-1383 R14
Node Addresses
“On” (UP)
9600 Even Network Terminated
1 4 7
12345 12345 12345
Baud Control Network
Parity
Rate Mode Termination
2 5 8
12345 12345 12345
No Stand Not
19200
Parity Alone Terminated
3 6 9 “Off ” (Down)
12345 12345 12345
Terminal 9, Jumper To
Terminal 13
Terminal 5, Demand Wire
Terminal 13, L1
and Jumpered
to Terminal 9
Terminal 14, L2
Figure 16 – E2 Jumpers
35
AE4-1383 R14
(Terminated)
(Terminated)
(Terminated)
(Terminated)
(Terminated)
(Terminated)
(Terminated)
(Terminated)
36
AE4-1383 R14
Compressor
Operation
DIP Switches
Current Toroid Plugin
Digital Input 1-5V
Diagnostic (Analog Input)
LED Lights
Top Cap Thermistor
Module Modbus®
Communication Communication
DIP Switches Plugin
Ground Screw
37
AE4-1383 R14
Intermediate
Floating
Seal Cavity
Removable External
Solenoid and Coil
Figure 20
Digital Compressor Cutaway View
38
AE4-1383 R14
90%
80%
Compressor Capacity (Percent of Full Load)
70%
60%
50%
40%
30%
20%
10%
0%
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Solenoid On -Time (Seconds)
Figure 21A
ZBD*K5E Digital Operation Cycle Time
Figure 21B
ZFD*K5E Digital Operation Cycle Time
39
AE4-1383 R14
Figure 22
40
AE4-1383 R14
Table 1
Injection Accessories
Reference
Application Injection Refrigerants Required Kits
Figure
ZB
N/A All Top Cap Thermistor is Factory Installed (no kits required) See Figure 21
(Medium Temp)
998-0229-00: Top Cap Thermistor Kit
404A/507 See Figure 21
*Top Cap Thermistor is factory installed on -260 BOM
Vapor
ZF Injection 407A/C/F 998-0500-03: 250°F DTC Kit Including Temperature Probe
See Figure 3C
(Low Temp) 448A/449A 998-0177-00: DTC Vapor Injection Adapter
Liquid
All 998-0500-03: 250°F DTC Kit Including Temperature Probe See Figure 3B
Injection
Table 2
External Wrap-Around Crankcase Heaters
Crankcase Crankcase Lead Length Ground Wire Conduit Ready Box for
Volts Watts
Heater Kit P/N Heater P/N (in) Length (in) Crankcase Heater
918-0047-00 018-0091-00 120 90 48 48
918-0047-01 018-0091-01 240 90 48 48
998-7029-00
918-0047-02 018-0091-02 480 90 48 48
918-0047-03 018-0091-03 575 90 48 48
Table 3
Kriwan INT69 Module Specifications
41
AE4-1383 R14
Table 4
K5 Compressor for Refrigeration Additional Accessories
42
AE4-1383 R14
Table 5
K5 Compressor for Refrigeration (8 to 17 HP) Fitting Sizes
Table 6
High and Low Pressure Control Settings
Table 7A Table 7B
Low Temperature Digital Modulation MediumTemperature Digital Modulation
Capacity(%)/Analog (V) Capacity(%)/Analog (V)
Digital Digital
Analog Analog
Digital Solenoid Digital Solenoid
Voltage Input Voltage Input
Capacity % On time Capacity % On time
(Volts) (Volts)
(Seconds) (Seconds)
100% 5.00 0 100% 5.00 0
90% 4.60 2 90% 4.60 2
80% 4.20 4 80% 4.20 4
70% 3.80 6 70% 3.80 6
60% 3.40 8 60% 3.40 8
50% 3.00 10 50% 3.00 10
40% 2.60 12 40% 2.60 12
30% 2.20 14 30% 2.20 14
20% 1.80 16
10% 1.40 18
43
AE4-1383 R14
Table 8
R1011 Alert Code Descriptions
44
AE4-1383 R14
Table 9
CoreSense™ Diagnostics Module Troubleshooting
45
AE4-1383 R14
46
AE4-1383 R14
Table 12
CoreSense™ Module DIP Switch Scenarios
The contents of this publication are presented for informational purposes only and are not to be construed as warranties or guarantees, express or implied, regarding the products or
services described herein or their use or applicability. Emerson Climate Technologies, Inc. and/or its affiliates (collectively "Emerson"), as applicable, reserve the right to modify the
design or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for
proper selection, use and maintenance of any Emerson product remains solely with the purchaser or end user.
47
CoreSense™ Diagnostics for Copeland Scroll™ K5 Refrigeration Compressors
Modbus® Specification
Table of Contents
3.0 Module Type Identification ......................................... 2 5.0 Data Link Layer ........................................................... 4
3.1 CoreSense Diagnostics Pre January 2015 DIP Switch Settings & 5.1 Node Address ............................................................................ 4
Configurations ................................................................................. 2 5.2 RTU Transmission Mode ........................................................... 5
3.1.1 Main DIP Switch Board .......................................................... 3 5.3 Response Message Timeout ..................................................... 5
3.1.2 Communication DIP Switch Board ......................................... 3
3.2 CoreSense Diagnostics After January 2015 DIP Switch Settings 6.0 Application Layer ........................................................ 5
& Configurations .............................................................................. 3 6.1 Available Functions ................................................................... 5
3.2.1 Main DIP Switch Board .......................................................... 3 6.2 Data Types ................................................................................ 5
3.2.2 Communication DIP Switch Board ......................................... 3 6.3 Functions Supported ................................................................. 6
6.3.1 Input Register (Command 0x04) ............................................ 6
4.0 Physical Layer ............................................................. 3 6.3.2 Hold Register (Command 0x03, 0x06, 0x10) ....................... 12
4.1 Topology.................................................................................... 3
4.1.1 Wire Used ............................................................................... 3 7.0 Troubleshooting ........................................................ 14
4.1.2 Bus Bias ................................................................................. 3
4.1.3 Termination ............................................................................ 4
Communication
DIP Switch
Board
Figure 4: After January 2015 Main DIP Switch Board
Figure 1: Pre January 2015 CoreSense™ Diagnostics DIP
Switch Panels 3.2.2 Communication DIP Switch Board
See 3.1.2 for details.
3.1.1 Main DIP Switch Board
DIP Switches 1-5 are reserved for future use. DIP
switch 6 is used to enable/disable lockouts. The UP 4.0 Physical Layer
position enables lockout and the DOWN position
disables lockout. This layer defines the hardware interface to the
network.
3.1.2 Communication DIP Switch Board
4.1 Topology
The CoreSense Diagnostics module for Copeland
Scroll K5 refrigeration compressors uses the ‘two-wire’
configuration (two signal wires plus a ground). The
standard configuration will be to directly wire to the
cable forming a daisy-chain.
Main DIP
Figure 5: Recommended Communication Wire
Switch
Board 4.1.2 Bus Bias
All master devices must provide a means to bias the
network. The recommended pull-down on the RS485
‘+’ output is a 511 ohm resistor, but up to a 1K ohm
Communication resistor is acceptable. The recommended pull-up
DIP Switch resistor on the RS485 ‘-’ output is a 511 ohm resistor,
Board but up to 1K ohms is acceptable. These bias resistors
can either be always enabled or they can be enabled
through jumpers. The bias is applied at one point in the
Figure 3: After January 2015 CoreSense™ Diagnostics DIP
Switch Panels
network.
4.1.3 Termination • Middle Connection is not labeled and is
The last slave in the network shall have a 150 ohm ground
resistor for termination. In this module, there is a • ‘+’ Positive
termination DIP switch on the communication DIP
See Figure 6 for reference.
switch panel. Position 10 DIP switch is used for
termination. See Figure 2 for reference. The last 4.4 Connector
CoreSense module in the network shall be terminated
by sliding DIP switch 10 up, to the ON position. For the A three position screw cable connector is used for
other CoreSense modules in the network, DIP switch Modbus communication.
10 shall be down, in the OFF position.
4.5 Wiring and Connections
4.2 Data Signaling Rate
The Modbus wiring should be connected to module
The communications port default settings are 19200, connector ‘-’, ‘GND’, ‘+’
no Parity, 8 data, 2 Stop bits. The baud rate (19200 or
9600), parity (even or no parity) and stop bits (1 bit or 2
bit) are user selectable through DIP switches. Data
length is not configurable. See Figure 2 Error!
Reference source not found. and Figure 4 for DIP
switch reference.
Address
(Hex) Contents Quantity Data Description
Start Stop
0000 001B Division Name 28 'X'
001C 0021 Product Name 6 'X'
0022 0029 Product Code 8 'X'
002A 0030 Module Version Number 7 'X'
Today compressor run time
0077 0077
One counter means 6 minutes
Today-1 compressor run time
0078 0078
One counter means 6 minutes
Today-2 compressor run time
0079 0079
One counter means 6 minutes
Seven Days of Today-3 compressor run time
007A 007A 7
Compressor Run Time One counter means 6 minutes
Today-4 compressor run time
007B 007B
One counter means 6 minutes
Today-5 compressor run time
007C 007C
One counter means 6 minutes
Today-6 compressor run time
007D 007D
One counter means 6 minutes
Today compressor start times
007E 007E
One counter means 1 time
Today-1 compressor start times
007F 007F
One counter means 1 time
Today-2 compressor start times
0080 0080
One counter means 1 time
Seven Days of Today-3 compressor start times
0081 0081 7
Compressor Start Times One counter means 1 time
Today-4 compressor start times
0082 0082
One counter means 1 time
Today-5 compressor start times
0083 0083
One counter means 1 time
Today-6 compressor start times
0084 0084
One counter means 1 time
Total Compressor Run One counter means 1 hours
0085 0086 2
Time 0-4294967295
Total Compressor Start One counter means 1 start
0087 0088 2
Times 0-4294967295
Protection Trip For Seven One counter means one time
008E 008E 1
Days 0-65535
Protection Trip After One counter means one time
008F 0090 2
Power Up 0 - 4294967295
009B 009B 1 Alarm Id of tenth most recent alarm
009C 009C 1 Alarm Id of ninth most recent alarm
Ten Most Recent Alarm
009D 009D 1 Alarm Id of eighth most recent alarm
009E 009E 1 Alarm Id of seventh most recent alarm
009F 009F 1 Alarm Id of sixth most recent alarm
00A0 00A0 1 Alarm Id of fifth most recent alarm
00A1 00A1 1 Alarm Id of most fourth recent alarm
00A2 00A2 1 Alarm Id of third most recent alarm
00A3 00A3 1 Alarm Id of second most recent alarm
00A4 00A4 1 Alarm Id of most recent alarm
BIT0 - Today:
(0 - Not present / 1 - Present)
BIT1 - Today-1:
Eight Days Alarm History
00AA 00AA 5 (0 - Not present / 1 - Present)
of DLT Fault
……………………………..
BIT7 - Today-7:
(0 - Not present / 6 - Present)
BIT0 - Today:
(0 - Not present / 1 - Present)
BIT1 - Today-1:
Eight Days Alarm History
00AB 00AB 6 (0 - Not present / 1 - Present)
of CT Fault Warning
……………………………..
BIT7 - Today-7:
(0 - Not present / 8 - Present)
BIT0 - Today:
(0 - Not present / 1 - Present)
Eight Days Alarm History BIT1 - Today-1:
00AC 00AC of Loss Comm From E2 7 (0 - Not present / 1 - Present)
Warning ……………………………..
BIT7 - Today-7:
(0 - Not present / 9 - Present)
BIT0 - Today:
(0 - Not present / 1 - Present)
BIT1 - Today-1:
Eight Days Alarm History
00AF 00AF 10 (0 - Not present / 1 - Present)
of Short Cycling Warning
……………………………..
BIT7 - Today-7:
(0 - Not present / 12 - Present)
BIT0 - Today:
(0 - Not present / 1 - Present)
BIT1 - Today-1:
Eight Days Alarm History
00B0 00B0 11 (0 - Not present / 1 - Present)
of Open Circuit Warning
……………………………..
BIT7 - Today-7:
(0 - Not present / 13 - Present)
BIT0 - Today:
(0 - Not present / 1 - Present)
Eight Days Alarm History BIT1 - Today-1:
00B1 00B1 of Welded Contactor 12 (0 - Not present / 1 - Present)
Warning ……………………………..
BIT7 - Today-7:
(0 - Not present / 14 - Present)
BIT0 - Today:
Eight Days Alarm History (0 - Not present / 1 - Present)
00B4 00B4 of High Discharge Line 15 BIT1 - Today-1:
Temperature Alarm (0 - Not present / 1 - Present)
……………………………..
BIT7 - Today-7:
(0 - Not present / 17 - Present)
BIT0 - Today:
(0 - Not present / 1 - Present)
BIT1 - Today-1:
Eight Days Alarm History
00B5 00B5 16 (0 - Not present / 1 - Present)
of System Trip Alert
……………………………..
BIT7 - Today-7:
(0 - Not present / 18 - Present)
BIT0 - Today:
(0 - Not present / 1 - Present)
BIT1 - Today-1:
Eight Days Alarm History
00B6 00B6 17 (0 - Not present / 1 - Present)
of Locked Rotor Alert
……………………………..
BIT7 - Today-7:
(0 - Not present / 19 - Present)
BIT0 - Today:
(0 - Not present / 1 - Present)
BIT1 - Today-1:
Eight Days Alarm History
00B7 00B7 18 (0 - Not present / 1 - Present)
of Missing Phase Alert
……………………………..
BIT7 - Today-7:
(0 - Not present / 20 - Present)
BIT0 - Today:
(0 - Not present / 1 - Present)
BIT1 - Today-1:
Eight Days Alarm History
00B8 00B8 19 (0 - Not present / 1 - Present)
of Reverse Phase Alert
……………………………..
BIT7 - Today-7:
(0 - Not present / 21 - Present)
BIT0 - Today:
(0 - Not present / 1 - Present)
Eight Days Alarm History BIT1 - Today-1:
00BA 00BA of Module Low Voltage 21 (0 - Not present / 1 - Present)
Alert ……………………………..
BIT7 - Today-7:
(0 - Not present / 23 - Present)
BIT0 - Today:
(0 - Not present / 1 - Present)
Eight Days Alarm History BIT1 - Today-1:
00C6 00C6 of High Discharge 33 (0 - Not present / 1 - Present)
Temperature Lockout ……………………………..
BIT7 - Today-7:
(0 - Not present / 35 - Present)
BIT0 - Today:
(0 - Not present / 1 - Present)
BIT1 - Today-1:
Eight Days Alarm History
00C7 00C7 35 (0 - Not present / 1 - Present)
of Locked Rotor Lockout
……………………………..
BIT7 - Today-7:
(0 - Not present / 37 - Present)
BIT0 - Today:
(0 - Not present / 1 - Present)
BIT1 - Today-1:
Eight Days Alarm History
00C9 00C9 36 (0 - Not present / 1 - Present)
of Missing Phase Lockout
……………………………..
BIT7 - Today-7:
(0 - Not present / 38 - Present)
BIT0 - Today:
(0 - Not present / 1 - Present)
BIT1 - Today-1:
Eight Days Alarm History
00CA 00CA 37 (0 - Not present / 1 - Present)
of Reverse Phase Lockout
……………………………..
BIT7 - Today-7:
(0 - Not present / 39 - Present)
One counter means one times
00E3 00E3 OAC of DLT Fault 5
0 - 65535
One counter means one times
00E4 00E4 OAC of CT Fault Warning 6
0 - 65535
OAC of Loss Comm From One counter means one times
00E5 00E5 7
E2 Warning 0 - 65535
OAC of Short Cycling One counter means one times
00E8 00E8 10
Warning 0 - 65535
OAC of Open Circuit One counter means one times
00E9 00E9 11
Warning 0 - 65535
OAC of Welded Contactor One counter means one times
00EA 00EA 12
Warning 0 - 65535
OAC of High Discharge One counter means one times
00ED 00ED 15
Line Temperature Alarm 0 - 65535
One counter means one times
00EE 00EE OAC of System Trip Alert 16
0 - 65535
OAC of Locked Rotor One counter means one times
00EF 00EF 17
Alert 0 - 65535
OAC of Missing Phase One counter means one times
00F0 00F0 18
Alert 0 - 65535
OAC of Reverse Phase One counter means one times
00F1 00F1 19
Alert 0 - 65535
OAC of Module Low One counter means one times
00F3 00F3 21
Voltage Alert 0 - 65535
OAC of High Discharge One counter means one times
00FF 00FF 33
Temperature Lockout 0 - 65535
OAC of Locked Rotor One counter means one times
0101 0101 35
Lockout 0 - 65535
OAC of Missing Phase One counter means one times
0102 0102 36
Lockout 0 - 65535
OAC of Reverse Phase One counter means one times
0103 0103 37
Lockout 0 - 65535
1:Normal off
2: Normal Running
101:Temperature Probe Failure Warning
106:DLT Open Warning
107:DLT Short Warning
108:CT Fault Warning
109:Loss Comm From E2 Warning
112:Short Cycling Warning
113:Open Circuit Warning
114:Welded Contactor Warning
117:Module Failure
118:Modulation Code1
119:Modulation Code2
0117 0117 Current Alert 1
120:Modulation Code3
200:High Discharge Line Temperature Alarm
201:System Trip Alert
202:Locked Rotor Alert
203:Missing Phase Alert
204:Reverse Phase Alert
206:Module Low Voltage Alert
300:High Discharge Temperature Lockout
301:System Trip Lockout
302:Locked Rotor Lockout
303:Missing Phase Lockout
304:Reverse phase Lockout
311:Module Failure Lockout
101:Temperature Probe Failure Warning
106:DLT Open Warning
107:DLT short Warning
108:CT Fault Warning
109:Loss Comm From E2 Warning
112:Short Cycling Warning
113:Open Circuit Warning
114:Welded Contactor Warning
117:Module Failure
118:Modulation Code1
119:Modulation Code2
120:Modulation Code3
0118 0118 Previous Alert 1
200:High Discharge Line Temperature Alarm
201:System Trip Alert
202:Locked Rotor Alert
203:Missing Phase Alert
204:Reverse Phase Alert
206:Module Low Voltage Alert
Address
(Hex) Contents Quantity Data Description
Start Stop
0025 0036 Compressor Module Number 18 'X'
0037 0042 Compressor Serial Number 12 'X'
0051 005C Module Part Number 12 'X'
005D 0069 Module Serial Number 13 'X'
0x00 – Automatic based on the temperature;
0076 0076 EXV Control Type 1 0x01 - Manual control
Default: Automatically
if the EXV control type is automatic, then ignore this
EXV Position for Manual
0077 0077 1 item;
Control
0~100 means the EXV open is 0%~100%
0078 0078 Proportionality Coefficient Set 1 0~65535 means 0~655.35
0079 0079 Integral Coefficient Set 1 0~65535 means 0~655.35
007A 007A Differential Coefficient Set 1 0~65535 means 0~655.35
007B 007B PID Sample Time 1 One Counter Means One Second (1~50s)
0~65535 means -70~585.35°F
The temperature value
007D 007D PID Set Point Value Set 1
= ( (( High byte << 8) + Low byte) - 7000) / 100
The default value should be: 255°F
Default : 6 seconds
0080 0080 Minimum On Time 1 Unit : 1 Seconds
Range : 0 - 65535 seconds
Default : 6 seconds
0081 0081 Minimum Off Time 1 Unit : 1 Seconds
Range : 0 - 65535 seconds
DLT temp trip set point value,
Unit : 0.01°F ;
0085 0085
Range: -70 to 585.35 °F
Alert Trigger Parameters
20 Set point = (Word - 7000 )/ 100 (°F)
Configuration
Default: 297°F
0086 0086 DLT temp trip reset point value,
Unit : 0.01°F ;
Range: -70 to 585.35 °F
Reset point =( Word -7000 )/100 (°F)
The
Address
Length
request
CMD
CRC
Start
and
response is
hex value.
Request for
0 0 0 0 0 0 5 9
version
8 4 0 2 0 8 0 5
number
Address
Bytes
CMD
CRC
1 . 0 1 R 0 0