Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

RSLF Artillery Brigade Al Yamama

Eastern Province, Kingdom of Saudi Arabia

core-drilled hole are completely grouted smooth.

2.13.2.2 Sleeves Not in Masonry and Concrete

Provide 26 gage galvanized steel sheet or PVC plastic pipe sleeves.

2.13.3 Pipe Hangers (Supports)

Provide MSS SP-58 Type 1 with adjustable type steel support rods, except
as specified or indicated otherwise. Attach to steel joists with Type 19
or 23 clamps and retaining straps. Attach to Steel W or S beams with Type
21, 28, 29, or 30 clamps. Attach to steel angles and vertical web steel
channels with Type 20 clamp with beam clamp channel adapter. Attach to
horizontal web steel channel and wood with drilled hole on centerline and
double nut and washer. Attach to concrete with Type 18 insert or drilled
expansion anchor. Provide Type 40 insulation protection shield for
insulated piping.

2.13.4 Nameplates

Provide 3.2 mm thick melamine laminated plastic nameplates, black matte


finish with white center core, for equipment, gages, thermometers, and
valves; valves in supplies to faucets will not require nameplates.
Accurately align lettering and engrave minimum of 6.4 mm high normal block
lettering into the white core. Minimum size of nameplates shall be 25 by
63 mm. Key nameplates to a chart and schedule for each system. Frame
charts and schedules under glass and place where directed near each
system. Furnish two copies of each chart and schedule.

PART 3 EXECUTION

3.1 GENERAL INSTALLATION REQUIREMENTS

Piping located in air plenums shall conform to NFPA 90A requirements.


Piping located in shafts that constitute air ducts or that enclose air
ducts shall be noncombustible in accordance with NFPA 90A. Installation
of plastic pipe where in compliance with NFPA may be installed in
accordance with PPFA Fire Man. The plumbing system shall be installed
complete with necessary fixtures, fittings, traps, valves, and
accessories. Water and drainage piping shall be extended 1.5 m outside
the building, unless otherwise indicated. A ball valve and drain shall be
installed on the water service line inside the building approximately 150
mm above the floor from point of entry. Piping shall be connected to the
exterior service lines or capped or plugged if the exterior service is not
in place. Sewer and water pipes shall be laid in separate trenches,
except when otherwise shown. Exterior underground utilities shall be at
least 300 mm below the finish grade or as indicated on the drawings. If
trenches are closed or the pipes are otherwise covered before being
connected to the service lines, the location of the end of each plumbing
utility shall be marked with a stake or other acceptable means. Valves
shall be installed with control no lower than the valve body.

3.1.1 Water Pipe, Fittings, and Connections

3.1.1.1 Utilities

The piping shall be extended to fixtures, outlets, and equipment. The


hot-water and cold-water piping system shall be arranged and installed to
permit draining. The supply line to each item of equipment or fixture,

SECTION 22 00 00 Page 19
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia

Unless otherwise indicated, sleeves shall be of a size to provide a


minimum of 6 mm clearance between bare pipe or insulation and inside of
sleeve or between insulation and inside of sleeve. Sleeves in bearing
walls and concrete slab on grade floors shall be steel pipe or cast-iron
pipe. Sleeves in nonbearing walls or ceilings may be steel pipe,
cast-iron pipe, galvanized sheet metal with lock-type longitudinal seam,
or plastic.

Except as otherwise specified, the annular space between pipe and sleeve,
or between jacket over insulation and sleeve, shall be sealed as indicated
with sealants conforming to ASTM C920 and with a primer, backstop material
and surface preparation as specified in Section 07 92 00 JOINT SEALANTS.
The annular space between pipe and sleeve, between bare insulation and
sleeve or between jacket over insulation and sleeve shall not be sealed
for interior walls which are not designated as fire rated.

Sleeves through below-grade walls in contact with earth shall be recessed


12 mm from wall surfaces on both sides. Annular space between pipe and
sleeve shall be filled with backing material and sealants in the joint
between the pipe and concrete wall as specified above. Sealant selected
for the earth side of the wall shall be compatible with
dampproofing/waterproofing materials that are to be applied over the joint
sealant. Pipe sleeves in fire-rated walls shall conform to the
requirements in Section 07 84 00 FIRESTOPPING.

3.1.4.2 Flashing Requirements

Pipes passing through roof shall be installed through a 4.9 kg per square
meter copper flashing, each within an integral skirt or flange. Flashing
shall be suitably formed, and the skirt or flange shall extend not less
than 200 mm from the pipe and shall be set over the roof or floor membrane
in a solid coating of bituminous cement. The flashing shall extend up the
pipe a minimum of 250 mm. For cleanouts, the flashing shall be turned
down into the hub and caulked after placing the ferrule. Pipes passing
through pitched roofs shall be flashed, using lead or copper flashing,
with an adjustable integral flange of adequate size to extend not less than
200 mm from the pipe in all directions and lapped into the roofing to
provide a watertight seal. The annular space between the flashing and the
bare pipe or between the flashing and the metal-jacket-covered insulation
shall be sealed as indicated. Flashing for dry vents shall be turned down
into the pipe to form a waterproof joint. Pipes, up to and including 250
mm in diameter, passing through roof or floor waterproofing membrane may
be installed through a cast-iron sleeve with caulking recess, anchor lugs,
flashing-clamp device, and pressure ring with brass bolts. Flashing
shield shall be fitted into the sleeve clamping device. Pipes passing
through wall waterproofing membrane shall be sleeved as described above.
A waterproofing clamping flange shall be installed.

3.1.4.3 Waterproofing

Waterproofing at floor-mounted water closets shall be accomplished by


forming a flashing guard from soft-tempered sheet copper. The center of
the sheet shall be perforated and turned down approximately 40 mm to fit
between the outside diameter of the drainpipe and the inside diameter of
the cast-iron or steel pipe sleeve. The turned-down portion of the
flashing guard shall be embedded in sealant to a depth of approximately 40
mm; then the sealant shall be finished off flush to floor level between
the flashing guard and drainpipe. The flashing guard of sheet copper

SECTION 22 00 00 Page 23
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia

shall extend not less than 200 mm from the drainpipe and shall be lapped
between the floor membrane in a solid coating of bituminous cement. If
cast-iron water closet floor flanges are used, the space between the pipe
sleeve and drainpipe shall be sealed with sealant and the flashing guard
shall be upturned approximately 40 mm to fit the outside diameter of the
drainpipe and the inside diameter of the water closet floor flange. The
upturned portion of the sheet fitted into the floor flange shall be sealed.

3.1.4.4 Optional Counterflashing

Instead of turning the flashing down into a dry vent pipe, or caulking and
sealing the annular space between the pipe and flashing or
metal-jacket-covered insulation and flashing, counterflashing may be
accomplished by utilizing the following:

a. A standard roof coupling for threaded pipe up to 150 mm in diameter.

b. A tack-welded or banded-metal rain shield around the pipe.

3.1.4.5 Pipe Penetrations of Slab on Grade Floors

Where pipes, fixture drains, floor drains, cleanouts or similar items


penetrate slab on grade floors, except at penetrations of floors with
waterproofing membrane as specified in paragraphs FLASHING REQUIREMENTS
and WATERPROOFING, a groove 6 to 13 mm wide by 6 to 10 mm deep shall be
formed around the pipe, fitting or drain. The groove shall be filled with
a sealant as specified in Section 07 92 00 JOINT SEALANTS.

3.1.4.6 Pipe Penetrations

Provide sealants for all pipe penetrations. All pipe penetrations shall
be sealed to prevent infiltration of air, insects, and vermin.

3.1.5 Fire Seal

Where pipes pass through fire walls, fire-partitions, fire-rated pipe


chase walls or floors above grade, a fire seal shall be provided as
specified in Section 07 84 00 FIRESTOPPING.

3.1.6 Supports

3.1.6.1 General

Hangers used to support piping 50 mm and larger shall be fabricated to


permit adequate adjustment after erection while still supporting the
load. Pipe guides and anchors shall be installed to keep pipes in
accurate alignment, to direct the expansion movement, and to prevent
buckling, swaying, and undue strain. Piping subjected to vertical
movement when operating temperatures exceed ambient temperatures shall be
supported by variable spring hangers and supports or by constant support
hangers. In the support of multiple pipe runs on a common base member, a
clip or clamp shall be used where each pipe crosses the base support
member. Spacing of the base support members shall not exceed the hanger
and support spacing required for an individual pipe in the multiple pipe
run. Threaded sections of rods shall not be formed or bent.

3.1.6.2 Pipe Supports and Structural Bracing, Seismic Requirements

Piping and attached valves shall be supported and braced to resist seismic

SECTION 22 00 00 Page 24
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia

loads as specified in Section 13 48 00 SEISMIC PROTECTION FOR


MISCELLANEOUS EQUIPMENT. Structural steel required for reinforcement to
properly support piping, headers, and equipment, but not shown, shall be
provided. Material used for supports shall be as specified in Section
05 50 13 MISCELLANEOUS METAL FABRICATIONS.

3.1.6.3 Pipe Hangers, Inserts, and Supports

Installation of pipe hangers, inserts and supports shall conform to


MSS SP-58 except as modified herein.

a. Types 5, 12, and 26 shall not be used.

b. Type 3 shall not be used on insulated pipe.

c. Type 18 inserts shall be secured to concrete forms before concrete is


placed. Continuous inserts which allow more adjustment may be used if
they otherwise meet the requirements for type 18 inserts.

d. Type 19 and 23 C-clamps shall be torqued per MSS SP-58 and shall have
both locknuts and retaining devices furnished by the manufacturer.
Field-fabricated C-clamp bodies or retaining devices are not
acceptable.

e. Type 20 attachments used on angles and channels shall be furnished


with an added malleable-iron heel plate or adapter.

f. Type 24 may be used only on trapeze hanger systems or on fabricated


frames.

g. Type 39 saddles shall be used on insulated pipe 100 mm and larger when
the temperature of the medium is 15 degrees C or higher. Type 39
saddles shall be welded to the pipe.

h. Type 40 shields shall:

(1) Be used on insulated pipe less than 100 mm.

(2) Be used on insulated pipe 100 mm and larger when the temperature
of the medium is 15 degrees C or less.

(3) Have a high density insert for all pipe sizes. High density
inserts shall have a density of 128 kg per cubic meter or greater.

i. Horizontal pipe supports shall be spaced as specified in MSS SP-58 and


a support shall be installed not over 300 mm from the pipe fitting
joint at each change in direction of the piping. Pipe supports shall
be spaced not over 1.5 m apart at valves. Operating temperatures in
determining hanger spacing for PVC or CPVC pipe shall be 49 degrees C
for PVC and 82 degrees C for CPVC. Horizontal pipe runs shall include
allowances for expansion and contraction.

j. Vertical pipe shall be supported at each floor, except at


slab-on-grade, at intervals of not more than 4.5 m nor more than 2 m
from end of risers, and at vent terminations. Vertical pipe risers
shall include allowances for expansion and contraction.

k. Type 35 guides using steel, reinforced polytetrafluoroethylene (PTFE)


or graphite slides shall be provided to allow longitudinal pipe

SECTION 22 00 00 Page 25
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia

movement. Slide materials shall be suitable for the system operating


temperatures, atmospheric conditions, and bearing loads encountered.
Lateral restraints shall be provided as needed. Where steel slides do
not require provisions for lateral restraint the following may be used:

(1) On pipe 100 mm and larger when the temperature of the medium is 15
degrees C or higher, a Type 39 saddle, welded to the pipe, may
freely rest on a steel plate.

(2) On pipe less than 100 mm a Type 40 shield, attached to the pipe or
insulation, may freely rest on a steel plate.

(3) On pipe 100 mm and larger carrying medium less that 15 degrees C a
Type 40 shield, attached to the pipe or insulation, may freely
rest on a steel plate.

l. Pipe hangers on horizontal insulated pipe shall be the size of the


outside diameter of the insulation. The insulation shall be
continuous through the hanger on all pipe sizes and applications.

m. Where there are high system temperatures and welding to piping is not
desirable, the type 35 guide shall include a pipe cradle, welded to
the guide structure and strapped securely to the pipe. The pipe shall
be separated from the slide material by at least 100 mm or by an
amount adequate for the insulation, whichever is greater.

n. Hangers and supports for plastic pipe shall not compress, distort, cut
or abrade the piping, and shall allow free movement of pipe except
where otherwise required in the control of expansion/contraction.

3.1.6.4 Structural Attachments

Attachment to building structure concrete and masonry shall be by cast-in


concrete inserts, built-in anchors, or masonry anchor devices. Inserts
and anchors shall be applied with a safety factor not less than 5.
Supports shall not be attached to metal decking. Supports shall not be
attached to the underside of concrete filled floor or concrete roof decks
unless approved by the Contracting Officer. Masonry anchors for overhead
applications shall be constructed of ferrous materials only.

3.1.7 Pipe Cleanouts

Pipe cleanouts shall be the same size as the pipe except that cleanout
plugs larger than 100 mm will not be required. A cleanout installed in
connection with cast-iron soil pipe shall consist of a long-sweep 1/4 bend
or one or two 1/8 bends extended to the place shown. An extra-heavy
cast-brass or cast-iron ferrule with countersunk cast-brass head screw
plug shall be caulked into the hub of the fitting and shall be flush with
the floor. Cleanouts in connection with other pipe, where indicated,
shall be T-pattern, 90-degree branch drainage fittings with cast-brass
screw plugs, except plastic plugs shall be installed in plastic pipe.
Plugs shall be the same size as the pipe up to and including 100 mm.
Cleanout tee branches with screw plug shall be installed at the foot of
soil and waste stacks, at the foot of interior downspouts, on each
connection to building storm drain where interior downspouts are
indicated, and on each building drain outside the building. Cleanout tee
branches may be omitted on stacks in single story buildings with
slab-on-grade construction. Cleanouts on pipe concealed in partitions
shall be provided with chromium plated bronze, nickel bronze, nickel brass

SECTION 22 00 00 Page 26
100% Site and Facility Design Submittal

You might also like