Professional Documents
Culture Documents
Spec - Supports For Plumbing
Spec - Supports For Plumbing
Provide MSS SP-58 Type 1 with adjustable type steel support rods, except
as specified or indicated otherwise. Attach to steel joists with Type 19
or 23 clamps and retaining straps. Attach to Steel W or S beams with Type
21, 28, 29, or 30 clamps. Attach to steel angles and vertical web steel
channels with Type 20 clamp with beam clamp channel adapter. Attach to
horizontal web steel channel and wood with drilled hole on centerline and
double nut and washer. Attach to concrete with Type 18 insert or drilled
expansion anchor. Provide Type 40 insulation protection shield for
insulated piping.
2.13.4 Nameplates
PART 3 EXECUTION
3.1.1.1 Utilities
SECTION 22 00 00 Page 19
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia
Except as otherwise specified, the annular space between pipe and sleeve,
or between jacket over insulation and sleeve, shall be sealed as indicated
with sealants conforming to ASTM C920 and with a primer, backstop material
and surface preparation as specified in Section 07 92 00 JOINT SEALANTS.
The annular space between pipe and sleeve, between bare insulation and
sleeve or between jacket over insulation and sleeve shall not be sealed
for interior walls which are not designated as fire rated.
Pipes passing through roof shall be installed through a 4.9 kg per square
meter copper flashing, each within an integral skirt or flange. Flashing
shall be suitably formed, and the skirt or flange shall extend not less
than 200 mm from the pipe and shall be set over the roof or floor membrane
in a solid coating of bituminous cement. The flashing shall extend up the
pipe a minimum of 250 mm. For cleanouts, the flashing shall be turned
down into the hub and caulked after placing the ferrule. Pipes passing
through pitched roofs shall be flashed, using lead or copper flashing,
with an adjustable integral flange of adequate size to extend not less than
200 mm from the pipe in all directions and lapped into the roofing to
provide a watertight seal. The annular space between the flashing and the
bare pipe or between the flashing and the metal-jacket-covered insulation
shall be sealed as indicated. Flashing for dry vents shall be turned down
into the pipe to form a waterproof joint. Pipes, up to and including 250
mm in diameter, passing through roof or floor waterproofing membrane may
be installed through a cast-iron sleeve with caulking recess, anchor lugs,
flashing-clamp device, and pressure ring with brass bolts. Flashing
shield shall be fitted into the sleeve clamping device. Pipes passing
through wall waterproofing membrane shall be sleeved as described above.
A waterproofing clamping flange shall be installed.
3.1.4.3 Waterproofing
SECTION 22 00 00 Page 23
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia
shall extend not less than 200 mm from the drainpipe and shall be lapped
between the floor membrane in a solid coating of bituminous cement. If
cast-iron water closet floor flanges are used, the space between the pipe
sleeve and drainpipe shall be sealed with sealant and the flashing guard
shall be upturned approximately 40 mm to fit the outside diameter of the
drainpipe and the inside diameter of the water closet floor flange. The
upturned portion of the sheet fitted into the floor flange shall be sealed.
Instead of turning the flashing down into a dry vent pipe, or caulking and
sealing the annular space between the pipe and flashing or
metal-jacket-covered insulation and flashing, counterflashing may be
accomplished by utilizing the following:
Provide sealants for all pipe penetrations. All pipe penetrations shall
be sealed to prevent infiltration of air, insects, and vermin.
3.1.6 Supports
3.1.6.1 General
Piping and attached valves shall be supported and braced to resist seismic
SECTION 22 00 00 Page 24
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia
d. Type 19 and 23 C-clamps shall be torqued per MSS SP-58 and shall have
both locknuts and retaining devices furnished by the manufacturer.
Field-fabricated C-clamp bodies or retaining devices are not
acceptable.
g. Type 39 saddles shall be used on insulated pipe 100 mm and larger when
the temperature of the medium is 15 degrees C or higher. Type 39
saddles shall be welded to the pipe.
(2) Be used on insulated pipe 100 mm and larger when the temperature
of the medium is 15 degrees C or less.
(3) Have a high density insert for all pipe sizes. High density
inserts shall have a density of 128 kg per cubic meter or greater.
SECTION 22 00 00 Page 25
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia
(1) On pipe 100 mm and larger when the temperature of the medium is 15
degrees C or higher, a Type 39 saddle, welded to the pipe, may
freely rest on a steel plate.
(2) On pipe less than 100 mm a Type 40 shield, attached to the pipe or
insulation, may freely rest on a steel plate.
(3) On pipe 100 mm and larger carrying medium less that 15 degrees C a
Type 40 shield, attached to the pipe or insulation, may freely
rest on a steel plate.
m. Where there are high system temperatures and welding to piping is not
desirable, the type 35 guide shall include a pipe cradle, welded to
the guide structure and strapped securely to the pipe. The pipe shall
be separated from the slide material by at least 100 mm or by an
amount adequate for the insulation, whichever is greater.
n. Hangers and supports for plastic pipe shall not compress, distort, cut
or abrade the piping, and shall allow free movement of pipe except
where otherwise required in the control of expansion/contraction.
Pipe cleanouts shall be the same size as the pipe except that cleanout
plugs larger than 100 mm will not be required. A cleanout installed in
connection with cast-iron soil pipe shall consist of a long-sweep 1/4 bend
or one or two 1/8 bends extended to the place shown. An extra-heavy
cast-brass or cast-iron ferrule with countersunk cast-brass head screw
plug shall be caulked into the hub of the fitting and shall be flush with
the floor. Cleanouts in connection with other pipe, where indicated,
shall be T-pattern, 90-degree branch drainage fittings with cast-brass
screw plugs, except plastic plugs shall be installed in plastic pipe.
Plugs shall be the same size as the pipe up to and including 100 mm.
Cleanout tee branches with screw plug shall be installed at the foot of
soil and waste stacks, at the foot of interior downspouts, on each
connection to building storm drain where interior downspouts are
indicated, and on each building drain outside the building. Cleanout tee
branches may be omitted on stacks in single story buildings with
slab-on-grade construction. Cleanouts on pipe concealed in partitions
shall be provided with chromium plated bronze, nickel bronze, nickel brass
SECTION 22 00 00 Page 26
100% Site and Facility Design Submittal