Elsum 2023 Rofiul Huda
Elsum 2023 Rofiul Huda
Elsum 2023 Rofiul Huda
Presented by:
ROFIUL HUDA
AMN DAL HAR RING UIT JBB
2009 - 2012 2012 - 2018 2018 - 2019 2019 - 2021 Jan 23 - present
2 rofi91.blogspot.co.id
Outline
Transmission System Overview
Overview of UIT JBB, total assets and
asset growth
4
Transmission and Transformation
“PLN UIT JBB memiliki bidang usaha utama jasa penyaluran tenaga listrik dari pembangkit ke distribusi dan pelanggan
di wilayah DKI Jakarta, Provinsi Banten dan sebagian Provinsi Jawa Barat dengan cara pengoperasian dan
pemeliharaan instalasi penyaluran tenaga listrik “
Modern Grid (Smart Grid)
▪ Extensive communication
▪ More inverters in the grid
▪ More green energy
▪ Dynamic pricing
▪ Demand response
▪ Use of Non-Conventional
Instrument Transformers
www.pln.co.i |
d
VISI PLN
KOMPETENSI INTI PLN UIT JBB
www.pln.co.id 7
|
PERAN PLN UIT JBB
untuk mewujudkan Visi PLN
“Menjadi Perusahaan Listrik Terkemuka se-Asia
Tenggara
dan #1 Pilihan Pelanggan untuk Solusi Energi” Terkemuka se-Asia
Perusahaan Listrik Tenggara
PLN UIT JBB mendukung upaya
perusahaan untuk memiliki bisnis utama PLN UIT JBB mendukung upaya
berupa penyediaan tenaga listrik dengan perusahaan untuk mampu
mengelola bisnis penyaluran tenaga menyediakan penyaluran tenaga listrik
listrik di wilayah DKI Jakarta, Banten dan di wilayah DKI Jakarta, Banten dan
sebagian Jawa Barat untuk mendukung sebagian Jawa Barat dengan standar
keberlanjutan industri ketenagalistrikan kualitas pelayanan kelas dunia
di Indonesia. sehingga menjadikan Indonesia sebagai
pilihan investasi utama di Asia
Tenggara.
#1 Pilihan
Solusi Energi
Pelanggan
PLN UIT JBB mendukung upaya perusahaan untuk
dapat memberikan nilai kepada pelanggan berupa PLN UIT JBB mendukung perusahaan agar
solusi terhadap setiap permasalahan terkait menjadi pilihan utama pelanggan di wilayah
penyaluran tenaga listrik di wilayah DKI Jakarta, DKI Jakarta, Banten dan sebagian Jawa Barat
Banten dan sebagian Jawa Barat untuk karena kualitas dan pelayanan penyaluran
mengantisipasi berbagai peluang dan tantangan tenaga listrik yang diberikan sehingga
usaha serta konsisten dalam pengembangan konsumen menjadi loyal.
standar kerja.
www.pln.co.id 8
|
MISI PLN UIT JBB
(Sesuai Peraturan Direksi No. 0086.P/DIR/2022)
1
Melakukan Pengembangan dan Pengelolaan Aset.
2
Melakukan Pengendalian Investasi dan Logistik Transmisi.
3
Melaksanakan Operasi dan Pemeliharaan Aset Transmisi.
www.pln.co.id 9
|
SEJARAH SINGKAT PLN UIT JBB
PLN P3B Jawa Bali PLN TJBB PLN UIT JBB PLN UIT JBB
Penetapan Organisasi Perubahan Pertama Susunan Organisasi Reorganisasi sesuai
sesuai KEPDIR sesuai PERDIR sesuai PERDIR PERDIR
093.K/023/DIR/1995 0093.P/DIR/2016 0137.P/DIR/2018 0280.P/DIR/2022
tgl 2 Okt 1995 dan tgl 4 Mar 2016 tgl 6 Jun 2018 Tgl 12 Des 2022
Struktur terbaru PLN P3B Jawa Bali (3 Bidang menjadi PLN TJBB ▪ TJBB > UIT JBB
PLN UIT JBB
KEPDIR 4 Bidang) ▪ APP > UPT
Reorganisasi dari PLN Perubahan Kedua Reorganisasi sesuai
SK 259.K/DIR/2009 tgl ▪ Penambahan Layer
P3B Jawa Bali sesuai sesuai PERDIR PERDIR
23 Okt 2009 dan Jumlah ULTG.
PERDIR 0044.P/DIR/2017 0050.P/DIR/2021
▪ Bid KSA > Bid Keu &
018.P/DIR/2015 tgl 9 Jun 2017 tgl 12 Mar 2021
Bid SDMU.
tgl 31 Agt 2015 (Tidak meliputi Bid Keu dan SDM &
▪ K3L dan Pengadaan
pengembangan aset) Umum (SDMU),
menjadi Biro.
menjadi Bid Keu, Kom
& Umum (KKU)
www.pln.co.id
|
WILAYAH KERJA PLN UIT JBB
SRLYRU SLIRA
LBE
SRLYA
PENDO
▪ ULTG TANGERANG
JAWA7 PINKA DNMGT GRGBR
▪ ULTG TANGERANG
NBLRJ KMYRN KLPGD
JTAKE MGBSR HRPIN
MNA CKRBR KTPNG
CKUPA TOSAN PGSAN JGC
BLRJA ANCOL
SPMIL TGLMACKRNG WHANA PLGD SNTER
SELATAN
KDL
KOTA
KRWTU CKNDE GSHRI GMBRU PKRNG
INDFR DKSBI ANGKE KBSRH MGRAI
IKPP LSTEL ALSTR KARET BKASI
SRANG MLNUM DKSB7 KBJRK BDKML KRBRU GDPLA
PLYPR CLDUG
ASAHI SGS KBGAN SBUDI TNTGI PGLGN SMRCN
GMS CBTAT RAKUN
NSYAN DKTAS TRSNA
CURUG ULJMI SNYAN RAWAM PDKLP
DRTGA MPBRU PLMAS
UPT CILEGON
PTKGN
UPT PULOGADUNG
PCAM BNTR2
CNSRI
DNYSA CWANGMPDUA MNTUR Tambun
GORDA TGKSA LEGOK BNTRO GNDUL AGP
CIPNG
LKNG2 SPONG CRNDU
▪ ULTG CILEGON ▪ ULTG PULOGADUNG
Poncol
MDERN LKON7 BSD ATSRI
LKONG PNDAH KMANG
ANYER
CIBNG
CBBUR
ITP
▪ ULTG RANGKAS ▪ ULTG BEKASI
SEMEN CB
BUNAR CLGSI
Saguling
Tasik
MALINGPING
BAYAH
PRATU
Ket:
UPT : Unit Pelaksana Transmisi
Gardu Induk 500 kV Saluran Transmisi 500 kV
3.070,34 KMS
Saluran Transmisi
Udara
Transmission Overhead Line
37.150 MVA
Kapasitas Trafo
Tenaga
Transformers Capacity
*) Data Aset Per Juni 2023
http://bit.ly/Dashboard-UITJBB www.pln.co.id 12
|
Transmission System Overview
Asset Profile of 22nd JMCC Members
EVN NPT - VIETNAM
Substation : 179 Unit SESB - SABAH
Transformer Capacity : 112,675 MVA SEB - SARAWAK
Circuits Length : 28,679 Kmc Substation : 47 Unit Substation : 49 Unit
Unit of Transformer : 371 Units Transformer Capacity : 13,586 MVA Circuits Length : 3,301.94 Kmc
Peak Demand : Circuits Length : 5,109.57 Kmc Unit of Transformer : 110 Units
Unit of Transformer : 111 Units Peak Demand : 1,032.06 MW
Peak Demand : 4,398 MW
EGAT - THAILAND
Substation : 234 Unit
Transformer Capacity : 135,882 MVA PLN - INDONESIA
Circuits Length : 38,546.30 Kmc
Substation : 984 Unit
Unit of Transformer : 820 Units
Transformer Capacity : 150,319 MVA
Peak Demand : 32,254.5 MW
Circuits Length : 59,190.65 Kmc
Unit of Transformer : 2053 Units
Peak Demand : 39,515.91 MW
TNB - MALAYSIA
Substation : 473 Unit
Transformer Capacity : 130,770 MVA
Circuits Length : 24,146 Kmc
Unit of Transformer : 1349 Units
Peak Demand : 19,183 MW
13
PROFIL SDM PLN UIT JBB
913 170
(84%) TOTAL (16%)
1083
Laki-laki Wanita
Customer Focus
15 PLN Mobile 16 Yantek
Optimization Legend: Digital Breakthrough
Relaunch
HV Transmission Assessment Challenges
Current Conductor, Jumper Conductor, Midspan compression
Carrying joint
2. Supporting Component
3.
Environment
17
Experience Sharing
Transmission Lines Failure due to Tree Falls
Event 1 Event 2
❑ 150 kV transmission lines ❑ 150 kV transmission lines
Lopana – Otam routes Kasongan – Sudan &
(North Sulawesi province) Kasongan – Parenggean
❑ Type of conductor ACSR routes (West Kalimantan
240/40 mm2 province)
❑ Failure event at May 18th ❑ Type of conductor ACSR
2021, 13:12 WITA 2x240/40 mm2
❑ Energy not served 591.89 ❑ Failure event at October 11th
MWh (There were 13 2022, 22:25 WITA
substations missing ❑ Energy not served 1148.908
voltage) MWh (There were 6
❑ Facts & findings : broken 3 substations missing voltage)
phase conductors and ❑ Facts & findings : live
tower bent due to tree falls conductor connected to
outside ROW (span of ground by broken OPGW due
tower no 178-179) to tree falls outside ROW
(span of tower no 221-222)
18
Experience Sharing
Transmission Lines Failure due to Tree Falls
T/L 150 kV Lopana – Otam Interruption event
◄ Line Line 2
❑ This disruption caused several power plants
1 ► trip so the frequency of the system dropped
Landslides
Point
and caused the UFLS and island operation
defense scheme work (3 islands).
❑ The total substations that lost voltage were 13
Substations with Energy Not Served (ENS) of
591,891.99 kWh.
T.177
Suspensio ❑ System recovery taken 6 hours 42 minutes
n
T.178 T.179 (Trip at 13:12 WITA, all load normal at 19:55
Tensio Suspensio
n n T.180 WITA)
Tensio
n T.181
◄◄ Tensio Otam ►►
Lopana n 19
Kerawanan Aset Tower Transmisi
www.pln.co.id 20
|
Riwayat Konduktor Putus ACSR, HTLS
SUTT 150 kV Bintaro-Serpong #2 (HVCRC) SUTET 500 kV Lengkong-Gandul #1 (ACCC)
Operasi: 17 Oktober 2017 (usia: + 3 Thn) Operasi: 21 Maret 2019 (usia: + 2 Thn)
Gangguan: 17 September 2020 (Putus) Gangguan: 14 Februari 2022 (Putus)
Baturaja - Bukit Kemuning
Riwayat Putus Saat Rekonduktoring: SUTT 150 kV Keramatwatu-Serang
Lahat - Bukit Asam - SUTT 150 kV Keramatwatu-Serang, 2016 (ACCC)
- SUTET 500 kV Suralaya-Balaraja, 2019 Operasi: Tahun 2016 (usia: < 1 Thn)
Gangguan: 23 Oktober 2016 (Putus)
Bintaro - Serpong
Gandul - Lengkong Mandirancan-New Ujungberung
Suralaya - Balaraja
Gilimanuk - Celukan Bawang
www.pln.co.id 21
|
RCPS Konduktor Putus ACSR, HTLS
www.pln.co.id 22
|
Case in Indonesia
Causes
● For the past 6 years, 18 times have been counted as disturbances caused by broken conductors in the PLN UIT JBT
area.
● One of the causes of broken conductors is caused by physical deterioration of the conductor due to loose spacers
● On August 31, 2022 at SUTET Mandirancan-New Ujungberung span T.143-144, it was discovered that a fault occurred
due to a broken conductor which was thought to be due to mechanical stress on the conductor due to the loose
spacer.
www.pln.co.id 31
|
Transmission Asset Population (Conductor HTLS)
Number of failures:
10
Number of failures:
2
www.pln.co.id 31
|
Case in Malaysia
www.pln.co.id 31
|
Field Finding Facts
www.pln.co.id 32
|
Event Analysis
The spacer is loose so there is a minor
cross
www.pln.co.id 34
|
Cases
16 April 2022. 500 kV Mae Moh - Tha Tako T.134/1 - 134/2 31 August 2022. 500 kV Mandirancan - New
Ujungberung T.143-144
www.pln.co.id
|
Improvement Opportunities
03
Verticality Online Monitoring System
29
VENOM
Verticality Online Monitoring System
DATA KONTINYU
Alat monitoring kondisi kemiringan tower secara realtime Mendapatkan data secara
sekaligus sebagai Early Warning System terhadap kondisi kontinyu sehingga kondisi
01
tower dapat terpantau
tower Transmisi
02
EFISIENSI
Efisiensi waktu, tenaga dan
biaya
Pengujian Fungsi atau komisioning Blok Diagram Node dan Power Suplai VENOM
www.pln.co.id
|
Kajian Literatur
*PT PLN (Persero) REGIONAL JAMALI, “Pedoman Pemeliharaan Peralatan Penyaluran Tenaga Listrik PT PLN (Persero) di www.pln.co.id
Regional Jawa Madura Bali
|
Milestone
• Identifikasi
Masalah
• Perumusan
alternatif-altern
atif solusi
• Pembuatan
flowchart dan
perancangan
hardware
www.pln.co.id
|
Desain
www.pln.co.id
|
DESAIN
www.pln.co.id
|
Tampilan Website VENOM (http://venom-uitjbb.id)
www.pln.co.id
|
Implementasi
19 LOKASI :
-500 kV Tasikmalaya – Depok
-150 kV Cilegon Baru - Posco
-150 kV Pucam – Modern
-Gardu Induk Bayah
-150 kV Pelabuhan Ratu – Bayah
-150 kV Kebon Agung - Sutami
-150 kV Sutami –Wlingi
-150 kV Lembursitu – Cianjur
-150 kV Ungaran – Wleri
-150 kV Lembursitu - Cianjur
www.pln.co.id
|
Dokumentasi Pemasangan
www.pln.co.id
|
Early Warning System
www.pln.co.id
|
Kalibrasi dan Hasil Uji
KALIBRASI IP 65
www.pln.co.id
|
Improvement Opportunities
04
Thermal Inspection Using Drone
41
Population & Inspection Frequency
Type of drones DJI Phantom 4 DJI Phantom 4 Pro DJI M300, Mavic 2 DJI M210, Mavic DJI M300, DJI M210,DJI
V1, DJI Phantom 4 Zoom, Mavic 2 2E, Phantom 4 Pro Mavic 2, Mavic M300,DJI M600,
Pro V2, DJI Mavic 2 Enterprise 3, Phantom 4, Mavic Mini 2,
Zoom, Mavic 3 Advanced, Phantom Mavic2 Zoom Mavic Pro,Mavic 2
4, Phantom 4-RTK Pro, Mavic Air 2,
Mini 2, Mavic 2
Zoom, Drone
Inspire 2,
Phantom 3 Pro,
Phantom 4 Pro
V2.0, Inspire 1
Pro
Frequency 2 years (handheld) 5 years & 6 monthly 2 times/year 3 year 5 years 2 times/year
(Line Crossing) - (drone/handheld) (drone/handheld) (handheld) (drone/handheld)
Handheld Every year for
important line
(helicopter)
www.pln.co.id
|
Comparison
Thermal Handheld & Drone Operation Photos - 275kV DJI M210 & Mavic 2 Operation Photos - 275kV
Similajau-Murum Junction L1, T54 Similajau-Murum Junction L1, T100
34.1°C
29.6°C
FLIR T620 DJI M210 + Zenmuse XT DJI M210 + Zenmuse XT DJI Mavic 2 Enterprise
Advanced
Optimal distance :
Handheld: 40-50 m
drone : 2.5 - 3 m Thermal Inspection using Drone has advantages on its easiness, price, visual close up and long range
www.pln.co.id
|
Comparison
Drone Handheld
useful in difficullt access / terrain &long range Access Depend on the access & limited distance
www.pln.co.id
|
Emissivity & Solar Heating
Example: Example:
Unreliable readings caused by thermal reflections Surface heating by direct sunlight gives false analysis
(low emissivity = higher reflection)
Mitigation: Mitigation:
Adjusting the emissivity based different object / materials Performing the inspection at early morning or late evening / night
where solar heating on the surface is significantly reduced
The Emissivity and solar heat affect the readings of the thermal inspection
www.pln.co.id
|
Thermal Condition
www.pln.co.id
|
Commissioning & Frequency of inspection
Inspection
Sighting 4 months monthly Yearly yearly weekly
Climb Up - conditional 5 years years
UAV - monthly - conditional conditional
Action for anomaly replace replace replace replace Mechanical& repair/
elastomer replace
test
www.pln.co.id
|
Improvement Opportunities
05
Broken Conductor Preventive Action
48
Rekomendasi Assessment Konduktor
www.pln.co.id
|
Commissioning & Assessment Method
www.pln.co.id
|
Preventive Action Konduktor Putus ACSR & HTLS
03 Pemasangan spacer
pengapit dan atau Pemasangan Spacer Pengapit pada Midspant Joint
reinforcment wedge
jarak 1 meter di kanan & kiri
midspant joint
04 Pengukuran thermovisi
midspant joint dan
junction seuai kepdir 520
atau pada saat kondisi
beroperasi 1 ruas penghantar
www.pln.co.id
|
Improvement Opportunities
06
Security Monitoring System
52
Case: AI algorithms proactively identify risks and improve inspection
efficiency(Transmission line)
54
Overview New Srintami
▪ GP melakukan inspeksi di tower ▪ LW melakukan inspeksi di tower
▪ Formulir inspeksi bersifat umum (general) NEW ??? (jam awal inspeksi = jam check in)
▪ Data disimpan di tower yang sama ▪ Formulir inspeksi memunculkan checklist sesuai
▪ Data tegakan susah divalidasi peralatan yang ada
▪ Lock Inspeksi minimal 10 menit [1]
▪ LW menyusuri jalur transmisi dan absen check
poin data ROW pada jalur tersebut
▪ Data inspeksi hanya bisa disimpan setelah LW
tiba di tower berikutnya
▪ Pengaturan jadwal inspeksi tower sesuai SLA[2]
Ground Patrol
Line Walker
▪ GP melaporkan ke Gardu Induk tiap minggu ▪ Data inspeksi diupload dengan trigger sinkronisasi dari
▪ Sinkronisasi Data SRINTAMI Mobile ke SRINTAMI Gardu SRINTAMI Gardu
▪ Sinkronisasi sekaligus menjadi nilai absensi GP ▪ Data KDAV GP dan hasil inspeksi
www.pln.co.id 10
|
OVERVIEW NEW SRINTAMI
www.pln.co.id
|
NEW SRINTAMI MOBILE
Absensi Online
Tracking Online
Push Notification
Content Amplification
www.pln.co.id 11
|
NEW SRINTAMI MOBILE
Absensi Online
Tracking Online
Push Notification
Content Amplification
www.pln.co.id 12
|
NEW SRINTAMI MOBILE
Absensi Online
Tracking Online
Push Notification
VALIDASI
Content Amplification
www.pln.co.id 13
|
NEW SRINTAMI MOBILE
Absensi Online
Tracking Online
Push Notification
Content Amplification
www.pln.co.id 14
|
NEW SRINTAMI MOBILE
Absensi Online
Push Notification
Content Amplification
www.pln.co.id 15
|
NEW SRINTAMI MOBILE
Absensi Online
Tracking Online
Push Notification
Content Amplification
www.pln.co.id 16
|
NEW SRINTAMI MOBILE
Absensi Online
Tracking Online
Push Notification
Content Amplification
www.pln.co.id 17
|
NEW SRINTAMI WEB
Vegetation Data
www.pln.co.id 18
|
NEW SRINTAMI WEB
Vegetation Data
www.pln.co.id 19
|
NEW SRINTAMI WEB
Vegetation Data
www.pln.co.id 20
|
NEW SRINTAMI WEB
Vegetation Data
www.pln.co.id 21
|
NEW SRINTAMI WEB
Vegetation Data
www.pln.co.id 22
|
Maintenance Strategy
www.pln.co.id
|
Maintenance Strategy
LEVEL 1 PER WEEK
GROUND
Monitoring
PATROL
PER THREE MONTH
IMPLEMENTED BY COLLABORATION THIRD THIRD PARTY OR TYPE OF CHECK LIST PERIODIC INSIDENTAL
PARTY & INTERNAL INTERNAL CHECK LIST CHECK LIST
www.pln.co.id
|
“The Biggest Part of Digital
Transformation Is Not About Technology.
It is Changing The Way We Think.”
Terima Kasih