Af 55 JV 1 Maee
Af 55 JV 1 Maee
Af 55 JV 1 Maee
Basic : AF55JV1MAEE
Model : AC048KNPPCC / AC048KXQPCC
AC036KNPPCC / AC036KXQPCC
AC140KNPDEH / AC140KXADGH
AC100KNPDEH / AC100KXADEH
AC048KNPDEC / AC048KXADGC
AC036KNPDEC / AC036KXADEC
Model Code : AC048KNPPCC/MG AC048KXQPCC/MG
AC036KNPPCC/MG AC036KXQPCC/MG
AC140KNPDEH/EU AC140KXADGH/EU
AC100KNPDEH/EU AC100KXADEH/EU
AC048KNPDEC/TL AC048KXADGC/TL
AC036KNPDEC/TL AC036KXADEC/TL
AC048KNPDEC/SV AC048KXADGC/SV
1. Precautions
2. Product Specifications
4. Troubleshooting
5. PCB Diagram
6. Wiring Diagram
7. Reference Sheet
1-4 Others
O Never store or load the air conditioner upside down or sideways to prevent the damage to the compressor.
O Young children or infirm persons should be always supervised when they use the air conditioner.
O Max current is measured according to IEC standard for safety.
O Current is measured according to ISO standard for energy efficiency.
O When installing, make sure there is no leakage. When recovering the refrigerant, ground the compressor first before removing the
connection pipe. If the refrigerant pipe is not properly connected and the compressor works with the service valve open, the pipe
inhales the air and it makes the pressure inside of the refrigerant cycle abnormally high. It may cause explosion and injury.
O Pump Down Procedure (When removing the product)
- Turn on the air conditioner and select Cool mode to run the compressor for 3 minutes.
- Release the valve caps on High and Low pressure side.
- Use L wrench to close the valve on the high pressure side.
- Approximately 2 minutes after, close the valve on the low pressure side.
- Stop operation of the air conditioner.
- Disconnect the pipes.
2. Product Specifications
2-1-1 Features
O Strong Turbo/convenient long-distance operation
Quicker and more consistent air cooling/warming is guaranteed by turbo operation that provides strong
cooling/warming for 30 minutes or by long-distance operation that ensures cooling/warming even in places a
long way from the air conditioner.
Outdoor Unit
(AC100KXADEH
AC036KXADEC)
- -
Indoor Unit
Design
Outdoor Unit
2-3-1 Filter
Item Descriptions Code-No. Remark
Basic/
Air Filter DB63-02928B
Water Washing
2-3-2 Accessory
Item Descriptions Code-No. Q'ty Remark
Manual
DB68-04872A 1
(AC048/036KNPPCC)
Manual DB68-06271A
1
(AC140/100KNPDEH) DB68-06272A
Manual
DB68-06270A 1
(AC048/036KNPDEC)
Insulation
DB72-50300A 1
(AC048/036KN*)
Insulation
DB72-50300C 1
(AC140/100KN*)
+Screw driver
Monkey spanner
2 Ass'y Inlet Part 1) Open the Ass'y Inlet and remove the
safety clips.
Horizontal blade
Panel Motor-In
Vertical blade
Detaching Detaching
direction direction
❷
❶
Detaching direction
Product operation
Diagnosis
Display Explanation Check list
Indoor Outdoor Method
COMP
FAN FAN
Indoor and Outdoor unit ● Check the connection wire. Operation Operation Operation
communication Error ● Change the Main PCB. OFF OFF OFF
Indoor unit Eva_in sensor ● Change the temperature sensor. Operation Operation Operation
SHORT/OPEN (Wire type) OFF OFF OFF
Outdoor unit
If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and
INVERTER PCB.
2. Check procedure
Yes
Yes
Good
Bad
+0.7V
-0.7V
cf.) If there is no oscillo scope, it can be replaced multimeter instead of osillo scope.
Yes Yes
2. Check procedure
Yes
Yes
Yes
No
Is the fuse connected? Replace the fuse
Yes
No
Is the resistance value of R001 200Ω? Replace the inverter PBA
Yes
Cont.
Cont.
Yes
Yes
1. Check items:
1) Is the power supply voltage 380V?
2) Is the AC power connected correctly?
3) Are the LEDs in the main PCB and inverter PCB of the outdoor unit ON?
4) Is the input power voltage of the indoor unit 220V?
5) Is the wired remote controller connected correctly?
2. Troubleshooting procedure
Is the indoor unit power supply No Check the connection wires and
voltage (L-N) 220Vac? connectors of the indoor and outdoor units
Is the indoor unit power supply No Replace the PCB of the indoor unit if
voltage (V1-V2) 12Vdc? the PCB (Transformer, fuse, pcd, etc.) fails
Cont.
Cont.
Yes
Yes
Yes
2. Troubleshooting procedure
Yes
Yes
Yes
4-3-5 External Sensor Error (Error Code: E221, E231, E251, E320)
1. Test Item
1) Check the connection of the temperature sensor connector. Error Code Description
2) Check the resistance value of the temperature sensor. E221 Error of the temperature sensor of the outdoor unit
E231 Error of the COND. sensor of the outdoor unit
E251 Error of the discharge sensor of the outdoor unit
2. Check procedure E320 Error of the OLP sensor of the outdoor unit
Power OFF
Yes
(Example) COND. sensor/outdoor unit temperature sensor measuring resistance value by temperature: E231, E221
Current tem- Resistance Current tem- Resistance e.g.) Room temperature: 26ఁ
perature (°C) (KΩ) perature (°C) (KΩ) - Resistance: 10.28 KΩ
Yes 70 4 20 10
60 5 10 20
50 6 0 30
40 7 -10 40
30 8
(Example) OLP sensor/discharge temperature sensor measuring resistance value by temperature: E320, E251.
Current tem- Resistance Current tem- Resistance e.g.) Room temperature: 21ఁ͑
perature (°C) (KΩ) perature (°C) (KΩ) - Resistance: 205.4 KΩ
80 40 30 180
70 50 20 220
60 60 10 320
50 90 0 550
40 110
Does the same error occur again No After confirming the state is normal,
after power is on? end the service.
Yes
Criteria t"MMUIFPQFSBUJOHJOEPPSNBDIJOFTEPOPUSFBDI¡$GPSNPSFUIBOGJWFNJOVUFT
t$IFDLJGUIFJOEPPS'"/.0503PQFSBUFTOPSNBMMZ
t$IFDLJGUIFJOEPPS&&7PQFSBUFTOPSNBMMZ
Cause of problem
t$IFDLUIFJOEPPSIFBU&YDIBOHFShT*/065TFOTPS
t$IFDLGPSDMPHHJOHJOUIFTVDUJPOBSFBPGUIFJOEPPSNBDIJOF
1. How to check
No
The indoor FAN/MOTOR operates normally? Check the indoor fan.
Yes
No
The indoor EEV operates normally? Check the EEV.
Yes
No
The indoor heat Exchanger sensor displays the Same as when checking other temp sensors.
temperature ok?
Yes
Criteria t5IFDPNQSFTTPSUFNQFSBUVSFBCPWF¡$
t*OTVGGJDJFOUDPPMBOU
t$MPHHJOHJOUIFPVUEPPSNBDIJOFhTTPMFOPJEWBMWF
t$MPHHJOHJOUIFTVCWBMWF
Cause of problem
t.BMGVODUJPOJOHFYIBVTUHBTUFNQTFOTPS
t$MPHHJOHJOUIFQJQFMJOFBOEUIFGJMUFS
t-JRVJE&&7EBNBHFE
1. How to check
Yes
Test operation
Yes
Yes
4-3-8 E440, E441 : Abnormal outside temperature halts operation of the compressor
E440 (No heater operation with the outside temperature above 30°C.)
Outdoor unit display
E441 No AC operation with the outside temperature below -10°C.)
Criteria t5IFDPNQSFTTPSUFNQFSBUVSFBCPWF¡$
E440: If the outside temperature is above 30°C, operation of the indoor heater with a
remocon causes this error.
Cause of problem
E441:The indoor machine remocon ON signal. If the outside temperature is below -10°C
before the AC runs, this error occurs.
1. How to check
The above malfunction codes do not indicate a malfunction of the product. All you have to do is change the temperature suitably for
the limits shown in the manual. When the product malfunctions, if the actual situation does not match the above diagnosis, measure
the temperature of incoming air with S-net to see if the measurement is the same as the actual outdoor temperature. If not, replace
the temperature sensor.
4-3-9 Outdoor unit BLDC Fan1 or Fan2 error (E458 : Fan1 error, E475 : Fan2 error)
1. Checklist :
1) Isn’t the fan locked?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull_up correct?
2. Troubleshooting procedure
Yes
No
No
Is the connector connected correctly? Connect the connector.
Yes
No
Is the color of Fan wire matched correctly? No
Replace the Fan.
Yes
Replace the PCB. Normal operation
Exit
2. Troubleshooting procedure
No
Is the restart error occurred again? Terminate the service.
Yes
Yes
Yes
Yes
Cause of problem
t$IFDLUIFPWFSDVSSFOUPQUJPOTFUUJOH
1. How to check
No
Compressor input voltage supplied ok? Check the input power terminal.
No
Overcurrent option setting ok? Correct the overcurrent setting.
Yes
Finished inspections
1. How to check
Yes
Test operation
No
All the sub valves open? Open the sub valve.
Yes
No
The outdoor/indoor EEV operates normally? Check the EEV.
Yes
No
Clogging in the pipeline? Check the pipeline.
(ex-filter)
No
2. Troubleshooting procedure
No
Is the installation of outdoor unit good? Reinstall and remove the obstruction
Yes
No
Is the installation of indoor unit good? Reinstall and remove the obstruction
Yes
No
Are the service valves full opened? Open valve screw to the end.
Yes
Yes
Yes
No
Does the compressor rotate normally? Replace the compressor
Yes
No
2. Troubleshooting procedure
Is the AC Power cable connection to the outdoor No Check and reconnecting the
unit terminal block good? AC power cable wire
Yes
Yes
Yes
Are the FUSEs on EMI PCB blown? Replace the blown FUSE
No
Yes
Yes
Does the error reappear frequently Replace INVERTER PCB
No
2. Check procedure
Check the opening of the outdoor unit No Check whether the pipe is empty and open all
service valve. the service valves on the gas and liquid pipes.
Yes
Yes
Yes
7. Outdoor overload protection control (at the stop of the compressor.) : E404
t Check whether the fan and the motor operate normally.
t Check the operation of EEV.
t Check the temperature sensor of the indoor unit heat Exchanger.
t Check the indoor unit inlet blocking.
䯴 Setting an indoor unit installation option(suitable for the condition of each installation location)
CN802 - EEV CN806 - EEPROM CN305 - COMM INV CN401 - LOW PRESSURE
#1 ~ #4 : EEV SIGNAL #1 ~ #7 : EEPROM #1 : COMM SIGNAL #1 : N.C
#5,#6 : DC 12V #2 : COMM SIGNAL #2 : SENSOR SIGNAL
#3 : GND #3 : GND
#4 : DC 5V #4 : DC 5V
#5 : DC 12V
#6 : COMM SIGNAL
QAC048KXQPCC
QAC140KXADGH / AC048KXADGC
QAC140KXADGH / AC048KXADGC
6. Wiring Diagram
QAC140KXADGH / AC048KXADGC
Model Code
AC
+ 048
+ K+ N+ P+ P+ C+ C+ /+ MG
+
Buyer Name
Capacity (3 DIGIT)
KW / BTU / Liter
Rating Voltage
Code Type
Product Type
A A(115V, 60hz, 1Ф)
Code Type
B B(220V, 60Hz, 1Ф)
E 2012
C C(208~230V, 60Hz)
F 2013
D D(200~220V, 50Hz)
H 2014
E E(220~240V, 50Hz)
J 2015
F F(208~230V, 60Hz, 3Ф)
K 2016
G G(380~415V, 50Hz, 3Ф)
L 2017
H H(380V, 60Hz, 3Ф)
J J(460V, 60Hz, 3Ф)
K K(220~240V, 50/60Hz, 1Ф)
Product Type M M(127V, 50Hz)
Code Type N N (380~415V, 50/60Hz, 3Ф)
Product Type
AM DVM
Code Type
AJ PMA
S Set (NASA) Refrigerant
AC CAC (USD) / ASD
N Indoor (NASA) Code Type Refrigerant
AE EHS
X Outdoor(NASA) C COOLING ONLY
AN VTL
A Set ( NASA) H HEAT PUMP R410a
PAK (Packaged
AK B Indoor ( No NASA) R HEAT RECOVERY
System)
AG CHR C Outdoor (No NASA) D COOLING ONLY
R22
E HEAT PUMP
A Cooling only
Product Type (Indoor) Product Type (Outdoor) R134
B Heat Pump
Code Type Code Type
N N/A
1 1 WAY CST A Inv+Side+General Temp
2 2 WAY CST S Inv+Side+Low Temp
N MINI 4 WAY CST Q Inv+Side+Tropical Temp Product Type (Indoor) Product Type (Outdoor)
4 4 WAY CST F Inv+Top+Tropical Temp Code Type Code Type
H HSP DUCT B Non Inv+Side+General Temp F FLAGSHIP STANDARD+GENERAL
A
M MSP DUCT N Non Inv+Side+Low Temp P PREMIUM Temp.+MODULE
STANDARD+LOW
L LSP DUCT R Non Inv+Side+Tropical Temp D DELUXE B Temp.+MODULE
E FRESH AIR INTAKE Z Non Inv+Top+Tropical Temp S STANDARD
DUCT C STANDARD+
CEILING CONCEILED 1:1 TROPICAL+MODULE
G DUCT ->4Way : 4 , MSP Duct : STANDARD+GENERAL
(In/ D
C CEILING M , Ceiling : C Temp.+NON MODULE
out)
J CONSOLE S STANDARD
F FLOOR MOUNTING T DELUXE + TROPICAL
P FAC / PAC
ö/ can be removed from the buyer card if there are not enough digits.
QAC036KXQPCC
QAC100KXADEH
QAC036KXADGC
$VLD JVSQVDPVXQJFVSRUWDOFRP
&KLQD FKLQDVDPVXQJSRUWDOFRP
This Service Manual is a property of Samsung Electronics Co., Ltd. © Samsung Electronics Co., Ltd. May. 2016.
Any unauthorized use of Manual can be punished under applicable Printed in Korea.
International and/or domestic law. Code No. AC-00163E_1