Product data sheet 3RP1511-1AP30

TIME RELAY, SOLID-STATE, ON-DELAY,


1 CHANGEOVER CONTACT,
1 TIME RA 0.5S TO 10S, AC 24,
200 TO 240V AND DC 24V, WITH LED,
SCREW TERMINAL

General technical data:


product brand name SIRIUS

Product designation timing relay

Protection class IP / of the terminal IP20

mounting position any

Product function

• at the relay outputs / changeover delayed/without delay No

Product component / semi-conductor output No

Product extension / optional / remote control No

Product extension / strictly required / remote control No

Installation altitude / at a height over sea level / maximum m 2,000

Ambient temperature

• during storage °C -40 … +85

• during operating °C -25 … +60

• during transport °C -40 … +85

Relative humidity

• during operating phase % 15 … 70

Conductor-bound parasitic coupling BURST / according to IEC 2 kV network connection / 1 kV control connection
61000-4-4

Conductor-bound parasitic coupling conductor-earth SURGE / 2 kV


according to IEC 61000-4-5

3RP1511-1AP30 subject to modifications


Page 1/ 5 06/30/2014 © Copyright Siemens AG 2014
Conductor-bound parasitic coupling conductor-conductor 1 kV
SURGE / according to IEC 61000-4-5

Electrostatic discharge / according to IEC 61000-4-2 4 kV contact discharge / 8 kV air discharge

Field-bound parasitic coupling / according to IEC 61000-4-3 10 V/m

Impulse voltage resistance / rated value V 4,000

Active power loss / total / typical W 2

Reference code / according to DIN 40719 extended according to K


IEC 204-2 / according to IEC 750

Reference code / according to DIN EN 61346-2 K

Category / according to EN 954-1 none

Protection against electrical shock finger-safe

Switching Function:
Switching function

• slow-operating Yes

• making pulse contact No

• relapse delayed No

• with control signal

• additive ON delay No

• passing break contact No

• OFF delay No

• slow-operating/instantaneous contact No

• with control signal

• OFF delay/instantaneous No

• ON delay/OFF delay/instantaneous No

• making pulse contact/instantaneous contact No

• with control signal

• passing break contact/instantaneous No

• pulse-shaping/instantaneous No

Adjustable time s 0.5 … 10

Control circuit/ Control:


Voltage type / of control feed voltage AC/DC

Control supply voltage frequency

•1 Hz 50 … 60

Control supply voltage

•1

• at 50 Hz / for AC / rated value V 24

• at 60 Hz / for AC / rated value V 24

• for DC / rated value V 24

•2

3RP1511-1AP30 subject to modifications


Page 2/ 5 06/30/2014 © Copyright Siemens AG 2014
• at 50 Hz

• for AC V 200 … 240

• at 60 Hz

• for AC V 200 … 240

Operating range factor control supply voltage rated value

• at 50 Hz

• for AC 0.85 … 1.1

• at 60 Hz

• for AC 0.85 … 1.1

• for DC 0.85 … 1.1

Auxiliary circuit:
Operating current / of auxiliary contacts

• as normally closed contact / for AC-15

• at 24 V A 3

• at 250 V A 3

• as normally open contact / for AC-15

• at 24 V A 3

• at 250 V A 3

• at AC-15

• maximum A 3

• at DC-13

• at 24 V A 1

• at 125 V A 0.2

• at 250 V A 0.1

Number of NC contacts / delayed switching 0

Number of NC contacts / non-delayed 0

Number of NO contacts / delayed switching 0

Number of NO contacts / non-delayed 0

Number of change-over switches / delayed switching 1

Number of change-over switches / non-delayed 0

Short-circuit:
Design of the fuse link / for short-circuit protection of the fuse gL/gG: 4 A
auxiliary switch / required

Mounting type screw and snap-on mounting onto 35 mm standard


mounting rail

Installation/ mounting/ dimensions:


Width mm 22.5

Height mm 83

Depth mm 91

3RP1511-1AP30 subject to modifications


Page 3/ 5 06/30/2014 © Copyright Siemens AG 2014
Distance, to be maintained, to the ranks assembly

• upwards mm 0

• forwards mm 0

• sidewards mm 0

• backwards mm 0

• downwards mm 0

Distance, to be maintained, to earthed part

• backwards mm 0

• sidewards mm 0

• upwards mm 0

• forwards mm 0

• downwards mm 0

Distance, to be maintained, conductive elements

• downwards mm 0

• backwards mm 0

• sidewards mm 0

• forwards mm 0

• upwards mm 0

Connections/ terminals:
Design of the electrical connection

• for auxiliary and control current circuit screw-type terminals

General Product Approval Declaration of Test Certificates


Conformity

Special Test
Certificate

Shipping Approval

Shipping Approval other

Confirmation other Environmental


Confirmations

Further information:
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs

Industry Mall (Online ordering system)


http://www.siemens.com/industrial-controls/mall

3RP1511-1AP30 subject to modifications


Page 4/ 5 06/30/2014 © Copyright Siemens AG 2014
Cax online generator
http://www.siemens.com/cax

Service&Support (Manuals, Certificates, Characteristics, FAQs,...)


http://support.automation.siemens.com/WW/view/en/3RP1511-1AP30/all

Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3RP1511-1AP30

last change: Jun 16, 2014

3RP1511-1AP30 subject to modifications


Page 5/ 5 06/30/2014 © Copyright Siemens AG 2014