300kWp BONGANDANGA
300kWp BONGANDANGA
300kWp BONGANDANGA
1 .DO NOT SCALE DRAWINGS , IF UNABLE TO LOCATE DIMENSIONS FORANY ITEM OFWORK , CONSULT ARCHITECT /
PV INVERTER RATINGS
ENGINEER FOR DIRECTIONS BEFORE PROCEEDING . INVERTER MFR : HUAWEI
INVERTER MODEL : SUN2000-100 KTL
2 .IN THE ABSENCE OF THE EXACT ROOF DIMENSIONS , THE DRAWING WILL BASED ON GOOGLE MAP, THEREFORE THESE DC VOLT RATING MAX. = 1100 V
MAY NOT BE ACCURATE . CONTRACTOR ON SITE TO VERIFY ALL OBSTACLES ON THE ROOF AND ENSURE ALL REQUIRED OPERATING VOLTAGE =580 -950 V
CLEARENCES WITH AUTHORITY HAVING JURISDICTION (S ) PRIOR TO INSTALLATION , ORDERING MATERIAL OR FABRICATION DC MAX USABLEINPUTCURRENT :
PER MPPT = 30A
MAX SC CURRENT PER MPPT = 40A
3 . CONTRACTOR SHALL OBTAIN ELECTRICAL AND OTHER PERMITS PRIOR TO INSTALLATION AND SHALL COORDINATE ALL
INSPECTIONS BY THE CITY INSPECTORS , TESTING / COMMISSIONING BY THE UTILITY CO . AND ACCEPTANCE BY THE AC MAX RATED OUTPUTPOWER = 100000 W
CLIENT , AS NEEDED . AC MAX OUTPUTCURRENT = 160.4 A
4 .ROUTING OR RACEWAYS MATERIAL SHALL BE ATTHE OPTION OFTHE CONTRACTOR , WITHIN THE CODE , UNLESS
OTHERWISE NOTED AND SHALL BE COORDINATED WITH OTHER TRADES .
PV MODULE RATINGS
MODULE MFR : risen MODEL : RSM 144-9-540M-560M
5 . IF THE ROOF MATERIAL OR ROOF STRUCTURE IS NOT ADEQUATE FOR PV INSTALLATION , CALL ENGINEER PRIOR TO CAPACITY : 550 Wp
INSATLL . THE CONTRACTOR IS RESPONSIBLE TO VERIFY THAT ROOF IS CAPABLE OF WITHSTANDING THE EXTRA WEIGHT . VOC = 49.80V
VMP = 42.20V
6 .WHENEVER A DISCREPANCY INQUANTITY OF EQUIPMENTARISES ONTHE DRAWING ORSPECIFICATIONS , THE ISC = 13.94 A
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIALAND SERVICES REQUIRED BY
STRICTEST CONDITIONS NOTED ON THE DRAWING OR IN THE SPECIFICATIONS TO ENSURE COMPLETE COMPLIANCE AND IMP = 13.04A
LONGEVITY OF THE OPERABLE SYSTEM REQUIRED BY THE ARCHITECT/ENGINEER
7 .THIS DESIGN IS FULLY BASED ON THE INFORMATION PROVIDED BY THE DEVELOPER , ANY MODIFICATIONS OR REMOVAL
OF THE LOGO OF THE EPC ; "VARIETAS PROJECT MANAGERS & ENGINEERS " IS NOT ALLOWED AND WILL RENDER THIS
DESIGN VOID.
8 .THE WORKING CLEARANCE AROUND THE EXISTINGELECTRICAL EQUIPMENTS ASWELL AS THE NEWELECTRICAL
EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH .
9 . ADEQUATE SPACING MUST BE MAINTAINED BETWEEN ANY PLUMBING / SEWER VENTS EXTENDING THROUGH THE ROOF
AND UNDERSIDE OF THE PHOTOVOLTAIC PANELS (6 '' MINIMUM RECOMMENDED).
BONGANDANGA_300kWP
ELECTRICAL NOTES AND STANDARDS TO FOLLOW :
IEC 60050 V (826 ) ELECTRICAL INSTALLATIONS OF BUILDINGS
IEC 60068 ENVIRONMENTAL TESTING
PROJECT TITLE :
IEC 60364 -7-712 REQUIREMENTS FORSPECIAL INSTALLATIONS ORLOCATIONS – SOLARPHOTOVOLTAIC (PV) POWERSUPPLY SYSTEMS
IEC 60439 -1 LOW VOLTAGE SWITCHGEAR & CONTROL GEARASSEMBLIES
IEC 60755 GENERAL REQUIREMENTS FORRESIDUAL CURRENT – OPERATED PROTECTIVE DEVICES (OCPD )
IEC 61215 CRYSTALLINE SILICON TERRESTIAL PHOTOVOLTAIC (PV ) MODULES – DESIGN QUALIFICATION AND TYPE APPROVAL
IEC 61683 EFFICIENCY MEASUREMENTS AND ENVIRONMENTAL TESTS OF POWERCONDITIONING UNITS (PCUs )
IEC 61701 PV MODULES TO BE USED IN A HIGHLY CORROSIVE ATMOSPHERE
IEC 61724 PHOTOVOLTAIC SYSTEMPERFORMANCE MONITORING – GUIDELINES FORMEASUREMENT , DATA EXCHANGE AND ANALYSIS
IEC 61730 PART -2 : REQUIREMENTS FORCONSTRUCTION & PART -2: REQUIREMENTS FORTESTING , FORSAFETY QUALIFICATION
IEC 62305 LIGHTING PROTECTION
IEC 62446 GRID CONNECTED PHOTOVOLTAIC SYSTEMS – MINIMUM REQUIREMENTS FOR SYSYTEM DOCUMENTATION , COMMISSIONING TESTS AND INSPECTION
SHEET TITLE :
TUV 2 PfG 1169 TUV INTERNAL CABLE STANDARD
GENERAL NOTES
ELECTRICAL
AS1319 SAFETY SIGNS FORTHE OCCUPATIONAL ENVIRONMENT
APPLICABLE JUNCTION BOX
STANDARDS CREEPAGE DISTANCES AND CLEARANCES
IEC 60664 JUNTION BOXES
IEC 50548 DEGREES OF PROTECTION PROVIDED BY THE ENCLOSURES
IEC 60529 LOW VOLTAGE FUSES
IEC 60269 COPPERBUS BARS /TERMINAL BLOCKS HOUSED IN THE JUNCTION BOX WITH SUITABLE TERMINATION THREADS
IEC 62208 CHROMATED DIN RAIL
EN 60715
APPLICABLE SWITCHBOARD
STANDARDS
IEC 60439
ICE 60947
IEC
LOW VOLTAGE AC SWITCHGEARAND CONTROL GEARS SPECIFICATIONS
LOW VOLTAGE AC SWITCHGEARAND CONTROL GEARS ASSEMBLIES
GENERAL REQUIREMENTS FORAC SWITCHGEAR & CONTROL GEARVOLTAGE <1000 V
Engineer :
IEC 60529 DEGREE OF PROTECTION FORLOW VOLTAGE SWITCHGEAR & CONTROL ENCLOSURES Ihereby certify that this drawingwas prepared
IEC 60404 ELECTROLYTIC COPPER / ALUMINIUM by meor under my supervision
IEC 62056 AC ELECTRIC METERS
IEC 60364 EARTHING
Date Issue
IEC 60947 .2 DANGERNOTIC PALTES
IEC 60439 CIRCUIT BREAKERS VOLTAGE UP TO 1000 V Battery Energy Storage
BESS
IEC EN 60269 -1 AIRBREAK SWITCHES /DISCOONECTS FORVOLTAGES < 1000 VAC & 1200 VDC Date Marks Revisions
IEC 60529 MAKING AND ARRANGEMENTS FORSWITCHGGEAR , BUS BARS , MAIN CONNECTIONS
Motorised Circuit Breaker
APPLICABLE STANDARDS FORLOW
PV String Array
VOLTAGE AC CABLES XLPE INSULATED PVC SHEATHED CABLES FORWORKING VOLTAGES <1100 V ON OFF TRIP
Indication Circuit
IEC 60840 RECOMMENDED CABLE CURRENT RATINGS
DIESEL /GAS GEN SET DESIGNED BY Project Consultant
IEC 60502 CONDUCTORS FORINSULATED CABLES MFM Multi function meter
IEC 60227 , 60228 DRAWN BY : Darshit vyas
APPLICABLE
SP 30 LOCAL STANDARDS NATIONAL ELECTRICAL CODES
IS 875 WIND LOADS ON BUILDINGS AND STRUCTURES
CHECKED BY : Swapnil deshmukh
IS 2062 : 1992 THE MOUNTING STRUCTURE STEEL SUPERVISED BY : Swapnil deshmukh
IS 2309 PROTECTION OF BUILDINGS AND ALLIED STRUCTURES AGAINST LIGHTING
IS 3043 – 1987 EACH ARRAY STRUCTUTRE OF THE PV YARD
IS 4759 GALVANIZATION OF THE MOUNTING STRUCTURE
Drawing Number
G101
Scale : Date :
AS SHOWN 16/10/2023
Sheet No .
01 OF 03
Battery Data
POWER ONE -LINE DIAGRAM Cell Material : LFP
Module rated Voltage : 57.6 V
Module Capacity: 16.13kWH
C rate: 0.5
CT RS485
BONGANDANGA_300kWP
MFM
1 2 3 4
1 2 3 4
160 A 160 A
DC Cable Cu. CABLE FRLS
RCCB
(0/L,S/C,E/F) (0/L,S/C,E/F) (0/L,S/C,E/F) (0/L,S/C,E/F) 433V 110V 10A, 30mA
630 A
3 3
ON OFF TRIP ON OFF TRIP ON OFF TRIP ON OFF TRIP
PROJECT TITLE :
MCCB ON OFF TRIP
SPARE CL:1.0,
3Nos. x 1Ph
BESS -2 - 196kWH , Battery Cabinet - LUNA -200kWH LUNA2000 RS485 4RX3.5CX240 SQ. MM
PCS#2 110kVA XLPE/PVC/SWA/FRLS/AL. CABLE
EMS
DC BUS
BESS -2
DC BUS
BESS + PV
COMBINER
1RX3.5CX150 SQ. MM SPARE
LUNA2000 RS485
BESS -3 - 196kWH , Battery Cabinet - LUNA -200kWH PCS#3 110kVA XLPE/PVC/SWA/FRLS/AL. CABLE
630 A 630 A 630 A
EMS
DC BUS MCCB MCCB MCCB
BESS -3 DC BUS
(0/L,S/C,E/F) (0/L,S/C,E/F) (0/L,S/C,E/F)
POWER LINE
ON OFF TRIP ON OFF TRIP ON OFF TRIP
DIAGRAM
SHEET TITLE :
1RX2CX95 SQ. MM
DC Cable Cu. CABLE FRLS MCB
AUX
1250A TRIP
ACB
4P RS485
50KA
MFM
1000/5A
CL.0.5,15VA
3 CT
E
50x6 MM
GI Strip CBCT ELR 50x6 MM
GI Strip
D.G. SET
Engineer :
5RX3.5CX300 SQ. MM 80 KVA
XLPE/PVC/SWA/FRLS/AL. CABLE
415V, 50 Hz Ihereby certify that this drawingwas prepared
by meor under my supervision
1RX3.5CX240 SQ. MM
XLPE/PVC/SWA/FRLS/AL. CABLE
Date Issue
RE +DG Combiner
DG INCOMER
RE INCOMER MCB MCB
DRAWN BY : Darshit vyas
1250A 400A
ACB
4P
AUX
TRIP
MCCB
4P
AUX
TRIP CHECKED BY : Swapnil deshmukh
M 50KA M
50KA
1000/5A MFM
RS485
200/5A
MFM
RS485 SUPERVISED BY : Swapnil deshmukh
CL.0.5,15VA
CL.0.5,15VA 3 CT
E
3 CT E
200/5A
CL.0.5,15VA
3 CT
E
E103
ON OFF
SWITCH
50x6 MM
50x6 MM GI Strip
GI Strip
5RX3.5CX300 SQ. MM
XLPE/PVC/SWA/FRLS/AL. CABLE
Scale : Date :
AS SHOWN 16/10/2023
LOAD
Sheet No .
02 OF 03
Battery Data
Cell Material : LFP
Module rated Voltage : 57.6 V
Module Capacity: 16.13kWH
C rate: 0.5
PV MODULE RATINGS
MODULE MFR : risen MODEL : RSM 144-9-540M-560M
CAPACITY : 550 Wp
VOC = 49.80V
58175
VMP = 42.20V
ISC = 13.94 A
17190
1135 100
1000 3605
IMP = 13.04A
2280
4660
100
BONGANDANGA_300kWP
13320
4000
DCDB-1
PROJECT TITLE :
10000
Isolation
Transformer WC
(315kVA)
Panel
ATS
PCS-1
PCS-2
10000
PCS-3
47960
DCDB-2
UPS
PV-BESS
Combiner
BESS Junction
ACDB
POWER LINE
Solar
Board
DIAGRAM
SHEET TITLE :
Inv-1 Inv-2 Inv-3
Engineer :
Ihereby certify that this drawingwas prepared
by meor under my supervision
DCDB-3
Date Issue
Drawing Number
E103
Scale : Date :
AS SHOWN 16/10/2023
Sheet No .
0 OF 03