kW DC = 18.43 MWp
kW AC = 16.10 MW
GRID-TIED PV SYSTEM
SITE PLAN - 2
Area for the MV transmission
systems and interconnection
2000sq.m
REVISIONS
1 SITE PLAN
PV-2 SCALE: NTS
PV-2
CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS
GENERAL ELECTRICAL NOTES
CURRENT-CARRYING MAX.
CONT. CURRENT VOLTAGE
ID CONDUCTOR CONDUIT CONDUCTORS IN OCPD EGC LENGTH UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL
CURRENT DROP
(125%)
3 300 SQ.MM XLPO/PVC, CU TRAY 22 SET PER PHASE 4000A 120 SQ.MM, COPPER 11684A 14605A 100 mtr 1.4% CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE
4 240 SQ.MM XLPO/PVC, CU TRAY 2 SET PER PHASE 630A 70 SQ.MM, COPPER 467.3A 584.2A 200 mtr 0.1% 2 LISTED AS SUNLIGHT RESISTANT PER NEC ARTICLE kW DC = 18.43 MWp
300.6 (C) (1) AND ARTICLE 310.10 (D).
kW AC = 16.10 MW
CONDUCTORS EXPOSED TO WET LOCATIONS SHALL
3 BE SUITABLE FOR USE IN WET LOCATIONS PER NEC
ARTICLE 310.10 (C).
GROUNDING NOTES
GRID
ALL EQUIPMENT SHALL BE PROPERLY GROUNDED
1 PER THE REQUIREMENTS OF NEC ARTICLES 250 &
690
GRID-TIED PV SYSTEM
RAILS USING MODULE LUGS OR RACKING
INTEGRATED GROUNDING CLAMPS AS ALLOWED BY
2
LOCAL JURISDICTION. ALL OTHER
EXPOSED METAL PARTS SHALL BE GROUNDED
USING UL-LISTED LAY-IN LUGS.
MODULES
QTY 29500
PMAX 625W
ISC 14.27A
IMP 13.56A
VOC 55.72V
INVERTER-1 INVERTER-6 INVERTER-7 INVERTER-24
VMP 46.10V
SUNGROW SUNGROW SUNGROW SUNGROW
SG-350HX
350kW, 800V
SG-350HX
350kW, 800V
SG-350HX
350kW, 800V
SG-350HX
350kW, 800V TEMP. COEFF. OF Voc SINGLE LINE DIAGRAM
-0.25 %/C
FUSE RATING
30A
INVERTER
JINKO SOLAR
JKM625N-78HL4-BDV(625W)
JINKO SOLAR
JKM625N-78HL4-BDV(625W)
JINKO SOLAR
JKM625N-78HL4-BDV(625W)
JINKO SOLAR
JKM625N-78HL4-BDV(625W)
GROUND SOLIDLY GROUNDED REVISIONS
25 STRINGS OF 25 MODULES 25 STRINGS OF 25 MODULES 26 STRINGS OF 25 MODULES 26 STRINGS OF 25 MODULES
RATED POWER 350kW
1 SINGLE-LINE DIAGRAM
MAX INPUT VOLTAGE 1500Vdc
PV-4