Mat-Cscec-12-Me-Hd-0072-04 - H
Mat-Cscec-12-Me-Hd-0072-04 - H
Mat-Cscec-12-Me-Hd-0072-04 - H
3. Delivery :
Country of origin : UAE
Availability
Locally Manufactured Overseas
We certify that the above submitted items have been reviewed in detail and are correct and in strict conformity with the contract drawings and specifications except
as otherwise stated; also that the material sources indicated above have been reviewed in detail and that they will supply the submitted items in conformity with the
above and deliver same timely.
S-PRC-SS-02(F26) Rev 2
Submittal For Approval Of Materials
Date: 09 MAR. 2022
Request no: MAT-CSCEC-12-ME-HD-0072-03
Project No. & Title: E18066-0200S - The Central Business District of the New Administrative Capital of Egypt
3. Delivery :
Country of origin : UAE
Availability
Locally Manufactured Overseas
We certify that the above submitted items have been reviewed in detail and are correct and in strict conformity with the contract drawings and specifications except
as otherwise stated; also that the material sources indicated above have been reviewed in detail and that they will supply the submitted items in conformity with the
above and deliver same timely.
S-PRC-SS-02(F26) Rev 2
CENTRAL BUSINESS DISTRICT – NEW ADMINISTRATIVE CAPITAL
MAT-CSCEC-12-ME-HD-0072-03
1- As per your compliance all fans housing shall be heavy gauge steel hot dip galvanized,
otherwise will not be accepted (mentioned PPGI, PPGL sheet in your catalogue or in
compliance is not accepted).
2- As for EF-D01-BS1-02 which is serving UPS room, motor must be explosion proof, your
proposed fan PR -AC ATX 456T is polyethylene casing not accepted, reselect another model.
3- Comparison table showing IFC data in equipment schedule (unit no. , location, system served, fan
type, flow rate and external static pressure, quantity and remarks) and proposed model by supplier.
Noted.
Rev.3:- Noted.
4- Compliance statement should be stamped by supplier and CSCEC, as well mention your page
reference in case compliance. As for fans construction and accessories will be according MAT-
CSCEC-02-ME-HD-0024-03,
REV3. Still valid.
5- In computer selection per each fan, add pages for all accessories (vibration isolators, sound
attenuator, seismic restraints, extra material, -----etc.).
Rev3. Still valid, the contractor /supplier is requested to provide all specified accessories
otherwise will not be accepted, your mentioned accessories in your letter MGU-EGY-029-R1
are not matching with specified accessories you are obligated to provide all specified
accessories otherwise will not be accepted.
6- As per specs 233416-1.3-F, Overall efficiency shall be minimum 60 percent, some proposed fans
have overall efficiency less than 60 % such as EF-D01-MEP-03, EF-D01-BS1-04, EF-D01-GF-
01&2, follow specs.
Rev.3:- Efficiency less than 60 % can be accepted for low flow rate (500 l/s and less).
7- As per specs 233416-1.3-D, Noise level shall not exceed level allowed for place of installation.
Noise level for all ceiling mounted equipment shall not exceed NC35, some proposed fans have NC
higher than 35 such as EF-D01-MEP-02, EF-D01-MEP-04, EF-D01-GF-02, follow specs, and
indicate all fans that are located above reflected ceiling clearly in your submission.
Rev.3. Still valid, the contractor is responsible for achieve specified noise criteria, study by
specialist shall be submitted.
Rev.3.Noted.
Page 1 of 3
CENTRAL BUSINESS DISTRICT – NEW ADMINISTRATIVE CAPITAL
MAT-CSCEC-12-ME-HD-0072-03
Rev.3 Noted.
10- Approval of external static pressure for fans to be attached in computer selection per each fan. Still
valid.
Rev, 3 Noted.
11- Mentioned altitude in your selection is incorrect and also related air density, rectify.
Rev.3, Still valid, follow project altitude for basement, MEP and roof floors.
*Rev.2:- your reply is not accepted refer to material submittals reference (MAT-CSCEC-13-
ME-HD-0038-01& MAT-CSCEC-14-ME-HD-0029-01 ) from another manufacturer where fan
speed less than 1450 r. p.m. at low flow rates.
Rev. 3, as agreed till 1900 rpm can be accepted only for emergency fan (pressurization and
smoke).
14- Fans allocated for car park ventilation shall be submitted in separate submittal complete with
CFD report.
Rev.3, Still valid.
15- Where IFC equipment schedule mentioning that V.F.D , submit evidence in your computer
selection and related catalogue showing that selected models have motor suitable for V.F.D.
Rev3, Noted.
Page 2 of 3