Cartridge Pressure Switch Type ACB and CCB: Data Sheet
Cartridge Pressure Switch Type ACB and CCB: Data Sheet
Cartridge Pressure Switch Type ACB and CCB: Data Sheet
Fixed setpoints
Features:
• Wide range
• Fixed pressure set points
• Automatic or manual reset
• Various port fittings for soldering or direct
mounting
• Spades or cables
• Stripped ends or customer specific electrical
plug
• Open or water-proof (IP65) version
• Type ACB for use as high and low pressure cut
in and cut out as well as fan cycling
• Type CCB available for CO2 refrigerants
• Compact design and easy to install
AI224286438133en-000901
Cartridge pressure switch, type ACB and CCB
Applications
5
6 Evaporator
4
7 Expansion valve
6
Product specification
Technical data
Table 1: Technical data
ACB CCB
Type
Water-proof (W) Open – spade connector (O) Water-proof (W)
R22, R134a, R404A, R407C, R407F, R410A, R438A, R448A, R449A, R452A, R513A.
For flammable refrigerants please contact your nearest Danfoss office. For com-
Medium R744 (CO2)
plete list of approved refrigerants, visit www.products.danfoss.com and search for
individual code numbers, where refrigerants are listed as part of technical data
Range -0.5 – 45 bar / -7 – 652 psi 100 – 150 bar / 1450 – 2176 psi
Reset Automatic, Manual Automatic
Contact function SPST-NO, SPST-NC, SPDT SPST-NC
Electrical connections AWG18 cables Spades (size 6.35mm x 0.8 mm) AWG18 cables
Cable length 150 cm (black) - 150 cm (black)
6 A @ 250 V AC for SPST
Contact load variants 4 A @ 250 V AC for SPDT -
0,01 - 0,05 A @ 12/24 V DC
1⁄4 in ODM solder
6 mm ODM solder
Pressure connections 6.35 mm solder
1⁄4 in SAE female flare
with depressure pin
Maximum working pressure PS / MWP 45 bar / 650 psi 165 bar / 2393 psi
Burst pressure 140 bar / 2030 psi 375 bar / 5440 psi
Media temperature – 55 – 135 °C / –67 – 275 °F – 30 – 100 °C / –20 – 210 °F
Ambient temperature –30 – 85 °C / -20 – 185 °F
Enclosure IP65 No electrical protection IP65
Lifetime
Switch type:
SPST auto reset, Normally open
Pressure setting : max 3 MPa
As general rule, ACB pressure switches are capable to cover applications requiring cycling from 100000 to 1500000
cycles dependent on current load. The exact number of cycles in any of given application is to be determined by
appropriate testing.
Manufacturer reserves the right to change or modify specifications at any time without prior notice.
C Number of cycles
60N9020
Danfos
L Electrical load
L
Electrical connection
Cable lenght in cm
Electrical rating
Port fitting
Cable plug
Approvals
Enclosure
Housing
Product
Contact
Reset
Requested specs:
Example: ACB 2U B 1 W A R L 20,0 1,0 15,0 1,5 A 100 0
Electrical rating
1U 1A @ 250V AC
2U 6A @ 250V AC (SPST), 4A @ 250V AC (SPDT)
4U 0,05A @ 12/24V DC (gold contacts)
Contact
A SPST-NO
B SPST-NC
C SPDT
Approvals
0 CE [category II] approval
1 CE [category II + IV], TÜV, VDE, UL & C-UL approvals (only with ACB)
2 UL & C-UL approvals (only with ACB)
3 CE [category II + IV] approval (only with ACB)
Enclosure
O Open
W Waterproof IP65 (only with cables)
Reset
A Automatic
M Manual (not SPST-NO; SPDT only in Panel mount housing)
Housing
R Regular hot-melt
E Epoxy type
P Panel mount (mandatory for SPDT Manual reset versions)
Port fitting
M 1/4” SAE female flare w. deflator
V 1/4” SAE female flare w. 1mm deflator
H 1/4” SAE male flare
P 1/4” solder Cu-tube (tip = 3 mm)
X 1/4” solder Cu-tube (tip = 7 mm)
S 1/4” solder Cu-tube (no tip)
L 6 mm solder Cu-tube (tip = 7mm)
E 1/8-27 NPT male
Y R (PT) 1/8”
Electrical connections
Table 2: Electrical connections
SPDT SPDT with manual reset SPST NO SPST NC SPST with manual reset
C C C C C
p p p p p
H L H L L H H
61F010.10
Danfoss
Design
Figure 2: ACB - SPST manual reset
1 1 Wires
2 Reset button
2
3 Water-proof casing
3
4 Diaphragm
4
5 Pressure connection (1⁄4 in female flare)
6 Electrical terminals
5
7 Micro-switch
8 Shaft
9 Depressure pin
7 8
9
As pressure is applied through the connection on to the diaphragm, the diaphragm is pushed up against the
operation shaft.
When the operation shaft rises, it pushes up the contact plate, so that contacts become connected (in normally
open) or disconnected (in normally closed).
As the pressure in the connection decreases, the diaphragm returns to its original state, and the operation shaft
lowers, causing the contact plate to return to its original position.
1500 ±50
HEAT PROOF ELECTRIC VINYL WIRE
UL3173, AWG18, 125 °C (BLACK)
2500 ±80
LABEL
33
24
LABEL
33
24
58.2
16.4 ±1.5
HEX 14
7/16-20 UNF FOR FLARE
Danfoss
61F015
φ6.35 ±0.1
Danfoss
61F014
(φ8)
Net weight: 0.072 kg Net weight: 0.080 kg
780 ±30
1000±50
RESET BUTTON
LABEL
LABEL 33
32±1
24
φ6.35 ±0.1
φ6.35±0.1
58.2
59
7
φ6±0.1
Danfoss
61F004
(φ7) φ6 ±0.1
Danfoss
61F016
(φ7)
Net weight: 0.078 kg Net weight: 0.072 kg
10
RED
RED 39
13
φ25.4
LABEL
15
LABEL
4
50.4
53.4
16.4
16.4
HEX 14
7/16-20 UNF FOR FLARE
Danfoss
61F006
LABEL
C
0.76"{19.2}
3.51"{89.1}
2.32"{59}
Danfoss
61F010
0.12"{3}
φ0.25"{φ6.35}
Danfoss
61F008
(φ0.31"{φ8})
Net weight: 0.024 kg Net weight: 0.029 kg
1500±50
(24.5)
44±2
LABEL
57.7±2
+1
80
Danfoss
61F001
φ6.35±0.1
Net weight 0.125 kg
Ordering
Standard models
Type ACB
Table 8: High pressure cut out
Cut out Cut in Contact system / enclosure Connection type
type W-water-proof types
Solder Flare
Reset with cable (IP65) O-open
[bar] [psi] [bar] [psi] (spade connector) types / no 7⁄16-20 UNF with de‐
6 mm 1⁄4 in
cable (IP00) pressure pin
061F7504 061F7505 061F7506
SPST-NC / W
ACB-2UB504W ACB-2UB505W ACB-2UB506W
18 ± 0.7 / 260 ± 10 13 ± 1.2 / 190 ± 17
061F9057
Auto. SPDT / W – –
ACB-2UC59W
061F8710 061F8708
20 ± 1 / 290 ± 14 16 ± 1.5 / 230 ± 21 SPST-NC / O –
ACB-2UB210 ACB-2UB208
061F8494
SPST-NC / W – –
ACB-2UB465W
061F8707 061F8703
Auto. SPST-NC / O –
ACB-2UB207 ACB-2UB203
23 ± 0.7 / 335 ± 10 19 ± 1.2 / 275 ± 17
061F9056
– –
ACB-2UC58W
SPDT / W
061F9243
Man. – –
ACB-2UC63MW
061F7507 061F7508 061F7509
SPST-NC / W
ACB-2UB507W ACB-2UB508W ACB-2UB509W
Auto.
061F8705 061F8701
SPST-NC / O –
ACB-2UB205 ACB-2UB201
26 ± 1 / 380 ± 15 20 ± 1.5 / 290 ± 22
061F9703 061F9714 061F9713
Man. SPST-NC / W
ACB-2UB803MW ACB-2UB814MW ACB-2UB813MW
061F9055
Auto. SPDT / W – –
ACB-2UC57W
061F7510 061F7513 061F7514
Auto.
ACB-2UB510W ACB-2UB513W ACB-2UB514W
SPST-NC / W
061F9522
Man. – –
ACB-2UB327MW
061F8704 061F8700
Auto. 28 ± 1 / 405 ± 14 21 ± 1.5 / 305 ± 22 SPST-NC / O –
ACB-2UB204 ACB-2UB200
061F9054
Auto. SPDT / W – –
ACB-2UC56W
061F9242
Man. SPDT / W – –
ACB-2UC62MW
NOTE:
Other code numbers are available upon request.
Type CCB
Figure 3: Type CCB
61F8025.10
Danfoss
Accessories
Figure 4: Rubber plug
A wide variety of cartridge switches are available with open enclosure - no electric protection. For these switches a
water-proof rubber plug has been specially designed.
When the plug is installed on the switch a water-proof seal IP64 is obtained. The water-proof rubber plug is available
with many different cable lengths.
(1)
Other cable lengths available upon request.
The list contains all certificates, declarations, and approvals for this product type. Individual code number may have
some or all of these approvals, and certain local approvals may not appear on the list.
Some approvals may change over time. You can check the most current status at danfoss.com or contact your local
Danfoss representative if you have any questions.
• CE according to EN 12263
• Technical Inspection Association TÜV TUV certificate no. 01 202 931/Q-04 0018 and 01 202 971/B-17-0002
• Low Voltage Directive 2014/35/EU
• UL recognized (type ACB only):
◦ UL 873 and CSA C22.2 No. 24-93
◦ UL 121201 and CSA C22/2 No.213-17 (for flammable refrigerants only)
Danfoss offers a wide range of support along with our products, including digital product information, software,
mobile apps, and expert guidance. See the possibilities below.
Danfoss Learning
Danfoss Learning is a free online learning platform. It features courses and materials specifically
designed to help engineers, installers, service technicians, and wholesalers better understand the
products, applications, industry topics, and trends that will help you do your job better.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its
products without notice. This also applies to products already on order provided that such alterations can be made without subsequential
changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and
the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.