Control System Training: FT8 Vibration Alarms
Control System Training: FT8 Vibration Alarms
Control System Training: FT8 Vibration Alarms
VT
001
Alarm 2 Mils.
Trip 4 Mils.
FT8 Vibration Alarms
VT
001
The filter is set to look at vibrations between 421 and 451 Hz to detect
instability in the combustion flame, which can excite various parts of the
turbine causing wear, cracking etc. Also a jumpered signal.
The filter is set to look at vibrations between 40 and 300 Hz to detect PT rotor issues.
Alarm - 3 Mils.
Trip - 4
FT8 Vibration Alarms
Oil film
No signal integration !
Plain journal Generator shaft
bearing