HSF-65 T5 48KW Fpt-Iveco
HSF-65 T5 48KW Fpt-Iveco
HSF-65 T5 48KW Fpt-Iveco
HS | STATIONARY RANGE
Powered by FPT_IVECO
POWER kVA 60 63
POWER kW 48 50
230/115 · 380/220 ·
AVAILABLE VOLTAGES V 415/240
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HSF-65 T5
Rated Engine Output (COP) kW 43,2 Lube oil consumption with 0,1 % of fuel
full load consumption
Rated Engine Output (PRP) kW 54,5
Total oil capacity including
Rated Engine Output (ESP) kW 60 L 12,8
tubes, filters
Manufacturer FPT_IVECO Total coolant capacity L 18,5
Model NEF45SM1F Governor Type Mechanical
Engine Type 4-stroke diesel Air Filter Type Dry
Injection Type Direct
Aspiration Type Turbocharged
Number of cylinders and 4-L
arrangement
Bore and Stroke mm 104 x 132
Displacement L 4,5
Liquid (water +
Cooling System 50% glycol)
Lube Oil Specifications ACEA E3 - E5
Compression Ratio 17,5:1
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HSF-65 T5
SOUND PRESSURE
Sound pressure level dB(A)@7m 67 ± 2,4
APPLICATION DATA
EXHAUST SYSTEM NECESSARY AMOUNT OF AIR
Exhaust Gas Flow kg/s 0,0945 Cooling Air Flow m³/s 2,2
Maximum allowed back pressure kPa 5 Alternator fan air flow m³/s 0,216
Fuel Consumption 70 % PRP l/h 11,83 Other fuel tank capacities L 405, 785
STARTING SYSTEM
Starting power kW 3
Soundproofed version
2023-MAY.-25 22:20
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
• Steel chassis • 4 side lifting points • Epoxy polyester powder coating
• Lower power cable outlet with • Anti-vibration shock absorbers • Full access for maintenance (water, oil
aluminum cover and filters, no need to remove the
• Fuel tank canopy)
• Side auxiliary cable outlet with
aluminum cover • Fuel level gauge • Versatility to assemble a high capacity
• External emergency stop switch chassis with a metallic fuel tank
• Modular tank and retention tray
system. Allows easy removal and / or
• Bodywork made from high quality • IP Protection according to ISO
maintenance of the equipment 8528-13:2016
steel plate
• Wide access to the engine • High mechanical strength
• Manual oil extraction pump (Opcional).
compartment because of a removable • Noise reduction kit (Opcional).
door
• Fuel transfer pump (Opcional).
• Fuel tank in retention tray
• Soundproofing with foam and
polyurethane film
HSF-65 T5
FEATURES OF THE
CONTROL UNITS
M7X CEM 7 CEA 7 CEC 7 M7X+CEC7
Voltage between phases • • • • •
Voltage between neutral and phase • • • • •
Current intensities • • • • •
Generator Readings
Frequency • • • • •
Apparent power (Kva) • • • • •
Active power (Kw) • • • • •
Reactive power (kVAr) • • • • •
Power factor • • • • •
Voltage between phases • • •
Voltage between phases and neutral • • •
Current intensities • • •
Frequency • • •
Mains Readings
Apparent power •
Active power •
Reactive power •
Power factor •
Coolant temperature • • • •
Oil pressure • • • •
Engine Readings
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HSF-65 T5
Short-circuit • • • •
Asymmetry between phases • • • • •
Incorrect phase sequence • • • • •
Inverse power • • • •
Overload • • • •
Genset signal drop • • • • •
Total hour counter • • • • •
Partial hour counter • • • • •
Kilowatt meter • • • • •
Starts valid counters • • • • •
Counters
GSM/GPRS modem ⓪ ⓪ ⓪ ⓪
Remote screen ⓪ ⓪
Tele signal ⓪ (8 + 4) ⓪ (8 + 4)
J1939 ⓪ M7XJ ⓪ ⓪ ⓪ M7XJ
Alarm history • (100) • (100)
• (100)
• (100)
• (100)
External start • • • • •
Start inhibition • • • • •
Mains failure start • • •
Start under normative EJP • • • •
Pre-heating engine control • • • •
Genset contactor activation • • • • •
Mains & Genset contactor activation • • •
Fuel transfer control • • • •
Engine temperature control • • • •
Manual override • • • •
Programmable alarms • • • •
Genset start function in test mode • • • • •
Features
Programmable outputs • • • •
Multilingual • • • •
GPS Positioning ⓪ ⓪
Synchronisation
Special Functions
⓪ ⓪
Mains synchronization ⓪ ⓪
Second Zero elimination ⓪ ⓪
RAM7 ⓪ ⓪
Remote screen ⓪ ⓪
• Standard Optional
2023-MAY.-25 22:20
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HSF-65 T5
CONTROL
PANELS
AS5 AS7
Automatic panel Automatic control
WITHOUT transfer panel WITHOUT
switch and Transfer Switch and
WITHOUT mains WITHOUT mains
control with CEM7 control with M7X
unit. (*) AS5 as unit.
optional with CEA7
unit. Automatic panel Digital control unit
without transfer M7X
switch and WITH
mains control.
CC2 AS5 +
CC2
Himoinsa Switching
cabinet WITH display. Automatic panel
Digital control unit WITH transfer switch
CEC7 and with mains
control. The display
will be on the genset
and on the cabinet.
Digital control unit
CEM7+CEC7
AS7 + AC5
CC2
Automatic mains
Automatic control failure control panel.
panel WITH transfer Wall-mounted
switch and WITH cabinet WITH
mains control. The transfer switch and
display will be on the thermal magnetic
genset and on the protection
cabinet. (depending on
current and voltage).
Digital control unit
M7X+CEC7 Digital control unit
CEA7
Electrical system
• Electric control and power panel • Heating resistor (standard on • Battery Switch (Opcional).
with measurements devices sets with automatic control • Leakage detector (Opcional).
and control unit (according to panels)
necessity and configuration) • Optional Battery (Optima)
• Battery charger alternator with (Opcional).
• 4-pole thermal magnetic circuit ground connection
breaker
• Starter battery/ies installed
• Adjustable earth leakage (cables and bracket included)
protection
• Ground connection electrical
• Battery charger (standard on installation with connection
gensets with automatic control ready for ground spike (not
panels) supplied)
2023-MAY.-25 22:20
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com