HSF-65 T5 48KW Fpt-Iveco

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

HSF-65 T5

HS | STATIONARY RANGE
Powered by FPT_IVECO

Công suất liên tục Công suất thiết kế


SERVICE PRP ESP

POWER kVA 60 63

POWER kW 48 50

RATED SPEED r.p.m. 1.500

MAIN VOLTAGE V 400/230

230/115 · 380/220 ·
AVAILABLE VOLTAGES V 415/240

RATED AT POWER Cos Phi 0,8


FACTOR

HS | STATIONARY RANGE STANDARD SOUNDPROOFING


HIMOINSA Company with quality certification ISO 9001
HIMOINSA gensets are compliant with EC mark which includes the following
directives: HS40
• 2006/42/CE Machinery safety.
• 2014/30/UE Electromagnetic compatibility.
• 2014/35/UE electrical equipment designed for use within certain voltage limits
• 2000/14/EC Sound Power level. Noise emissions outdoor equipment. (amended by
2005/88/EC) WATER-COOLED
• 97/68/EC Emissions of gaseous and particulate pollutants.
• EN 12100, EN 13857, EN 60204

Ambient conditions of reference according to ISO 8528-1:2018 normative: 1000 mbar,


25ºC, 30% relative humidity. THREE PHASE
Prime Power (PRP):
According to ISO 8528-1:2018, Prime power is the maximum power which a
generating set is capable of delivering continuously whilst supplying a variable
electrical load when operated for an unlimited number of hours per year under the
agreed operating conditions with the maintenance intervals and procedures being 50 HZ
carried out as prescribed by the manufacturer. The permissible average power output
(Ppp) over 24 h of operation shall not exceed 70 % of the PRP.

Emergency Standby Power (ESP):


According to ISO 8528-1:2018, Emergency standby power is the maximum power STAGE 3A
available during a variable electrical power sequence, under the stated operating
conditions, for which a generating set is capable of delivering in the event of a utility
power outage or under test conditions for up to 200 h of operation per year with the
maintenance intervals and procedures being carried out as prescribed by the
manufacturers. The permissible average power output over 24 h of operation shall not
exceed 70 % of the ESP DIESEL
Continuous Power (COP): According to Standard ISO 8528-1:2018, this is the
maximum power available for continuous loads for unlimited running hours a year
between the maintenance times recommended by the manufacturer under the
environmental conditions established by the same.
Himoinsa has the right to modify any feature without prior notice.
G2 class load acceptance in accordance with ISO 8528-5:2018
Weights and dimensions based on standard products. Illustrations may
HIMOINSA HEADQUARTERS: include optional equipment.
Fábrica: Ctra. Murcia - San Javier, Km. 23,6 | 30730 SAN JAVIER (Murcia) Spain
Tel.+34 968 19 11 28 Fax +34 968 19 12 17 Fax +34 968 19 04 20 | Technical data described in this catalogue correspond to the available
info@himoinsa.com | www.himoinsa.com information at the moment of printing.
Manufacture facilities: The illustrations and images are indicative and may not coincide in their
SPAIN • FRANCE • INDIA • CHINA • USA • BRAZIL • ARGENTINA entirety with the product.
Subsidiaries:
PORTUGAL | POLAND | GERMANY | UK | SINGAPORE | UAE | PANAMA | Industrial design under patent.
DOMINICAN REPUBLIC | ARGENTINA | ANGOLA | SOUTH AFRICA
2023-MAY.-25 22:20

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HSF-65 T5

Engine Specifications | 1.500 r.p.m.

Rated Engine Output (COP) kW 43,2 Lube oil consumption with 0,1 % of fuel
full load consumption
Rated Engine Output (PRP) kW 54,5
Total oil capacity including
Rated Engine Output (ESP) kW 60 L 12,8
tubes, filters
Manufacturer FPT_IVECO Total coolant capacity L 18,5
Model NEF45SM1F Governor Type Mechanical
Engine Type 4-stroke diesel Air Filter Type Dry
Injection Type Direct
Aspiration Type Turbocharged
Number of cylinders and 4-L
arrangement
Bore and Stroke mm 104 x 132
Displacement L 4,5
Liquid (water +
Cooling System 50% glycol)
Lube Oil Specifications ACEA E3 - E5
Compression Ratio 17,5:1

• Diesel engine • 12V electrical system • Mechanical governor


• 4-stroke cycle • Dry air filter • Hot parts protection
• Water-cooled • Radiator with pusher fan • Moving parts protection

Generator Specifications | STAMFORD

Manufacturer STAMFORD Enclosure (according IP23


IEC-34-5)
Model UCI224E
Self-excited,
Poles No. 4 Exciter system brushless
Connection type (standard) Star-series Voltage regulator A.V.R. (Electronic)
Mounting type S-3 11"1/2 Bracket type Single bearing
Insulation Class H class Coupling system Flexible disc
Standard (Vacuum
Coating type impregnation)

• Self-excited and self-regulated


• IP23 protection
• H class insulation
2023-MAY.-25 22:20

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HSF-65 T5

WEIGHT AND DIMENSIONS


Standard Optional Optional
Version version version
Length (L) mm 2.600 2.600 2.600
Height (H) mm 1.500 1.630 1.850
Width (W) mm 910 910 910
Maximum shipping volume m³ 3,55 3,86 4,38
Weight with liquids in radiator Kg 1171 1176 1330
and sump
Fuel tank capacity L 195 405 785
Autonomy (100% PRP) Hours 12 24 47
Steel tank Steel tank Steel tank

SOUND PRESSURE
Sound pressure level dB(A)@7m 67 ± 2,4

APPLICATION DATA
EXHAUST SYSTEM NECESSARY AMOUNT OF AIR

Maximum exhaust temperature ºC 492 Intake air flow m³/h 289

Exhaust Gas Flow kg/s 0,0945 Cooling Air Flow m³/s 2,2

Maximum allowed back pressure kPa 5 Alternator fan air flow m³/s 0,216

Heat dissipated by exhaust pipe KCal/Kwh 493

FUEL CONSUMPTION FUEL SYSTEM

Fuel Consumption ESP l/h 18 Fuel Oil Specifications Diesel

Fuel Consumption 100% PRP l/h 16,7 Fuel Tank L 195

Fuel Consumption 70 % PRP l/h 11,83 Other fuel tank capacities L 405, 785

Fuel Consumption 50 % PRP l/h 9,5

STARTING SYSTEM

Starting power kW 3

Starting power CV 4,08

Recommended battery Ah 100

Auxiliary Voltage Vdc 12

Soundproofed version
2023-MAY.-25 22:20

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
• Steel chassis • 4 side lifting points • Epoxy polyester powder coating
• Lower power cable outlet with • Anti-vibration shock absorbers • Full access for maintenance (water, oil
aluminum cover and filters, no need to remove the
• Fuel tank canopy)
• Side auxiliary cable outlet with
aluminum cover • Fuel level gauge • Versatility to assemble a high capacity
• External emergency stop switch chassis with a metallic fuel tank
• Modular tank and retention tray
system. Allows easy removal and / or
• Bodywork made from high quality • IP Protection according to ISO
maintenance of the equipment 8528-13:2016
steel plate
• Wide access to the engine • High mechanical strength
• Manual oil extraction pump (Opcional).
compartment because of a removable • Noise reduction kit (Opcional).
door
• Fuel transfer pump (Opcional).
• Fuel tank in retention tray
• Soundproofing with foam and
polyurethane film
HSF-65 T5

FEATURES OF THE
CONTROL UNITS
M7X CEM 7 CEA 7 CEC 7 M7X+CEC7
Voltage between phases • • • • •
Voltage between neutral and phase • • • • •
Current intensities • • • • •
Generator Readings

Frequency • • • • •
Apparent power (Kva) • • • • •
Active power (Kw) • • • • •
Reactive power (kVAr) • • • • •
Power factor • • • • •
Voltage between phases • • •
Voltage between phases and neutral • • •
Current intensities • • •
Frequency • • •
Mains Readings

Apparent power •
Active power •
Reactive power •
Power factor •
Coolant temperature • • • •
Oil pressure • • • •
Engine Readings

Fuel level (%) • • • •


Battery voltage • • • •
R.P.M. • • • •
Battery charge alternator voltage • • • •
High water temperature • • • •
High water temperature by sensor • • • •
Low water temperature by sensor • • • •
Low oil pressure • • • •
Low oil pressure by sensor • • • •
Low water level • • • •
Unexpected shutdown • • • •
Fuel storage • • • •
Fuel storage by sensor • • • •
Stop failure • • • •
Battery voltage failure • • • •
Engine Protections

Battery charge alternator failure • • • •


Overspeed • • • •
Underspeed • • • •
Start failure • • • •
Emergency stop • • • • •
• Standard Optional
2023-MAY.-25 22:20

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HSF-65 T5

M7X CEM 7 CEA 7 CEC 7 M7X+CEC7


High frequency • • • • •
Low frequency • • • • •
High voltage • • • • •
Low voltage • • • • •
Alternator Protections

Short-circuit • • • •
Asymmetry between phases • • • • •
Incorrect phase sequence • • • • •
Inverse power • • • •
Overload • • • •
Genset signal drop • • • • •
Total hour counter • • • • •
Partial hour counter • • • • •
Kilowatt meter • • • • •
Starts valid counters • • • • •
Counters

Starts failure counters • • • • •


Maintenance • • • • •
RS232 ⓪ ⓪ ⓪ ⓪
RS485 ⓪ ⓪ ⓪ ⓪
Modbus IP ⓪ ⓪ ⓪ ⓪
Modbus ⓪ ⓪ ⓪ ⓪
CCLAN ⓪ ⓪
Software for PC ⓪ ⓪ ⓪ ⓪
Analogue modem ⓪ ⓪ ⓪ ⓪
Communications

GSM/GPRS modem ⓪ ⓪ ⓪ ⓪
Remote screen ⓪ ⓪
Tele signal ⓪ (8 + 4) ⓪ (8 + 4)
J1939 ⓪ M7XJ ⓪ ⓪ ⓪ M7XJ
Alarm history • (100) • (100)
• (100)
• (100)
• (100)

External start • • • • •
Start inhibition • • • • •
Mains failure start • • •
Start under normative EJP • • • •
Pre-heating engine control • • • •
Genset contactor activation • • • • •
Mains & Genset contactor activation • • •
Fuel transfer control • • • •
Engine temperature control • • • •
Manual override • • • •
Programmable alarms • • • •
Genset start function in test mode • • • • •
Features

Programmable outputs • • • •
Multilingual • • • •
GPS Positioning ⓪ ⓪
Synchronisation
Special Functions

⓪ ⓪
Mains synchronization ⓪ ⓪
Second Zero elimination ⓪ ⓪
RAM7 ⓪ ⓪
Remote screen ⓪ ⓪

• Standard Optional
2023-MAY.-25 22:20

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HSF-65 T5

CONTROL
PANELS

AS5 AS7
Automatic panel Automatic control
WITHOUT transfer panel WITHOUT
switch and Transfer Switch and
WITHOUT mains WITHOUT mains
control with CEM7 control with M7X
unit. (*) AS5 as unit.
optional with CEA7
unit. Automatic panel Digital control unit
without transfer M7X
switch and WITH
mains control.

CC2 AS5 +
CC2
Himoinsa Switching
cabinet WITH display. Automatic panel
Digital control unit WITH transfer switch
CEC7 and with mains
control. The display
will be on the genset
and on the cabinet.
Digital control unit
CEM7+CEC7

AS7 + AC5
CC2
Automatic mains
Automatic control failure control panel.
panel WITH transfer Wall-mounted
switch and WITH cabinet WITH
mains control. The transfer switch and
display will be on the thermal magnetic
genset and on the protection
cabinet. (depending on
current and voltage).
Digital control unit
M7X+CEC7 Digital control unit
CEA7

Electrical system
• Electric control and power panel • Heating resistor (standard on • Battery Switch (Opcional).
with measurements devices sets with automatic control • Leakage detector (Opcional).
and control unit (according to panels)
necessity and configuration) • Optional Battery (Optima)
• Battery charger alternator with (Opcional).
• 4-pole thermal magnetic circuit ground connection
breaker
• Starter battery/ies installed
• Adjustable earth leakage (cables and bracket included)
protection
• Ground connection electrical
• Battery charger (standard on installation with connection
gensets with automatic control ready for ground spike (not
panels) supplied)