Structural Guidelines

RAKG-S-2021
Ras Al Khaimah Structural Guidelines

Revision History

Revision Revision Description Date


0 First Issue January 2021
1 Second Issue January 2023

All Rights Reserved for Ras Al Khaimah Municipality. All or any part of the contents of this document including, but
not limited to: text, logos, images, files, etc… are the sole property of Ras Al Khaimah Municipality.

Ras Al Khaimah Structural Guidelines-RAKG-S-2021.


First Edition, January, 2021.

Government of Ras Al Khaimah Page 1 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

Contents
1. Introduction ........................................................................................................................................................... 4
1.1. Scope of Document ...................................................................................................................................... 4
1.2. Disclaimer ..................................................................................................................................................... 4
2. General Requirements and Conditions ................................................................................................................ 5
2.1. General Requirements ................................................................................................................................. 5
2.2. Third Party Requirements............................................................................................................................. 5
2.3. Acceptable Software ..................................................................................................................................... 6
2.4. Unit System .................................................................................................................................................. 6
2.5. Building Life Time ......................................................................................................................................... 6
2.6. Fire Rating .................................................................................................................................................... 6
3. Approved Codes and Standards .......................................................................................................................... 7
4. Materials ............................................................................................................................................................... 8
4.1. Concrete ....................................................................................................................................................... 8
4.2. Reinforcement .............................................................................................................................................. 8
4.3. Structural Steel ............................................................................................................................................. 8
5. Loading Criteria .................................................................................................................................................... 9
5.1. Loading Notations ......................................................................................................................................... 9
5.2. Gravity Loads................................................................................................................................................ 9
5.2.1. Dead Loads .............................................................................................................................................. 9
5.2.2. Live loads................................................................................................................................................ 11
5.3. Soil Lateral Loads ....................................................................................................................................... 13
5.4. Uplift Load................................................................................................................................................... 13
5.5. Thermal Effect due to Seasonal Variation and Self-Straining Actions ....................................................... 14
5.6. Seismic Loads ............................................................................................................................................ 15
5.6.1. Seismic Scaling ...................................................................................................................................... 17
5.6.2. P-delta Effects ........................................................................................................................................ 17
5.6.3. Torsional Irregularity ............................................................................................................................... 17
5.7. Wind Loads ................................................................................................................................................. 18
5.7.1. Wind Tunnel Test.................................................................................................................................... 18
5.8. Helipad Loads ............................................................................................................................................. 18
5.9. Minimum Lateral Forces ............................................................................................................................. 19
5.10. Loading Combinations ............................................................................................................................ 19
6. Serviceability Requirements ............................................................................................................................... 20
6.1. Control of Deflection in Concrete Elements ............................................................................................... 20
6.2. Control of Deflection in Steel Elements ...................................................................................................... 21
6.3. Control of Lateral Drifts ............................................................................................................................... 21
6.3.1. Seismic Drift............................................................................................................................................ 21
6.3.2. Wind Drift ................................................................................................................................................ 21
6.4. Human Comfort and Vibration .................................................................................................................... 22
6.4.1. Building Acceleration .............................................................................................................................. 22
6.4.2. Vertical Vibration..................................................................................................................................... 22
6.4.3. Other Considerations .............................................................................................................................. 23
7. Structural Integrity .............................................................................................................................................. 24
7.1. Load Path Connections. ............................................................................................................................. 24
8. Durability Requirements ..................................................................................................................................... 25
8.1. Waterproofing Requirement ....................................................................................................................... 25
8.2. Control of Cracking ..................................................................................................................................... 25
8.3. Concrete Cover........................................................................................................................................... 26
8.4. Spacing Between Bars ............................................................................................................................... 26
9. Concrete General Design Requirements ........................................................................................................... 27
9.1. Cracking Stiffness Modifiers ....................................................................................................................... 27
9.2. Columns and Walls ..................................................................................................................................... 28
9.3. Beams......................................................................................................................................................... 28
9.4. Slabs ........................................................................................................................................................... 28
9.5. Transfer Beams and Transfer Slabs........................................................................................................... 30
9.6. Structural Movement Joints ........................................................................................................................ 30
9.7. Additional Control Measures for Below Grade Construction ...................................................................... 30
10. Foundation .......................................................................................................................................................... 31
10.1. General Requirements ........................................................................................................................... 31

Government of Ras Al Khaimah Page 2 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

10.2. Shallow Foundation ................................................................................................................................ 32


10.2.1. Foundations on/or adjacent to slopes .................................................................................................... 32
10.3. Retaining Walls ....................................................................................................................................... 33
10.4. Deep Foundation (Piles) ......................................................................................................................... 34
10.4.1. General Requirements ........................................................................................................................... 34
10.4.2. Pile tests ................................................................................................................................................. 35
10.4.3. Piling Package by the Consultant ........................................................................................................... 35
10.4.4. Piling Package by the Piling Contractor ................................................................................................. 36
10.4.5. Pile Caps Requirements ......................................................................................................................... 36
11. Pre-Stressed Concrete ....................................................................................................................................... 38
11.1. General Design Requirements ............................................................................................................... 38
11.2. Serviceability Requirements-Flexural Members ..................................................................................... 39
11.3. Permissible Stresses in Pre-Stressing Steel .......................................................................................... 39
11.4. Pre-Compression Stresses..................................................................................................................... 39
11.5. Minimum Bonded Reinforcement ........................................................................................................... 39
11.5.1. Bottom Reinforcement. ........................................................................................................................... 39
11.5.2. Top Reinforcement. ................................................................................................................................ 39
11.6. Reinforcement Detailing ......................................................................................................................... 40
11.6.1. Edge Reinforcement ............................................................................................................................... 40
11.6.2. Reinforcement Between Tendon Anchorages........................................................................................ 40
12. Steel Structures .................................................................................................................................................. 42
12.1. General requirements ............................................................................................................................. 42
12.2. Structural Integrity .................................................................................................................................. 42
13. Geotechnical and Soil Investigation ................................................................................................................... 44
13.1. Boreholes and Site Testing .................................................................................................................... 44
13.1.1. Boreholes Number .................................................................................................................................. 44
13.1.2. Boreholes Depth ..................................................................................................................................... 44
13.1.3. Soil Investigation Report......................................................................................................................... 45
13.1.4. Information to be Included in the Soil Investigation Report .................................................................... 45
13.1.5. Recommendation to be Included in the Soil Investigation Report.......................................................... 46
.14 Enabling Works .................................................................................................................................................. 47
14.1. Open Excavation .................................................................................................................................... 47
14.2. Backfill Materials and Compaction ......................................................................................................... 47
14.3. Shoring ................................................................................................................................................... 47
14.4. Submission Methods for Excavation and Shoring Permit ...................................................................... 48
14.4.1. Method A ................................................................................................................................................ 48
14.4.2. Method B ................................................................................................................................................ 48
14.5. Required Documents for Excavation and Shoring Permit ...................................................................... 49
15. Items to Be Included in Structural Submission ................................................................................................... 50
16. Extension and Modification of Existing Buildings ............................................................................................... 52
16.1. General Requirements ........................................................................................................................... 52
16.2. Building Classification ............................................................................................................................. 52
16.2.1. Buildings with a Structural Age Over 15 Years ...................................................................................... 52
16.2.2. Buildings with a Structural Age of 10 to 15 Years .................................................................................. 52
16.2.3. Buildings with a Structural Age Less Than 10 Years ............................................................................. 52
16.3. Soil Testing Procedures ......................................................................................................................... 52
16.4. Decisions and Procedures...................................................................................................................... 53
17. Inspection of Buildings Construction .................................................................................................................. 54
17.1. Inspection of concrete works .................................................................................................................. 54
17.2. Inspection of Structural Steel Works ...................................................................................................... 54
17.3. Inspection of Founding Soil .................................................................................................................... 54
18. Approval of New Structural Systems .................................................................................................................. 55
18.1. General requirements ............................................................................................................................. 55
18.2. Technical requirements .......................................................................................................................... 55

Government of Ras Al Khaimah Page 3 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

1. Introduction

1.1. Scope of Document


• This document is prepared to provide a sort of guidance for structural design engineers working on
projects in Ras Al Khaimah. The main scope of this document is to provide main headings and
important aspects which should be considered while processing the design of any project.
• The main objective of the structural guidelines is to ensure that all projects under the jurisdiction of
Ras Al Khaimah Municipality follow a uniform approach for the design and construction of all
structures. These guidelines seek to assist all structural engineers submitting project(s) to Ras Al
Khaimah Municipality to better understand the minimum requirements for the design, review and
checking the design of any structure with Ras Al Khaimah Municipality team during the approval
process that will facilitate and ease the permits issuance. It is anticipated that the use of these
guidelines will result in a unified form of design and construction of buildings throughout all types of
structures.
• These Guidelines are intended to be used in conjunction with international, federal and local design
codes, standards and other widely accepted references.
• In the case of any conflict between these guidelines and the mentioned design codes and
standards, the requirements as outlined in the Ras Al Khaimah Municipality structural guidelines will
prevail.

1.2. Disclaimer
• This document has been prepared only to provide some guidance for the design engineers and It
shall be read in conjunction with all the applicable federal and local laws, codes, standards,
regulations, circulars, manuals, policies and procedures as implemented by Ras Al Khaimah
Municipality.
• All requirements indicated within this structural guideline may be amended whenever required and
no prior notice required.
• The full responsibility and liability of the design and construction of any project is on the consultant
and the contractor without any responsibility or liability on the municipality.
• Ras Al Khaimah Municipality is not liable for any defects, deficiencies, collapse or fatal mistakes in
the design or execution of any project for which it has given approval.

Government of Ras Al Khaimah Page 4 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

2. General Requirements and Conditions

2.1. General Requirements


• Structural design for buildings and facilities shall be prepared by a qualified structural engineer
licensed to practice the profession and approved by the Municipality.
• The structural calculations shall be prepared using recognized engineering software approved
internationally.
• The structural package for the different structural elements shall be submitted by the approved
consultant by Ras Al Khaimah Municipality.
• All buildings’ parts and related building’s materials shall have adequate safety and durability.
• Structures shall be designed to withstand the most critical straining actions resulting from the
codified load combinations, provided that the effect of the maximum resultant loads shall not exceed
the allowable stress limit of the construction material.
• Structures shall be designed to have sufficient stiffness to maintain any deformation due to vertical,
horizontal loads and vibration within the allowable limits and without affecting the function of the
structure.
• Structures shall be designed to ensure the overall stability and individual elements’ stability under all
loads’ types and cyclic loads.
• All approved codes limits for strength, materials properties, durability and serviceability of structures
are deemed to be satisfied wherever applicable.
• Concrete mix design should be satisfying specified codes requirements.
• Code minimum and maximum percentage of reinforcement related to different straining actions are
deemed to be satisfied for all members.
• Reinforcement details, development lengths and splices should be according to specified codes
requirements.

2.2. Third Party Requirements


• Third party review may be required for any of the following structures subjected to the pre-
agreement with Ras Al Khaimah municipality:
- Any building of height more than G+40 floors.
- Irregular, complicated and un-usual structures.
• Whenever there is any doubt about the need for a third party reviewer for a project, it is the
consultant responsibility to approach the Ras Al Khaimah Municipality to confirm the requirements
for third party reviewer. The consultant shall raise an official letter to address the query.
• Ras Al Khaimah Municipality has the right to request a third party reviewer for any project if the
consultant or specialist sub-contractor is found to be incompetent enough.
• The third party consultant shall be registered as a third part reviewer in any of the municipalities
within United Arab Emirates, and shall be submitted to Ras Al Khaimah municipality for approval at
the early stage of the design.
• Third party reviewer shall have similar experience in the project under review with proven track
record of reviewing similar projects.
• Third party reviewer is required to adhere to Ras Al Khaimah municipality’ design guidelines and
circulars regularly.

Government of Ras Al Khaimah Page 5 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

2.3. Acceptable Software


The software approved by RAK Municipality as follows.
• CSI Software (ETABS, SAFE, SAP 2000 and CSI-Columns).
• MIDAS.
• STAAD.
• PROKON.
• SP COLUMN
• RAM CONCEPT.
• ADAPT.
• PLAXIS.
Any other internationally recognized software and regionally/locally standard software can be used for
analysis and design subjected to pre-approval from the municipality.

2.4. Unit System


All structural calculations, analysis models’ output, technical reports and drawings shall be presented in
SI unit system.
The following table gives a guidance for the consistent SI units’ system to be used:
Measurement item Measurement unit
Levels m
Dimensions mm
Force KN
Stresses N/mm2
Bending moment KN.m
Bearing Pressure KN/m2
Temperature Co
Deformations/Deflection mm

2.5. Building Life Time


Building life time shall be defined according to the code requirements, construction, regular maintenance
and client requirements.

2.6. Fire Rating


• All structural elements and/or members shall have the following minimum fire rating unless otherwise
noted by certified Fire and Life Safety specialist.
- Two hours for horizontal elements.
- Three hours for vertical elements and transfer elements.
• The proper fire rating for concrete elements shall be achieved by defining the proper element size/
concrete cover, and for steel elements shall be achieved by proper coating thickness of cementitious
or intumescent materials.

Government of Ras Al Khaimah Page 6 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

3. Approved Codes and Standards

The following are the main codes and standards that shall be followed for the structural design along
with the other American Concrete Institute (ACI) publications.
The defined version is the minimum approved publication version.

Publication Publication Title Application of


Reference Publication
Minimum Design Loads for Buildings and Other Gravity loads, Wind loads
ASCE7-05
Structures and load combinations
Uniform Building Code Seismic load
UBC 97

Building Code Requirements for Structural Concrete Concrete structural design


ACI318-11

PCI Design Handbook - Precast and Pre-Stressed Design of Pre-cast


PCI 6th edition.
Concrete elements
Building Code Requirements for Structural Concrete Design of post tension
ACI318-11 elements
Post-Tensioned Concrete Floors Design Handbook
TR43 2nd edition
(Second Edition)
Code Requirements for Environmental Engineering Durability of concrete
ACI 350-06
Concrete Structure and commentary
Control of Cracking in Concrete Structures
ACI224R-01

Early-age Thermal Crack Control in Concrete


CIRIA 660-7

Code Requirements for Evaluation, Repair, and Assessment and testing of


ACI562-19
Rehabilitation of Concrete Buildings existing structures
Guide for Evaluation of Concrete Structures Prior to
ACI364.1 R-94
Rehabilitation
Specification for Structural Steel Buildings Steel structural design
AISC 360-05

Seismic Provisions for Structural Steel Buildings


AISC 341-10

Guide to Design, Manufacture, and Installation of Pile Design


ACI 543R-12
Concrete Piles
UAE Fire and Life Safety Code of Practice Fire rating

IBC 2009 International Building Code General

Government of Ras Al Khaimah Page 7 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

4. Materials

4.1. Concrete
• Minimum concrete grade for structural members is accepted as per code limits.
• Concrete grade is accepted up to f’c 70Mpa. Any concrete with higher grades cannot be used
without prior approval from municipality.
• Modulus of elasticity has to be calculated in accordance with ACI 318 formula.
Ec = (4700 √fc’) MPa.
• In case of using High Strength Concrete (HSC) with f’c more than 60MPa, the modulus of elasticity
has to be calculated in accordance with Technical Report No.49’s provided formula
Ec = (3320 √fc’ + 6900) x (Wc /2346)1.5) MPa.
• Concrete grades input in design should be noted always as cylindrical compressive strength f’c.
• High strength concrete -if any- should be achieved via the addition of silica fume to the mix.
• The water/cement ratio in the concrete mix shall not exceed 0.40.
• A durable low heat of hydration concrete for sub structure elements (foundations, raft slabs and
basement walls) can be achieved using a combination of OPC and GBBS in the concrete mix. GGBS
percentage in the mix shall be within 36% to 65%.

4.2. Reinforcement
• Reinforcing steel shall be High Yield Strength deformed bars type 2 with minimum characteristic
strength of fy =460 N/mm2 unless otherwise justified by the designer.
• For shear design; the maximum yield strength to be used is fy=420 N/mm2.
• All reinforcement shall conform to BS 4449 grade 460 or Equivalent ASTM specifications as a
minimum.
• Welded wire mesh: Steel fabric reinforcement will comply with BS 4483 or Equivalent ASTM
specifications.
• The preferred range of designated fabric types will be as per Table A.1 of BS 4483 or Equivalent
ASTM specifications.

4.3. Structural Steel


• In accordance with procurement requirements typical in UAE, all steelwork shall adopt standard section
dimensions as defined by British Standards. However, the material shall be procured to demonstrate
compliance to ASTM standards and the design shall be in accordance with the provisions as defined
herein in this report.

Government of Ras Al Khaimah Page 8 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

5. Loading Criteria

5.1. Loading Notations


The following loading notations are the recommended notations to be generally used in loading
definitions such as load cases and load combinations in structural analysis software and calculations.

Load type Notation


Self-weight SW
Super imposed dead load SDL
Live load-non reducible LL
Live load-reducible LLr
Mechanical load Mech
Thermal load T
Earthquake load E
Wind load W
Lateral earth pressure load H
Water uplift load F

5.2. Gravity Loads


5.2.1. Dead Loads
All Dead Loads are established based upon the self-weight of the structure and combined with the super
imposed dead loads (finishes, partitions and other dead loads). The characteristic densities are listed
under this section.
Self-weight of the primary structural elements shall be defined as a part of the material definition in the
analysis software and not part of the applied superimposed dead load.
The following table illustrate the minimum density of the main materials to define the material self-weight.

Typical materials densities


Item Density (KN/m3)
Reinforced Concrete; In-Situ Topping 25.0
Plain concrete 22.0
Normal weight screed (Typical finishes) 20.0
Plaster 20.0
Lightweight concrete fill U.N.O. 13.0
Glass 27.0
Steel 78.5
Landscaping / Retained wet soils 20.0
Dry soils 18.0

For Hollow block system (Hordi); the self-weight of the hordi blocks shall be considered in the analyses
as per the actual weight of the blocks from the manufacturer data sheet.

Government of Ras Al Khaimah Page 9 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

5.2.1.1. Partitions
• As a general principle, the partitions’ loads shall be applied as an equivalent uniform load. However,
actual partition line load assignments shall be required in some instances. The blockwork type and
density to be confirmed with architectural drawings and included in the submitted general notes
drawings and calculation.
• The partition load shall be calculated in details as per the architectural layout.
• Minimum partition block density shall not be taken less than the following values unless proved
otherwise by certified manufacture/supplier:

Typical block wall densities (unless otherwise provided from project supplier)
Item Density (KN/m3)
Normal weight solid blocks 21.0
Normal weight hollow blocks (200mm thickness) 14.0
Normal weight hollow blocks (100mm thickness) 17.5
Light weight Aerated Autoclaved Concrete blocks (AAC) 6.0
Normal weight thermo blocks 15.0
Light weight thermo blocks 8.8

Uniform distributed load on plan due to partitions only shall not be taken less than the following minimum
values.
Minimum partition distributed loads on plan
Main Partitions Type Load (KN/m2)
Dry wall partitions 1.0
Light weight block partitions 2.5
Solid block work partitions 3.5

5.2.1.2. Finishes
The density of the finishes on the slab shall be 20 KN/m3, and the actual thickness of the finishes shall
be considered in the loading calculations.

Typical finishes distributed loads (unless otherwise calculated)

Finish thickness (mm) Load (KN/m2)


50mm 1.0
75mm 1.5
100mm 2.0

Government of Ras Al Khaimah Page 10 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

5.2.1.3. Other Loads

A. Ceiling and services:


Load shall be 0.5 KN/m2 as a minimum uniform load on plan to be considered unless more accurate
calculation is available to justify lesser loads.
Moreover, the actual uniform load for the suspended services shall be calculated at the mechanical
floors and parking floors’ ceiling.

B. Façade load:
The actual façade load to be calculated and applied as a line load on the slab wherever applicable.
In the case of having façade with more than one type of materials, equivalent line load to be
calculated based on each material density and distribution.
In the absence of accurate façade load or justification from façade specialist; it shall be considered
as 1.0 KN/m2 (on elevation). This value is not applicable for the heavy façade system such as GRC,
stone cladding, etc., it shall be calculated accurately.

C. Machines’ plinth/base:
In the MEP areas, the equivalent load of the machine’s support plinths to be calculated.

5.2.2. Live loads

5.2.2.1. Reducible Live load


The live loads with a value that not exceeds 4.8 KN/m2 considered as Reducible live load.

5.2.2.2. Non-Reducible Live load


The heavy Live load with value exceeds 4.8 KN/m2, car parking load and public assembly occupancies
shall be considered as non-reducible live load.

5.2.2.3. Permanent Live Load


The Mechanical and water tanks load shall be considered as permanent live load. The Load of
Mechanical zones to be calculated as per the equipment manufacturer catalogue. However, the
Mechanical load value shall not be less than the value in the minimum live load values shown in the
following table.

Government of Ras Al Khaimah Page 11 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

5.2.2.4. Minimum Live Loads


The following table represents the minimum distributed live load which shall be considered in the design.
Any other live loads not mentioned shall be referred from ASCE7-05.

Description of Live Load Uniform Load (KN/m2)


Residential (***) 2.0
Hotel rooms (***) 2.0
Balconies (up to 9.3m2 area) 3.0
Balconies (more than 9.3m2 area) 5.0
Corridors between apartments/rooms 2.0
Lobbies and public corridors 4.8
Staircases 4.8
Public Spaces 4.8
Retail Areas 4.8
Offices 2.5
General Plant rooms and MEP spaces (**) 7.5
Transformers and generators rooms 10.0
Car park 3.5
Loading Bay Areas (unless accurately justified) 15.0
Fire truck routes 20.0
Roofs * 2.0
Non-accessible steel roofs / Dooms /Folded roofs 0.6
Gym / Health club 5.0
Cinema 5.0
Water storage (to be calculated according to water height) 10xh
Notes:
• (*) Roof usage shall be confirmed with Architectural drawings, the loads on roof used for garden or
assembly purposes shall be 4.8 KN/m2 as a minimum. Any loads for MEP equipment or water tanks
on roof shall be considered separately.
• (**) The mentioned MEP loads is the minimum applied value unless required more values based on
actual equipment loads.
• (***) For the design of all flat slabs and post tensioned slabs, a minimum live load of 3KN/m2 shall be
considered.
• It is allowed to round up the live load of 4.8KN/m2 to 5.0KN/m2 for simplicity without changing any of
the relevant code conditions.

Government of Ras Al Khaimah Page 12 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

5.3. Soil Lateral Loads


Soil pressure load and water load shall be calculated based on the soil investigation parameters.
As applicable, Soil lateral loads shall be determined using the equations for the at-rest earth pressure
coefficient (KO) for the case of basement retaining walls, while it is allowed to use (Ka) only for the case
of cantilever retaining walls.

Soil properties to be used in case of backfilled soil behind basement walls:


Where new fill is placed behind the retaining walls, the following provisions for the fill material properties
is to be attained as a minimum unless more accurate details are specified by certified geotechnical
engineer and properly supervised in site.
Soil Density Average Angel of KO Ka Kp
(kN/m3) Internal Friction
18-20 30° 0.50 0.33 3.0

Soil properties to be used in case of shoring behind basement walls:


Where there is an existing shoring placed or casted directly against the native soils behind the retaining
basement walls; the soil properties provided in the soil report shall be used for basement wall design.

Surcharge loads
For all permanent retaining structures, the vertical surcharge loading on retaining structure shall be
considered as per the following cases;

Case Surcharge loads (KN/m2)


Adjacent building at higher level (on shallow Actual loads from the building at foundation level
foundation) (located at higher level)
Adjacent roads 20
Construction site (current or future) 20
Minimum value 5

5.4. Uplift Load.


When considering the requirement for water uplift loads in design, the following should be taken into
consideration by the consultant:
• For the purpose of analysis and design, the actual water table level shall be considered plus
minimum seasonal variation of 1.0m.
• Dewatering effect of neighboring areas shall be considered.
• The effect of future developments (canal, water bodies, landscaping…. etc.) on the water table level
shall be considered.
• Minimum factor of safety for overall stability against uplift shall not be less than 1.10 and considering
the self-weight only during permanent cases and temporary cases (e.g discontinuity of dewatering
activity).
• The consultant shall include clear notes in the structural general notes drawings stating clearly at
which level of construction the dewatering will stop.

Government of Ras Al Khaimah Page 13 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

5.5. Thermal Effect due to Seasonal Variation and Self-Straining Actions


• The design shall account for the forces and movements resulting from an imposed thermal load due
to seasonal variation, considering building enclosure conditions and continuous long spans.
• Thermal loads shall be considered for concrete structures if the building length is more than 50m.
• Thermal loads shall be applied to any steel structure regardless the building length.
• The thermal load due to seasonal variation shall be applied in the 2D and 3D analysis models
considering positive/negative effects as per the following minimum values.

Temperature
Location Structural Element
(Co)
Retaining walls/columns/shear
Below Ground (Basement) +/- 10
walls/Beams/slabs (excluding Ground slab)
Ground level and upper levels
Columns/shear walls/Beams/slabs/ +/- 20
(Superstructure)
General Steel structural elements +/- 25

When incorporating the requirement for self-straining loads in a design, the following should be
considered:
• Creep effect.
• Thermal effect.
• Shrinkage effect (early and long-term).

Late pour strip can be provided to reduce the effect of the early thermal cracking only and subjected to
proper calculation for the consultant.

Government of Ras Al Khaimah Page 14 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

5.6. Seismic Loads


The following requirements along with the requirements of the applicable code (UBC97) should be
referred to when considering the technical requirements for seismic load design.

Item Description

Applicable standards UBC97


Seismic Zone Zone 2A
For all buildings unless otherwise exempted in the following clause.
Mass Source 100% Dead loads, 100% permanent live loads and 25% of non-
reducible live loads (LL).
Damping Ratio 5% for concrete and 2.5% for Steel.
Importance factor “I” and To be considered as per recommendations of the applicable codes
ductility factor “R” and standards.
Effects of Vertical To be considered in the dead load component of seismic load
Component of Earthquake combination according to the applicable codes and standards adopted
Ground Motion for analysis and design.
Where; Ev=0.5CaID as per UBC97.
Elements supporting To be designed using the provisions of the applicable codes and
discontinuous members of standards, with special seismic load combinations and appropriate
lateral load resisting systems overstrength factor (W).

P-Delta effect. To be considered according to the following combination;


1.2(Dead loads) +0.5(Reducible live load) +1.0(Non-reducible live
load)
Dynamic Analysis To be considered as per recommendations of the applicable codes
and standards.
Minimum Scale Factor for g*I/R
Response Spectrum g=9.81 m/sec2
Analysis
Soil Profile According to the soil report recommendation.
When the soil properties are not known in sufficient detail to determine
the soil profile type, Type SD shall be used.
Mass Participation Ratio To be checked for a minimum of 90 %.
Torsional Irregularity To be calculated as per applied code, and additional eccentricity to be
applied if any.
Orthogonal Effect To be considered either by the SRSS method or X/Y direction + 30%
of Y/X direction.

Government of Ras Al Khaimah Page 15 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

Exemptions:
- Detached one and two family residential villas including the attached service blocks.
- Less than G+4 residential buildings (e.g. 4 suspended slabs).
- Single story shops with height not more than 6m and total area of complex not more than 500m2.
- G+1 shop with total height not more than 8m and total area of complex not more than 500m2.
- Up to G+1 motel (small hotels with limited number of rooms).
- Service buildings of mosques (such as ablution building, Imam house).

Commentary:
• The following typical buildings shall be designed for seismic loads regardless the number of stories
or height:
- Any building housing facilities required for emergency support.
- Hospitals.
- Fire and police stations.
- Governmental and public buildings.
- Schools and universities buildings.
- Hotels.
- Mosques and minarets.
- Churches.
- Shopping centers and hypermarkets.
- Cinemas and theaters.
- Multi-function halls (such as but not limited to ballrooms, sports’ hall, etc.).
- Commercial and office buildings.
- Multi story car parks.
- Airport’s buildings and aviation control towers.
- Buildings which have special structural systems (such as but not limited; irregular shape, long
spans, etc.).
- Industrial buildings.

• All the buildings (even if not designed for seismic) shall include proper lateral resisting system
arrangement to resist minimum magnitude of potential lateral loads.
For example; it shall include at least one of the following systems:
- Set of minimum 2 clear framing system in each principle direction.
- Shear walls in each principle direction.
- Proper core wall.

Government of Ras Al Khaimah Page 16 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

5.6.1. Seismic Scaling


• Whenever dynamic analysis is adopted; dynamic seismic load shall not be less than 100% of
equivalent static loads at the base level.
• Base level definition is the level of foundation or at which major change in stiffness occurs.
• It is allowed to ignore the seismic mass bellow the presumed base level while studying the structural
elements above the scaling level.
• Seismic scaling down is not allowed (e.g. dynamic is more than static).

5.6.2. P-delta Effects


• P-delta effects should be considered for all the buildings following UBC97 for a proper columns’
design including the slenderness effect.

5.6.3. Torsional Irregularity


• Torsional irregularity shall be considered to exist when the maximum story drift, computed including
accidental torsion, at one end of the structure transverse to an axis is more than 1.2 times the
average of the story drifts of the two ends of the structure.
• Where torsional irregularity exists, as defined in UBC97, the effects shall be accounted for by
increasing the accidental torsion at each level by an amplification factor, Ax, determined from the
following formula:

Where;
davg = the average of the displacements at the extreme points of the structure at Level x.
dmax = the maximum displacement at Level x.
The value of Ax need not exceed 3.0.

Government of Ras Al Khaimah Page 17 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

5.7. Wind Loads


The following requirements along with the requirements of the applicable code (ASCE7-05) should be
referred to when considering the technical requirements for wind load design.

Item Description

Applicable standards ASCE7-05


Wind Speed 45 m/s, 3-second gust measured at 10 meters’ height above ground level for
50 years return period (For ultimate design).
38 m/s, for 10 years return period (For serviceability check).
Exposure Category To be considered as per recommendations of the applicable codes and
standards.
Importance factor “I” To be considered as per recommendations of the applicable codes and
standards.
Directionality Factor “Kd” 0.85
Gust factor “G” To be calculated as per recommendations of the applicable codes and
standards.
Minimum value = 0.85.

Commentary and Exemptions:


• Wind load is mandatory for all steel structure buildings’ types.
• Wind load is mandatory for all reinforced concrete structure buildings more than G+15 stories.
• Wind load may be exempted for reinforced concrete structure buildings below G+15 stories
subjected to the municipality’s engineer judgment based on the building behavior (such as but not
limited to; the slenderness, building irregularity, special structural system, wind load effect governing
the design for any structural element).
• It is the consultant responsibility to investigate the requirement for wind load application on the
building before submission to the municipality.

5.7.1. Wind Tunnel Test.


• Wind tunnel test shall be conducted in the following conditions.
- Irregular, complicated, unusual structure. It shall be pre-agreed with Ras Al Khaimah
Municipality.
- Tall buildings more than 40 stories above ground.
• Wind base shear from wind tunnel test shall not be less than 80% of the calculated code wind base
shear.
• Maximum damping ratio shall be 2% for ultimate design and 1.5% for serviceability checks.

5.8. Helipad Loads


For Helipad load, ASCE7-05 requirements shall be followed in addition to the following requirements:
• Minimum live load of 5 KN/m2 to be applied.
• Concentrated loads to be applied separately with factor 1.5 to cover the impact load of the helicopter.

Government of Ras Al Khaimah Page 18 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

• The application of the helicopter concentrated load shall be studied as per the worst-case scenario in
terms of load location with reference to the slab geometry.

5.9. Minimum Lateral Forces


Each structure shall be analyzed for the effects of static lateral forces applied independently in each of
two orthogonal directions. In each direction, the static lateral forces at all levels shall be applied
simultaneously. For purposes of analysis, the force at each level shall be determined using the following
equation.
Fx = 0.01Wx
where
Fx = the design lateral force applied at story x, and
Wx = the portion of the total dead load of the structure (SW & SDL) located or assigned to level x.

Structures explicitly designed for stability, including second-order effects, shall be deemed to comply
with the requirements of this section.

5.10. Loading Combinations


• The Ultimate limit states shall be in accordance with ASCE7-05 Section 2.3.2. These Load
Combinations shall be used in the design of all structural elements. The Load Combinations
producing the most adverse load effects will be used in the design.
• The Serviceability limit states shall be in accordance with ASCE7-05 Section 2.4.1. These Load
combinations shall be used in the analysis of foundation capacities and reactions, and all the
serviceability checks such as crack width limitation. The Load Combinations producing the most
adverse load effects will be used in the design.

Government of Ras Al Khaimah Page 19 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

6. Serviceability Requirements

Adequate provisions shall be adopted to limit the deflection of structural elements and eliminate risk of
damage to non-structural elements due to vertical deflection and inter-story drift.

6.1. Control of Deflection in Concrete Elements


• Immediate and long-term deflections shall be within code accepted limits for all concrete slabs and
beams.
• Non-linear cracked sections properties and effect of shrinkage and creep shall be considered in
deflection calculations.
• Modulus of rupture should be considered as per ACI435R-95 code requirements.
fcr=0.33√fc’
• Only actual provided top and bottom reinforcement should be considered in deflection calculations.

Structural Concrete Load Combination Limit


Component Description
Vertical deflection of floor elements Total deflection (long term deflection under sustained loads L/240
not supporting brittle elements or plus immediate deflection under non-sustained loads)
facade Live L/360
Vertical deflection of floor elements Total deflection (long term deflection under sustained loads L/240
supporting brittle elements or plus immediate deflection under non-sustained loads)
facade Total deflection occurred after attachment of non-structural L/480
elements (excluding immediate deflection occurred before the
attachment of non-structural component).
Live L/360
Vertical deflection of transfer Total deflection (long term deflection under sustained loads L/750
elements (beam or slab) (**) plus immediate deflection under non-sustained loads)
Notes:
- (**) In case of excessive deflection regardless the limit is achieved; the vertical deflection shall be considered
in the design of the floors above subjected to the engineering judgment.

Government of Ras Al Khaimah Page 20 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

6.2. Control of Deflection in Steel Elements

Structural Steelwork Load Combination Limit


Component Description
Vertical deflection of floor elements Dead + Live L/240
not supporting brittle elements or Live L/360
facade
Vertical deflection of floor elements Dead + Live L/240
supporting brittle elements or Live L/360
facade
Differential Live L/500
Vertical deflection of flat roofs not Dead + Live L/180
supporting brittle elements or Live L/240
facade
Wind* L/240
Vertical deflection of flat roofs Dead + Live L/240
supporting brittle elements or Live L/360
facade
Wind* L/360
Differential Live L/500
Vertical deflection of flat roofs not Dead + Live L/120
supporting any elements Live L/180
Wind* L/180
Vertical deflection of transfer Dead + Live L/750
element (**)
Notes:
- (*) Wind load shall be 0.7x”50-year return period wind load” or “10-year return period wind load”.
- The above deflection limits do not consider pre-cambering. Pre-cambering may be used to reduce the total
deflection as deemed necessary.
- (**) In case of excessive deflection regardless the limit is achieved; the vertical deflection shall be considered
in the design of the floors above subjected to the engineering judgment.

6.3. Control of Lateral Drifts

6.3.1. Seismic Drift


Buildings’ lateral drifts under seismic loads should be checked against UBC97 code specified limits.
Structural Component Description Limit
Inelastic inter-storey drift Fundamental period > 0.7 sec Floor height (h) / 50
Fundamental period < 0.7 sec Floor height (h) / 40
• Load combination for seismic drift shall be as per ultimate load combinations including seismic load
case.

6.3.2. Wind Drift


Buildings’ lateral drifts under wind loads should be checked against ASCE7-05 code specified limits.
Structural Component Description Limit
Inter-storey drift Floor height (h) / 400
Overall building drift Building height (H) /500

Government of Ras Al Khaimah Page 21 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

• Load combination for wind drift check is D+0.5L+0.7W, where wind load (W) is based on the 50-year
return period.
• Wind Inter-story drift and overall building drift shall be limited to the standards limits (ASCE7-05) for
all the building wherever wind load is applicable.
• Wind Inter-story drift shall be considered in the design of façade and cladding system in order to be
protected as required.

6.4. Human Comfort and Vibration

6.4.1. Building Acceleration


Buildings should be designed and checked to meet human comfort of occupants as required.
Buildings accelerations shall be checked for high rise buildings for wind loads (10-year return period),
and shall be less than the following limits.

Occupancy Maximum acceleration limit


Residential and Hotels 15 mg
Offices 20 mg

6.4.2. Vertical Vibration


Vibration check is mandatory for members subjected to dynamic loadings, all thin slabs (where span to
thickness ratio is more than 42) and long cantilevers.
The susceptibility of floors to excessive vibrations due to walking excitation or equipment operation shall
be assessed according to SCI Publication P354-“Design of Floors for vibrations” or DG11-“Floor
Vibrations due to Human Activity”.

The following table provides the Vibration and Acceleration limits that shall be adopted in the design of
the structures in terms of occupancy for the building facilities.
Occupancy Acceleration Limit (%g)
Offices, Residential 0.5%
Dining, Dancing and Gym 1.5 to 2.5%
Aerobics, rhythmic activities only 4.0% to 7.0%
Shopping malls 1.5%

Government of Ras Al Khaimah Page 22 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

Alternative Approximated Approach


Vibration assessment based on the relation between natural frequency and deflection can be verified
from the following formula.
f =18 /√d(mm) for intermediate spans.
f =20 /√d(mm) for cantilevers.
Where:
- d is the maximum deflection due to loading in reference to the mass (m).
It can be considered for 100% Dead loads and 10% Live loads.
- f is the natural frequency (1/T).
- Minimum natural frequency of 4 HZ can be used as a limit for a building of normal usage (e.g.
residential, offices).

6.4.3. Other Considerations


• The consultant shall ensure for buildings with irregular façade shapes and where a potential noise
expected to occur, the tonal noise generated as part of vortex shedding mechanism shall be properly
addressed by wind specialist. The consultant is solely responsible to undertake the necessary study
and to propose any effective remedial measures to resolve the problem (if any).

• Effects of axial long term shortening due to elastic, shrinkage and creep effects shall be investigated
and accounted for in the design and construction. It is mandatory for buildings more than 40 stories.
Deferential shortening between columns shall be limited to the minimum possible in order to
minimize the impact on the horizontal elements design.

Government of Ras Al Khaimah Page 23 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

7. Structural Integrity

Buildings and other structures shall be designed to sustain local damage with the structural system as a
whole remaining stable and not being damaged to an extent disproportionate to the original local
damage. This shall be achieved through an arrangement of the structural elements that provides stability
to the entire structural system by transferring loads from any locally damaged region to adjacent regions
capable of resisting those loads without collapse. This shall be accomplished by providing sufficient
continuity, redundancy, or energy-dissipating capacity (ductility), or a combination thereof, in the
members of the structure.

7.1. Load Path Connections.


All parts of the structure between separation joints shall be interconnected to form a continuous path to
the lateral force-resisting system, and the connections shall be capable of transmitting the lateral forces
induced by the parts being connected. Any smaller portion of the structure shall be tied to the remainder
of the structure with elements having the strength to resist a force of not less than 5% of the portion’s
weight.

Government of Ras Al Khaimah Page 24 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

8. Durability Requirements

8.1. Waterproofing Requirement


Waterproofing is mandatory for all members in contact with groundwater or soil.
Any waterproofing material specifications and methodology of application should be shown on the
submitted structural drawings.

8.2. Control of Cracking


• Crack control for all parts of the structure should be satisfied following the requirements of ACI318,
ACI 224R-01 and ACI_350 codes unless otherwise noted in this clause.
• Crack control requirements are not limited to structural members subjected to ground water.
• Early thermal and long-term cracking shall be verified for concrete structural elements according to
CIRIA660-7.
Limiting cracks widths considered for different categories are presented in the following table.

Exposure condition Limiting Crack


Width (mm)
Structural elements exposed to humidity, moist air. 0.3

Structural element in contact with wet or dry soil (with or without ground water table). 0.2*
(e.g. Retaining wall’s outer face, under-side of Raft).
Water retaining structures. 0.1
(e.g. Swimming Pool, Water Tanks).
Piles in contact with wet soil and under permanent tension stresses. 0.2

Note:
- (*) unless otherwise required for deep retaining walls and foundation below ground water table.
Maximum permissible crack width for deep retaining walls and foundation below ground water table
should be defined as per the following chart.

Where:
- (hf)is the depth of the water table till the soffit of the structural element.
- (h) is the structural element thickness.

Government of Ras Al Khaimah Page 25 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

8.3. Concrete Cover


The following clear concrete covers shall be provided as a minimum for different reinforced concrete
elements unless otherwise required for fire rating and durability requirements.

Structural Element Min. Clear


Cover (mm)
Concrete for deep foundations (e.g. Piles) 75
Concrete permanently exposed to earth (e.g. Foundation and retaining wall’s outer face) 75
Raft and basement retaining wall’s internal face 50
Water tanks 50
Slabs 25
Beams 40
Ribs 25
Columns 40
Walls 30
Stairs 25
Transfer beams 50
Transfer slabs 45

8.4. Spacing Between Bars


The spacing between bars in different concrete elements shall be strictly followed as per ACI318, and
considering all the conditions related to constructability (e.g. vibrator size and proper vibration for
concrete compacting).

Government of Ras Al Khaimah Page 26 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

9. Concrete General Design Requirements

9.1. Cracking Stiffness Modifiers


All stiffness modifiers for ultimate limit state analysis should be as per ACI318 code provisions.

Beams Slabs
Element Walls Columns
RC/PT RC PT
Required Cracked 0.7Ig* 0.7Ig* 0.35Ig 0.25Ig 0.35Ig
Properties
Equivalent Stiffness m11 =0.7 I33 =0.7 I33=0.35 m11 =0.25 m11 =0.35
Modifiers in 3D m22 =0.7 I22 =0.7 I22=0.35 m22 =0.25 m22 =0.35
analysis (e.g. ETABS)
m12 =0.7 T =0.7 T =0.35*** m12 =0.25 m12 =0.35
f11 =0.7 f11 =0.25 f11 =0.35
f22 =0.7 f22 =0.25 f22 =0.35
f12 =0.7 f12 =0.25 f12 =0.35
Equivalent Stiffness m11 =1.0 I33 =1.0 I33 =1.0 m11 =1.0 N.A.
Modifiers in 2D slab m22 =1.0 I22 =1.0 I22 =1.0 m22 =1.0
analysis (e.g. SAFE)
m12 =1.0 T =1.0 T =0.1 m12 =1.0
f11 =1.0 f11 =1.0**
f22 =1.0 f22 =1.0**
f12 =1.0 f12 =1.0**
Notes:
- Where “m” is the flexural stiffness of shell elements, “f” is the membrane axial stiffness of shell
elements, “I” is the inertia of frame elements and “T” is the torsional stiffness of frame elements.
- (*) Columns and walls cracking modifiers can be used 0.35 if proved by calculation that it is
further cracked as per ACI318.
- Cracking modifiers of retaining walls can be reduced to f=m=0.35.
- (**) Membrane cracking modifiers in slab’s 2D model (f11,f22,f12) during thermal analysis can be
reduced to 0.25 for reinforced concrete slabs.
- (***) Torsional modifiers can be further reduced for compatibility torsion only. Beam should be
designed to resist a minimum torsional moment equal to the code cracking torque (Tcr).
- Stiffness modifiers of transfer beams can be used as 1.0.

For service analysis models used for wind lateral drifts calculations, stiffness modifiers can be calculated
by multiplying the ultimate reduced stiffnesses into 1.4 as per ACI318 code provisions.

Government of Ras Al Khaimah Page 27 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

9.2. Columns and Walls


• Columns shall be detailed as per Intermediate moment resistance frame requirements.
• Columns and walls shall satisfy the slenderness requirements of compression members as per
ACI318.
• Moment magnification factor (dsn) for columns and walls shall not exceed 1.4.
• Column minimum longitudinal reinforcement shall not be less than 1% of column’s cross section.
• Column maximum longitudinal reinforcement shall not be more than 8% of column’s cross section at
splice location.
• Wall minimum longitudinal reinforcement shall not be less than 0.4% of wall’s cross section.
• If columns and walls’ longitudinal reinforcement ratio is more than 4% (at the location other than
splices’ locations) mechanical couplers shall be used at splice locations.
• Mechanical couplers shall be used if spliced bar size is more than T32.

9.3. Beams
• Beams shall be detailed as per Intermediate moment resistance frame requirements. This is not
applicable for coupling beams, coupling beams need to follow requirements of ACI318-11, clause
21.9.
• For beams subjected to equilibrium torsion, no torsion redistribution is allowed.
• For beams subjected to compatibility torsion only. Beam should be designed to resist a minimum
torsional moment equal to the code cracking torque (Tcr).
• Beams shall be checked for long-term deflection limits.
• Mechanical couplers shall be used if spliced bar size is more than T32.

9.4. Slabs
• Slabs shall be designed for combined effect of gravity and self-straining action loads where
applicable.
• Slabs shall be designed for combined effect of gravity and lateral loads (seismic or wind) where
applicable.
• Slabs shall be checked for punching shear stresses due to combined effect of shear and unbalanced
moment together as applicable.
• Punching shear shall be checked so that the ratio between the applied shear (actual) and the
allowable concrete shear (without shear links) is not more than 0.9 due to pure gravity load
combination, and not more than 1.0 for other load cases.
If the ratio exceeds the mentioned limits above but not more than the maximum allowable limit
(concrete with shear links); shear links shall be provided.
• Slabs shall be checked for long-term deflection limits considering cracking non-linear analysis,
defined modulus of rapture and reinforcement as per clause 6.1.
• For non-monolithically construction between slab and vertical elements; the consultant shall ensure
that the slab is checked for shear friction resistance at the connections’ location.
• Concrete grade (fc’) of columns/walls shall not be more than 1.4 times the concrete grade of slab.
Otherwise the precautions of ACI318 shall be followed.

Government of Ras Al Khaimah Page 28 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

Figure 9-1: Column / Beam Connection Detail

Government of Ras Al Khaimah Page 29 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

9.5. Transfer Beams and Transfer Slabs


• Transfer beams are to be supported on at least two direct supports till the foundation.
• The eccentricity of the planted column axis relative to that of the longitudinal axis of the beam is not
permitted unless properly calculated.
• The gravity load transferred through the planted column to the transfer element should not be less
than the loads calculated by manual method (tributary area).
• Transfer element deflection shall be limited to the minimum possible to ensure minimum additional
deflection impact on the slabs/beams above which are supported by planted column.
• Transfer elements and the element supporting them shall be designed for special seismic load
combination including seismic over strength factor.
• Construction sequence analysis should be performed wherever deemed required.
• Reinforcement should be detailed to ensure robustness by means of provision of adequate
peripheral, vertical and horizontal ties.

9.6. Structural Movement Joints


• In case thermal analysis is not taken into consideration for concrete structures; movement joints shall
be provided between the parts of the concrete building with lengths exceeding 50m.
• These joints are designed and executed in the super structure of the building only and not allowed
within the basement retaining walls and foundation.
• The width of the expansion joints shall be calculated between the two masses of the building
according to UBC97 clause 1633.2.11.
• Expansion joints are used in fences at spacing not more than 15 m of fence length.

9.7. Additional Control Measures for Below Grade Construction


• Control of shrinkage and early age thermal stresses by applying limitations on the design and
specification of the concrete mix, including minimization of Portland cement content and substitution
by fly ash or blast-furnace slag and silica fume.
• Selection of coarse aggregate with a (verified) low coefficient of thermal expansion.
• Control of on peak concrete temperature and temperature difference across the section during
placing and early age curing, including appropriate site monitoring.
• Design of shrinkage and temperature control reinforcement, determined by analysis of the type of
concrete used, restraint conditions expected and effect of local geometrical constraints.
• Limitations on concrete pour sizes and timing between pours.
• Design for thermal loads and considering its impact on deferent structural elements
• Specification of infill strip joints (late pour strips) at agreed locations by the consultant and cast circa
45 days after the concrete structures either side.

Government of Ras Al Khaimah Page 30 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

10. Foundation

10.1. General Requirements


• The presence of soil investigation report is mandatory to execute the design of the foundation and to
conclude all the relevant foundation recommendations.
• Soil investigation report shall be carried out by competent and accredited geotechnical specialist.
• Foundation type shall be as per the soil investigation report’s recommendation.
• Foundation level should not be shallower than the geotechnical foundation level recommended by
soil investigation report.
• Foundation level should be in compliance with the architectural levels and service requirements.
• The weight of foundations, soil filling weight above foundation shall be considered when calculating
the design load. Soil filling can be only ignored if the specified allowable bearing pressure by soil
investigation report is the net bearing pressure.
• The effect of uplifting in the sub-structure shall be considered in the design and stability checks of
foundation.
• Raft of deep basements below ground water table shall be designed properly to resist the resultant
hydrostatic pressure due to water uplift load.
• The foundations of buildings or boundary walls are not permitted outside the boundaries of the plot.
• Boundaries of the plot shall be shown in the Foundation, Basement, and Ground Floor plans.
• The foundation of the fences shall be designed and implemented from all sides as a strip foundation
with at least 800 mm below ground level.
• The bases of columns/walls shall be simulated as per the following criteria unless further detailed
scheme is studied to simulate the foundation/soil interaction.

Foundation type Base simulation


Pile caps Fixed
Raft (shallow / on piles) Fixed
Isolated / combined footings Hinged
Isolated / combined footings which are mandatory to be simulated as fixed Fixed
base for the super structure’ stability

Government of Ras Al Khaimah Page 31 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

10.2. Shallow Foundation


• Shallow foundation shall be sized and designed according to the recommended allowable bearing
pressure as per soil investigation report.
• Allowable bearing pressure shall correspond to maximum settlement of 25mm for isolated footings
and 50mm for raft unless otherwise agreed before the design of the project.
• The foundations shall be constructed under the natural ground level sufficiently to achieve stability
and shall be protected from soil erosion and moisture changes resulting from climatic and thermal
conditions, provided that the foundation level shall not be less than 1000 mm below road level.
• Soil stiffness shall be simulated in the foundation Finite Element Analysis (FEA) model as area
springs (based on specified subgrade modulus), the subgrade modulus shall be clearly defined in the
soil investigation report.
• Shallow foundation shall satisfy both structural design including flexural, one-way shear, punching,
and stability requirements (e.g. Overturning, Sliding, Uplift).
• Shallow foundations shall satisfy crack width requirements as required.
• Punching reinforcement is not allowed in isolated and combined footings.
• Raft occupying big area shall be checked for early thermal and long-term thermal cracking.

10.2.1. Foundations on/or adjacent to slopes


The placement of buildings and structures on or adjacent to slopes steeper than 1V:3H (33.3% slope)
shall comply with the requirements of IBC2009, Sections 1808.7.1 through 1808.7.5.

10.2.1.1. Building clearance from ascending slopes


In general, buildings below slopes shall be set a sufficient distance from the slope to provide protection
from slope drainage, erosion and shallow failures. Except as provided in Figure 10-1, the following
criteria will be assumed to provide this protection. Where the existing slope is steeper than 1V:1H (100%
slope), the toe of the slope shall be assumed to be at the intersection of a horizontal plane drawn from
the top of the foundation and a plane drawn tangent to the slope at an angle of 45o to the horizontal.
Where a retaining wall is constructed at the toe of the slope, the height of the slope shall be measured
from the top of the wall to the top of the slope.

10.2.1.2. Foundation setback from descending slope surface.


Foundations on or adjacent to slope surfaces shall be founded in firm material with an embedment and
set back from the slope surface sufficient to provide vertical and lateral support for the foundation without
detrimental settlement. Except as provided in the previous Section and Figure 10-1, the following
setback is deemed adequate to meet the criteria. Where the slope is steeper than 1:1 (100-percent
slope), the required setback shall be measured from an imaginary plane 45 degrees to the horizontal,
projected upward from the toe of the slope.

Figure10-1: Foundation Clearances from Slops

Government of Ras Al Khaimah Page 32 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

Figure 10-2: Explanatory figures for clause 10.2.1

10.3. Retaining Walls


• The retaining walls shall be reinforced concrete, taking into account any recommendations of the
reinforced concrete adjacent to the soil such as cement type, concrete cover, water proofing and
crack width limitation.
• It is mandatory to have retaining wall structure when the difference in level between the plot and
adjacent plots/ roads and sikas is 1.50m or more. Retaining wall may be required even if the
difference in level is less than 1.5 meters if the municipality deems it necessary
• It is the responsibility of the consultant to investigate, collect and submit all the necessary
information, the information shall include (but not limited to); affection plan and different level
certificate which are mandatory for defining the requirements for retaining walls.
• The requirements for retaining walls shall be clearly defined at the early stage of the design and shall
be properly coordinated with the main building foundation.
• Retaining walls shall be designed for the combination of lateral loads due to earth pressure,
surcharge loads, ground water load, backfilled loads and gravity loads. Soil lateral loads shall follow
clause 5.3.
• The retaining wall shall be designed to resist sliding and overturning with safety factors not less than
(1.5). The bearing pressure below the retaining wall’s foundation shall be within the allowable
bearing pressure and considering the eccentric loading condition.
• The most critical loads’ combination shall be considered in the stability checks of retaining walls (e.g.
with/without surcharge loads).
• The thickness of the retaining wall shall be at least 250 mm, and the thickness at the bottom shall be
sufficient to resist the resultant shear and flexural, as a result of the most critical loading case.
• Long retaining walls shall be checked for early thermal and long-term thermal cracking.

Government of Ras Al Khaimah Page 33 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

10.4. Deep Foundation (Piles)


10.4.1. General Requirements
• It is not permitted to use the (driven piles) method to execute the piles. If this method is used in the
foundations, prior approval should be obtained from the municipality.
• Piles shall be sized and designed according to the recommended geotechnical piles’ capacity as per
soil investigation report.
• Piles should be designed to resist all loads (vertical and lateral) transferred from foundation element.
• Axial compressive working stresses on piles should not exceed 0.30.fc’.
• Design lateral shear force should be as per calculations, but not to be less than 5% of the vertical
load on the pile.
• Curtailment of longitudinal pile’s reinforcement shall follow the resultant ultimate bending moment
profile along the pile.
• Shear reinforcement of piles shall be designed according to the ultimate resultant shear force profile
along the pile.
• Shear design of the pile shall account for the effect of the corresponding axial force on the pile (e.g.
tension).
• Circular section of pile shall be considered as an equivalent rectangular section for shear design
purpose as follows:
- Depth (d)=0.8xDiameter (D).
- Width (bw) = D.

• Pile’s reinforcement shall follow the following minimum requirements.


Longitudinal Minimum bar diameter 16mm
Reinforcement Minimum reinforcement 0.5% of pile’s cross section area
Requirements
Extend of reinforcements Longitudinal reinforcing should continue at least with the
minimum percentage for the full length of the pile.
Ties Minimum bar diameter of ties 10mm
Requirements Maximum spacing (Smax) of Within distance Lo from 8 times of longitudinal
ties foundation soffit. bar diameter,
Where Lo = 3 times pile and not more than
diameter. 150mm
Outside distance Lo 12 times of longitudinal
bar diameter,
and not more than
200mm

• Piles stiffness shall be simulated in the foundation Finite Element Analysis (FEA) model as point
springs (vertical and horizontal), the point springs shall be clearly defined in the soil investigation
report. In the absence of horizontal pile stiffness information; it shall not be less than 10% of vertical
pile stiffness.
• The pile diameter shall be selected to satisfy structural requirements of flexural and shear before
executing the final pile design by piling specialist.
• Structural design of piles shall consider the following allowable tolerances’ effects:
- Moment due to allowable eccentricity of 75mm.
- Lateral load due to allowable out of plumb 1:75.

Government of Ras Al Khaimah Page 34 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

• Design lateral load of the pile shall be the resultant of both X and Y directions of the same load case.
• Piles shall be designed structurally as fixed head piles as long as the pile cap is restrained in both
directions.
• Spacing between center of piles shall not be less than 2.5 times pile diameter.
• For bored cast-in-situ piles, settlements of the order of 1% of the pile diameter is normally required to
mobilize full skin friction whereas full bearing is developed at much higher settlements (usually at
10% of pile diameter). Therefore, it is highly recommended that the pile capacity shall be based on
full skin friction and minimum partial end bearing.
• The contractor shall submit the as-built of piles after finishing piling construction to the consultant.
The consultant is responsible to ensure that all the piles are executed within the allowable tolerance.
if any of the piles are exceeding the tolerance, then it is the responsibility of the consultant to verify
the impact of the deviated setting-out of piles on the foundation and/or piles design.
It is the sole right of the municipality to request the as-built of the piles for verification whenever
deemed required.

10.4.2. Pile tests


• The necessary tests for the endurance and quality of piles should be carried out.
• The tests shall be submitted to the inspection Engineer of the municipality prior to casting the
foundations, results shall be verified to ensure that they conform to the technical specifications and
standards.
• The following are minimum tests requirements for piling works approval.

Pile Test Minimum percentage of piles


Integrity 100%
Dynamic load (load test magnitude 150% of working load) 5%
Static load (load test magnitude 150% of working load) 1%
& Minimum one pile of each pile type
Sonic (recommended for dimeter more than 750mm) 10%

10.4.3. Piling Package by the Consultant


Piling package by the structural consultant shall present the following information in the piling package.

• Structural calculations and analysis models to demonstrate the piles loads.


• Preliminary structural drawings to demonstrate the overall structural feasibility and piles’ loads.
• Piles’ layout drawings showing piles’ arrangement, setting-out and piles’ types.
• Piles’ general notes drawings covering but not limited to:
- Piles’ concrete and reinforcement grade.
- Concrete cover.
- Piles tests’ types and failure criteria.
• Piles’ schedule covering the following information:
- Pile type (legend).
- Pile diameter.
- Number of piles within each type.
- Pile cutoff level.
- Pile tentative toe level (to be verified by piling specialist during the piling specialist submission).

Government of Ras Al Khaimah Page 35 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

- Pile’s working loads


- Maximum Compression load and corresponding lateral loads from same load case.
- Maximum Tension load and corresponding lateral loads (if any).
- Number or percentage of tests for each pile’s type.

Recommended sample for piling schedule:


Pile Pile Working Loads (KN) Piles Test Quantity
Diame Cut off Toe
Pile Pile Number level level Case 1 Case 2
ter Working Dynamic Integrity Sonic
Type Legend of piles Maximum Maximum
(mm) (m) (m) Lateral Lateral load test tests tests tests
Compression Tension
P1 O 100 750 -1.00 -15.00 +3000 150 -500 100 1% 5% 100% 10%
P2
P3
Total Number
Note: The consultant can specify more load cases if deemed required.

10.4.4. Piling Package by the Piling Contractor


• Final piles’ design shall be done by a licensed piling specialist. The design shall be based upon the
piling reaction schedule prepared by the consultant and the soil investigation report information
provided.
• Piling specialist shall present piles’ information in a form of piles layout and schedule similar to the
consultant presented information in addition to the followings;
- Toe level confirmed based on the specialist’s design and/or verification.
- Piles’ full reinforcement details.
• Geotechnical and structural design calculations of piles.
• Soil investigation report.

10.4.5. Pile Caps Requirements


• Pile cap shall satisfy structural design including flexural, one-way shear and punching.
CRSI 2015 can be referred for one-way shear whenever deep action is satisfied.
• Punching reinforcement is not allowed in pile caps.
• Pile caps shall be restrained to ensure no moment transferred to the piles.
- Single pile cap must be restrained in the two main directions.
- Piles cap having two or more aligned piles must be restrained in the perpendicular direction to
these piles.
• The pile cap restraining can be satisfied by tie beams or connecting slab.
• Minimum clear edge distance between face of pile and pile cap edge shall not be less than 250mm.
• The pile cap bottom cover to be considered in the ultimate design shall not be less than 125mm.
• The depth of pile cap shall be properly coordinated by the consultant to ensure the sufficient depth
for the development detail of pile longitudinal reinforcement.

Government of Ras Al Khaimah Page 36 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

Figure 10-3: Pile reinforcement development details within pile cap

Government of Ras Al Khaimah Page 37 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

11. Pre-Stressed Concrete

• The current pre-stressed guidelines are relevant to the post tensioning bonded systems only,
whereas the other pre-stressed systems shall be submitted for review and approval prior to work.
• The post tension structural elements shall be designed and executed by a specialized company in
this field.
• The post tension elements shall be designed by a qualified engineer who is approved by the
Competent Department.
• It is the consultant responsibility to communicate the approved loading criteria and loading plans to
the post tension specialist.
• The structural calculation shall be submitted according to approved engineering software, in addition
to the detailed drawings of the elements used, according to the international codes, with the stamp of
the Consultant and the post tension specialist.
• All material shall be approved by the Consultant prior to commencement of execution and
installation.
• Unless otherwise required by the design, the general requirements below shall be complied with
according to the directions of the Ras Al Khaimah Municipality.

11.1. General Design Requirements


• The minimum thickness of the pre-stressed concrete slab shall be at least (Span/40) and not less
than 200mm. For any further deviation from these limits; vibration shall be properly analyzed by the
post tension specialist and verified by the consultant.
• Structural calculations shall verify both short term and long-term deflection, camber and vibration are
within the permissible limits.
• Temperature and lateral loads analysis should be done using 3D building model, and the resultant
forces shall be considered in addition to the gravity loads from the pre-stressed analysis.
• Cubic strength for the concrete used in pre-stressed slabs shall not be less than 40 N/mm2.
• Concrete cover shall comply with durability or fire resistance requirements, whichever condition is the
more onerous. The cover shall be measured to the outside surface of the duct; the minimum net
cover for bonded system shall be 35 mm.
• The spacing between the ducts shall not exceed 1500mm. or 8 times the slab thickness whichever is
less.
• All columns within flat slab system should be checked for punching shear as per the identified code.
• The uplift Force resulting from tension cables shall not exceed (0.6-0.9) of self-weight (according to
ACI code recommendations). This limit can be waived considering that top reinforcement to be
provided in the mid span as per code requirements.
• Tension shall be made from both sides if the length of the cable is greater than 35m.
• The ducts surrounding the cables shall be of a bonded duct, where the cables shall be covered with
a certified grouting material.
• Rectangular spiral stirrups can be added in tension areas, not less than 6 laps of 12 mm diameter.
• Pan ducts for tension shall be performed if the cable track runs past the columns to prevent any extra
non-considerable overshoots in the design of the columns.
• The cable routing shall be set by metal supports installed in the metal scaffolding, the dimension
among them shall not exceed one meter.
• The locations of the cables shall be clearly indicated on the pre-stressed concrete slabs.

Government of Ras Al Khaimah Page 38 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

• The number of sample cubes taken for testing from casted concrete shall be at least 6 for each 50
cubic meters. Tests shall be scheduled according to the approved code.

11.2. Serviceability Requirements-Flexural Members


Design for serviceability requirements of members shall comply with ACI318 or Technical Report No.43-
Euro Code.

11.3. Permissible Stresses in Pre-Stressing Steel


Case Maximum limit
Jacking force for post tension elements 0.75 fpu
Post-tensioning tendons immediately after tendon anchorage 0.70 fpu

11.4. Pre-Compression Stresses


• For slabs with varying cross section along the slab span, either parallel or perpendicular to the tendon
or tendon group, the minimum average effective pre-compression stresses of 0.9 MPa is required at
every cross-section tributary to the tendon or tendon group along the span.
Pre-compression of 0.9 MPa shall be used if the prestressing is used to address the punching shear
of lightly reinforced slabs, otherwise, 0.7 MPa may be maintained as a minimum pre-compression.
• If the average pre-compression stresses exceed 3.0 MPa, the design engineer shall explicitly
recognize and account for the consequence of shortening of the member in connection with the
restraint of the member’s supports.

11.5. Minimum Bonded Reinforcement


11.5.1. Bottom Reinforcement.
• Minimum area of bonded reinforcement shall be As=0.004Act.
• In positive moment areas, minimum length of bonded reinforcement shall be one-third the clear span
length, ln, and centered in positive moment area.
• Bottom steel at columns and support locations should be not less than 30% of the top steel at the
same location and not less than the requirements of lateral loads analysis.
• Moreover, the slab shall be provided with a bottom reinforcement mesh not less than T10-250.

11.5.2. Top Reinforcement.


• All support areas shall have the applicable code specified minimum reinforcement in the top for
purpose of distributing the cracks and strength design requirements.
• Minimum area of bonded reinforcement in the negative moment zone at column supports shall be
As=0.00075Acf.
Where Acf is the larger gross cross-sectional area of the slab-beam strips in two orthogonal
equivalent frames intersecting at a column in a two-way slab.
• In negative moment areas, bonded reinforcement shall extend one-sixth the clear span on each side
of support.
• The slab shall be provided with a top reinforcement mesh not less than T10-250 for slab thickness
more than or equal 300mm.

Government of Ras Al Khaimah Page 39 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

• Moreover; the slab reinforcement shall be provided wherever deemed required for lateral and
different thermal effects.

11.6. Reinforcement Detailing


11.6.1. Edge Reinforcement
• Un-tensioned reinforcement should be placed along edges of all slabs. This should include U-bars
laced with at least two longitudinal bars top and bottom.

Fig.: Reinforcement layout at the edge of a slab.

11.6.2. Reinforcement Between Tendon Anchorages


• The slab zone between tendon anchorages requires reinforcement to span the unstressed zones.
Any prestressed tendons that pass through this zone, parallel to the slab edge, may be included with
the relevant reinforcement, provided it is in the local tension zone.
• The area of tension reinforcement (and/or prestressed tendons) provided parallel to the slab edge
should resist bending moments from the ultimate vertical loads calculated for a continuous slab
spanning la. This reinforcement should be evenly distributed across a width equal to 0.7la, and should
be continuous along the edge.
• The area of reinforcement placed perpendicular to the slab edge should be the greater of 0.13% bh,
or a quarter of the reinforcement provided parallel to the edge. It should be placed evenly between
anchorages, and extend the greater of la or 0.7la plus a full anchorage length into the slab.

Fig.: Unstressed areas of slab edges between tendons requiring reinforcement

Government of Ras Al Khaimah Page 40 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

• For situations where it is not practically possible to place the prestressing tendons within 0.5h from
the column, reinforcement should be placed to bridge the vertical force from the adjacent tendon to
the columns as shown. The reinforcement should:
- Be placed under the prestressing tendon.
- Have sufficient area to transmit the vertical component of prestressing for that tendon to the
column extend a full anchorage length beyond the tendon lie within 0.5h of the column and at
least one bar should pass over the column.
Where “h” is section depth.

Fig.: Additional reinforcement required where tendons are not within 0.5h from the column

Government of Ras Al Khaimah Page 41 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

12. Steel Structures

12.1. General requirements


• Steel structure buildings shall be designed by a specialist in terms of design and execution
experience.
• The structural design of steel buildings shall be prepared by a qualified structural engineer licensed
to practice the profession and approved by the municipality.
• The detailed design calculations shall be submitted using approved analysis software in addition to
the detailed shop drawing for the various steel elements, with the stamp of the consultant and the
steel contractor.
• Maximum capacity ratio of all steel elements under the maximum effect of design load and its
combination should not exceed 95%.
• All the requirements and limitations of both ultimate and service limit status should be satisfied
according to the design code.
• Design shall include all limit states in addition to the limit states of strength and serviceability as
follows:
- Strength limit states including general yielding, rupture, yielding, buckling and transformation into
a mechanism.
- Serviceability limit states
- Stability against overturning & sway.
- Fracture due to fatigue and brittle fracture.
- Corrosion and durability.
• In order to ensure the durability of the structure under conditions relevant both to its intended use
and to its intended life, the following factors should be considered in design:
- Environment around the structure and the degree of exposure.
- Shape of the members and structural detailing.
- Protective coatings.
- Whether inspection and maintenance are possible.
• All steelwork exposed to the external environment shall be either hot dipped galvanized or will have a
suitable paint system to protect against corrosion in compliance with minimum client requirements.
• The proper fire rating for steel elements shall be achieved by proper coating thickness of
cementitious or intumescent materials.

12.2. Structural Integrity


• All buildings shall be effectively tied together at each principal floor level.
• Each column shall be effectively held in position by means of horizontal ties in two directions,
approximately at right angles, at each principal floor level supported by that column.
• Horizontal ties shall be provided at roof level, except where the steelwork only supports cladding that
weighs not more than 0.7 KN/m2 and that carries only imposed roof loads and wind loads.
• Continuous lines of ties should be arranged as close as practicable to the edges of the floor or roof
and to each column line. Ties designed and provided as shown in following figures are acceptable.
• All horizontal ties, and all other horizontal members, should be capable of resisting a factored tensile
load, which should not be considered as additive to other loads, of not less than 75 KN.

Government of Ras Al Khaimah Page 42 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

• Each portion of a building between expansion joints shall be treated as a separate building.
• For special buildings where it is stipulated to be designed to avoid disproportionate collapse, all
requirements with regard to tying of columns, continuity of columns, resistance to horizontal forces,
notional removal of column, accidental loading and key element design etc. shall be carefully studied
and designed as required by the relevant sections of codes.

Fig.: Tying of columns

Government of Ras Al Khaimah Page 43 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

13. Geotechnical and Soil Investigation

13.1. Boreholes and Site Testing


13.1.1. Boreholes Number
• For single small plot of less than 1600m2; it shall be minimum 2 boreholes.
• For moderate plots; it can be one borehole for each 750-1000m2 and not less than 3 boreholes.
• For plots of large area; the exploration points may be placed in a grid. The mutual distance between
the boreholes points that considered an appropriate for structures should normally be 30-50 m.
• Where a certain project consists of a number of adjacent units, one exploration point per unit may
suffice if the data of the boreholes have shown a uniform soil formation.
• In uniform soil conditions, the borings or excavation pits may be partially replaced by penetration
tests or geophysical survey. (B.S.5930-1999).
• For structures which have main core walls as part of the structural system; at least single borehole
shall be located below the core.

13.1.2. Boreholes Depth


• The boreholes, penetration tests or other site tests should normally be performed to explore the
ground conditions to such depth to ensure the design certainty of foundation, and should be
undertaken below all layers that may be unsuitable for foundations purposes (e.g. made ground and
weak compressible soils, including weak strata overlaid by a layer of higher bearing capacity). If rock
is found, a penetration of at least 3.00 m in more than one borehole may be required to establish
whether bedrock or a boulder has been encountered.
• For shallow foundation; the depth of boreholes below the anticipated foundation level shall be 2-3
times the width of the foundation element.
• For deep foundation; the depth of the borehole shall be taken below the anticipated pile toe level as
5 times the pile diameter or 5m whichever is greater.
• Minimum depth of borehole shall not be less than 8m.
• The greater the natural variability of the soil condition, the greater the extent of the ground
investigation required to obtain a confident indication of the soil characteristics to establish the
overall foundation design.
• The data from boreholes should be recorded and analyzed by qualified and experienced
geotechnical engineer.
• Boreholes should be carefully backfilled, concreted or grouted up. Trial pits should be outside the
proposed foundation areas.

Government of Ras Al Khaimah Page 44 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

13.1.3. Soil Investigation Report


• Soil investigation tests is required for all types of buildings without exception, and a special report by
a licensed soil testing laboratory in Ras Al Khaimah should be conducted exclusively.
• All laboratories employed for soil investigation purposes must be licensed, approved and accredited
by Ras Al Khaimah Municipality. Certified laboratories from other emirates might be allowed
subjected to advance approval of Ras Al Khaimah Municipality.
The appointed laboratory shall conduct soil investigations in strict adherence to the procedures and
recommendations as illustrated in the international codes and Ras Al Khaimah Municipality
guidelines during the soil investigation operation, with proper sampling and extraction materials.
• All soil reports shall be stamped and signed by a professional geotechnical engineer.
• Soil investigation report shall be mainly based upon specific location with specified coordinates as
per affection plan and geographical maps from the concerned authority. It shall also relevant to the
information about magnitude of superimposed loads, number of floors, land use history, surface
topography, geological features and surface drainage.

13.1.4. Information to be Included in the Soil Investigation Report


The soil investigation report shall include (but not limited to) the following information. However;
geotechnical specialist is responsible to provide any further information deemed required based on the
site and project condition.

• Overall site description and location.


• Plan showing boreholes’ location and levels referred to site map.
• Laboratory testing results.
• Sub surface condition profile, based on boring and showing a cross-sectional view of all boreholes.
• Water table levels.
• Presence of cavities.
• Liquefaction risk study (if applicable).
• Complete borehole logs showing detailed records of soil strata, soil classification, ground water level,
SPT, RQD, TCR and SCR values at different levels.
• Filed tests results such as;
- Standard penetration test (SPT) results.
- In-situ Permeability test results.
- Pressuremeter test results.
- Cone penetration test (CPT) results.
- Down Hole test Report.
- Groundwater readings from Installed standpipe piezometers.
• Laboratory tests results such as;
- Physical / Mechanical and Index properties results.
- Compaction related test results.
- Chemical testing results.
- Shear Strength test results.
- Uniaxial compressive strength (UCS) test results.
- Direct shear test results.
- Permeability of the soil for different layers.
• Photographs of cores’ samples.

Government of Ras Al Khaimah Page 45 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

13.1.5. Recommendation to be Included in the Soil Investigation Report


The soil investigation report shall include (but not limited to) the following recommendations. However;
geotechnical specialist is responsible to provide any further recommendation deemed required based on
the site and project condition.

• Shallow foundation recommendation including allowable bearing pressure (stating clearly if gross or
net) and subgrade modulus and foundation level.
Noting that the safety factor for soil bearing capacity shall be at least 3.0 for permanent structures,
and 2.0 for temporary structures.
• Deep foundation recommendation including piles geotechnical capacities in compression and
tension, and pile point stiffness (vertical and lateral).
Noting that the safety factor for piles shall be at least 2.5 for both compression and tension.
• Open excavation recommendations including but not limited to allowable slopes’ recommendations.
• Shoring recommendations for deep excavation including soil parameters required for shoring design
such as average bulk density, angle of shearing resistance, cohesion, coefficient of active, passive
and at-rest pressure for different layers of soil profile.
• Dewatering recommendations if ground water table is encountered including the permeability of the
different soil layers.
• Soil seismic classification based on top 30m of soil strata and matching with UBC97 classification.
• Recommendation on the earth work, excavation, filling and compaction.
• Recommendations for suitability of site material to be used as fill material.
• Cement recommendation based on the chemical results of soil and ground water.
• Soil improvement recommendations and methodology (if applicable).
• Liquefaction risk study recommendation (if applicable).
• Any recommendation regarding problematic soil (if applicable).

Government of Ras Al Khaimah Page 46 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

14. Enabling Works

14.1. Open Excavation


• Angle of inclination for all open excavations should be as reported in soil investigation report but not
more than 30 degrees. In some cases where high ground water table is encountered, a lower angle
might be required to maintain safety of slopes.
• In case of high ground water table above target excavation level, dewatering shall be executed
before starting excavation and dewatered level shall be at least 1.0 m below the target excavation
level.
• Open cut excavations are not allowed along the plot boundaries unless a No Objection Certificate is
encountered from the municipality and/or adjacent plot owner.
• All precautions should be considered for ensuring stability and safety of slopes for any open
excavation.
• All existing utilities shall be protected at all times during excavation and construction.

14.2. Backfill Materials and Compaction


• The material used for backfilling purpose shall be of selected fill composed of sand/granular mixture
free from organic materials or other deteriorates substances. The geotechnical specialist must state
whether the material available in site could be used for general backfilling or not after performing the
necessary analysis.
• The backfill materials shall be placed in layers of thickness 150mm to 250 mm and to be compacted
to not less than 95% of the maximum dry density.
• Sand cone test may be carried out to determine the degree of compaction.
• The plate load test (as per ASTM D1195/D1195M– 09) also is an acceptable test where the
allowable bearing capacity corresponds to the allowable settlement will be confirmed.

14.3. Shoring
• Shoring systems are allowed to be used as a temporary retaining structure to retain soil at
construction sites peripheries.
• Shoring system is mandatory for any sharp excavation deeper than 1.50 meters.
• Shoring system is not allowed to be extended outside the plot boundaries without prior approval from
the municipality and other relevant authorities.
• Ground tie back anchors should be avoided in neighboring plots unless a Non-Objection Certificate
(NOC) is encountered from the municipality and adjacent plot owner.
• Ground tie back anchors in public properties (roads, sikkas, etc.…) is subject to the approval of
authorities (municipality, electricity company, telephone company and water company).
• Shoring system should be designed according to height of retained soil and all different construction
cases conditions.
• Shoring system should be designed assuming extra unplanned excavation of minimum depth 0.50m.
• Shoring system shall take into consideration the ground water level and the water tightness
requirement during excavation. In the presence of ground water table above excavation level; It shall
be proper water tight shoring system (such as secant piles, diaphragm wall or sheet piles).
• All shoring works shall be continuously monitored by the contractor and consultant. If any corrective
action required during construction shall be approved by the municipality prior to execution.

Government of Ras Al Khaimah Page 47 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

• Surcharge loads should be considered with minimum value of 20KN/m2.


In case of adjacent structures, the resulting lateral and vertical reactions of the neighboring structure
should be considered if found more than the specified minimum surcharge.
• Cantilever soldier piles shoring system (steel beams with precast panels) is allowed up to 5m deep
excavation only. Any other requirements shall be approved in advance by the municipality.
• All existing utilities shall be protected at all times during excavation and construction.
• Shoring zone shall consider proper allowance between the shoring and the basement retaining wall
to account for water proofing, construction tolerance and allowable deflection.
• The allowable maximum deflection of shoring shall not be more than 30mm adjacent to roads.

14.4. Submission Methods for Excavation and Shoring Permit


The consultant may apply for the excavation and shoring permit through one of the following two
methods:

14.4.1. Method A
Applying for excavation and shoring permit before obtaining a building permit as follows:
The shoring permit can be independent from the building permit submission or can part of excavation
and site preparation permit of the project. The permit shall be handed to the shoring contractor after the
approval of the shoring drawings submitted by him, and obtain preliminary approval of the submitted
drawings and enclose the necessary commitments.

14.4.2. Method B
The shoring permit can be submitted as a part of building permit submission at the final stage of the
project, where the shoring drawings are submitted along with the final structural drawings and the
consultant undertakes to make the necessary modifications to the project’s drawings according to the
conditional approval and final requirements of the NOCs. The permit issuing will be conditional in this
case till the appointment of the shoring contractor, and the issuing of the final construction drawings for
the project.

Government of Ras Al Khaimah Page 48 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

14.5. Required Documents for Excavation and Shoring Permit


• The general site plan of the plot with complete details of the surroundings in terms of buildings and
its heights, distance from plot boundaries, adjacent foundations’ type and number of basements (if
any).
• The type of the structural system of the shoring and the design of the system to ensure its safety and
feasibility.
• Structural sections through the shoring showing the followings;
- Excavation depth from natural ground level and the adjacent roads,
- Any other nearby facilities.
- Level of additional local excavation due to water tanks, lift pits or any other facilities below the
basement level.
- Gap allowance between shoring inner face and basement wall face for construction tolerance
and water proofing allowance.
- Ground water table level.
• Full details of strutting system and/or anchoring system.
• In all case, “No Objection Certificates” shall be obtained from the department of Sewage, Electricity,
Water and Telecommunication or any other authorities with the commitment to comply with their
requirements and attach it in the documents.
• Full coordination shall be carried on between relevant architectural, structural and shoring drawings.
• The shoring contractor shall provide a valid license to carry out the required activity before assigning
the work to him.
• Soil investigation report and shoring design calculations shall be submitted as a part of enabling
package.
• Shoring contractor shall provide an under taken letter covering the responsibility of any damage or
cracks in the adjacent buildings or roads as a result of shoring and excavation works.
• The consultant shall review and approve the shoring drawings and design prepare by the shoring
contractor before submitting to the municipality.

Government of Ras Al Khaimah Page 49 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

15. Items to Be Included in Structural Submission

The following items shall be included and properly covered in the structural submissions:
• Soil investigation report.
• Detailed design calculations and design basis report.
• Analysis models (e.g. ETABS, SAFE, PROKON, etc.).
• Different levels certificate and/or levels difference confirmation by the consultant.
• General notes and standard details for structural elements including the following minimum
information.
- Concrete grade (Cube/Cylinder).
- Reinforcement grade.
- Allowable soil bearing pressure.
- Foundation level.
- Ground water level (if any).
- Dewatering information (if any).
- Waterproofing types.
- Type of used partitions.
- Reference datum level (e.g. Gate level, etc…).
- Concrete cover of different elements; foundation, slabs, beams, ribs, columns.
- Standard details of beams and foundation.
• Structural Drawings
- Shoring plans and details; in case of deep excavation.
- Loading plans.
- Raft foundation plans showing general arrangement (GA) and reinforcement details. Location
and dimensions of lift pits/sump pits to be shown clearly on GA drawings.
- Isolated/combined footing plans and schedules. Foundation plan shall show the dimensions of
strap beams (if existing).
- In case of deep foundation (piles), piles layout and general notes drawings shall be submitted for
piles showing the different piles types and the required tests to be done on piles.
- Retaining wall details including plans, setting out and reinforcement details sections.
- Column layouts plan showing clear setting out of columns.
- Schedule of columns including reinforcement, sizes and detailed sections.
- Floor plans showing general arrangement, concrete sizes of all the elements and setting out
(such as slab thickness, beam sizes, opening sizes) and reinforcement details.
- Schedule of beams, with reinforcement and sizes, including typical beam elevation and sections
for different beam types.
- Detailed sectional plans and elevations for shear walls showing all dimensions, openings and
reinforcement.
- Plans, sections and details of swimming pools, reinforced concrete water tanks, level differences
and significant architectural features.
- Plan & section for staircases showing all dimensions and reinforcement.

Government of Ras Al Khaimah Page 50 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

• The name of all the structural floor plans shall be labelled similar to architectural floors plans. Refer
to the following figure for further explanation.

Figure 15-1: Structural Floor Plans Labeling System

Government of Ras Al Khaimah Page 51 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

16. Extension and Modification of Existing Buildings

16.1. General Requirements


• The study of the building shall be carried on by a specialized consultant approved by Ras Al
Khaimah Municipality who shall study the status of the building, its structural age and determine the
possibility of modification, addition and defining all the necessary precautions.
• The Structural elements that are included in the extension and/or modifications, shall be
strengthened and enhanced in order to accommodate the additional design loads or geometric
changes according to the applicable design methods and applicable standards.
• All strengthening works in site shall be carried by approved specialist with proven track record.

16.2. Building Classification


Buildings subjected to modification and additions shall be classified according to their structural age as
follows:
16.2.1. Buildings with a Structural Age Over 15 Years
• Any structural modification or additional loads to those buildings are allowed only subjected to proper
and detailed study performed by specialized approved consultant.

16.2.2. Buildings with a Structural Age of 10 to 15 Years


• The structural analysis of the building shall be carried out using one of the approved structural
software, the tests for the buildings under execution or parts of it. It shall be carried out when there
are reasons to doubt the performance of the building or any part thereof to resist the expected loads
or doubt in its validity for use.
• All or some of the following tests might be required according to the directions of the municipality:
- Core test.
- Ultrasonic pulse velocity.
- Schmidt Hummer.
- Load tests.
- Check of specific parts of the foundations as required.
- Soil Report for the added parts (if any).
• Load tests shall be carried out in such a way to ensure the safety of individuals and property, and
shall not affect the test itself or its results.

16.2.3. Buildings with a Structural Age Less Than 10 Years


• The Municipality has the right to request any tests or structural analysis deemed necessary to take
the appropriate decision regarding the acceptance or rejection of the required modification.

16.3. Soil Testing Procedures


• In order to expedite obtaining the license for modification or addition to an inhibited building; where it
is difficult to carry out soil tests; it is possible to postpone the necessary soil testing until the start of
execution. The results shall be presented to the Licensing Structural Engineers after being studied

Government of Ras Al Khaimah Page 52 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

and modified by the consultant, and based on this; he shall submit modified drawings for final
approval (if necessary).
16.4. Decisions and Procedures
• If the building does not meet the satisfactory criteria for the different construction materials or the
proper structural analysis according to the previous provisions; the Municipality has the right to take
one of the following actions:
- Reform and rehabilitation.
- Allow the use of the building under reduced loads based on the results of analysis or load tests.
- Rejection of the modifications or additions.
- Demolition of the building.

Government of Ras Al Khaimah Page 53 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

17. Inspection of Buildings Construction

Inspection of construction works shall be carried out according to the approved manual’s requirements of
buildings construction and considering the followings:

17.1. Inspection of concrete works


• Inspection shall include the reinforced concrete, pre-stressed concrete and pre-cast concrete works
to ensure that they conform to the approved drawings. (Plain concrete works and non-structural
elements are excluded).
• The inspection shall include (but not limited to) reinforcement bars, its locations, quantities,
arrangements, overall lengths, development lengths, and lap splices.
• Inspection shall include the results of concrete cubes tests of different structural elements.
• The inspection shall include the results of the piling tests during the inspection of pile caps and raft
on piles.
• Pre-stressed concrete, pre-cast concrete and special works shall be delivered by the designated
engineer from the executing company for those works.
• The Consultant and the Competent Engineer shall ensure the availability of all approved documents
and drawings in the construction site.

17.2. Inspection of Structural Steel Works


• Inspection shall include steel elements and sections of steel structures, high-strength bolts, nuts,
sealing rings, welding and measuring work, and joints with bolts or welds and their arrangements
according to the approved drawings.
• The steel works shall be delivered by the designated Engineer of the executing company for those
works.
• The Consultant and the Competent Engineer shall ensure the availability of all approved documents
and drawings in the construction site.

17.3. Inspection of Founding Soil


• The inspection shall include the founding soil below any type of foundation.
• The inspection shall include all earthworks in site including excavation, backfilling, compaction,
dewatering and shoring works.

Government of Ras Al Khaimah Page 54 Ras Al Khaimah Municipality


Ras Al Khaimah Structural Guidelines

18. Approval of New Structural Systems

Any new structural system or material (non-conventional) shall be submitted in advance to Ras Al
Khaimah Municipality for approval before implementing by the consultant in the design, even if the
system is approved in any other emirate.

18.1. General requirements


• Company profile, including the company classification in Ras Al Khaimah municipality or any other
municipality within UAE.
• Copy from factory and trade licenses, indicating the particular activities in production of the new
structural system.
• Full set of drawings for a project executed by means of the new structural system, including
architectural and structural drawings.
• List of previous projects with photos and copy of building completion certificates (BCC).
• Approval of the new system from all relevant authorities such as (but not limited) civil defense.

18.2. Technical requirements


• Full set of general structural notes and details, including sections, materials specifications,
connection details, and data sheets.
• Used materials specifications for galvanized coating, steel, concrete, bolts, screws, insulation
system, etc.….; including factory data sheets, warranties, related tests and sources.
• Design codes and applicable software; including gravity and wind loads definition, analysis method,
serviceability and strength criteria.
• Specific test results such as (but not limited) acoustic test, fire resistance test, insulation test and
strength tests.
• Specific arrangement to control the cracks caused between two different materials.
• Water tightness specifications of the system: gaps in cladding and walls, condensation, wetted area,
water leakage, coats and finishing, wall and roof insulation.
• Proposed system durability and warranty in years.
• Supplementary evidences indicate that the new system is compliant with international standards and
codes (BSI & ASTM).
• Substructure system details and specification (foundation level, ground floor slab, and tie beams).

Government of Ras Al Khaimah Page 55 Ras Al Khaimah Municipality