Generator Protection Schemes

This document discusses generator protection applications including: 1. Protection of individual generators such as internal fault protection, network fault protection, and temperature and voltage/frequency monitoring using devices like the Sepam G40 or G60. 2. Protection of generator-transformer units including internal fault protection, network fault protection, and temperature monitoring using devices like the Sepam G40 or G60 for separate units or the Sepam G82 for units coupled to other equipment. 3. Generator differential protection using devices like the Sepam G87 for phase protection or the Sepam G88 for generator-transformer units.

Uploaded by

陆华林
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views

Generator Protection Schemes

This document discusses generator protection applications including: 1. Protection of individual generators such as internal fault protection, network fault protection, and temperature and voltage/frequency monitoring using devices like the Sepam G40 or G60. 2. Protection of generator-transformer units including internal fault protection, network fault protection, and temperature monitoring using devices like the Sepam G40 or G60 for separate units or the Sepam G82 for units coupled to other equipment. 3. Generator differential protection using devices like the Sepam G87 for phase protection or the Sepam G88 for generator-transformer units.

Uploaded by

陆华林
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Generator applications

Generator protection
b internal generator fault protection
b network fault protection
b driving machine fault protection
b RTD temperature monitoring (ANSI 38/49T)
b voltage and frequency monitoring.

Protection of a separate generator: Sepam G40 or G60


Earth fault protection: Earth fault protection:
b 50G/51G b 50G/51G.
b 59N.

DE60550

DE60551

Protection of a generator coupled to other generators or to a network:


Sepam G62 or G82
Short-circuit detection on generator side.
Control fault protection.
Earth fault protection: Earth fault protection: Earth fault protection:
b 50G/51G b 100 % stator earth fault b 64REF and 50G/51G
b 59N. 64G. b 50N/51N.
DE60552

DE88068

DE88069
Generator applications

Generator differential protection: Sepam G87


Phase protection by self-balancing differential scheme: Generator differential protection: 87M.
50/51.
Earth fault protection: 50G/51G. Earth fault protection: Earth fault protection: Earth fault protection:
b 50G/51G b 100 % stator earth fault b 50N/51N.
b 59N. 64G.
DE88070

DE88071

DE88072

DE88073
Generator-transformer unit protection
b generator and transformer protection against internal faults
b network fault protection
b driving machine fault protection
b RTD temperature monitoring (ANSI 38/49T)
b voltage and frequency monitoring.

Separate generator-transformer unit protection. Sepam G40 or G60


Earth fault protection:
b 50G/51G.
Note: monitoring of generator insulation must be ensured by another device.
DE60553
Generator applications

Protection of a generator-transformer unit coupled to other generators or to


a network: Sepam G82

1
Short-circuit detection on generator side: 67.
Control fault protection.
Internal transformer protection: Thermostat / Buchholz (ANSI 26/63).
b generator earth fault protection: b generator earth fault protection:
50G/51G 100 % stator earth fault 64G
b transformer secondary earth fault b transformer secondary earth fault
protection: protection:
v 50G/51G v 50G/51G
v 59N. v 59N.

DE88075

DE88076

Generator-transformer unit differential protection: Sepam G88


Generator-transformer unit differential protection: 87T.
b generator earth fault protection: b generator earth fault protection:
50G/51G 100% stator earth fault 64G
b transformer secondary earth fault b transformer secondary earth fault
protection: protection:
v 50G/51G. v 50G/51G
v 64REF.
DE88077