DSLP
DSLP
DSLP
PROTECTION ZONE
CALCULATION FOR LIGHTING
Name Date Signature
INDEX OF REVISIONS:
Lightning stroke can cause fatality structural damage, and could lead to malfunction of the
electric equipment. The lightning stroke will vary by characteristics from area to area. The
lightning itself is an emission or discharge of electricity from cloud to ground, from ground to
cloud and from cloud to cloud. When the lightning strikes the ground, it chooses a path with
low resistance. According to the IEEE standard 998-1996 “the stroke occurs in two steps, the
first is ionization of the air surrounding the centre and the development of stepped leaders,
which propagate charge from the cloud into the air”. The second step is return stroke,
according to the same standard, “the return stroke is the extremely bright streamer that
propagates upward from the earth to the cloud following the same path as the main channel
of the downward stepped leader”.
Direct stroke lightning protection for Bhulta 230/132kV Sub-station is provided by shield wire.
Each lightning conductor consists shield wire, the earthing grid and the conductor which
connects the shield wire with the earthing grid meant to carry the lightning current away safely
to the ground.
The submitted calculation is done by the “Rolling Sphere Method” as per the description of
IEEE standard 998-1996.
Basics for the calculation:
❖ Rolling sphere method:
The technique involves rolling an imaginary sphere of prescribed radius over the surface of a
substation. The sphere rolls up and over lightning shield and other grounded metal objects
intended for lightning protection. A piece of equipment is protected from a direct stroke if it
remains below the curved surface of the sphere by virtue of the sphere being elevated by
shield wires or other devices. Equipment that touches the sphere or penetrates its surface is
not protected.
❖ Shield wire (Overhead ground wire/Sky wire):
A wire suspended above the phase conductors positioned with the intention of having lightning
strike it instead of the phase conductors.
❖ Striking Distance:
The length of the final jump of the stepped leader as its potential exceeds the breakdown
resistance of this last gap; found to be related to the amplitude of the first return stroke.
❖ Surge Impedance:
3. Reference documents:
IEEE std 998-1996: IEEE Guide for Direct Lightning Stroke Shielding of Substations.
4. Calculation:
Substation Data
1 Rated voltage = 230 kV
2 Average height of the conductor, h = 7.9 m
3 Rated lighting impulse withstand V0 = 1050 kV
voltage,
4 Limiting corona gradient, E0 = 1500 kV/m
5 Radius of conductor, r = 0.0192 m
6 No of conductor in a = 1 nos
bundle,
7 Spacing between adjacent conductors l = 0 m
8 The basic impulse level in kilovolts, BIL = 1050 kV
Here,
Height of shield wire, H = 22 m
Height of equipment or Bus conductor, A = 7.9 m
Striking distance (S) = 28.04 m
𝑅 = √(𝑆 2 + (𝑆 − 𝐻)2 )
= 27.37 m
T = √(𝑆 2 + (𝑆 − 𝐴)2 )
= 19.50 m
C = 𝑅 −𝑇
= 7.87 m
Conclusion:
The maximum height of equipment under a single shield wire in 230kV Side is a 230kV Bushing of
the transformer which is 7.9m. The maximum horizontal distance of bushing from the single shield
wire is 3.4m which is less than protected distance 7.87m.
Here,
L = 𝑋/2
= 8 m
E = √(𝑆 2 − 𝐿2 )
= 26.86 m
𝐷 = 𝑆 −𝐸
1.17 m
𝐴 = 𝐻 −𝐷
= 20.83 m
Conclusion:
Under zone 3 the maximum height conductor is 7.9m (230kV transformer bushing) which is less
than protection Zone height (A) 20.83m. So, all equipment height within 7.9m under zone 3 is
protected.
Substation Data
1 Rated voltage = 132 kV
2 Average height of the conductor, h = 4.5 m
Rated lighting impulse withstand
3 voltage, V0 = 650 kV
4 Limiting corona gradient, E0 = 1500 kV/m
5 Radius of conductor, r = 0.0192 m
6 No of conductor in a bundle, = 1 nos
7 Spacing between adjacent conductors l = 0 m
8 The basic impulse level in kilovolts, BIL = 650 kV
9 strikes on shield wire K = 1
The corona radius (Rc)
The corona radius is given by the following equation,
Rc x ln {(2xh)/ Rc } – (V0 / E0) = 0 ... (equation C.1: IEEE Std 998-2012.)
After solving equation, Rc = 0.0953 m
Surge impedance(Zs):
The surge impedance of conductors under corona is given as,
60 x √(ln(2 x h/Rc) x ln
Zs = (2xh/r)) ... (equation C.5: IEEE Std 998-2012.)
= 317.33 ohm
Here,
Height of shield wire, H = 16.2 m
Height of equipment or Bus conductor, A = 4.5 m
Striking distance (S) = 21.29 m
𝑅 = √(𝑆 2 + (𝑆 − 𝐻)2 )
= 20.67 m
T = √(𝑆 2 + (𝑆 − 𝐴)2 )
= 13.09 m
C = 𝑅 −𝑇
= 7.58 m
Conclusion:
The maximum height of equipment under a single shield wire in 132kV Side is a CSE which is
4.5m. The horizontal distance of CSE from the shield wire is 5m which is less than protected
distance 7.58m.
Substation Data
1 Rated voltage = 132 kV
2 Average height of the conductor, h = 12.7 m
3 Rated lighting impulse withstand V0 = 650 kV
voltage,
4 Limiting corona gradient, E0 = 1500 kV/m
5 Radius of conductor, r = 0.0192 m
6 No of conductor in a = 1 nos
bundle,
7 Spacing between adjacent conductors l = 0 m
8 The basic impulse level in kilovolts, BIL = 650 kV
Surge impedance(Zs):
The surge impedance of conductors under corona is given as,
Zs = 60 x √(ln(2 x h/Rc) x ln (2xh/r)) ... (equation C.5: IEEE Std 998-
2012.)
= 388.679 ohm
Here,
Height of shield wire, H = 16.2 m
Striking distance (S) = 18.68 m
Distance between two parallel shield Wire (SW), X = 12
L = 𝑋/2
= 6 m
E = √(𝑆 2 − 𝐿2 )
= 17.67 m
𝐷 = 𝑆 −𝐸
0.99 m
𝐴 = 𝐻 −𝐷
= 15.21 m
Conclusion:
According to the layout, maximum height of conductor in the 132kV Side under 2 parallel shield
wire is 12.7m. So, all the equipment under zone 2 is protected.