Features
• Provides four monitored inputs
• Easily plugged onto each other or onto other I/O
modules on a standard mounting rail
• Automatic addressing of the I/O module
• Designed to meet EN-54 and LPCB requirements,
and conforms to CE standards

Applications
The Input Module BSE-310 provides four monitored
inputs for digital input devices and other controlling
inputs.

The I/O module is easily plugged onto a mounting


rail inside the Fire Alarm Control Panel (BS-310/320)
or the Controller (BC-320).
Versions
Each input circuit is connected to a closed loop with
known resistance. A change in the resistance is de- Front view when mounted on rail
tected by the module.

The I/O module will automatically detect its own ad-


dress; no Dip-switch or jumper settings are required.
Screw
terminal 10

Screw
terminal 1

The I/O module has the following connections:

Screw Terminal no. Signal


1 IN1 +
2 IN1 - (0V)
3 IN2 +
4 IN2 - (0V)
5 IN3 +
6 IN3 - (0V)
7 IN4 +
8 IN4 - (0V)
9 24 VBAT
10 0 VBAT

P-BSE310/CE - Rev. C, 040630 Protecting life, environment and property...


Input Module, Monitored - BSE-310

Technical Specifications Connections


Dimensions (mm) 95 x 89 x 32
Weight (g) 81
Materials Top and bottom: Zytel 1 Signal resistor
FR7200
250-2000 Ohm
Input 2K
Snap-on mounting device: (Recommended value
Zytel 7335S is 470 Ohm)
Electrical connection Internal system: plug-in
2
connection Monitoring resistor
(end of line resistor)
External connection: screw
terminals (maximum cable
dimension 2,5mm2)
Mounting Onto a standard mounting
rail inside the Fire Alarm
Control Panel or Controller Schematics
Number of inputs per Four pieces monitored
module
Internal current consumption 24V reg.: 15 mA R Signal
V+
Terminal point 1, 3, 5, 7
Input line monitoring: Sense
- end of line resistor 2 kOhm 0V
- short-circuit < 200 Ohm Terminal point 2, 4, 6, 8
0V
- activated (alarm) ≥ 200 < 1 kOhm
- normal ≥ 1 kOhm < 3 kOhm
- break ≥ 3 kOhm

Order Numbers
Order numbers Description
BSE-310 Input Module, Monitored

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99
Maritime Sales, Spikkestad, Norway. Phone: + 47 31 29 55 00, fax: + 47 31 29 55 01

Visit Autronica Fire and Security’s website: www.autronicafire.com