APMR Series R 22

REFRIGERANT

Packaged Air Conditioners

50Hz

Range 5 TR to 28 TR
(17 kW to
R kW)
98
22
REFRIGERANT

S.K.M Air Conditioning LLC


1
Contents Introduction
Legend ................................................. 2 Electrical Data ...................................... 12
Nomenclature ....................................... 2 Field Connection................................. 13
SKM APMR New Packaged Air Conditioners
Introduction ......................................... 2 Typical Wiring Diagram ....................... 14 Series are designed and manufactured to meet
General Features ............................... 3 Dimensional Data ............................... 17 the requirements of Gulf’s severe climatic
Main Component Features .................. 3 Loading Points ....................................... 20 conditions and are built specifically for ducted
Optional Features ................................4 Recommended Clearances ............... 21 systems which will enable them to be installed
Engineering Specifications ..................7 Installation & Commissioning ............... 23 easily on roof tops or on the ground.
Capacity Ratings ................................. 9 Guide Specifications ............................. 24
Fan Performance ............................... 11 The APMR series Packaged Air Conditioners
are compact, quiet, most efficient and self
contained units are ideal for commercial and
Legend top end residential applications.

The following legends are used throughout this manual: Available in 15 different sizes from 5 to 28
TR (17kW to 98kW) in 50 Hz at nominal
AFR ................................... Air Flow Rate lbs......................................Pounds weight AHRI conditions. APMR series packaged air
BPF..................................By Pass Factor L/s.................................Liters per second conditioners are designed to operate in a wide
CFM.....................Cubic feet per minute MBh.....................................BTUHx1000
ambient temperature range between 50°F
Pa..................................................Pascal
EER..................Energy Efficiency Ratio (10°C) to 125°F (51.7°C), based on specific
Ph....................................................Phase
ESP.................External Static Pressure conditions & model applies. Two independent
PI ......Power Input of Compressor in kW
Hz ....................................................Hertz RPM ...................Revolutions Per Minute refrigeration circuits are provided where two
in. wg...............................Inch water gauge RPS...........................Rated Power Supply compressors are used.
kW.............................................Kilowatts TR.............................Tons of Refrigeration
V..........................................................Volts APMR units are designed, rated and
kg........................................Kilogram
manufactured in accordance with AHRI
210/240 and 340/360 standards.

APMR series units from SKM are completely


Nomenclature assembled, leak tested, vacuumed, internally
wired and fully charged with R-410A refrigerant
A P M R - 5 1 050 Y at factory. Each unit is fully factory tested
before dispatch and is ready for installation.
Air Cooled Power Supply Code All that is required on the site is to connect
Y : 380V-415/3Ph/50Hz ducts, drain lines, main power supply and field
Package P : 440V/3Ph/50Hz
wiring to the thermostat. This greatly reduces
Scroll
Compressor
the installation work and cost.

R-410A
SKM provides qualified service and stock
Nominal Capacity in MBh
5 = 50 Hz of replacement parts in all major cities of the
1 : Single Circuit G.C.C. countries, Egypt, Jordan, and Pakistan.
2 : Double Circuit See back cover for details or call SKM.

SKM Air Conditioning LLC

SKM reserves the right to change, in part or in


whole the specifications of its Air Conditioning
Equipment at any time in order to add the latest
technology. Therefore, the enclosed information
may change without any prior notice.

You name it.....We cool it


General Features Condenser Coils R 22
REFRIGERANT
The APMR Series is a modern, diversified and environment Condenser coils are manufactured from Corrugated fin and Hi-X
friendly series of packaged air conditioners which use R-410A seamless copper tubes mechanically bonded to aluminium fins
refrigerant. to ensure optimum heat transfer. All coils are tested against
leakage by high air pressure 715psig (4930kPa) under water.
The APMR Series Packaged Air Conditioners are yet another An integral subcooling circuit is incorporated in the lower section
new unique series from SKM incorporates many salient features of the condenser to increase system capacity. The additional
which, together, provides a heavy duty, robust, long lasting condenser surface provides more cooling using less energy at
commercial unit meant for high end residential and commercial no additional cost.
applications. The APMR series models combine high efficiency
condenser and cooling coils, evaporator blower and heavy duty
Condenser Fans
motor in addition to premium safety and operational controls.
Condenser fans are propeller type with aluminum alloy blades
The complete APMR packaged unit provides an extremely and are directly driven by electric motors. Motors are Totally
rugged, long life, energy efficient, self contained packaged air Enclosed Air Over (TEAO), six pole or four pole with Class F
conditioner that will provide cooling with higher efficiency over insulation and IP54/55 protection depending on models. Complete
a long and extended life. fan assembly is provided with fan guard.

What makes APMR series yet another model in the top class
range of SKM products is the use of:
Evaporator
• High efficiency totally sealed scroll hermetic compressors. Evaporator coils are manufactured from Hi-X seamless copper
• Totally enclosed, Class F insulated,condenser and evaporator tubes mechanically bonded to aluminium Corrugated fins to
fan motors. ensure optimum heat transfer. All evaporator coils are tested
• Heavy duty condenser and evaporator coils optimised in against leakage by high air pressure of 450 psig (3100kPa) under
water. Coils conform to AHRI-410.
design for long-life maintenance free operation.
• Cabinet construction specifically designed for Gulf climates.
• Electronic control board for the unit operation.
• Typically, much heavier gauge tubing and thicker fins for Evaporator Fan & Drive
ruggedness and long life. Evaporator fans are forward curved centrifugal double inlet, double
width, statically and dynamically balanced. Bearings used in the
fans are self aligning and lubricated for life. Evaporator fans are
belt driven and use “V” belts with an adjustable variable pitch
motor pulley resulting in an accurate fan air flow adjustment.
Main Component Features
Fans are driven by Totally Enclosed, IP-55 Protected, 4 pole
The common standard features of all APMR series packaged
Class F insulated electric motors. The motors are factory wired to
units include the following
the control panel where the motor starters are located to control
the operation of the motors. The motors conform to relevant IEC
Compressors standards.

Compressors used in APMR packaged unit series are


hermetically sealed, compact scroll with the following features: Casing and Structure
• High Efficiency. The unit casing used in APMR series is made of hot dip
galvanized (zinc coated) steel sheets, conforming to JIS-G
• Quiet operation, Low Sound levels.
3302 and ASTMA653, which is phosphatized and baked after an
• Compact and light.
electrostatic powder coat of approx. 60 microns. This finish and
• Limited wear. coating can pass a 1000 hour in 5% salt spray testing at 95°F
• 70% fewer moving parts than comparably sized reciprocating (35°C) and 95% relative humidity as per ASTM B117.
compressors.
• Unique ability to hadle liquid refrigerant. The evaporator section is insulated from all the sides with 1”
• Suction gas motor cooling. thick fiber glass insulation with extremely tough and durable
• Suction screen. black composite surface. The insulation cum sound liner meets
• Centrifugal oil pumps with filter and magnet. the fire requirements of NFPA90A & 90B and is secured with
• Brazed fittings or Rotalock options. mechanical fasteners in addition to water resistant adhesive.
• Two refrigerant circuits on larger units provides efficient
part load.
• No internal valves.

S.K.M Air Conditioning LLC


3
SKM Packaged Air Conditioners APMR Series

Refrigerant R- 410A Optional Features


Why 410A?
As with all SKM air conditioning units, the APMR Series
R-410A has a higher volumetric cooling capacity compared to Packaged Units are available with multitude of optional features
R-22 and has better thermal exchange properties. This results available on request:
in overall performance gains in terms of system efficiency. The
greater density of the vapour in R-410A permits higher system Double Skin Evaporator (DSE)
velocities, reduces pressure drop losses and allows smaller
diameter tubing to be used. In other words a smaller unit can Double skin evaporator section with galvanized inner skin.
be developed using a smaller displacement compressor, less
coil and less refrigerant while maintaining system efficiencies Double Skin Insulation (DSI)
comparable to current day R-22 equipment. Inner skin in the evaporator section is provided with foam board
insulation.
Benefits
Temperature Based Economizer (ECRU)
• No ozone depletion potential or phase-out date Simple temperature based economizer.
Using chlorine-free R-410A with zero Ozone Depletion
Potential (ODP) helps protect both the environment and your 2” (50mm) Flat Filter Section (FSIP2)
investment. That’s because new equipment using R-410A
For heavy filtration need a section can be provided without or
faces no mandated phase-out date over a 20 to 30 year
with aluminium cleanable filter.
equipment life expectancy.

• Reduced service costs


Alternative Condenser Material
R-410A refrigerant has no significant “glide.” If a leak occurs, Made of copper tubes and alternative fin material and/or
only the lost refrigerant must be replaced. protective coating.
• Pre Coated aluminum fins (FAP).
Attention points • Aluminum Fins with Aeris post Coat Protection (FAA).
• Copper Fins (FC).
• Pressure level: 1.6 times of R-22. • Copper Fins with Aeris post Coat Protection (FCA).
• Lubricating oil: Ester Oil absorb moisture easily
(Never mix with mineral oil).
Alternative Evaporator Material
• Tools exclusive for R-410A.
• Never mix R-410A with other refrigerant. Made of copper tubes and alternative fin material and/or
• Driers, valves and even copper tube must be approved for protective coating.
use with R-410A. • Pre Coated aluminum fins (EFAP).
• Never allow refrigerant cylinders to exceed 60°C. • Aluminum Fins with Aeris post Coat Protection (EFAA).
• Copper Fins (EFC).
• Copper Fins with Aeris post Coat Protectionn (EFCA).
Control Panel Anti-Freeze Thermostat (AFT)
For evaporator coil freeze -up protection.
The APMR packaged Air Conditioners are provided with IP-54
control panel enclosure comprising all starting, operating & safety
Western Make Scroll Compressor (WMSC)
controls. The panel is factory wired in accordance with NEC
430 & 440, labelled, tagged and features 220V / 240V controls. Western make scroll compressor.

• Starting contactors for compressors and motors. Compressor Run Hour Meter (RHM)
• Internal overload protection for compressors. To monitor operating hours of each compressor.
• Internal or External overload protection for the motors
(depending on the model).
Circuit Breaker for compressor (CBC)
For those electrical specification which requires additional short
• Electronic control board for unit operation.
circuit and overload protection for the compressors.
• Diagnostic LEDs on the control board for easy
troubleshooting . Rotalock Valves on compressors (RVC)
• Compressor short cycling protection. For additional facilitation of maintenance of unit.
• Control switch for unit on/off.
• Control circuit breaker.
External Overload Protection (EOP)
• Power and control circuit terminal blocks. For those electrical specification requires additional overload
protection for the compressors.(Not required with CBC option)
• High pressure protection.
• Low pressure protection.

4
Electric Heating (HTR1) Pump Down Facility with solenoid Valve (PDS)
Electric heating batteries are made up of finned heating elements,
R 22
The compressors will switch off each time with a Pumpdown
REFRIGERANT
constructed from high quality 80/20 nickel chrome resistance wire Cycle in order to prevent Liquid refrigerant migration to the
centred in metal tube by compressed magnesium oxide. compressor during Off Cycle periods.
Helical fins are tightly wound around the tubular heating element.
Applicable for models from APMR-51050 to 52270
Heater batteries when ordered comes with stage contactors,
primary auto reset thermal safety cut-out, secondary manual Extra Ball Valve (XFV)
reset thermal safety cut-out and air flow switch.
Extra ball valve can be incorporated in the liquid line.
Control of the heaters will be from the unit controller.
Following are the optional kW ratings for electric heater. Ratings Pressure relief valve (PRV)
other than those specified here can be supplied on request. To protect the unit from being over - pressurized.
Consult SKM for details
Pressure Gauges (SDG1)
MODEL Suction and discharge indication of each refrigerant circuit.
HEATER (kW) STAGES Gauges mounted outside the Control Panel.
APMR
51050
4.5 Manual Reset Type High Pressure Switch (MHP)
51060
To replace standard auto reset, capsule type pressure switch.
51075 1
51080 9 Liquid Line Sight Glass (RSG)
51100 For monitoring refrigerant charge and to provide visual indication
52115 of moisture presence in the system.
52125
52150
Condenser Coil Guard (CGP)
18 Wire mesh guard, in painted finish for condensers coils.
52170
Recommended on ground level installation where coil needs to
52200
2 be protected against vandalism.
52230
52240 Stainless Steel Drain Pan (Grade 304) (SDP)
52270 Stainless steel drain pan(Grade 304). Insulation under drain pan
24
Table 1

52300 as per SKM standard.


52340
Stainless Steel Drain Pan (SSP)
Heavy gauge 316 stainless steel drain pan under the entire cooling

Advanced Micro Processor Control System (AMCS) coil.

An advanced microprocessor based controller can be provided Insulation under drain pan as per SKM standard.
for the units as option, in case required. This controller
will be with built-in display keypad and has many features. Marine Painted Inner Skin (IS-MP)
For this feature, additional options can be provided and to be
specified during time of order:
Painted Inner Skin (IS-P)
● DTS – Duct Temperature Sensor *
(In order to control the unit based on return/supply air duct Marine Paint (MP)
temperature.) (This is not required with CHTS/CHTS-Wifi To provide increased corrosion resistance for coastal environments
options)
and offshore location.
● BMSP – BMS Protocol *
(For interfacing the units with major BMS protocols such as Stainless Steel SS316L Fasteners (SSF)
BACnet, Modbus or LON. An extra hardware may be required
depending on the protocol) Anti-corrosion clear coating for fasteners (JHT)
Anti-corrosion clear coating for fasteners applicable with SSF option.
Pump Down Facility (PD)
The compressor will switch off each time with a Pump Down Cycle
Marine Painted Condenser Coil end plate (MP-CCEP)
in order to prevent Liquid refrigerant migration to the compressor
during off Cycle periods. Marine Painted Evaporator Coil end plate (MP-ECEP)
With this option, each circuit will be provided with an additional
SS316L Laser Printed Unit Tag Plates (TO-SS-LA)
discharge check valve (if required) to prevent Refrigerant
Migration from High side to Low side when the compressor is off.
Applicable for models from APMR-52300 & 52340

S.K.M Air Conditioning LLC


5
SKM Packaged Air Conditioners APMR Series

Up Size Evaporator Motor** (USM) Options for Field Installation


Unit with one up size evaporator motor.

Circuit breaker for Motors** (CBM) Anti-vibration mounts (CAVM)


Recomended for roof mounted units or other location in the vicinity
For those electrical specification which requires additional short
of occupied spaces. where noise may be objectionable.
circuit and overload protection for the fan motors.

IP 55 Control Panel (ICP) Low Voltage Thermostat (CHTS)


Control Panel for special applications to meet IP55 requirements. For wall mounting and for cooling /heating operation with 1 or 2
stages as per model. (Not required with AMCS/CHTS-Wifi
Main Isolator (without door interlock) (ISO) options).
For main power isolation. (Consult SKM)
Low Voltage Thermostat with Wi-Fi (CHTS-WiFi)
Control Transformer (CXT) For wall mounting and for cooling /heating operation with 1 or 2
This option is necessary and available for unit models rated for stages as per model and with wireless connectivity or Wi-Fi. (Not
440V/3PH/50Hz or power supplies without neutral. required with AMCS/CHTS options).
When ordering for these voltages, this option must be ordered.
● DTS-TH – Duct Temperature Sensor for 24V Thermostat *
(In order to control the unit based on return/supply air duct
BMS Interface Volt Free Contacts (BMVF) temperature.) (This is not required with AMCS options)
Volt free contacts for run status, common fault status, auto
mode status and provision for remote on/off shall be provided Note:
as option if required.
For additional requirements, please contact SKM. - *DTS & BMSP options are only available along with AMCS option.

Voltage Monitor Module (VMM) - *DTS-TH option is only available along with CHTS/CHTS-Wifi
options.
Provides protection in the event of:
• Phase burn-out. - **If CBM combined with USM option please consult SKM as
• Phase reversal. component might changed.
• Under / over voltage on the incoming line voltage.
- Whenever multiple options related to unit control, please consult
Voltage Monitoring Module as per DEWA (DVM) SKM for the drawings, as the size of the control panel might change.
Under voltage relay as per DEWA regulations. This option is
available for Dubai, UAE only.(VMM option is not required if
this option is opted.)

Ball Valve (BLV)


Ball valve can be incorporated in the liquid line.

Fan Cycling Switch (FCS)


Fan Cycling switch for single compressor units with two condenser
fans.(Not required with AMCS option)

Fire Alarm Interlock (VFC-F)


To provide provision for fire alarm interlock.

6
ENGINEERING SPECIFICATIONS - 50 Hz R 22
REFRIGERANT

Model APMR 51050 51060 51075 51080 51100 52115 52125


MBh 53.4 59.0 74.4 80.4 98.6 113.7 120.0
Cooling Capacity (1)
kW 15.6 17.3 21.8 23.6 28.9 33.3 35.2
MBh 47.4 52.4 66.4 70.8 87.6 99.9 106.8
Cooling Capacity (2)
kW 13.9 15.4 19.5 20.7 25.7 29.3 31.3
MBh 46.1 51.1 64.6 68.8 85.2 97.2 103.8
Cooling Capacity (3)
kW 13.5 15.0 18.9 20.2 25.0 28.5 30.4
Type - Hermetic Scroll
Quantity - 1 1 1 1 1 2 2
Compressor
US Gal 0.45 0.47 0.48 0.71 0.9 0.9 0.94
Oil Charge
Litre 1.7 1.77 1.8 2.7 3.4 3.4 3.54
Type - Hi-X tubes
Condenser Coil ft 19.4 26.7 26.7 26.7 26.7 26.7 40
Face Area
m 1.8 2.5 2.5 2.5 2.5 2.5 3.7
Type - Propeller Direct Drive
Condenser Fan
Code / Quantity - 550/1 550/2 550/2 550/2 550/2 550/2 630/2

Condenser
Type - Totally Enclosed Air Over, Class-F insulation, 4 pole or 6 pole, IP54 protected
Motor
Type - Hi-X-Tubes
Evaporator Coil ft 4.6 4.6 6.4 6.4 8.7 9.7 9.7
Face Area
m 0.4 0.4 0.6 0.6 0.8 0.9 0.9
Type - Centrifugal DIDW Belt Drive

Code / Quantity - 10/10 10/10 10/10 12/12 12/12 12/12 12/12


Evaporator Fan
cfm 1670 2000 2400 2900 3220 4000 4000
Air Flow Rate
l/s 788 944 1133 1369 1520 1888 1888
Evaporator Type - Totally Enclosed Fan Cooled, Class-F insulation, 4-pole, IP55 Protected.
Motor Size kW 0.55 0.55 0.75 1.1 1.1 1.5 1.5
Refrigerant (R - 410A) Operating lbs 7.5 10 10 10 17 17 26
Charge kg 3.4 4.5 4.5 4.5 7.7 7.7 11.8
Number of Refrigerant Circuits - 1 1 1 1 1 2 2
lbs 673 783 800 887 1045 1207 1428
Unit Operating Weight
kg 305 355 363 402 474 547 648
Table 2

Notes:
(1) Capacity ratings are based on AHRI Standard 210/240 & 340/360. Evaporator entering air conditions of 80°/67°F (27°/19.5°C)
dry bulb/wet bulb and condenser entering air temperature of 95°F (35°C) dry bulb.
(2) Evaporator entering air conditions of 80°/67°F (27°/19.5°C) dry bulb/wet bulb and condenser entering air temperature of 114.8°F
(46°C ) dry bulb.
(3) Evaporator entering air conditions of 80°/67°F (27°/19.5°C) dry bulb/wet bulb and condenser entering air temperature of 118.4°F
(48°C ) dry bulb.
(4) Capacity is gross capacity which does not include the effect of evaporator fan motor heat.

S.K.M Air Conditioning LLC


7
SKM Packaged Air Conditioners APMR Series

ENGINEERING SPECIFICATIONS - 50 Hz
Model APMR 52150 52170 52200 52230 52240 52270 52300 52340
MBh 150.3 168.1 194.6 227.1 233.7 264.5 299.5 337.6
Cooling Capacity (1)
kW 44.1 49.3 57.0 66.6 68.5 77.5 87.8 98.9
MBh 134.6 149.3 173 198.3 206.8 229.1 259.9 298.9
Cooling Capacity (2)
kW 39.4 43.8 50.7 58.1 60.6 67.1 76.2 87.6
MBh 131.0 145.1 168.3 192.8 200.9 222.5 252.3 290.7
Cooling Capacity (3)
kW 38.4 42.5 49.3 56.5 58.9 65.2 73.9 85.2
Type - Hermetic Scroll
Quantity - 2 2 2 2 2 2 2 2
Compressor
US Gal 0.95 1.43 1.80 1.80 1.80 1.80 1.80 1.80
Oil Charge
Litre 3.6 5.4 6.8 6.8 6.8 6.8 6.8 6.8
Type - Hi-X tubes
Condenser
ft 40.0 40.0 48.0 48.0 54.7 54.7 53.3 53.3
Coil Face Area
m 3.7 3.7 4.5 4.5 5.1 5.1 5.0 5.0
Type - Propeller Direct Drive
Condenser
Fan Code /
- 630/2 710/2 710/2 710/2 800/2 800/2 800/2 800/2
Quantity
Condenser
Type - Totally Enclosed Air Over, Class-F insulation,6 pole, IP54/IP55 depending on models
Motor
Type - Hi-X-Tubes
Evaporator
ft 12.5 13.3 15.6 15.6 19.5 19.5 21.7 21.7
Coil Face Area
m 1.2 1.2 1.4 1.4 1.8 1.8 2.0 2.0
Type - Centrifugal DIDW Belt Drive
Evaporator Code / Qty. - 15/15 12/12 R2 12/12 R2 12/12 R2 15/15 R2 15/15 R2 15/15 R2 15/15 R2
Fan cfm 5000 6000 7000 7000 8000 8000 9100 10500
Air Flow Rate
l/s 2360 2832 3304 3304 3776 3776 4295 4955
Evaporator Type - Totally Enclosed Fan Cooled, Class-F insulation, 4-pole, IP55 Protected.
Motor Size kW 2.2 2.2 3 3 3 3 3 4
Refrigerant (R - 410A) lbs 26.0 26.0 30.0 31.0 34.0 36.0 51.0 52.0
Operating Charge kg 11.8 11.8 13.6 14.1 15.4 16.3 23.1 23.6
Number of Refrigerant
- 2 2 2 2 2 2 2 2
Circuits
lbs 1468 1689 1966 2003 2160 2215 2357 2559
Unit Operating Weight
kg 666 766 892 907 979 1005 1070 1160
Table 3
Notes:
(1) Capacity ratings are based on AHRI Standard 210/240 & 340/360. Evaporator entering air conditions of 80°/67°F (27°/19.5°C)
dry bulb/wet bulb and condenser entering air temperature of 95°F (35°C) dry bulb.
(2) Evaporator entering air conditions of 80°/67°F (27°/19.5°C) dry bulb/wet bulb and condenser entering air temperature of 114.8°F
(46°C ) dry bulb.
(3) Evaporator entering air conditions of 80°/67°F (27°/19.5°C) dry bulb/wet bulb and condenser entering air temperature of 118.4°F
(48°C ) dry bulb.
(4) Capacity is gross capacity which does not include the effect of evaporator fan motor heat.

8
GROSS CAPACITY RATINGS - 50 Hz R 22
AFR Condenser Entering Air Temperature REFRIGERANT
Model cfm EWB 95°F (35°C) 105°F (40.6°C) 114.8°F (46°C) 118.4°F (48°C) 125°F (51.7°C)
APMR l/s Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI
(BPF) °F °C MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW
1260 62 16.7 47 13.8 39.4 11.5 4.2 43.7 12.8 37.9 11.1 4.9 40.4 11.8 36.5 10.7 5.5 39.3 11.5 36 10.6 5.7 -- -- -- -- --
595 67 19.4 51 14.9 33 9.7 4.3 48.1 14.1 31.8 9.3 4.9 45.3 13.3 30.7 9 5.5 44.3 13 30.4 8.9 5.7 -- -- -- -- --
0.17 72 22.2 55 16.1 26.4 7.8 4.4 51.9 15.2 25.4 7.4 4.9 48.9 14.3 24.3 7.1 5.4 47.9 14 24 7 5.6 -- -- -- -- --
1670 62 16.7 48.2 14.1 44.9 13.2 4.3 44.9 13.2 43.5 12.8 4.9 41.7 12.2 41.7 12.2 5.5 40.6 11.9 40.6 11.9 5.7 -- -- -- -- --
51050 788 67 19.4 53.4 15.6 37.4 10.9 4.3 50.3 14.8 36.2 10.6 4.9 47.4 13.9 35.1 10.3 5.5 46.1 13.5 34.6 10.2 5.6 -- -- -- -- --
0.2 72 22.2 57.4 16.8 29.1 8.5 4.4 54.2 15.9 28.1 8.2 4.9 51.1 15 27.1 7.9 5.4 50 14.6 26.7 7.8 5.6 -- -- -- -- --
2521 62 16.7 50.1 14.7 50.1 14.7 4.3 46.8 13.7 46.8 13.7 4.9 43.7 12.8 43.7 12.8 5.5 42.6 12.5 42.6 12.5 5.7 -- -- -- -- --
1190 67 19.4 56.2 16.5 45.4 13.3 4.4 52.3 15.3 44 12.9 4.9 48.7 14.3 42.7 12.5 5.4 47.4 13.9 42.3 12.4 5.6 -- -- -- -- --
0.26 72 22.2 60.2 17.6 34.1 10 4.4 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
1260 62 16.7 50.7 14.9 41 12 4.2 47.9 14 39.8 11.7 4.8 44.5 13 38.2 11.2 5.4 43.1 12.6 37.6 11 5.6 40.7 11.9 36.6 10.7 6.1
595 67 19.4 54.7 16 34.5 10.1 4.3 51.9 15.2 33.3 9.8 4.9 48.8 14.3 32.1 9.4 5.5 47.7 14 31.7 9.3 5.7 45.6 13.4 30.9 9.1 6.1
0.17 72 22.2 59.1 17.3 27.9 8.2 4.3 56 16.4 26.8 7.9 4.9 52.7 15.4 25.6 7.5 5.6 51.5 15.1 25.2 7.4 5.8 49.3 14.4 24.4 7.2 6.2
2000 62 16.7 53.5 15.7 51 15 4.2 50 14.7 49.6 14.5 4.8 46.5 13.6 46.5 13.6 5.4 45.2 13.2 45.2 13.2 5.7 43 12.6 43 12.6 6.1
51060 944 67 19.4 59 17.3 42.2 12.4 4.3 55.8 16.3 41 12 4.9 52.4 15.4 39.8 11.7 5.6 51.1 15 39.3 11.5 5.8 48.4 14.2 38.3 11.2 6.2
0.22 72 22.2 63.3 18.6 32.7 9.6 4.4 59.8 17.5 31.5 9.2 5 56.2 16.5 30.4 8.9 5.7 54.8 16.1 29.9 8.8 6 -- -- -- -- --
2521 62 16.7 54.5 16 54.5 16 4.2 51.1 15 51.1 15 4.8 47.6 13.9 47.6 13.9 5.5 46.3 13.6 46.3 13.6 5.7 44.1 12.9 44.1 12.9 6.1
1190 67 19.4 60.7 17.8 47 13.8 4.4 57.3 16.8 45.8 13.4 5 53.2 15.6 44.3 13 5.6 51.7 15.2 43.8 12.8 5.8 49.1 14.4 42.9 12.6 6.2
0.26 72 22.2 65 19 35.6 10.4 4.4 61.3 18 34.5 10.1 5.1 -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
1769 62 16.7 65.4 19.2 55 16.1 5.5 61.2 17.9 53.2 15.6 6.3 57.1 16.7 51.4 15.1 7.1 55.6 16.3 50.7 14.9 7.3 53 15.5 49.6 14.6 7.8
835 67 19.4 70.8 20.8 46 13.5 5.6 67.2 19.7 44.6 13.1 6.4 63.5 18.6 43.1 12.6 7.2 62.2 18.2 42.6 12.5 7.5 59.7 17.5 41.7 12.2 7.9
0.17 72 22.2 76.4 22.4 36.8 10.8 5.7 72.4 21.2 35.4 10.4 6.5 68.4 20 34.1 10 7.3 67 19.6 33.6 9.8 7.6 -- -- -- -- --
2400 62 16.7 67 19.7 63.5 18.6 5.5 62.9 18.4 61.8 18.1 6.3 59 17.3 59 17.3 7.1 57.5 16.9 57.5 16.9 7.4 55 16.1 55 16.1 7.9
51075 1133 67 19.4 74.4 21.8 52.7 15.4 5.7 70.5 20.7 51.2 15 6.5 66.4 19.5 49.7 14.6 7.3 64.6 18.9 49.1 14.4 7.5 -- -- -- -- --
0.2 72 22.2 79.9 23.4 41 12 5.8 75.6 22.2 39.6 11.6 6.6 71.4 20.9 38.2 11.2 7.4 -- -- -- -- -- -- -- -- -- --
3538 62 16.7 69.5 20.4 69.5 20.4 5.6 65.4 19.2 65.4 19.2 6.4 61.4 18 61.4 18 7.2 60 17.6 60 17.6 7.4 57.4 16.8 57.4 16.8 7.9
1670 67 19.4 77.8 22.8 63.3 18.6 5.8 72.8 21.3 61.5 18 6.6 68 19.9 59.9 17.5 7.3 66.3 19.4 59.3 17.4 7.6 -- -- -- -- --
0.26 72 22.2 83.5 24.5 47.6 14 5.9 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
1769 62 16.7 69.3 20.3 56.7 16.6 5.9 65.2 19.1 54.9 16.1 6.9 60.3 17.7 52.8 15.5 7.9 58.5 17.2 52 15.2 8.2 55.6 16.3 50.7 14.9 8.7
835 67 19.4 74.6 21.9 47.5 13.9 6.1 70.5 20.7 45.9 13.4 7.1 66.3 19.4 44.2 13 8 64.8 19 43.7 12.8 8.3 -- -- -- -- --
0.17 72 22.2 80.2 23.5 38.2 11.2 6.3 75.8 22.2 36.6 10.7 7.2 71.4 20.9 35.1 10.3 8 69.8 20.5 34.5 10.1 8.3 -- -- -- -- --
2900 62 16.7 72.7 21.3 71.7 21 6 67.9 19.9 67.9 19.9 7 63.2 18.5 63.2 18.5 7.9 61.6 18.1 61.6 18.1 8.2 -- -- -- -- --
51080 1369 67 19.4 80.4 23.6 59 17.3 6.3 75.8 22.2 57.4 16.8 7.2 70.8 20.7 55.6 16.3 8 68.8 20.2 54.9 16.1 8.3 -- -- -- -- --
0.23 72 22.2 86 25.2 45.4 13.3 6.5 81.1 23.8 43.8 12.8 7.3 -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
3538 62 16.7 73.8 21.6 73.8 21.6 6.1 69.1 20.2 69.1 20.2 7 64.5 18.9 64.5 18.9 7.9 62.8 18.4 62.8 18.4 8.2 -- -- -- -- --
1670 67 19.4 82.2 24.1 64.9 19 6.4 77 22.6 63 18.5 7.3 71.5 21 61.1 17.9 8 69.6 20.4 60.4 17.7 8.3 -- -- -- -- --
0.26 72 22.2 87.8 25.7 49 14.4 6.6 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
2387 62 16.7 86.6 25.4 73.5 21.5 6.4 81 23.7 71.1 20.8 7.3 75.4 22.1 68.7 20.1 8.2 73.4 21.5 67.8 19.9 8.6 70 20.5 66.4 19.4 9.2
1127 67 19.4 94 27.6 61.5 18 6.5 89.3 26.2 59.6 17.5 7.4 84.3 24.7 57.7 16.9 8.4 82.4 24.2 57 16.7 8.7 79.1 23.2 55.7 16.3 9.3
0.17 72 22.2 101.3 29.7 49.1 14.4 6.6 96.1 28.2 47.3 13.8 7.6 90.7 26.6 45.4 13.3 8.5 88.7 26 44.7 13.1 8.9 85.2 25 43.5 12.8 9.5
3220 62 16.7 88.6 26 84.6 24.8 6.4 83.4 24.4 82.5 24.2 7.3 78 22.9 78 22.9 8.3 76.1 22.3 76.1 22.3 8.6 72.6 21.3 72.6 21.3 9.2
51100 1520 67 19.4 98.6 28.9 70.3 20.6 6.6 93.5 27.4 68.4 20 7.5 87.6 25.7 66.2 19.4 8.5 85.2 25 65.3 19.2 8.8 81.1 23.8 63.9 18.7 9.4
0.2 72 22.2 105.7 31 54.5 16 6.7 100.1 29.3 52.7 15.4 7.6 94.5 27.7 50.9 14.9 8.6 -- -- -- -- -- -- -- -- -- --
4774 62 16.7 92 27 92 27 6.5 86.7 25.4 86.7 25.4 7.4 81.3 23.8 81.3 23.8 8.3 79.3 23.3 79.3 23.3 8.7 75.8 22.2 75.8 22.2 9.3
2253 67 19.4 102.6 30.1 84.6 24.8 6.6 96.2 28.2 82.3 24.1 7.6 89.8 26.3 80.1 23.5 8.5 87.6 25.7 79.4 23.3 8.9 83.6 24.5 78 22.9 9.4
0.26 72 22.2 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
2674 62 16.7 98.3 28.8 82.9 24.3 8 91.3 26.8 79.9 23.4 9.2 84.6 24.8 76.9 22.6 10.4 82.2 24.1 75.9 22.3 10.9 78.2 22.9 74.3 21.8 11.6
1262 67 19.4 106.6 31.3 69.4 20.3 8.1 100.9 29.6 67.1 19.7 9.3 95 27.8 64.8 19 10.5 92.9 27.2 64 18.8 10.8 89.2 26.1 62.6 18.4 11.5
0.17 72 22.2 115.1 33.7 55.6 16.3 8.2 108.9 31.9 53.4 15.6 9.3 102.7 30.1 51.2 15 10.4 100.5 29.4 50.5 14.8 10.7 96.5 28.3 49.1 14.4 11.3
4000 62 16.7 101.6 29.8 100.5 29.5 8 95.1 27.9 95.1 27.9 9.2 88.7 26 88.7 26 10.5 86.4 25.3 86.4 25.3 10.9 82.5 24.2 82.5 24.2 11.6
52115 1888 67 19.4 113.7 33.3 83.2 24.4 8.2 107.4 31.5 80.9 23.7 9.3 99.9 29.3 78.2 22.9 10.4 97.2 28.5 77.3 22.6 10.8 92.5 27.1 75.6 22.2 11.4
0.22 72 22.2 121.9 35.7 64.1 18.8 8.2 115.3 33.8 62 18.2 9.3 -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
5347 62 16.7 104.4 30.6 104.4 30.6 8.1 98 28.7 98 28.7 9.2 91.6 26.8 91.6 26.8 10.5 89.3 26.2 89.3 26.2 10.9 85.3 25 85.3 25 11.5
2524 67 19.4 117.2 34.3 95.5 28 8.2 109.3 32 92.8 27.2 9.3 101.9 29.9 90.2 26.4 10.4 99.3 29.1 89.3 26.2 10.8 94.7 27.8 87.7 25.7 11.3
0.26 72 22.2 125.9 36.9 71.8 21.1 8.3 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
2674 62 16.7 104 30.5 85.5 25 8.2 98.3 28.8 82.9 24.3 9.4 90.7 26.6 79.6 23.3 10.7 88 25.8 78.4 23 11.1 83.3 24.4 76.4 22.4 12
1262 67 19.4 112.5 33 71.8 21 8.4 106.6 31.3 69.4 20.3 9.6 100.4 29.4 66.9 19.6 10.8 98.1 28.7 66 19.3 11.3 93.9 27.5 64.4 18.9 12.1
0.17 72 22.2 121.3 35.6 57.8 16.9 8.5 115 33.7 55.5 16.3 9.7 108.3 31.7 53.2 15.6 11 105.8 31 52.3 15.3 11.5 101.2 29.7 50.7 14.9 12.4
4000 62 16.7 108.6 31.8 103.4 30.3 8.3 101.6 29.8 100.5 29.5 9.5 94.6 27.7 94.6 27.7 10.7 92 27 92 27 11.2 87.5 25.6 87.5 25.6 12
52125 1888 67 19.4 120 35.2 85.6 25.1 8.5 113.6 33.3 83.2 24.4 9.7 106.8 31.3 80.7 23.6 11 103.8 30.4 79.6 23.3 11.4 98.3 28.8 77.6 22.8 12.2
0.22 72 22.2 128.8 37.8 66.4 19.5 8.6 121.7 35.7 64.1 18.8 9.9 114.4 33.5 61.7 18.1 11.3 111.7 32.7 60.8 17.8 11.8 -- -- -- -- --
5347 62 16.7 111.2 32.6 111.2 32.6 8.4 104.5 30.6 104.5 30.6 9.5 97.5 28.6 97.5 28.6 10.8 94.9 27.8 94.9 27.8 11.2 90.3 26.5 90.3 26.5 12
2524 67 19.4 124.5 36.5 98.1 28.7 8.6 117 34.3 95.5 28 9.8 108.6 31.8 92.5 27.1 11 105.5 30.9 91.5 26.8 11.5 100.2 29.4 89.6 26.3 12.3
0.26 72 22.2 133.1 39 74.1 21.7 8.7 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
3438 62 16.7 130.8 38.3 108.6 31.8 10.7 123.3 36.2 105.3 30.8 12.2 114.8 33.7 101.5 29.8 13.8 111.8 32.8 100.2 29.4 14.4 106.5 31.2 98 28.7 15.4
1623 67 19.4 141.5 41.5 91 26.7 10.9 134.5 39.4 88.2 25.8 12.5 127.2 37.3 85.3 25 14.1 124.5 36.5 84.3 24.7 14.7 119.6 35.1 82.4 24.1 15.6
0.17 72 22.2 152.7 44.8 73.1 21.4 11.1 145.1 42.5 70.4 20.6 12.7 137.1 40.2 67.6 19.8 14.4 134.2 39.3 66.6 19.5 14.9 129 37.8 64.8 19 15.8
5000 62 16.7 135.6 39.7 129.5 38 10.8 127.4 37.3 126.2 37 12.3 119.4 35 119.4 35 13.9 116.5 34.1 116.5 34.1 14.5 111.3 32.6 111.3 32.6 15.5
52150 2360 67 19.4 150.3 44.1 107.4 31.5 11.1 142.6 41.8 104.5 30.6 12.7 134.6 39.4 101.6 29.8 14.3 131 38.4 100.2 29.4 14.8 124.7 36.5 98 28.7 15.7
0.21 72 22.2 161.6 47.4 83.3 24.4 11.4 153.1 44.9 80.5 23.6 13 144.6 42.4 77.8 22.8 14.5 141.6 41.5 76.8 22.5 15 -- -- -- -- --
6875 62 16.7 139.4 40.9 139.4 40.9 10.9 131.3 38.5 131.3 38.5 12.4 123.3 36.1 123.3 36.1 14 120.4 35.3 120.4 35.3 14.6 115.1 33.7 115.1 33.7 15.6
3245 67 19.4 156.5 45.9 124.9 36.6 11.2 146.9 43 121.5 35.6 12.8 137.1 40.2 118.1 34.6 14.3 133.6 39.2 116.9 34.3 14.9 127.5 37.4 114.8 33.6 15.8
0.26 72 22.2 167.6 49.1 94.2 27.6 11.5 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --

Table 4
AFR Condenser Entering Air Temperature
See
Model Notes
cfm on
EWB page 10 95°F (35°C) 105°F (40.6°C) 114.8°F (46°C) 118.4°F (48°C) 125°F (51.7°C)
APMR l/s Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI
(BPF) °F °C MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW
3667 62 16.7 144.3 42.3 118 34.6 11 136.6 40 114.5 33.6 12.7 126.8 37.2 110.2 32.3 14.6 123.1 36.1 108.6 31.8 15.4 116.8 34.2 105.9 31 16.5
1731 67 19.4 155.7 45.6 99 29 11.2 147.7 43.3 95.8 28.1 13 139.3 40.8 92.4 27.1 14.9 136.2 39.9 91.2 26.7 15.6 130.5 38.3 89 26.1 16.7
0.17 72 22.2 167.7 49.2 79.7 23.4 11.6 159.1 46.6 76.7 22.5 13.3 150.1 44 73.5 21.5 15.1 146.8 43 72.3 21.2 15.7 140.7 41.2 70.2 20.6 16.6
6000 62 16.7 151.8 44.5 149 43.7 11.2 142.4 41.7 142.4 41.7 12.8 132.9 39 132.9 39 14.8 129.5 38 129.5 38 15.5 123.4 36.2 123.4 36.2 16.6
52170 2832 67 19.4 168.1 49.3 122.8 36 11.6 159.1 46.6 119.6 35 13.3 149.3 43.8 116.1 34 15.1 145.1 42.5 114.6 33.6 15.7 137.8 40.4 112 32.8 16.6
0.23 72 22.2 180.3 52.8 94.7 27.7 12 170.5 50 91.5 26.8 13.6 160.6 47.1 88.3 25.9 15.1 -- -- -- -- -- -- -- -- -- --
7333 62 16.7 154.2 45.2 154.2 45.2 11.2 145 42.5 145 42.5 12.9 135.5 39.7 135.5 39.7 14.8 132.1 38.7 S.K.M Air Conditioning LLC
132.1 38.7 15.5 126 36.9 126 36.9 16.6
3461 67 19.4 172.2 50.5 135 39.6 11.7 162.4 47.6 131.6 38.6 13.4 150.9 44.2 127.6 37.4 15.1 146.8 43 126.1 37 15.7 139.6 40.9 123.7 36.2 16.6
0.26
4278
72
62
22.2 184.3 54
16.7 166.9 48.9 136.9
102.2 30
40.1
12.1
12.9
174.3 51.1
158 46.3
99
133
29
39
13.7
14.7
--
146.6
--
43
--
128
--
37.5
--
16.6
--
142.5 41.8
-- --
126.2
--
37
--
17.3
--
135.4 39.7
-- --
123.1
--
36.1
--
18.5
9
2019 67 19.4 180.2 52.8 114.9 33.7 13.1 171.1 50.2 111.2 32.6 15 161.5 47.3 107.4 31.5 16.9 158 46.3 106 31.1 17.6 151.7 44.5 103.6 30.4 18.8
0.26 72 22.2 133.1 39 74.1 21.7 8.7 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
3438 62 16.7 130.8 38.3 108.6 31.8 10.7 123.3 36.2 105.3 30.8 12.2 114.8 33.7 101.5 29.8 13.8 111.8 32.8 100.2 29.4 14.4 106.5 31.2 98 28.7 15.4
1623 67 19.4 141.5 41.5 91 26.7 10.9 134.5 39.4 88.2 25.8 12.5 127.2 37.3 85.3 25 14.1 124.5 36.5 84.3 24.7 14.7 119.6 35.1 82.4 24.1 15.6
0.17 72 22.2 152.7 44.8 73.1 21.4 11.1 145.1 42.5 70.4 20.6 12.7 137.1 40.2 67.6 19.8 14.4 134.2 39.3 66.6 19.5 14.9 129 37.8 64.8 19 15.8

SKM Packaged Air Conditioners


52150
5000
2360
0.21
62
67
72
16.7
19.4
22.2
135.6
150.3
161.6
39.7
44.1
47.4
129.5
107.4
83.3
38
31.5
24.4
10.8
11.1
11.4
127.4
142.6
153.1
37.3
41.8
44.9
126.2
104.5
80.5
37
30.6
23.6
12.3
12.7
13
119.4
134.6
144.6
35
39.4
42.4
119.4
101.6
77.8
35
29.8
22.8
APMR Series
13.9
14.3
14.5
116.5
131
141.6
34.1
38.4
41.5
116.5
100.2
76.8
34.1
29.4
22.5
14.5
14.8
15
111.3
124.7
--
32.6
36.5
--
111.3
98
--
32.6
28.7
--
15.5
15.7
--
6875 62 16.7 139.4 40.9 139.4 40.9 10.9 131.3 38.5 131.3 38.5 12.4 123.3 36.1 123.3 36.1 14 120.4 35.3 120.4 35.3 14.6 115.1 33.7 115.1 33.7 15.6
3245 67 19.4 156.5 45.9 124.9 36.6 11.2 146.9 43 121.5 35.6 12.8 137.1 40.2 118.1 34.6 14.3 133.6 39.2 116.9 34.3 14.9 127.5 37.4 114.8 33.6 15.8
0.26 72 22.2 167.6 49.1 94.2 27.6 11.5 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --

GROSS CAPACITY RATINGS - 50 Hz


AFR Condenser Entering Air Temperature
Model cfm EWB 95°F (35°C) 105°F (40.6°C) 114.8°F (46°C) 118.4°F (48°C) 125°F (51.7°C)
APMR l/s Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI Total Capacity Sensible Capacity PI
(BPF) °F °C MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW
3667 62 16.7 144.3 42.3 118 34.6 11 136.6 40 114.5 33.6 12.7 126.8 37.2 110.2 32.3 14.6 123.1 36.1 108.6 31.8 15.4 116.8 34.2 105.9 31 16.5
1731 67 19.4 155.7 45.6 99 29 11.2 147.7 43.3 95.8 28.1 13 139.3 40.8 92.4 27.1 14.9 136.2 39.9 91.2 26.7 15.6 130.5 38.3 89 26.1 16.7
0.17 72 22.2 167.7 49.2 79.7 23.4 11.6 159.1 46.6 76.7 22.5 13.3 150.1 44 73.5 21.5 15.1 146.8 43 72.3 21.2 15.7 140.7 41.2 70.2 20.6 16.6
6000 62 16.7 151.8 44.5 149 43.7 11.2 142.4 41.7 142.4 41.7 12.8 132.9 39 132.9 39 14.8 129.5 38 129.5 38 15.5 123.4 36.2 123.4 36.2 16.6
52170 2832 67 19.4 168.1 49.3 122.8 36 11.6 159.1 46.6 119.6 35 13.3 149.3 43.8 116.1 34 15.1 145.1 42.5 114.6 33.6 15.7 137.8 40.4 112 32.8 16.6
0.23 72 22.2 180.3 52.8 94.7 27.7 12 170.5 50 91.5 26.8 13.6 160.6 47.1 88.3 25.9 15.1 -- -- -- -- -- -- -- -- -- --
7333 62 16.7 154.2 45.2 154.2 45.2 11.2 145 42.5 145 42.5 12.9 135.5 39.7 135.5 39.7 14.8 132.1 38.7 132.1 38.7 15.5 126 36.9 126 36.9 16.6
3461 67 19.4 172.2 50.5 135 39.6 11.7 162.4 47.6 131.6 38.6 13.4 150.9 44.2 127.6 37.4 15.1 146.8 43 126.1 37 15.7 139.6 40.9 123.7 36.2 16.6
0.26 72 22.2 184.3 54 102.2 30 12.1 174.3 51.1 99 29 13.7 -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
4278 62 16.7 166.9 48.9 136.9 40.1 12.9 158 46.3 133 39 14.7 146.6 43 128 37.5 16.6 142.5 41.8 126.2 37 17.3 135.4 39.7 123.1 36.1 18.5
2019 67 19.4 180.2 52.8 114.9 33.7 13.1 171.1 50.2 111.2 32.6 15 161.5 47.3 107.4 31.5 16.9 158 46.3 106 31.1 17.6 151.7 44.5 103.6 30.4 18.8
0.17 72 22.2 194.3 57 92.5 27.1 13.4 184.5 54.1 89 26.1 15.2 174.2 51.1 85.4 25 17.2 170.4 50 84.1 24.6 17.9 163.7 48 81.8 24 19
7000 62 16.7 175.3 51.4 173.1 50.7 13 164.7 48.3 164.7 48.3 14.8 154 45.1 154 45.1 16.7 150.1 44 150.1 44 17.4 143.3 42 143.3 42 18.6
52200 3304 67 19.4 194.6 57 142.8 41.8 13.4 184.4 54 139 40.7 15.2 173 50.7 135 39.6 17.1 168.3 49.3 133.3 39.1 17.8 160.2 46.9 130.4 38.2 18.9
0.23 72 22.2 208.7 61.2 109.9 32.2 13.6 197.6 57.9 106.3 31.2 15.5 186.5 54.7 102.8 30.1 17.5 -- -- -- -- -- -- -- -- -- --
8556 62 16.7 178.3 52.2 178.3 52.2 13.1 167.7 49.2 167.7 49.2 14.9 157 46 157 46 16.8 153.2 44.9 153.2 44.9 17.5 146.3 42.9 146.3 42.9 18.6
4038 67 19.4 199.4 58.4 157 46 13.5 187.8 55.1 153 44.8 15.3 174.9 51.3 148.4 43.5 17.2 170.3 49.9 146.9 43 17.9 162.4 47.6 144.1 42.2 19
0.26 72 22.2 213.3 62.5 118.7 34.8 13.7 201.9 59.2 115.1 33.7 15.7 -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
4278 62 16.7 191.1 56 153.8 45.1 15.4 180.1 52.8 148.7 43.6 17.8 166.6 48.8 142.5 41.8 20.2 161.7 47.4 140.3 41.1 21 153.2 44.9 136.6 40 22.4
2019 67 19.4 206.3 60.5 129.8 38.1 15.7 195.1 57.2 125.1 36.7 18.1 183.5 53.8 120.3 35.3 20.5 179.3 52.5 118.6 34.8 21.3 171.9 50.4 115.7 33.9 22.6
0.09 72 22.2 222.5 65.2 105.5 30.9 16 210.3 61.6 100.9 29.6 18.4 197.9 58 96.4 28.2 20.7 193.4 56.7 94.7 27.8 21.5 -- -- -- -- --
7000 62 16.7 203.7 59.7 196.4 57.6 15.6 190.5 55.8 190.5 55.8 18 177.5 52 177.5 52 20.4 172.9 50.7 172.9 50.7 21.2 164.8 48.3 164.8 48.3 22.6
52230 3304 67 19.4 227.1 66.6 163.3 47.9 16.1 214 62.7 158.4 46.4 18.5 198.3 58.1 152.5 44.7 20.7 192.8 56.5 150.5 44.1 21.5 -- -- -- -- --
0.13 72 22.2 243.2 71.3 126.5 37.1 16.6 229.2 67.2 121.8 35.7 18.9 -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
8556 62 16.7 208.2 61 208.2 61 15.7 195.1 57.2 195.1 57.2 18.1 182 53.3 182 53.3 20.5 177.3 52 177.3 52 21.3 169.2 49.6 169.2 49.6 22.6
4038 67 19.4 233.1 68.3 180 52.8 16.3 216.8 63.5 174.2 51 18.6 201.4 59 168.7 49.4 20.8 196.1 57.5 166.8 48.9 21.5 -- -- -- -- --
0.14 72 22.2 249.7 73.2 137.1 40.2 16.9 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
5362 62 16.7 202.4 59.3 168.6 49.4 14.5 190 55.7 163.1 47.8 16.7 176.1 51.6 157.1 46 19.1 171.1 50.2 154.9 45.4 20 162.4 47.6 151.2 44.3 21.5
2531 67 19.4 219.2 64.2 141.3 41.4 14.7 207.9 60.9 136.8 40.1 16.9 195.8 57.4 132 38.7 19.4 191.3 56.1 130.3 38.2 20.2 183.2 53.7 127.2 37.3 21.7
0.17 72 22.2 236.5 69.3 113.5 33.3 15 224.2 65.7 109.1 32 17.3 211.1 61.9 104.5 30.6 19.6 206.3 60.5 102.8 30.1 20.4 197.8 58 99.9 29.3 21.8
8000 62 16.7 210 61.6 203.9 59.7 14.6 197 57.7 197 57.7 16.8 183.8 53.9 183.8 53.9 19.2 179 52.5 179 52.5 20.1 170.5 50 170.5 50 21.6
52240 3776 67 19.4 233.7 68.5 168.8 49.5 14.9 221.2 64.8 164.2 48.1 17.2 206.8 60.6 159 46.6 19.5 200.9 58.9 156.9 46 20.4 190.6 55.9 153.3 44.9 21.8
0.22 72 22.2 250.9 73.5 130.6 38.3 15.3 237.3 69.5 126.1 37 17.6 223.3 65.4 121.6 35.6 19.8 -- -- -- -- -- -- -- -- -- --
10725 62 16.7 215.6 63.2 215.6 63.2 14.6 202.8 59.4 202.8 59.4 16.8 189.5 55.5 189.5 55.5 19.3 184.6 54.1 184.6 54.1 20.1 176 51.6 176 51.6 21.6
5062 67 19.4 242.3 71 194.1 56.9 15.1 226.5 66.4 188.6 55.3 17.3 210.4 61.7 183 53.6 19.6 204.7 60 181.1 53.1 20.4 194.9 57.1 177.7 52.1 21.8
0.26 72 22.2 259.3 76 146.3 42.9 15.6 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
5362 62 16.7 226.3 66.3 186.6 54.7 16.8 210.9 61.8 179.6 52.6 19.4 194.9 57.1 172.4 50.5 22.1 189.2 55.5 169.9 49.8 23.1 179.3 52.6 165.6 48.5 24.8
2531 67 19.4 244.9 71.8 157 46 17.2 231.3 67.8 151.4 44.4 19.9 217.1 63.6 145.6 42.7 22.6 211.8 62.1 143.5 42.1 23.6 202.4 59.3 139.8 41 25.3
0.09 72 22.2 263.7 77.3 126.6 37.1 17.6 248.8 72.9 121.1 35.5 20.3 233.4 68.4 115.5 33.9 23.1 227.7 66.8 113.5 33.3 24 217.7 63.8 110 32.2 25.7
8000 62 16.7 236.6 69.3 227.7 66.8 17.1 221.5 64.9 221.5 64.9 19.6 206.1 60.4 206.1 60.4 22.4 200.6 58.8 200.6 58.8 23.4 190.6 55.9 190.6 55.9 25
52270 3776 67 19.4 264.5 77.5 189.7 55.6 17.6 247.8 72.6 183.4 53.8 20.2 229.1 67.1 176.4 51.7 22.9 222.5 65.2 174 51 23.9 211 61.8 169.8 49.8 25.5
0.12 72 22.2 282.8 82.9 146.9 43 17.9 266.1 78 141.3 41.4 20.7 -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
10725 62 16.7 244.9 71.8 244.9 71.8 17.2 229.6 67.3 229.6 67.3 19.8 214 62.7 214 62.7 22.6 208.2 61 208.2 61 23.5 198.1 58.1 198.1 58.1 25.2
5062 67 19.4 271.6 79.6 218.2 64 17.7 253 74.2 211.7 62 20.4 234.9 68.9 205.3 60.2 23.1 228.5 67 203.1 59.5 24.1 217.3 63.7 199.1 58.4 25.7
0.14 72 22.2 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
5958 62 16.7 254.8 74.7 208.9 61.2 18.6 238.6 69.9 201.5 59.1 21.2 220.5 64.6 193.3 56.7 23.9 214 62.7 190.5 55.8 24.9 202.7 59.4 185.5 54.4 26.7
2812 67 19.4 275.7 80.8 175.9 51.6 19 260.8 76.4 169.8 49.8 21.7 244.9 71.8 163.3 47.9 24.4 239 70.1 160.9 47.2 25.4 228.3 66.9 156.6 45.9 27.1
0.09 72 22.2 297.3 87.1 142.2 41.7 19.4 280.9 82.3 136.1 39.9 22 263.4 77.2 129.8 38 24.8 256.9 75.3 127.5 37.4 25.7 245.3 71.9 123.4 36.2 27.4
9100 62 16.7 267.7 78.5 258 75.6 18.9 250.9 73.5 250.9 73.5 21.5 233.7 68.5 233.7 68.5 24.2 227.4 66.7 227.4 66.7 25.2 216.2 63.4 216.2 63.4 26.9
52300 4295 67 19.4 299.5 87.8 214.9 63 19.4 281.4 82.5 208.1 61 22 259.9 76.2 200.1 58.6 24.7 252.3 73.9 197.3 57.8 25.7 239 70 192.4 56.4 27.3
0.12 72 22.2 320.8 94 166.6 48.8 19.7 301.9 88.5 160.3 47 22.3 -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
11917 62 16.7 276.3 81 276.3 81 19 259.4 76 259.4 76 21.6 241.8 70.9 241.8 70.9 24.4 235.3 69 235.3 69 25.4 223.8 65.6 223.8 65.6 27.1
5624 67 19.4 307.6 90.2 244.6 71.7 19.5 286.6 84 237.1 69.5 22.1 265.7 77.9 229.8 67.4 24.8 258.3 75.7 227.2 66.6 25.8 245.2 71.9 222.6 65.2 27.4
0.14 72 22.2 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
5958 62 16.7 281.1 82.4 221.3 64.9 22.8 266.2 78 214.3 62.8 25.8 250.7 73.5 207 60.7 28.9 244.2 71.6 204 59.8 29.9 231.5 67.9 198.3 58.1 31.8
2812 67 19.4 302.4 88.6 187.3 54.9 23.4 287.2 84.2 180.8 53 26.4 271.4 79.6 174.1 51 29.4 265.6 77.8 171.7 50.3 30.5 255.1 74.8 167.4 49.1 32.4
0.09 72 22.2 326 95.5 153.1 44.9 24 309.5 90.7 146.8 43 26.9 292.5 85.7 140.4 41.2 29.9 286.3 83.9 138.1 40.5 31 274.8 80.5 133.9 39.2 32.8
10500 62 16.7 304.4 89.2 292.4 85.7 23.4 285.8 83.8 284.7 83.5 26.3 267.5 78.4 267.5 78.4 29.3 260.9 76.5 260.9 76.5 30.4 249.2 73 249.2 73 32.2
52340 4955 67 19.4 337.6 98.9 242.5 71.1 24.2 319.4 93.6 235.7 69.1 27.2 298.9 87.6 228 66.8 30.1 290.7 85.2 225 66 31.1 276.5 81 219.8 64.4 32.9
0.13 72 22.2 361.4 105.9 187.7 55 24.6 341.3 100 181.1 53.1 27.6 -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
11917 62 16.7 308.2 90.3 308.2 90.3 23.5 289.8 84.9 289.8 84.9 26.4 271.4 79.6 271.4 79.6 29.4 264.8 77.6 264.8 77.6 30.5 253 74.2 253 74.2 32.3
5624 67 19.4 343.7 100.7 257.7 75.5 24.3 323.8 94.9 250.4 73.4 27.3 301.2 88.3 242.3 71 30.1 293.2 85.9 239.5 70.2 31.1 279.1 81.8 234.5 68.7 32.9
0.14 72 22.2 367.2 107.6 197.2 57.8 24.7 346.7 101.6 190.5 55.8 27.7 -- -- -- -- -- -- -- -- -- -- -- -- -- -- --

Table 5
Notes:
1. See Page 2 for legend.
2. Ratings are based on 80°F (27°C) DB evaporator air entering temperature.
3. Direct interpolation is permissible. Do not extrapolate.
4. SKM Computer Selection Software are available for quick and accurate selections.
5. Capacity is gross capacity which does not include the effect of evaporator fan motor heat.
* Power input (PI) mentioned in this page is for compressor only and should not be used for cable or fuse selection.
MCA and MFA values given in the electrical data (page 12) should be referred for the same.

10
FAN PERFORMANCE - 50 Hz R 22
Internal Static External Static Pressure - in.wg (Pa) REFRIGERANT
Model AirFlowRate RPM Range
Pressure 0.2 (50) 0.4 (100) 0.5 (125) 0.6 (150) 0.8 (200) 1 (250) 1.25 (313)
APMR 50 Hz
cfm l/s in.wg Pa RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1260 595 0.24 59.69 606 0.12 726 0.16 784 0.18 841 0.21 - - - - - - 770
51050 1670 788 0.41 101 723 0.24 819 0.29 865 0.31 910 0.34 999 0.4 1085 0.46 1192 0.55 to
2521 1190 0.96 239.22 1017 0.73 1085 0.81 1118 0.84 1150 0.88 1213 0.96 1275 1.04 1350 1.14 993
1260 595 0.24 59.69 606 0.12 726 0.16 784 0.18 841 0.21 - - - - - -
51060 2000 944 0.59 147.23 833 0.38 916 0.44 956 0.47 995 0.51 1071 0.57 1145 0.64 1237 0.73
2521 1190 0.96 239.22 1017 0.73 1085 0.81 1118 0.84 1150 0.88 1213 0.96 1275 1.04 1350 1.14 809
to
1769 835 0.24 59.71 646 0.22 747 0.27 794 0.3 839 0.32 926 0.38 1011 0.44 1114 0.52
1043
51075 2400 1133 0.43 106.01 803 0.48 883 0.55 922 0.58 959 0.62 1031 0.69 1099 0.77 1181 0.86
3538 1670 0.96 239.14 1130 1.43 1184 1.53 1212 1.58 1239 1.63 1293 1.73 1345 1.84 1409 1.97
1769 835 0.24 59.71 - - 643 0.23 690 0.26 735 0.29 823 0.36 908 0.44 - -
739
51080 2900 1369 0.63 157.7 768 0.61 839 0.7 872 0.74 905 0.79 968 0.88 1028 0.98 1101 1.1 to
3538 1670 0.96 239.14 913 1.06 973 1.17 1001 1.23 1029 1.28 1084 1.39 1136 1.5 1200 1.64 922
2387 1126 0.24 59.71 - - 665 0.37 707 0.4 746 0.44 822 0.52 894 0.6 979 0.7
695
51100 3220 1520 0.42 104.78 713 0.63 784 0.73 818 0.78 851 0.83 915 0.93 976 1.03 1048 1.16 to
4774 2253 0.96 239.15 1006 1.9 1055 2.05 1080 2.12 1104 2.2 1152 2.34 1198 2.49 1255 2.68 866
2674 1262 0.24 59.73 - - 681 0.45 721 0.49 759 0.53 831 0.62 899 0.7 980 0.81
52115 4000 1888 0.52 130.04 816 1.07 875 1.18 904 1.25 933 1.31 989 1.43 1043 1.56 1108 1.71
793
5347 2523 0.96 239.16 1062 2.45 1106 2.6 1128 2.68 1150 2.76 1194 2.92 1237 3.09 1290 3.3
to
2674 1262 0.24 59.73 - - 681 0.45 721 0.49 759 0.53 831 0.62 899 0.7 980 0.81 989
52125 4000 1888 0.52 130.04 816 1.07 875 1.18 904 1.25 933 1.31 989 1.43 1043 1.56 1108 1.71
5347 2523 0.96 239.16 1062 2.45 1106 2.6 1128 2.68 1150 2.76 1194 2.92 1237 3.09 1290 3.3
3438 1622 0.24 59.73 481 0.4 556 0.5 591 0.55 624 0.6 686 0.71 745 0.83 816 0.98
622
52150 5000 2360 0.49 122.56 632 1.07 689 1.21 716 1.28 743 1.35 793 1.49 842 1.64 899 1.83 to
6875 3244 0.96 239.18 838 2.66 881 2.84 901 2.93 922 3.03 962 3.22 1001 3.41 1048 3.65 775
3667 1730 0.21 52.72 - - 662 0.5 711 0.57 758 0.64 849 0.78 937 0.95 1044 1.19
793
52170 6000 2831 0.56 140.61 787 1.32 861 1.52 897 1.62 931 1.72 997 1.93 1061 2.13 1137 2.39 to
7333 3460 0.87 215.63 938 2.32 1000 2.56 1030 2.69 1060 2.81 1117 3.06 1173 3.3 1239 3.61 989
4278 2019 0.21 52.72 - - 673 0.64 719 0.71 763 0.78 847 0.94 927 1.1 1023 1.32
52200 7000 3303 0.56 140.61 824 1.77 893 2.01 926 2.13 958 2.24 1021 2.48 1080 2.71 1152 3.01
8556 4038 0.87 215.67 985 3.13 1042 3.42 1070 3.56 1098 3.7 1152 3.99 1204 4.28 1267 4.64 769
to
4278 2019 0.25 62.7 - - 692 0.67 737 0.74 781 0.81 864 0.97 943 1.13 1038 1.36
993
52230 7000 3303 0.68 168.31 863 1.9 930 2.14 962 2.26 993 2.37 1054 2.61 1113 2.84 1183 3.14
8556 4038 1.04 259.22 1035 3.38 1091 3.67 1118 3.81 1145 3.95 1197 4.24 1248 4.53 1309 4.89
5362 2530 0.21 52.71 466 0.53 553 0.71 594 0.8 632 0.9 707 1.12 778 1.36 865 1.69
52240 8000 3775 0.46 115.22 611 1.44 678 1.69 710 1.82 740 1.95 798 2.22 853 2.49 919 2.86
624
10725 5061 0.87 215.65 787 3.27 839 3.6 864 3.76 889 3.93 936 4.27 982 4.62 1037 5.06
to
5362 2530 0.25 62.68 484 0.56 570 0.75 609 0.84 648 0.94 721 1.16 792 1.41 878 1.75 778
52270 8000 3775 0.55 137.75 642 1.55 707 1.81 737 1.94 767 2.07 823 2.34 878 2.62 943 2.99
10725 5061 1.04 259.19 832 3.56 882 3.89 907 4.06 930 4.23 976 4.57 1021 4.92 - -
5958 2812 0.25 62.69 493 0.67 576 0.87 614 0.97 650 1.07 720 1.3 786 1.54 866 1.87
700
52300 9100 4294 0.58 144.92 672 2.02 733 2.3 762 2.44 790 2.58 843 2.88 895 3.18 956 3.57 to
11917 5624 1.04 259.2 856 4.36 904 4.71 927 4.9 - - - - - - - - 872
5958 2812 0.25 62.69 493 0.67 576 0.87 614 0.97 650 1.07 720 1.3 786 1.54 866 1.87 750
52340 10500 4955 0.79 197.64 762 3.03 816 3.34 842 3.51 867 3.67 916 4 963 4.34 1019 4.77 to
11917 5624 1.04 259.2 856 4.36 904 4.71 927 4.9 - - - - - - - - 935
Table 6
Notes:
1. Areas shaded in blue indicate factory setting of RPM.
2. Areas shaded in grey indicate operating range outside the standard motor. Shift to larger motor size in this area.
3. Internal static pressure is based on pressure drops through evaporator coil, fan casing and 1” flat filter.
4. The shown RPM range is with standard pulleys combination.

S.K.M Air Conditioning LLC


11
SKM Packaged Air Conditioners APMR Series

ELECTRICAL DATA
Power Supply: 380~415V/3PH/50Hz
Unit Characteristic Compressor Condenser Fan Motor Evaporator Fan Motor
Model APMR
MFA MCA ICF QTY RLA LRA QTY FLA LRA FLA LRA
51050 32 17 68 1 11 64 1 0.9 2.6 1.4 7.3
51060 32 19 79 1 12 74 2 0.9 2.6 1.4 7.3
51075 40 22 106 1 14 101 2 0.9 2.6 1.9 9.7
51080 40 25 101 1 16 95 2 0.9 2.6 2.6 14.8
51100 50 29 117 1 19 111 2 0.9 2.6 2.6 14.8
52115 50 30 82 2 11 64 2 0.9 2.6 3.4 18.8
52125 50 33 94 2 12 74 2 1.2 3.6 3.4 18.8
52150 63 39 125 2 14 101 2 1.2 3.6 4.8 27.1
52170 63 46 127 2 16 95 2 2.2 9.0 4.8 27.1
52200 80 54 148 2 19 111 2 2.2 9.0 6.6 42.6
52230 80 56 156 2 20 118 2 2.2 9.0 6.6 42.6
52240 80 60 165 2 20 118 2 4.0 16.5 6.6 42.6
52270 100 62 166 2 21 118 2 4.0 16.5 6.6 42.6
52300 100 71 192 2 25 140 2 4.0 16.5 6.6 42.6
52340 125 82 232 2 29 174 2 4.0 16.5 8.6 53.6
Table 7

Power Supply: 440V/3PH/50Hz


Unit Characteristic Compressor Condenser Fan Motor Evaporator Fan Motor
Model APMR
MFA MCA ICF QTY RLA LRA QTY FLA LRA FLA LRA
51050 32 16 68 1 11 64 1 0.9 2.6 1.3 6.7
51060 32 19 79 1 12 74 2 0.9 2.6 1.3 6.7
51075 40 21 106 1 14 101 2 0.9 2.6 1.7 8.8
51080 40 25 101 1 16 95 2 0.9 2.6 2.3 13.5
51100 50 28 117 1 19 111 2 0.9 2.6 2.3 13.5
52115 50 30 82 2 11 64 2 0.9 2.6 3.1 17.0
52125 50 33 94 2 12 74 2 1.2 3.6 3.1 17.0
52150 63 39 124 2 14 101 2 1.2 3.6 4.4 24.6
52170 63 46 127 2 16 95 2 2.5 8.8 4.4 24.6
52200 80 54 147 2 19 111 2 2.5 8.8 6.0 38.8
52230 80 56 155 2 20 118 2 2.5 8.8 6.0 38.8
52240 80 59 162 2 20 118 2 3.7 14.0 6.0 38.8
52270 100 61 163 2 21 118 2 3.7 14.0 6.0 38.8
52300 100 70 189 2 25 140 2 3.7 14.0 6.0 38.8
52340 125 81 229 2 29 174 2 3.7 14.0 7.9 48.7

Table 8

Legend
MFA Maximum Fuse Amps (for fuse/circuit breaker sizing), RLA Rated Load Amps. (at worst operating condition)
complies with NEC Article 440-22 & 430-52. LRA Locked Rotor Amps
FLA Full Load Amps
MCA Minimum Circuit Amps.(for wire sizing), complies with NEC
article 440-33.
ICF Maximum Instantaneous Current Flow

Note : Voltage imbalance not to exceed ± 2 % of the rated voltage.

12
Field Connections R 22
REFRIGERANT
APMR series self-contained heavy field wiring
duty air cooled packaged units are designed for minimum field interaction. Power hook ups and
control wiring of room thermostat as per field wiring diagrm is all that is required to electrically connect any model of APMR series.
Every APMR series packaged air conditioning unit requires, at most,field installed fused disconnect switches or circuit breakers and
room thermostat.

Refer below for schematic representation of required field electrical hook-ups for a standard APMR series packaged air conditioning
unit. All field wiring must be done in accordance with applicable local & national codes. 19 & 20.

For the maximum fuse ampere for fuse sizing & minimum circuit amps for cable sizing, see page 12.

The APMR series is then ready to provide cooling, on demand.

S.K.M Air Conditioning LLC


13
SKM Packaged Air Conditioners APMR Series

Typical Wiring Diagram


APMR Model - 51050

APMR MODEL: 51005


PTB
*POWER SUPPLY(V/Ph/Hz)
**L1
L2
L3
N
E C1 C2

OL

HPS

LPS
OL
CS
L3
L1 L2

THERMOSTAT ( BY OTHERS )
CM CFM EFM
R C G Y

(HP 1)

HP 1

(HP 2)

HP 2

LP 1

LP 2
(ON / OFF)

(LP 1)

(LP 2)
ON / OFF
MCB
RLY1

R
C
C1
FAN2
OUT

RLY2

G
W2 W1 Y2 Y1
FAN1
OUT

RLY3

ECB
X2

CTB
RLY4
X1

RLY5
HTR2

P-COM1
RLY6
INFAN HTR1

LEGEND
RLY7

OD

FIELD WIRING & FIELD SUPPLIED DEVICES


RLY8
P2

LPS LOW PRESSURE SWITCH


1234
RLY9

HPS HIGH PRESSURE SWITCH


P1

ID
S1

CS CONTROL SWITCH
RLY10
CM2

CCH CRANK CASE HEATER


CCH

CM1

RLY11

MCB MINIATURE CIRCUIT BREAKER


EFM EVAPORATOR FAN MOTOR
CM+CFM

L1

T5A L250V

OL OVERLOAD RELAY
EFM

F1

SEC1

CFM CONDENSER FAN MOTOR


N1
PRI1

C2 C1 CM COMPRESSOR MOTOR

CONTROL CIRCUIT C CONTACTOR


BLACK
ECB ELECTRONIC CONTROL BOARD
10V
220~240V

RED BLACK
PTB POWER TERMINAL BLOCK
WHITE
RED
24V

CTB CONTROL TERMINAL BLOCK


TFR WHITE

TFR TRANSFORMER

APMR Models - 51060, 51075, 51080 & 51100 NOTE

APMR MODEL: 51006, 51075, 51080 & 51100 * TYPICAL WIRING DIAGRAM SHOWN IS SUITABLE FOR 380~415V/3Ph/50Hz
ONLY, FOR 440V/3Ph/50Hz PLEASE CONSULT SKM

PTB
*POWER SUPPLY(V/Ph/Hz) ** PROVIDE OVERCURRENT, EARTH FAULT PROTECTION, SHORT CIRCUIT AND

**L1 DISCONNECT MEANS AS REQUIRED BY LOCAL & NATIONAL ELECTRIC CODE.


L2
L3
N
E C1 C2
OL

HPS

LPS

OL CS
L3
L1 L2

THERMOSTAT ( BY OTHERS )
CM CFM1 CFM2 EFM R C G Y
(HP 1)

HP 1

(HP 2)

HP 2

LP 1

LP 2
(LP 1)

(LP 2)
(ON / OFF)

ON / OFF

MCB
RLY1

R
C
FAN2
OUT

RLY2

C1
G
Y1
FAN1
OUT

RLY3

ECB
W2 W1 Y2
X2

CTB
RLY4
X1

RLY5
HTR2

P-COM1
RLY6
INFAN HTR1

RLY7

OD
RLY8
P2

1234
RLY9
P1

ID
S1
RLY10
CM2
CCH

CM1

RLY11
CM+CFM1+CFM2

L1

T5A L250V
EFM

F1

SEC1
N1
PRI1

C2 C1

CONTROL CIRCUIT
BLACK
10V
220~240V

RED BLACK

WHITE
RED
24V

TFR WHITE

14
Typical Wiring Diagram R 22
REFRIGERANT
APMR Models - 52115, 52125 & 52150
APMR MODEL: 52115, 52125 & 52150
PTB
*POWER SUPPLY(V/Ph/Hz)
**L1
L2
L3
N

E C5
C1 C2 C3 C4

HPS1

HPS2

LPS1

LPS2
OL
OL CS

L3 L3
L1 L2 L1 L2 THERMOSTAT ( BY OTHERS )
R C G Y1 Y2
CM1 CM2 CFM1 CFM2 EFM

(HP 1)

HP 1

(HP 2)

HP 2

LP 1

LP 2
(ON / OFF)

(LP 1)

(LP 2)
ON / OFF
MCB

RLY1

R
C
FAN2
OUT

RLY2
C1 C2

G
W2 W1 Y2 Y1
FAN1
OUT

RLY3
ECB
FCS1

FCS2

X2
CTB

RLY4
X1

RLY5
HTR2

P-COM1
RLY6
INFAN HTR1

RLY7
LEGEND

OD
RLY8
FIELD WIRING & FIELD SUPPLIED DEVICES
P2

1234
RLY9 LPS LOW PRESSURE SWITCH
P1

ID
HPS HIGH PRESSURE SWITCH

S1
RLY10
CM2

CS CONTROL SWITCH
CCH CRANK CASE HEATER
CCH1

CCH2

CM1

RLY11

MCB MINIATURE CIRCUIT BREAKER


EFM EVAPORATOR FAN MOTOR
L1

T5A L250V
CFM1

OL OVERLOAD RELAY
CFM2

F1
CM2

CM1
EFM

SEC1
N1
PRI1

C4 C3 C5 C2 C1 CFM CONDENSER FAN MOTOR


CM COMPRESSOR MOTOR
CONTROL CIRCUIT
BLACK
C CONTACTOR
10V

ECB ELECTRONIC CONTROL BOARD


220~240V

RED BLACK

WHITE
PTB POWER TERMINAL BLOCK
24V

RED

TFR WHITE
CTB CONTROL TERMINAL BLOCK
TFR TRANSFORMER
TK THERMAL OVERLOAD PROTECTOR

APMR Models - 52170 to 52270


NOTE

* TYPICAL WIRING DIAGRAM SHOWN IS SUITABLE FOR 380~415V/3Ph/50Hz

APMR MODEL: 52170 ~ 52270


ONLY, FOR 440V/3Ph/50Hz PLEASE CONSULT SKM

PTB
*POWER SUPPLY(V/Ph/Hz) ** PROVIDE OVERCURRENT, EARTH FAULT PROTECTION, SHORT CIRCUIT AND
**L1 DISCONNECT MEANS AS REQUIRED BY LOCAL & NATIONAL ELECTRIC CODE.
L2
L3
N
E C5
C1 C2 C3 C4
HPS1

HPS2

LPS1

LPS2
OL

OL CS

L3 L3
L1 L2 L1 L2
THERMOSTAT ( BY OTHERS )

CM1 CM2 CFM1 CFM2 EFM R C G Y1 Y2


TK-2
TK-1

HP 1

HP 2

LP 1

LP 2
(LP 1)

(LP 2)
(HP 1)

(HP 2)
(ON / OFF)

ON / OFF

MCB
RLY1

R
C
FAN2
OUT

RLY2

C1 C2
G
W2 W1 Y2 Y1
FAN1
OUT

RLY3

ECB
FCS1

FCS2

X2

CTB
RLY4
X1

RLY5
HTR2

P-COM1
RLY6
INFAN HTR1

RLY7

OD
RLY8
TK-2

TK-1

P2

1234
RLY9
P1

ID
S1
RLY11 RLY10
CM2
CCH1

CCH2

CM1
L1

T5A L250V
CFM1
CFM2

F1
CM2

CM1
EFM

SEC1
N1
PRI1

C4 C3 C5 C2 C1

CONTROL CIRCUIT
BLACK
10V
220~240V

RED BLACK

WHITE
24V

RED

S.K.M Air Conditioning LLC


15
SKM Packaged Air Conditioners APMR Series

Typical Wiring Diagram


APMR Models - 52300 & 52340
APMR MODEL: 52300 & 52340
PTB
*POWER SUPPLY(V/Ph/Hz)
**L1
L2
L3
N
E C5
CS

HPS1

HPS2
C3 C4

LPS1

LPS2
OL
C1 C2

OL

L3 L3
L1 L2 L1 L2
THERMOSTAT ( BY OTHERS )

CM1 CM2 CFM1 CFM2 R C G Y1 Y2


EFM
TK-2
TK-1

(HP 1)

HP 1

(HP 2)

HP 2

LP 1

LP 2
(LP 1)

(LP 2)
ON / OFF
(ON / OFF)
MCB

RLY1

R
C
FAN2
OUT

RLY2
C1 C2 C1 C2

G
W2 W1 Y2 Y1
FAN1
OUT

RLY3
ECB
FCS1

FCS2

X2
CTB

RLY4
X1

RLY5
HTR2

P-COM1
RLY6
INFAN HTR1

LEGEND

RLY7
FIELD WIRING & FIELD SUPPLIED DEVICES

OD
RLY8
TK-2

TK-1

LPS LOW PRESSURE SWITCH


P2

1234
HPS HIGH PRESSURE SWITCH
RLY9
P1

ID
CS CONTROL SWITCH

S1
RLY10
CM2

CCH CRANK CASE HEATER


MCB MINIATURE CIRCUIT BREAKER
CCH1

CCH2

CM1

RLY11

EFM EVAPORATOR FAN MOTOR


LSV1 LSV2
OL OVERLOAD RELAY
L1

T5A L250V
CFM1

CFM CONDENSER FAN MOTOR


CFM2

F1
CM2

CM1
EFM

SEC1
N1
PRI1

C4 C3 C5 C2 C1 CM COMPRESSOR MOTOR
C CONTACTOR
CONTROL CIRCUIT
BLACK
ECB ELECTRONIC CONTROL BOARD
10V

RED PTB POWER TERMINAL BLOCK


220~240V

BLACK

RED
WHITE
CTB CONTROL TERMINAL BLOCK
24V

TFR WHITE
LSV LIQUID LINE SOLENOID VALVE
TFR TRANSFORMER
TK THERMAL OVERLOAD PROTECTOR

NOTE

* TYPICAL WIRING DIAGRAM SHOWN IS SUITABLE FOR 380~415V/3Ph/50Hz


ONLY, FOR 440V/3Ph/50Hz PLEASE CONSULT SKM

** PROVIDE OVERCURRENT, EARTH FAULT PROTECTION, SHORT CIRCUIT AND


DISCONNECT MEANS AS REQUIRED BY LOCAL & NATIONAL ELECTRIC CODE.

16
Dimensional Data R 22
REFRIGERANT
APMR Model - 51050

APMR Models - 51060 to 52115


DIMENSIONS
Model
APMR
L W A B C D J G

50.6 30 22 12.2 22 11.38 13.03


51060
61.5 [1285] [762] [559] [309] [559] [289] [331]
[1562] 50.6 38.6 24 10.2 22 11.38 13.03
51075
[1285] [980] [610] [259] [559] [289] [331]
50.6 38.6 24 8.1 28 13.43 15.55
51080
[1285] [980] [610] [207] [711] [341] [395]
67.5 62 50 25 7.1 28 13.43 15.55
51100
Table 9

[1714] [1575] [1270] [635] [181] [711] [341] [395]


68 56 25 7.1 28 13.43 15.55
*52115
[1727] [1422] [635] [181] [711] [341] [395]

*MODEL WITH TWO COMPRESSOR ALL DIMENSIONS ARE IN INCHES[MM]

S.K.M Air Conditioning LLC


17
SKM Packaged Air Conditioners APMR Series

Dimensional Data
APMR Models - 52125 & 52150

DIMENSIONS
Model
APMR

Table 10
L A B C D J G H

75 56 25 7.1 28 13.43 15.55 52.2


52125
[1905] [1422] [635] [181] [711] [341] [395] [1327]
77 60 30 8.5 30 15.91 18.5 61.12
52150
[1956] [1524] [762] [216] [762] [404] [471] [1552]
ALL DIMENSIONS ARE IN INCHES[MM]

APMR Models - 52170 to 52270

DIMENSIONS
Model
APMR
L W A B D J E H C H1

75 75 60 32 28 13.43 43.7 59.63 7.5 62.14


52170
[1905] [1905] [1524] [813] [711] [341] [1109] [1515] [191] [1578]
85 80 70 32 28 13.43 43.7 59.63 7.5 62.14
52200
[2159] [2032] [1778] [813] [711] [341] [1109] [1515] [191] [1578]
85 80 70 32 28 13.43 43.7 59.63 7.5 62.14
52230
[2159] [2032] [1778] [813] [711] [341] [1109] [1515] [191] [1578]
Table 11

101.6 88 78 36 38.6 15.91 52.3 67.11 8.5 63.9


52240
[2580] [2235] [1981] [914] [980] [404] [1328] [1705] [216] [1622]
101.6 88 78 36 38.6 15.91 52.3 67.11 8.5 63.9
52270
[2580] [2235] [1981] [914] [980] [404] [1328] [1705] [216] [1622]

ALL DIMENSIONS ARE IN INCHES[MM]

18
Dimensional Data R 22
REFRIGERANT
APMR Models - 52300 & 52340

S.K.M Air Conditioning LLC


19
SKM Packaged Air Conditioners APMR Series

Loading Points
MODEL LOAD AT EACH POINT Lbs (Kgs) TOTAL
APMR A1 A2 A3 A4 WEIGHT
163 178 166 166 673
51050
[74] [81] [75] [75] [305]
187 220 186 190 783
51060
[85] [100] [84] [86] [355]
189 220 194 197 800
51075
[86] [100] [88] [89] [363]
200 255 213 219 887
51080
[91] [116] [96] [99] [402]
255 292 247 251 1045
51100
[116] [132] [112] [114] [474]
285 351 279 292 1207
52115
[129] [159] [127] [132] [547]
377 383 324 344 1428
52125
[171] [174] [147] [156] [648]
378 385 343 362 1468
52150
[172] [175] [155] [164] [666]
432 440 396 421 1689
52170
[196] [200] [179] [191] [766]
503 511 463 489 1966
52200
[228] [232] [210] [222] [892]
504 512 480 507 2003
52230
[228] [232] [217] [230] [907]
543 551 521 545 2160
52240
[246] [250] [236] [247] [979]
550 558 541 566 2215
52270
[249] [253] [245] [257] [1004]
621 484 636 616 2357
52300
[282] [220] [288] [280] [1070]
690 553 667 649 2559
52340
[313] [251] [302] [294] [1160]
Table 12

20
Recommended Clearances R 22
REFRIGERANT

MODEL MODEL
A B C A B C
APMR APMR
44 72 60
51050 52125
[1118] 34 [1829] [1524]
[864]
51060 52150
64
[1626]
51075 52170
42
52 [1067] 88 52 88
51080 52200
[1321] [2235] [1321] 74 [2235]
54 [1880]
51100 52230
[1372]
Table 13

60
52115 52240
[1524]
ALL DIMENSIONS ARE IN INCHES [MM] 82
52270
[2083]
52300
68 120
[1727] [3048]
52340
ALL DIMENSIONS ARE IN INCHES [MM]

S.K.M Air Conditioning LLC


21
SKM Packaged Air Conditioners APMR Series

Recommended Clearances
B C MODEL A B C
APMR
72 60
52125
34 [1829] [1524]
[864]
52150
64
[1626]
52170
42
[1067] 88 52 88
52200
[2235] [1321] 74 [2235]
54 [1880]
52230
[1372]
60
52240
[1524]
N INCHES [MM] 82
52270
[2083]

Table 14
52300
68 120
[1727] [3048]
52340
ALL DIMENSIONS ARE IN INCHES [MM]

APMR-52125 &52150

22
Installation and Commissioning R 22
REFRIGERANT
• Install the unit in such a location which is flat and strong enough to support its weight.
• Provide a trap of over 2" (50mm) in the drain piping for water seal.
• All field wiring must comply with applicable local and national codes.
• Service spacing should be provided as shown in the figure. If any obstacles are around the unit, distributed air is short-circuited
INSTALLATION & COMMISSIONING
so that the unit stops frequently and access to the unit is difficult for inspection and aftersales services.

CONTROL No obstacle
PANEL BOX

3000
SPACING FOR AIRFLOW
POWER
SOURCE
CONTROL
CIRCUIT AIR IN
SPACING FOR SERVICE

S.AIR
AIR IN * SPACING FOR SERVICE FOR APMR- 52300 & 52340

R.AIR

No obstacle

APMR- 51050 CONTROL APMR- 51060 to 52115


PANEL BOX

3000
AIR OUT

POWER
SOURCE
CONTROL
CIRCUIT
AIR OUT AIR IN

S.AIR
No obstacle
AIR IN

AIR OUT CONTROL R.AIR


3000

AIR IN CONTROL CIRCUIT


AIR IN PANEL BOX
AIR OUT

POWER
SOURCE

AIR IN

S.AIR

AIR IN
R.AIR

APMR- 52125 & 52150 No obstacle


3000

AIR OUT
CONTROL CONTROL
AIR IN
AIR IN PANEL BOX CIRCUIT
AIR OUT

POWER
SOURCE

AIR IN

S.AIR *
S.AIR

R.AIR

APMR- 52170 to 52340

S.K.M Air Conditioning LLC


23
SKM Packaged Air Conditioners APMR Series

GUIDE SPECIFICATIONS
GENERAL
Packaged Air Conditioners shall be composed of REFRIGERANT PIPING
compressor(s), condenser & evaporator coils with fans, refrigerant The refrigerant circuit piping shall be fabricated from ACR grade
piping, electrical components & enclosing cabinet in one piece. copper piping, with 1 & 2 refrigeration circuits, each liquid line
These units shall be factory assembled, internally wired, fully shall include filter drier and thermostatic expansion valve.
refrigerant charged with R410A, tested under strict quality
standards & are suitable for outdoor installation on rooftop or Suction line shall be insulated with ½” (12mm) wall thickness
ground level with ducted system. enclosed cell pipe insulation with maximum K factor
0.28 Btu.in /ft2 .h.°F. (0.040 W/mK).
COMPRESSOR(S)
Compressor shall be hermetic scroll, refrigerant gas cooled
furnished with internal overload protection device, crankcase
heater, and shall be mounted on rubber isolators.
CASING
Casing shall be made of hot dip galvanized (zinc coated),
phosphatized steel sheets which are then electrostatically
polyester powder coated to provide an extremely tough, scratch
resistance & excellent anti-corrosive protection. Casing shall
CONDENSER COIL(S)
pass1000 hours in 5% salt spray testing at 95°F (35°C) & 95%
Condenser coils shall be air cooled with integral sub cooler,
relative humidity as per ASTM B117. Evaporator section shall
constructed of special inner grooved seamless copper tubes
be sealed with vinyl gaskets & completely insulated faced with
3/8” OD mechanically expanded into corrugated aluminum cross
black glass tissue (BGT) heavy density, fire retardant, permanent
fins with maximum 16 fpi (1.6mm) spacing. These coils shall be
odorless fiberglass insulation of minimum 1” (25 mm) thickness
tested against leakage by high air pressure air 715psig (4930kPa)
and 32 kg/m3 density having maximum k factor 0.23 Btu.in/ft2
under water, cleaned & dehydrated at the factory.
h°f. (0.033 W / m °k). Unit casing shall be provided with access
panels for easy service and maintenance of all unit parts.

CONDENSER FAN(S) & MOTOR(S)


Condenser Fans shall be direct driven propeller type discharging
air vertically upward, equipped with statically & dynamically
FILTER SECTION
Flat Filter Section incorporating 1” (25mm) thick is provided as
balanced aluminum alloy blades, inherent corrosion resistant
standard and 2” (50mm) thick filter having an average arrestance
shaft & PVC coated steel wire fan guard. Condenser fan
efficiency of 54% as per ASHRAE Standard 52.1 or equivalent
motor(s) shall be Totally Enclosed Air Over (TEAO), 4 pole or 6
can be provided as an option.
pole with class-F insulation, minimum IP-54 protection & wired
to unit control panel.

CONTROL PANEL
The panel shall be factory wired and confirm to IP-54 requirements.
EVAPORATOR COIL
Control panel shall contain compressor and motor starting
Evaporator coil shall be constructed of Hi-X copper tubes 3/8”
contactors, electronic control board for unit operation, compressor
OD mechanically bonded to aluminum (copper) corrugated fins
anti-recycle time delay, control on/off switch, control circuit breaker
with maximum 14 fpi (1.8mm) spacing. Coil consists of headers of
and power & control terminal blocks. High and Low pressure
seamless copper tubing, thermostatic expansion valve(s) & multi-
switches should be provided for protection.
circuited distributor(s). These coils shall be tested against leakage
by high air pressure 450psig(3100kPa) under water, cleaned &
dehydrated at the factory. Coil shall conform to AHRI-410.

EVAPORATOR FAN & MOTOR


Fans of evaporator shall be forward curved, double inlet double
width (DIDW), centrifugal type, statically & dynamically balanced,
mounted on a single heavy duty shaft with permanently lubricated
bearings and belt driven by V belts with an adjustable variable
pitch motor pulley. Motor shall be Totally Enclosed Fan Cooled
(TEFC), 4 poles, class-F insulated, minimum IP55 protection &
wired to unit control panel.

24
R 22
NOTES REFRIGERANT

S.K.M Air Conditioning LLC


25
SKM Packaged Air Conditioners APMR Series

NOTES

26
R 22
NOTES REFRIGERANT

S.K.M Air Conditioning LLC


27
SKM Packaged Air Conditioners
CONTACT
APMR Series
US
HEAD OFFICE

P.O Box: 6004, Sharjah,


United Arab Emirates

Tel: +971 6 514 3333


Fax: +971 6 514 3300

Email: sales@skmaircon.com
Email: info@skmaircon.com

Spare Parts Division


spareparts.skm@skmaircon.com

Service Center
aftersales.skm@skmaircon.com

For SKM Regional Offices & Distributors


visit: www.skmaircon.com

075/2021A
Supersedes # 075/2021
28

You might also like