Dog Wash Details: Window Notes
Dog Wash Details: Window Notes
Dog Wash Details: Window Notes
MEC DESIGN
6187 NW 167 STREET SUITE: H24
MIAMI, FLORIDA 33015
OFFICE: 305.356.1775
WWW.MECDESIGNMIAMI.COM
ID0001355
AR0007205 / PE31509
HOMERO CRUZ, L.I.D.
MANUEL A. VEGA, A.R.
JOSE A. MARTINEZ, P.E.
SEAL:
JOSE A. MARTINEZ
PROJECT NAME:
PROJECT ADDRESS:
PVC-1
PVC-1 SS-1
PVC-1
SEAMS
GFI OUTLET W/ OUTDOOR
COVER TO POWER DRYER
NEW CHASE WALL FOR
PLUMBING AND
SS-1
ELECTRICAL. WALL TO 8" 16" 16" 16" 12" 16" 16" 16" 8" GROOMING DRYER
TERMITE PROTECTION BE PAINTED.
SWITCH ALONG OUTSIDE WALL TO
HOOK FOR LEASHES - 5'-2" 4'-2" TURN ON DRYER. AT 48" AFF TO DRAWN BY:
TWO (2) AT EACH CENTER LINE. TYP. EACH SIDE
SWITCH ALONG OUTSIDE WALL TO
FVD
SHOWER BAY.
10'-0"
10'-0"
TURN ON DRYER. AT 48" AFF TO
CENTER LINE.
FAUCET FILE No.:
TYP. DOG WASH SINK - 48" LEFT SIDE (223-032)
1/2"
12 1/2" 12 1/2"
SS-1
CHECKED BY:
H.C.
4'-11 3/4"
±3"
16"
DATE:
4'-0"
3'-5 1/2"
GATE
07/10/2023
3'-2 1/4"
3'-6"
NOT
SHOWN
FOR
CLARITY
DOG WASH STATION FINISH: ACCESS DOOR SWINGS
GATE & PARTITION DETAIL SHEET TITLE:
TOWARD FAUCET WALL.
NOTE DIMENSIONS: DOG WASH DETAILS Printed copies of this document are not
considered signed and sealed and the
SHEET:
18 18 18
8 7 3
15 14 6 4 9 15
CL 2"
17" MIN. CLEAR 12"
5
34" MAX.
14 17 MAX.
5'-0"
3'-0" MIN.
1
8" 4'-0" MIN.
CL
MEC DESIGN
34" MAX.
MIN. 2
33"-36"
33"-36"
29" MIN.
KNEE
2'-4"
SPACE 13
17"-19"
Hi-Lo DRINKING FOUNTINS DETAIL 6187 NW 167 STREET SUITE: H24
Scale: N.T.S. MIAMI, FLORIDA 33015
1'-3" 16"-18"
OFFICE: 305.356.1775
ELEVATION C ELEVATION B ELEVATION A
MIN.
WWW.MECDESIGNMIAMI.COM
ID0001355
AR0007205 / PE31509
BATHROOM ELEVATIONS (HANDICAP ACCESSIBLE) HOMERO CRUZ, L.I.D.
MANUEL A. VEGA, A.R.
Scale: N.T.S. JOSE A. MARTINEZ, P.E.
SEAL:
1 12
2 13
3 14
4
15
5 METAL STUDS
6
WOOD BLOCK
FRAME
DOOR
7 16
8 JOSE A. MARTINEZ
17 DOOR
9 THRESHOLD PROJECT NAME:
18
10
11
MAX.
1/4"
GYPSUM
Leesburg Square Store
WALLBOARD
PROJECT ADDRESS:
HEAD/JAM/THRESHOLD DETAIL
Scale: N.T.S. 2219 CITRUS BOULEVARD
LEESBURG, FL 34748
REVISION
DATE BY
NO.
A B C
FILE No.:
8"
(223-032)
CHECKED BY:
H.C.
A B C DATE:
07/10/2023
8"
SHEET TITLE:
RESTROOMS
TO CENTERLINE
D E NOTE DIMENSIONS:
60" A.F.F.
DETAILS
This item has been digitally signed and
sealed by Jose A. Martinez, PE.
SHEET:
Printed copies of this document are not
considered signed and sealed and the
1
76'-6"
MEC DESIGN
12'-11"
6187 NW 167 STREET SUITE: H24
MIAMI, FLORIDA 33015
OFFICE: 305.356.1775
WWW.MECDESIGNMIAMI.COM
7'-8" 15'-4" 15'-4" 15'-4" 15'-4" 7'-8" ID0001355
AR0007205 / PE31509
HOMERO CRUZ, L.I.D.
24'-1"
SEAL:
VD
M
O/A
3,878 CFM
20'-0"
2 JOSE A. MARTINEZ
PROJECT NAME:
61'-1"
60'-2"
Leesburg Square Store
19'-7"
PROJECT ADDRESS:
VD
M
THIS DRAWING CONTAINS
PROPRIETARY INFORMATION AND IS
20'-0"
O/A THE PROPERTY OF "MEC DESIGN
4,266 CFM CONSULTANTS, INC." AND MAY NOT
BE REPRODUCED OR DISTRIBUTED
3 WITHOUT THE WRITTEN
PERMISSION OF "MEC DESIGN
CON SULTANTS, INC."
REVISION
DATE BY
NO.
16'-1"
7'-3"
4'-4" 7'-8" 15'-4" 15'-4" 15'-4" 15'-4" 7'-8"
DRAWN BY:
FVD
4
FILE No.:
(223-032)
CHECKED BY:
H.C.
DATE:
07/10/2023
MECHANICAL PLAN
SALES AREA
This item has been digitally signed and
sealed by Jose A. Martinez, PE.
SHEET:
Printed copies of this document are not
considered signed and sealed and the
signature must be verified on any
electronic copies. M-501
A B C D
89'-8"
27'-0" 30'-1" 30'-10"
1
76'-6"
MEC DESIGN
9'-0"
6187 NW 167 STREET SUITE: H24
MIAMI, FLORIDA 33015
52'-2" 5'-0" 31'-2" OFFICE: 305.356.1775
WWW.MECDESIGNMIAMI.COM
ID0001355
AR0007205 / PE31509
HOMERO CRUZ, L.I.D.
MANUEL A. VEGA, A.R.
24'-1"
7'-10"
JOSE A. MARTINEZ, P.E.
SEAL:
17'-2"
2 JOSE A. MARTINEZ
PROJECT NAME:
61'-1"
PROJECT ADDRESS:
7'-10"
LEESBURG, FL 34748
DRAWN BY:
FVD
4 FILE No.:
(223-032)
CHECKED BY:
H.C.
DATE:
07/10/2023
ROOF PLAN
This item has been digitally signed and
MECHANICAL-DRAIN
sealed by Jose A. Martinez, PE.
SHEET:
Printed copies of this document are not
considered signed and sealed and the
signature must be verified on any
electronic copies. M-102
MEC DESIGN
4 3 2 1
6187 NW 167 STREET SUITE: H24
MIAMI, FLORIDA 33015
OFFICE: 305.356.1775
WWW.MECDESIGNMIAMI.COM
ID0001355
AR0007205 / PE31509
HOMERO CRUZ, L.I.D.
MANUEL A. VEGA, A.R.
JOSE A. MARTINEZ, P.E.
A
SEAL:
JOSE A. MARTINEZ
PROJECT NAME:
PROJECT ADDRESS:
REVISION
DATE BY
NO.
FILE No.:
(223-032)
CHECKED BY:
H.C.
DATE:
07/10/2023
SHEET TITLE:
MECHANICAL PLAN
This item has been digitally signed and
BACK of HOUSE
sealed by Jose A. Martinez, PE.
SHEET:
Printed copies of this document are not
considered signed and sealed and the
signature must be verified on any
electronic copies. M-103
MEC DESIGN
6187 NW 167 STREET SUITE: H24
MIAMI, FLORIDA 33015
OFFICE: 305.356.1775
WWW.MECDESIGNMIAMI.COM
ID0001355
AR0007205 / PE31509
HOMERO CRUZ, L.I.D.
MANUEL A. VEGA, A.R.
JOSE A. MARTINEZ, P.E.
SEAL:
JOSE A. MARTINEZ
PROJECT NAME:
PROJECT ADDRESS:
REVISION
DATE BY
NO.
DRAWN BY:
FVD
FILE No.:
(223-032)
CHECKED BY:
H.C.
DATE:
07/10/2023
SHEET TITLE:
MECHANICAL
NOTES & DETAILS
This item has been digitally signed and
sealed by Jose A. Martinez, PE.
SHEET:
Printed copies of this document are not
considered signed and sealed and the
signature must be verified on any
electronic copies. M-501
HANGERS AND SUPPORTERS:
14"
1
4"x4" LAG EYEBOLT W/LAG SHIELD
SCALE: NTS
SCALE: NTS
Leesburg Square Store
PROJECT ADDRESS:
1-1/2"- 26 GAUGE
GALV. SHEET. METAL.
STRAP SUPPORT
PLENUM BOX PER SMACNA.
INSULATED TAKE-OFF CONNECT DUCT EXTENSION 2020 FBC - SECTION 606 SMOKE DETECTION SYSTEMS CONTROL
INSULATE TOP OF INSULATED NEW FLEX. DUCT
ALL AIR TERMINALS SEAL JOINT WITH EPOXY
AND DUCT TAPE (CONNECT TO EXIST. DIFF.)
LINEAR DIFFUSER
ADAPTER AS REQUIRED
NEW FLEX. DUCTWORK
DRAWN BY:
DIFFUSER
FVD
FILE No.:
NOTE: (223-032)
DATE:
07/10/2023
SHEET TITLE:
MECHANICAL
NOTES & DETAILS
This item has been digitally signed and
sealed by Jose A. Martinez, PE.
SHEET:
Printed copies of this document are not
considered signed and sealed and the
signature must be verified on any
electronic copies. M-502
A B C D
MEC DESIGN
6187 NW 167 STREET SUITE: H24
MIAMI, FLORIDA 33015
OFFICE: 305.356.1775
WWW.MECDESIGNMIAMI.COM
ID0001355
AR0007205 / PE31509
HOMERO CRUZ, L.I.D.
MANUEL A. VEGA, A.R.
JOSE A. MARTINEZ, P.E.
SEAL:
A-26
A-7
A-9
A-11
JOSE A. MARTINEZ
PROJECT NAME:
REVISION
DATE BY
NO.
DRAWN BY:
ELECTRICAL LEGEND ELECTRICAL NOTES FVD
1. ELECTRICAL SERVICE EQUIPMENT: PROVIDE ALL EQUIPMENT AS REQUIRED IN GENERAL NOTES, SPECIFICATIONS, AND AS SHOWN ON FLOOR
PLANS, AND RISER DIAGRAM. MAINTAIN CODE REQUIRED CLEARANCES FOR ALL EQUIPMENT PER NEC 110.26.
SYMBOL DESCRIPTION 2. INSTALL (1) 120V-20A DUPLEX 6" ABOVE STOREFRONT GLASS ON WALL FOR NEON SIGNS.
3. INSTALL (1) 120V-20A DEDICATED DUPLEX FOR BIRD CAGE. FILE No.:
4. INSTALL (1) 120V-20A DEDICATED QUA-DUPLEX FOR REPTILE UNIT. (223-032)
5. INSTALL (1) 120V-20A DEDICATED QUA-DUPLEX FOR BUG STATION..
6. INSTALL (1) 120V-20A DEDICATED GFI DUPLEX FOR FISH FOOD FREEZER.
7. INSTALL (1) 120V-20A DEDICATED GFI DUPLEX FOR MARS FISH SYSTEM.
8. INSTALL (1) 120V-20A DEDICATED DUPLEX FOR RAW FOOD FREEZER.
CHECKED BY:
9. INSTALL (1) 120V-20A DEDICATED SWITCHED DUPLEX MOUNTED AT 72" A.F.F. TO BOTTOM OF BOX. PROVIDE GFI BREAKER. H.C.
10. PROVIDE A NON-FUSED DISCONNECT SWITCH FOR WATER HEATER. CIRCUIT AS INDICATED. REFER TO PLUMBING PLAN SHEET FOR MOUNTING
INFORMATION. (SEE PLAN TO SPECIFICATION )
11. INSTALL (1) 208V-2x30A DEDICATED GFI SINGLE OUTLET FOR DRYER. COORDINATE EXACT LOCATIONS AND REQUIREMENTS WITH OWNER.
12. INSTALL (1) 120V-20A DEDICATED GFI DUPLEX OUTLET FOR WASHER AND COORDINATE EXACT LOCATIONS AND REQUIREMENTS WITH OWNER.
DATE:
13. INSTALL (2) QUA-DUPLEX MOUNTED AT 7'-0" AFF FOR VIDEO / IT CABINET. VERIFY EXACT LOCATIONS WITH OWNER. 07/10/2023
14. PROVIDE GFI DUPLEX RECEPTACLE ADJACENT TO UNIT IF NOT PROVIDED WITH UNIT. CIRCUIT AS INDICATED, FURNISH WEATHER PROOF
ENCLOSURES AND COVERS AS REQUIRED.
15. DUCT SMOKE DETECTOR/REMOTE TEST STATION: DUCT MOUNTED SMOKE DETECTOR IS FIELD INSTALLED. GENERAL CONTRACTOR SHALL
INTERLOCK SMOKE DETECTOR WITH HVAC UNIT, REMOTE TEST ALARM STATION. MAKE ALL FINAL CONNECTIONS AS REQUIRED FOR A COMPLETE
NOTE DIMENSIONS: SHEET TITLE:
SYSTEM. HVAC UNIT TO SHUT DOWN UPON ACTIVATION OF SMOKE DETECTOR. COORDINATE WITH LANDLORD TO AVOID CONFLICTS IN FIELD. ALWAYS VERIFY ALL EXISTING DIMENSIONS @ FIELD BEFORE BIDDING WORK
16.
17.
MECHANICAL EQUIPMENT CONNECTIONS: FEEDERS AND DISCONNECTS PER MECHANICAL EQUIPMENT FEEDER/CONNECTION SCHEDULE. REFER
TO DETAIL 'D' ON SHEET E4.0.
INSTALL (1) 120V-20A DEDICATED DUPLEX FOR CASHWRAP
LIGHTING
18. THERMOSTAT/SENSOR LOCATION TO BE COORDINATED WITH TENANT. PROVIDE 4" SQUARE BACK BOX, SINGLE GANG PLASTER RING AND 1/2"
19.
CONDUIT WITH PULL STRING BETWEEN THERMOSTAT LOCATION AND HVAC UNIT IT SERVES. REFER TO SHEET M1.0 FOR MORE INFORMATION.
PROVIDE A 100A-2P NON-FUSED DISCONNECT SWITCH FOR WATER HEATER. CIRCUIT AS INDICATED. REFER TO PLUMBING PLAN SHEET FOR
FLOOR PLAN
MOUNTING INFORMATION.
20. PROVIDE 4'x4'-4"x3/4" PLYWOOD TELEPHONE BOARD PAINTED WITH (2) COATS OF FIRE RETARDANT PAINT, MOUNTED VERTICALLY. PROVIDE
This item has been digitally signed and
SURFACE MOUNTED DUPLEX RECEPTACLE AND TELEPHONE/DATA OUTLET AT 75" A.F.F. ON PLYWOOD BACKER BOARD. COORDINATE EXACT sealed by Jose A. Martinez, PE.
LOCATIONS WITH TENANT REPRESENTATIVE.
21. SECURITY CAMERA: SUSPEND 3/4" CONDUIT TO 12'-6" AFF. IN OPEN CEILING AREAS. PROVIDE PULL STRING IN CONDUIT AND TERMINATE TO SHEET:
NEAREST STRUCTURAL ELEMENT AND CLAMP FOR SUPPORT. COORDINATE WITH LIGHT FIXTURES. OWNER'S VENDOR TO PULL (1) CAT-5E CABLE Printed copies of this document are not
TO HUB LOCATION AT TELEPHONE BLOCK AREA. TERMINATION AND TESTING BY OWNER'S VENDOR. REFER TO DETAIL 'N', SHEET E3.0.
22. SPEAKER: GC TO PROVIDE 1-1/2" UNISTRUT WITH OPEN END UP FOR SPEAKERS. UNISTRUT IS TO BE SUPPORTED FROM TOP CHORD OF ADJACENT considered signed and sealed and the
23.
24.
25.
JOISTS. SEE DETAIL 'N' ON SHEET E3.0. SPEAKERS ARE TO BE FURNISHED AND INSTALLED BY OWNER'S VENDOR.
FIRE ALARM DEVICE/EQUIPMENT: ONLY TO REFER TO SPECIFICATIONS ON SHEET FA-101, ("THE FIRE PLANS WILL BE SUBMITTED BY THE
SPECIALIZED COMPANY UNDER DIFFERENT PERMISSION") .
EXHAUST FAN: 120V, 1PH. CONTINUOUS OPERATION. PROVIDE DISCONNECT SWITCH. REFER TO M 1.0 FOR MORE INFORMATION.
45kVA TRANSFORMER, TO BE LOCATED ABOVE CEILING. PROVIDE ALL REQUIRED SUPPORTS.
signature must be verified on any
electronic copies. E-101
A B C D
MEC DESIGN
6187 NW 167 STREET SUITE: H24
MIAMI, FLORIDA 33015
OFFICE: 305.356.1775
WWW.MECDESIGNMIAMI.COM
Sink ID0001355
Jan Sink AR0007205 / PE31509
Washer / Dryer HOMERO CRUZ, L.I.D.
IWH
MANUEL A. VEGA, A.R.
JOSE A. MARTINEZ, P.E.
IWH
EP-A EP-B
SEAL:
RTD
IT
2
FRZ
Desk
REF
JOSE A. MARTINEZ
PROJECT NAME:
REVISION
DATE BY
NO.
DRAWN BY:
ELECTRICAL LEGEND ELECTRICAL NOTES FVD
1. ELECTRICAL SERVICE EQUIPMENT: PROVIDE ALL EQUIPMENT AS REQUIRED IN GENERAL NOTES, SPECIFICATIONS, AND AS SHOWN ON FLOOR
PLANS, AND RISER DIAGRAM. MAINTAIN CODE REQUIRED CLEARANCES FOR ALL EQUIPMENT PER NEC 110.26.
SYMBOL DESCRIPTION 2. INSTALL (1) 120V-20A DUPLEX 6" ABOVE STOREFRONT GLASS ON WALL FOR NEON SIGNS.
3. INSTALL (1) 120V-20A DEDICATED DUPLEX FOR BIRD CAGE. FILE No.:
4. INSTALL (1) 120V-20A DEDICATED QUA-DUPLEX FOR REPTILE UNIT. (223-032)
5. INSTALL (1) 120V-20A DEDICATED QUA-DUPLEX FOR BUG STATION..
6. INSTALL (1) 120V-20A DEDICATED GFI DUPLEX FOR FISH FOOD FREEZER.
7. INSTALL (1) 120V-20A DEDICATED GFI DUPLEX FOR MARS FISH SYSTEM.
8. INSTALL (1) 120V-20A DEDICATED DUPLEX FOR RAW FOOD FREEZER.
CHECKED BY:
9. INSTALL (1) 120V-20A DEDICATED SWITCHED DUPLEX MOUNTED AT 72" A.F.F. TO BOTTOM OF BOX. PROVIDE GFI BREAKER. H.C.
10. PROVIDE A NON-FUSED DISCONNECT SWITCH FOR WATER HEATER. CIRCUIT AS INDICATED. REFER TO PLUMBING PLAN SHEET FOR MOUNTING
INFORMATION. (SEE PLAN TO SPECIFICATION )
11. INSTALL (1) 208V-2x30A DEDICATED GFI SINGLE OUTLET FOR DRYER. COORDINATE EXACT LOCATIONS AND REQUIREMENTS WITH OWNER.
12. INSTALL (1) 120V-20A DEDICATED GFI DUPLEX OUTLET FOR WASHER AND COORDINATE EXACT LOCATIONS AND REQUIREMENTS WITH OWNER.
DATE:
13. INSTALL (2) QUA-DUPLEX MOUNTED AT 7'-0" AFF FOR VIDEO / IT CABINET. VERIFY EXACT LOCATIONS WITH OWNER. 07/10/2023
14. PROVIDE GFI DUPLEX RECEPTACLE ADJACENT TO UNIT IF NOT PROVIDED WITH UNIT. CIRCUIT AS INDICATED, FURNISH WEATHER PROOF
ENCLOSURES AND COVERS AS REQUIRED.
15. DUCT SMOKE DETECTOR/REMOTE TEST STATION: DUCT MOUNTED SMOKE DETECTOR IS FIELD INSTALLED. GENERAL CONTRACTOR SHALL
INTERLOCK SMOKE DETECTOR WITH HVAC UNIT, REMOTE TEST ALARM STATION. MAKE ALL FINAL CONNECTIONS AS REQUIRED FOR A COMPLETE
NOTE DIMENSIONS: SHEET TITLE:
SYSTEM. HVAC UNIT TO SHUT DOWN UPON ACTIVATION OF SMOKE DETECTOR. COORDINATE WITH LANDLORD TO AVOID CONFLICTS IN FIELD. ALWAYS VERIFY ALL EXISTING DIMENSIONS @ FIELD BEFORE BIDDING WORK
16. MECHANICAL EQUIPMENT CONNECTIONS: FEEDERS AND DISCONNECTS PER MECHANICAL EQUIPMENT FEEDER/CONNECTION SCHEDULE. REFER
17.
TO DETAIL 'D' ON SHEET E4.0.
INSTALL (1) 120V-20A DEDICATED DUPLEX FOR CASHWRAP
POWER
18. THERMOSTAT/SENSOR LOCATION TO BE COORDINATED WITH TENANT. PROVIDE 4" SQUARE BACK BOX, SINGLE GANG PLASTER RING AND 1/2"
19.
CONDUIT WITH PULL STRING BETWEEN THERMOSTAT LOCATION AND HVAC UNIT IT SERVES. REFER TO SHEET M1.0 FOR MORE INFORMATION.
PROVIDE A 100A-2P NON-FUSED DISCONNECT SWITCH FOR WATER HEATER. CIRCUIT AS INDICATED. REFER TO PLUMBING PLAN SHEET FOR
MOUNTING INFORMATION.
FLOOR PLAN
20. PROVIDE 4'x4'-4"x3/4" PLYWOOD TELEPHONE BOARD PAINTED WITH (2) COATS OF FIRE RETARDANT PAINT, MOUNTED VERTICALLY. PROVIDE
This item has been digitally signed and
SURFACE MOUNTED DUPLEX RECEPTACLE AND TELEPHONE/DATA OUTLET AT 75" A.F.F. ON PLYWOOD BACKER BOARD. COORDINATE EXACT sealed by Jose A. Martinez, PE.
LOCATIONS WITH TENANT REPRESENTATIVE.
21. SECURITY CAMERA: SUSPEND 3/4" CONDUIT TO 12'-6" AFF. IN OPEN CEILING AREAS. PROVIDE PULL STRING IN CONDUIT AND TERMINATE TO SHEET:
NEAREST STRUCTURAL ELEMENT AND CLAMP FOR SUPPORT. COORDINATE WITH LIGHT FIXTURES. OWNER'S VENDOR TO PULL (1) CAT-5E CABLE Printed copies of this document are not
TO HUB LOCATION AT TELEPHONE BLOCK AREA. TERMINATION AND TESTING BY OWNER'S VENDOR. REFER TO DETAIL 'N', SHEET E3.0.
22. SPEAKER: GC TO PROVIDE 1-1/2" UNISTRUT WITH OPEN END UP FOR SPEAKERS. UNISTRUT IS TO BE SUPPORTED FROM TOP CHORD OF ADJACENT considered signed and sealed and the
23.
24.
25.
JOISTS. SEE DETAIL 'N' ON SHEET E3.0. SPEAKERS ARE TO BE FURNISHED AND INSTALLED BY OWNER'S VENDOR.
FIRE ALARM DEVICE/EQUIPMENT: ONLY TO REFER TO SPECIFICATIONS ON SHEET FA-101, ("THE FIRE PLANS WILL BE SUBMITTED BY THE
SPECIALIZED COMPANY UNDER DIFFERENT PERMISSION") .
EXHAUST FAN: 120V, 1PH. CONTINUOUS OPERATION. PROVIDE DISCONNECT SWITCH. REFER TO M 1.0 FOR MORE INFORMATION.
45kVA TRANSFORMER, TO BE LOCATED ABOVE CEILING. PROVIDE ALL REQUIRED SUPPORTS.
signature must be verified on any
electronic copies. E-102
A A
1 1 DOG WASH
RTEX-13
UTILITY ROOM UTILITY ROOM
IWH
IWH
FD
LAV Restroom
LAV Hi-Lo
WATER PIPING ISOMETRIC
RTEX-08
IWH
IWH
FD Fountain
EP-A EP-B
EP-A EP-B
WC
Restroom
RTD RTD
IT IT
JOSE A. MARTINEZ
2 2
FRZ FRZ PROJECT NAME:
Desk Desk
DOG WASH
REF
REF
STO
BACK OF HOUSE BACK OF HOUSE W/D
PROJECT ADDRESS:
Sink
2219 CITRUS BOULEVARD
UTILITY ROOM LEESBURG, FL 34748
Jan. Sink
LAV
Restroom
LAV
WC
Restroom
SANITARY PIPING ISOMETRIC
LAV LAV
Restroom
4 4 FILE No.:
(223-032)
CHECKED BY:
H.C.
DATE:
07/10/2023
FLOOR PLAN - SANITARY FLOOR PLAN - WATER SHEET TITLE:
PLUMBING PLANS
& ISOMETRICS
This item has been digitally signed and
sealed by Jose A. Martinez, PE.
SHEET:
Printed copies of this document are not
considered signed and sealed and the
signature must be verified on any
electronic copies. P-101
1. ALL WORK UNDER THIS CONTRACT SHALL COMPLY WITH 2020 FBC 7th EDITION, AND ALL APPLICABLE LOCAL
TYPICAL SUMP PUMP DETAIL TANKLESS WATER HEATER DETAIL PLUMBING SYMBOL LEGEND
ORDINANCES. SYMBOL DESCRIPTION
2. CONTRACTOR SHALL VISIT THE SITE AND THOROUGHLY FAMILIARIZE HIMSELF WITH AND VERIFY ALL EXISTING
CONDITIONS AND REPORT ANY DISCREPANCIES TO THE ARCHITECT/ENGINEER PRIOR TO SUBMITTING BID AND PRIOR TO FOR C-PVC PIPES, USE AT LESS SANITARY LINE
COMMENCING WORK. 30" COPPER PIPE BEFORE AND
3. THE CONTRACTOR SHALL COORDINATE THE WORK OF THIS TRADE WITH ALL OTHER TRADES TO AVOID INTERFERENCE AFTER THE UNIT VENT LINE
4.
WITH THE PROGRESS OF CONSTRUCTION AND REPORT ANY DISCREPANCIES TO THE ARCHITECT/ENGINEER.
REQUIRED INSURANCE SHALL BE PROVIDED BY THIS CONTRACTOR FOR PROTECTION AGAINST PUBLIC LIABILITY AND
GW GREASE WASTE LINE MEC DESIGN
PROPERTY DAMAGE FOR THE DURATION OF WORK. BALL
SAFEWASTE LINE
VALVE
5. ALL PERMITS, FEES, INSPECTIONS AND TESTS SHALL BE THE RESPONSIBILITY OF THE PLUMBING CONTRACTOR. 6187 NW 167 STREET SUITE: H24
6. ALL HORIZONTAL SANITARY PIPING SHALL SLOPE AT 1/8 INCH PER FOOT MINIMUM FOR 3" AND LARGER AND AT 1/4"
CD CONDENSATE LINE MIAMI, FLORIDA 33015
SLOPE FOR 2 1/2" PIPES AND SMALLER. HOT RTEX-08 COLD OFFICE: 305.356.1775
& COLD WATER LINE WWW.MECDESIGNMIAMI.COM
7. ALL MATERIALS SHALL BE NEW, FREE OF DEFECTS AND CORRECTLY LABELED WITH THEIR APPROPRIATE LISTING RTEX-13
AGENCY. ID0001355
HOT WATER LINE
8.
AR0007205 / PE31509
SHOP DRAWINGS: CONTRACTOR SHALL SUBMIT FOR APPROVAL, WITHIN 30 DAYS OF SIGNING CONTRACT, A MINIMUM OF
ALWAYS USE THE HOMERO CRUZ, L.I.D.
FIVE COPIES OF FULLY DESCRIPTIVE LITERATURE, INCLUDING BUT NOT LIMITED TO: WATER HEATERS, AND PLUMBING GATE VALVE
COMPRESSION MANUEL A. VEGA, A.R.
FIXTURES. NO WORK SHALL PROCEED WITHOUT THE APPROVAL OF THESE SUBMITTALS.
FITTINGS THAT COME CLEAN OUT
9. PLUMBING FIXTURES: FIXTURES SHALL BE AS SELECTED BY OWNER AND SHALL BE FURNISHED AND INSTALLED BY THIS
CO JOSE A. MARTINEZ, P.E.
WITH THE UNIT
CONTRACTOR. FIXTURES SHALL BE COMPLETE WITH DRAINS, TRAPS, SUPPLIES AND ANY OTHER ACCESSORY
REQUIRED. FIXTURES AND FAUCETS SHALL COMPLY WITH THE FBC WATER SAVING STANDARDS. "P" TRAP
ELECTRIC SEAL:
10. ALL AUTOMATIC WATER HEATERS SHALL MEET THE STANDARDS OF THE LATEST ENERGY EFFICIENCY CODE.
SPECIFICATIONS SERVICE
11. VALVES: DOMESTIC WATER VALVES SHALL BE OF BRONZE BODY, SWEAT ENDS. RHEEM OR SIMILAR FLOOR PENETRATION
12. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS WITH THE ARCHITECTURAL PLANS. MODEL: --------------- RTEX-08 RTEX-13 RTEX-18
--
----
VOLTAGE: ------------ 240V 240V 240V
13. ALL MATERIALS SHALL BE FREE FROM DEFECTS, INDELIBLY MARKED WITH NAME OF MANUFACTURER, WEIGHT AND/ OR SHOCK MECHANICAL
MAX. AMPS:----------- 40 60 75
E
CLASS.
US
WIRE LINE: ------------ 2 # 6 AWG (CU) 2 # 6 AWG (CU) 2#6 AWG (CU) ARRESTOR
14. ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER. CONSUME kW: ------ 7.3 13.0 18.0
N'T
THE COMPLETE SYSTEM SHALL BE FULLY OPERATIVE. DIMENSIONS: -------- 13"X8"X3.50" 13"X8"X3.75" 18"x14"x3.50"
DO
WEIGHT: --------------- 7.0 Pounds 8.5 Pounds 15 Pounds WCO
15. ALL EXCAVATION, BACKFILL AND PATCHING THE SLAB SHALL BE PART OF THIS CONTRACT. WALL CLEANOUT
PIPE FITTING:---------- 1/2" STD. PIPE 1/2" STD. PIPE 3/4" SDT PIPE
--
TYP. FOUNDATION INFLUENCE
----
16. VERIFY LOCATION, SIZE AND ELEVATION OF ALL UTILITIES PRIOR TO BEGINNING CONSTRUCTION. ADVISE ARCHITECT/ PRESSURE REQUIREMENTS: 3 PSI MIN. /150 PSI MAX.
ENGINEER OF ANY DISCREPANCIES. ENERGY EFFICIENCY:----- UP TO 99.5 %
VTR VENT THRU ROOF
17. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS FOR THE EXACT LOCATION OF FIXTURES AND PIPING. JOSE A. MARTINEZ
E.W.H. ELECTRIC WATER HEATER
18. HOSE BIBBS: SHALL BE 3/4 INCH. ROUGH BRASS CONSTRUCTION WITH SHUT OFF VALVE AND VACUUM BREAKER.
PROJECT NAME:
19. ALL OUTDOORS FLOOR CLEAN OUTS SHALL BE TERMINATED UP TO GRADE AND SHALL BE MARKED. HB HOSE BIBB
20. PROVIDE WALL CLEANOUTS AT THE BASE OF EVERY STACK.
PIPE SLEEVES
PIPE, CONDUIT, ETC
1'-6"
MIN
TRENCH TYPICAL DRAIN PIPING DETAIL SHUT OFF VALVE
1. INTERIOR SLEEVES SHALL BE 22 GAUGE SHEET METAL. PROVIDE FOR PIPE PASSING THROUGH WALLS OR FLOORS FOOTING POLISHED CHROME FINISHED ON RISER.
BEFORE POURING CONCRETE. PROSET SLEEVES ARE PERMITTED. PIPE, CONDUIT, ETC
2. SLEEVES SHALL BE LARGE ENOUGH TO ALLOW FULL THICKNESS OF INSULATION THROUGH SLEEVES FOR INSULATED 1 1/2" VENT (MIN.)
(IN WALL)
Leesburg Square Store
PIPING, AND FOR TWO LAYERS OF 30 LB. FELT WRAPPING AROUND UN-INSULATED PIPING. WALL
1 1/2 BOTTOM OF EXCAVATION FOR TRENCH REF ARCH
3. AFTER PIPING IS INSTALLED THROUGH THE SLEEVES, COMPLETE WITH INSULATION OR WRAPPING, THE SLEEVES SHALL OR BOTTOM OF ADJACENT FOOTING
BE SEALED WATER-TIGHT WITH AN APPROVED MASTIC OR FIRE-RATED CAULKING COMPOUND. 1 2" X 1 1/4" (FOR LAVS AND EDFS) 2" X 1 PROJECT ADDRESS:
DIGGING OR PIPE TRENCHES 1 1/4" (LAVS & EDFS) 1/2" (FOR SINKS AND EYEWASHES)
SANITARY, GREASE, WASTE, VENT AND STORM DRAINAGE PIPING PARALLEL TO FOOTING NOT
1 1/2" (SINKS & EW) SANITARY TAPPED TEE.
PERMITTED BELOW THIS LINE
POLISHED CHROME
FIXTURE TYPE MAXIMUM FLOW RATE
1. ALL HORIZONTAL BRANCHES, SEWER AND DRAIN LINES SHALL BE SLOPED A MINIMUM OF 1/8 INCH PER FOOT UNLESS 2219 CITRUS BOULEVARD
NOTE: PLATED P-TRAP
OTHERWISE INDICATED ON PLANS. 2" WASTE (MIN.) LAVATORY FAUCET 1.5 GPM AT 60 PSI LEESBURG, FL 34748
(IN WALL)
2. EVERY FIXTURE CONNECTED TO THE DRAINAGE SYSTEM SHALL BE EQUIPPED WITH A WATER SEAL TRAP. POLISHED CHROME
LOWER FOOTING AS REQUIRED TO PROVIDE MAX 1-1/2:1 SLOPE PLATED BRASS NIPPLE SHOWER HEAD 1.5 GPM AT 80 PSI
3. VENT STACKS SHALL NOT PASS THROUGH ROOF AT VALLEYS, ROOF CRICKETS, IN FRONT OF WINDOWS OR WITHIN 6'-0" FROM BOTTOM EDGE OF FOOTING TO BOTTOM OF TRENCH POLISHED CHROME PLATED CAST SINK FAUCET 1.5 GPM AT 60 PSI
OF ROOF EDGE. EXCAVATION OR LOWER FOOTING SO THAT TOP OF FOOTING IS BRASS ESCUTCHEON WITH SET SCREW THIS DRAWING CONTAINS
4. MATERIALS SHALL BE AS FOLLOWS: BELOW PIPE, CONDUIT, ETC WATER CLOSET 1.28 GALLONS PER FLUSHING CYCLE PROPRIETARY INFORMATION AND IS
4.1. DRAINAGE AND VENT PIPING (BELOW GRADE): SHALL BE SHALL BE CENTRIFUGALLY CAST IRON PIPE THE PROPERTY OF "MEC DESIGN
DISHWASHER 6.5 GALLONS PER CYCLE OR LESS CONSULTANTS, INC." AND MAY NOT
CONFORM TO ONE OF THE STANDARDS ASTM A 74; ASTM A 888; CISPI 301, NO-HUB FITTINGS. POLYVINYL
CHLORIDE (PVC) PLASTIC PIPE ((TYPE DWV) ASTM D 2665, ASTM D 2949, CSA B181.2) IS ACCEPTABLE. WASHING MASHING WATER FACTOR OF 8 OR LOWER BE REPRODUCED OR DISTRIBUTED
WITHOUT THE WRITTEN
4.2. DRAINAGE AND VENT PIPING (ABOVE GRADE): SHALL BE SHALL BE CENTRIFUGALLY CAST IRON PIPE AND
CONFORM TO ONE OF THE STANDARDS ASTM A 74; ASTM A 888; CISPI 301, NO-HUB FITTINGS. POLYVINYL
CHLORIDE (PVC) PLASTIC PIPE ((TYPE DWV) ASTM D 2665, ASTM D 2949, ASTM F 1488, CSA B181.2) IS
TYPICAL CLEANOUT DETAILS NOTE: MIAMI DADE COUNTY ART. III, SEC.8.31 LOCAL TECHNICAL
AMENDMENTS TO FBC 2020. TABLE 604.4 MAXIMUM FLOW RATES AND
PERMISSION OF "MEC DESIGN
CON SULTANTS, INC."
ACCEPTABLE. CONSUMPTION FOR PLUMBING FIXTURES, FIXTURE FITTINGS AND
4.3. ALL PIPING IN RETURN PLENUM SHALL NOT BE PVC OR CPVC, ONLY METALLIC MATERIAL WILL BE USE APPLIANCES.
ADJUSTABLE COLLAR COVER SECURED REVISION
WITHIN THE PLENUM AREA. FACE OF WALL WITH SCREWS DATE BY
NO.
DOMESTIC COLD AND HOT WATER PIPING THREADED C.O. PLUG THREADED C.O. PLUG
ROUGH-IN CONNECTION
1. PROVIDE DIELECTRIC UNIONS WHERE DISSIMILAR METALS ARE JOINED. FIXTURE WAST I/D DESCRIPTION
FIN. FLOOR FIN. GRADE 2020 FBCR-P2708.4 SHOWER CONTROL
CW HW VENT
2. PROVIDE DIELECTRIC UNIONS WHERE DISSIMILAR METALS ARE JOINED. E WASTE STAINLESS
STEEL COVER
VALVES:
3. EACH HOSE BIBB SHALL BE FURNISHED WITH A VACUUM BREAKER AND SHUT-OFF VALVE. 1 1 MANUFACTURER AND MODEL TO BE
RESTROOM LAVATORY 2" 2" 1-1/2" 1-1/2" - SCREWED TO P2708.3 SHOWER CONTROL VALVES.
DETERMINED BY OWNER.
4. PROVIDE PIPING AS FOLLOWS: THREADED C.O. 4 X 6" DIA. INDIVIDUAL SHOWER AND TUB/ SHOWER COMBINATION VALVES SHALL BE EQUIPPED
MANUFACTURER AND MODEL TO BE CONCRETE PAD SLIP WITH CONTROL VALVES OF THE PRESSURE- BALANCE, THERMOSTATIC-MIXING OR
WATER CLOSET 1
4" - 3" 2" - PLUG.
4.1. WATER PIPING (BELOW GRADE): SHALL BE COPPER TYPE "K" ASTM B-88 WITH WROUGHT COPPER FITTINGS DETERMINED BY OWNER. FLUSH W/FIN. JOINT COMBINATION PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A HIGH
AND 95-5 SOLDERED JOINTS. PAINT WITH BITUMASTIC WHEN INSTALLED IN GRADE. GRADE LIMIT STOP IN ACCORDANCE WITH ASSE 1016 OR ASME A112.18.1/CSA B125.1. THE HIGH
1 1 MANUFACTURER AND MODEL TO BE
4.2. WATER PIPING (ABOVE GRADE): SHALL BE COPPER TYPE "L" ASTM B-88 WITH WROUGHT COPPER FITTINGS MOP SINK 2" 2" 2" 2" - LIMIT STOP SHALL BE SET TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN
DETERMINED BY OWNER.
AND 95-5 SOLDERED JOINTS. CPVC (CHLORINATED POLYVINYL CHLORIDE) ASTM D 2846 PIPE AND TUBING 120•F (49°C). IN-LINE THERMOSTATIC VALVES SHALL NOT BE USED FOR COMPLIANCE
FLOOR EXTERIOR TYPE
WITH CPVC PLASTIC FITTINGS ASTM F 437 IS ACCEPTABLE WITH THIS SECTION. DRAWN BY:
5. COPPER TYPE "M" AND CPVC IN CONCEALED SPACES ARE ACCEPTABLE. WALL FVD
6. PRESSURE AND TEMPERATURE RELIEF LINES: SHALL BE TYPE "M" COPPER WITH WROUGHT COPPER FITTINGS AND 50-50
SOLDERED JOINTS. MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURE (TABLE 403.1) FILE No.:
(223-032)
7. ALL EXPOSED PIPING WITHIN TOILET ROOMS SHALL BE CHROME PLATED.
No. CLASSIFICATION OCCUPANCY WATER CLOSET LAVATORIES DRINKING OTHERS WATER HAMMER ARRESTORS SHALL BE INSTALLED AT ANY QUICK CLOSING
TESTING MALE FEMALE MALE FEMALE FOUNTAIN NOTE DIMENSIONS: VALVES AND CONFORM TO ASSE 1010 PROVIDE ANTI-SCALD VALVE FOR
CHECKED BY:
H.C.
1. COMPLETE WATER PIPING SYSTEM SHALL BE PRESSURE TESTED BY CAPPING OR PLUGGING OPENINGS, FILLING SYSTEM 1 MERCANTILE - RETAIL M 1 PER 500 1 PER 750 1 PER 1000 1 SERVICE SINK WASHING AND BATHING AREA.
WITH WATER AND APPLYING HYDROSTATIC PRESSURE OF 125 PSI FOR PERIOD OF NOT LESS THAN 2 HOURS.
DATE:
2. SOIL, WASTE AND VENT PIPING SHALL BE TESTED BY CAPPING THE ENDS OF THE SYSTEM AND ALL LINES FILLED WITH
WATER TO HIGHEST POINT AND ALLOW TO STAND UNTIL INSPECTION IS MADE AND WATER LEVEL REMAINS CONSTANT.
07/10/2023
PROVIDED PLUMBING FIXTURE (SEE PLAN)
STERILIZATION
SHEET TITLE:
A AFTER WATER PIPING HAS BEEN THOROUGHLY FLUSHED OUT, STERILIZE THE LINES BY INTRODUCING INTO THEM A 1 MERCANTILE - RETAIL M 1 1 1 1 SERVICE SINK
SOLUTION OF CALCIUM HYPOCHLORITE OR CHLORIDE OF LIME. OPEN AND CLOSE ALL VALVES WHILE SYSTEM IS BEING
CHLORINATED. AFTER THE STERILIZING AGENT HAS BEEN APPLIED FOR 24 HOURS, TEST FOR RESIDUAL CHLORINE AT
OCCUPANCY ESTIMATED PER AREA:
PLUMBING
SEPARATE FACILITIES NOTE: RETAIL -----------------------------------------
OFFICE (Back of House)-------------------
82 PERSONS
10 PERSONS
NOTES & DETAILS
1. ONE UNI-SEX RESTROOM SHALL BE PROVIDED IN THE TENANT SPACE AS PER FBC-P; 403.2 (EXCEPTION #3). SEPARATE This item has been digitally signed and
FACILITIES SHALL NOT BE REQUIRED IN MERCANTILE OCCUPANCIES IN WHICH THE MAXIMUM OCCUPANT LOAD IS 100 OR sealed by Jose A. Martinez, PE.
TOTAL OCCUPANCY ESTIMATED OF 92 PERSONS
FEWER.
SHEET:
Printed copies of this document are not
considered signed and sealed and the
signature must be verified on any
electronic copies. P-501
A B C D
89'-8"
27'-0" 30'-1" 30'-10"
1
11'-0" 4" 76'-6"
4'-0"
3'-0"
MEC DESIGN
4'-0"
6187 NW 167 STREET SUITE: H24
24'-1"
MIAMI, FLORIDA 33015
OFFICE: 305.356.1775
WWW.MECDESIGNMIAMI.COM
ID0001355
AR0007205 / PE31509
HOMERO CRUZ, L.I.D.
MANUEL A. VEGA, A.R.
JOSE A. MARTINEZ, P.E.
SEAL:
25'-0"
2
= 9 2'-9"
EXITS
WO
61'-1"
EN T
B E TWE
CE
D IS TAN
ON AL
DIAG
19'-7"
Middle Point of
JOSE A. MARTINEZ
way, 56'-9"
Total Lenght: 113'- 6"
6'-0"
PROJECT NAME:
3'-2"
3 "
0'-9
10 Leesburg Square Store
=
NCE
S TA PROJECT ADDRESS:
DI
AL
16'-1"
N
15'-0"
REVISION
DATE BY
NO.
DRAWN BY:
FVD
FILE No.:
ADOPTED FIRE CODES IN EFFECT: (223-032)
LEGENT: DATE:
07/10/2023
SCOPE OF WORK NOTE DIMENSIONS:
SHEET TITLE:
LIVE
LIFE SAFETY PLAN:
SAFETY PLAN
SEQUENCE OF OPERATION NOTES: This item has been digitally signed and
sealed by Jose A. Martinez, PE.
SHEET:
Printed copies of this document are not
considered signed and sealed and the
signature must be verified on any
electronic copies. LS-101
A B C D
S
MEC DESIGN
6187 NW 167 STREET SUITE: H24
F MIAMI, FLORIDA 33015
OFFICE: 305.356.1775
WWW.MECDESIGNMIAMI.COM
SD
R
ID0001355
S AR0007205 / PE31509
HOMERO CRUZ, L.I.D.
MANUEL A. VEGA, A.R.
JOSE A. MARTINEZ, P.E.
F
SEAL:
F
2
F.A.C.P.
JOSE A. MARTINEZ
F
PROJECT NAME:
SD
R
3 F
Leesburg Square Store
S
PROJECT ADDRESS:
REVISION
DATE BY
NO.
FILE No.:
(223-032)
F
CHECKED BY:
H.C.
DATE:
07/10/2023
LF
S
SHEET TITLE:
SD FIRE ALARM
R
PLAN
This item has been digitally signed and
sealed by Jose A. Martinez, PE.
DEVICES MOUNTING HEIGHTS Printed copies of this document are not
SHEET:
considered signed and sealed and the
signature must be verified on any
electronic copies. FA-101
F S S F S S S F SD R F SD R F F
MEC DESIGN
6187 NW 167 STREET SUITE: H24
CS MIAMI, FLORIDA 33015
CS
Line 3 ANNUNCIATOR
OFFICE: 305.356.1775
WWW.MECDESIGNMIAMI.COM
Line 2 N.A.C.
AR0007205 / PE31509
Line 3 ANNUNCIATOR
FAA
SEAL:
FIRE ALARM
PANEL ES 50X
F.A.C.P.
FIRE ALARM
PANEL F.A.C.P. ES-50X
F.A.C.P. NAC = NOTIFICATION APPLIANCE CIRCUIT
F-1
NAC = NOTIFICATION APPLIANCE CIRCUIT
JOSE A. MARTINEZ
PROJECT NAME:
PROJECT ADDRESS:
REVISION
DATE BY
NO.
DRAWN BY:
FVD
FILE No.:
(223-032)
CHECKED BY:
H.C.
FIRE ALARM,
RISER & NOTES
This item has been digitally signed and
sealed by Jose A. Martinez, PE.
SHEET:
Printed copies of this document are not
considered signed and sealed and the
signature must be verified on any
electronic copies. FA-501
A B C D
89'-8"
27'-0" 30'-1" 30'-10"
1
11'-0" 4" 76'-6"
4'-0"
MEC DESIGN
3'-0"
6187 NW 167 STREET SUITE: H24
MIAMI, FLORIDA 33015
OFFICE: 305.356.1775
WWW.MECDESIGNMIAMI.COM
4'-0"
ID0001355
AR0007205 / PE31509
HOMERO CRUZ, L.I.D.
MANUEL A. VEGA, A.R.
24'-1"
SEAL:
25'-0"
2 JOSE A. MARTINEZ
PROJECT NAME:
61'-1"
PROJECT ADDRESS:
BE REPRODUCED OR DISTRIBUTED
3 WITHOUT THE WRITTEN
PERMISSION OF "MEC DESIGN
CON SULTANTS, INC."
REVISION
DATE BY
NO.
16'-1"
15'-0"
DRAWN BY:
FVD
4 FILE No.:
(223-032)
CHECKED BY:
H.C.
DATE:
07/10/2023
FIRE SPRINKLER
PLAN
This item has been digitally signed and
sealed by Jose A. Martinez, PE.
SHEET:
Printed copies of this document are not
considered signed and sealed and the
signature must be verified on any
electronic copies. FS-101
4 4A 5 2
Nonbearing Wall Ratings 1, 2, 3 or 4 Hr (See Items 4 & 5)
System No. UL 2083
1 Hour Fire Rated Through Penetration Firestop for Single
Plastic Pipe through Gypsum Walls using
TREMstop WS and TREMstop MCR. F-Rating = 1 Hr. /
T-Rating = 0 Hr.
MEC DESIGN
5 8
6187 NW 167 STREET SUITE: H24
2 MIAMI, FLORIDA 33015
OFFICE: 305.356.1775
WWW.MECDESIGNMIAMI.COM
ID0001355
AR0007205 / PE31509
HOMERO CRUZ, L.I.D.
Rating, Hr. Min Stud Depth, Min Stud Depth, No. of Layers & Min Thkns. of MANUEL A. VEGA, A.R.
in. Item 2 & 2E in. Item 2A Thkns of Panel Insulation (Item 4) JOSE A. MARTINEZ, P.E.
2 3-1/2 3-5/8 1 layer, 3/4 in. thick 3 in. 1. Pre-Rated Gypsum Wallboard/Stud Wall Assembly
3 1-5/8 2-1/2 3 layers, 1/2 in. thick Optional 2. Plastic Pipe - Nom. 4" diam. (or smaller) Sch. 40 PVC pipe for use in
open or closed piping systems. See table below for annular space
3 1-5/8 2-1/2 2 layers, 3/4 in. thick Optional requirements.
3 1-5/8 2-1/2 3 layers, 5/8 in. thick Optional JOSE A. MARTINEZ
3. TREMstop WS - Intumescent wrap strips, continuously wrapped
4 1-5/8 2-1/2 4 layers, 5/8 in. thick Optional around the outer circumference of the pipe on both sides of wall PROJECT NAME:
assembly.
4 1-5/8 2-1/2 4 layers, 1/2 in. thick Optional
1-1/2 1/16
Leesburg Square Store
2 3/16
3 1/8
PROJECT ADDRESS:
4 1/8
4 3/8
2219 CITRUS BOULEVARD
4. TREMstop MCR - Prefabricated steel collar wrapped over the wrap\ LEESBURG, FL 34748
Strips (Item 3) and mechanically fastened to both sides of the wall
assembly.
5. FYRE-SIL - Min. 1/4" thickness of sealant applied at the interface of
the wall and collar, and the interface of the collar and pipe. Sealant THIS DRAWING CONTAINS
applied on both sides of wall. PROPRIETARY INFORMATION AND IS
THE PROPERTY OF "MEC DESIGN
CONSULTANTS, INC." AND MAY NOT
BE REPRODUCED OR DISTRIBUTED
WITHOUT THE WRITTEN
System No. W-L-1054 PERMISSION OF "MEC DESIGN
F Ratings - 1 and 2 Hr (See Items 1 and 3) CON SULTANTS, INC."
T Rating - 0 Hr
L Rating At Ambient - Less Than 1 CFM/Sq Ft REVISION
L Rating At 400 F - 4 CFM/Sq Ft DATE BY
NO.
DRAWN BY:
FVD
FILE No.:
(223-032)
CHECKED BY:
H.C.
DATE:
07/10/2023
SHEET TITLE:
FIRE SPRINKLER
FIRE PARTITION
This item has been digitally signed and DETAILS
FIRE-RATED PARTITION (UL-U419) sealed by Jose A. Martinez, PE.
SHEET:
Printed copies of this document are not
considered signed and sealed and the
signature must be verified on any
electronic copies. FS-501
A B C D
89'-8"
27'-0" 30'-1" 30'-10"
8"
0 0
5"
1
5'-0"
0 MEC DESIGN
6187 NW 167 STREET SUITE: H24
MIAMI, FLORIDA 33015
OFFICE: 305.356.1775
5'-0"
WWW.MECDESIGNMIAMI.COM
ID0001355
AR0007205 / PE31509
HOMERO CRUZ, L.I.D.
MANUEL A. VEGA, A.R.
24'-1"
EXISTING AC ROOF
JOSE A. MARTINEZ, P.E.
5'-0"
PENETRATIONS
SEAL:
5'-0"
.EXISTING 18" DEEP
BARJOISTS @60" O/C (TYP)
5'-0"
EXISTING
. 16" I-BEAM
BOTTOM ELEV 12'-2" APF JOSE A. MARTINEZ
2
PROJECT NAME:
5'-0"
61'-1"
EXISTING
. 16" I-BEAM Leesburg Square Store
5'-0"
BOTTOM ELEV 12'-2" APF
19'-7"
PROJECT ADDRESS:
5'-0"
PENETRATIONS LEESBURG, FL 34748
5'-0"
CONSULTANTS, INC." AND MAY NOT
BE REPRODUCED OR DISTRIBUTED
3 WITHOUT THE WRITTEN
PERMISSION OF "MEC DESIGN
CON SULTANTS, INC."
5'-0"
REVISION
DATE BY
NO.
0
16'-1"
5'-0"
.EXISTING 18" DEEP
BARJOISTS @60" O/C (TYP)
5'-0"
DRAWN BY:
FVD
1 1
4 FILE No.:
6"
6"
(223-032)
CHECKED BY:
H.C.
DATE:
07/10/2023
STRUCTURAL NOTES
EXISTING ROOF STRUCTURE SHEET TITLE:
EXISTING
ROOF TOP UNITS RTU AND AHU ROOF STRUCTURE
1. ALL RTU UNITS ROOF OPENINGS ARE EXISTING AND TO REMAIN AS IS This item has been digitally signed and
2. NEW RTU UNITS ITS WILL BE MOUNTED ON EXISTING ROOF OPENING (FIELD VERIFY ). sealed by Jose A. Martinez, PE.
3. NEW AHU IS MOUNTAIN IN JOIST (FIELD VERIFY) SHEET:
4. GC. AND MECHANICAL CONTRACTOR TO FIELD VERIFY FOR MEASUREMENT. Printed copies of this document are not
considered signed and sealed and the
signature must be verified on any
electronic copies. S-101