Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Electrical Circuits Assignment

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 8

TECHNOLOGICAL UNIVERSITY OF THE PHILIPPINES – MANILA

COLLEGE OF ENGINEERING – ELECTRICAL DEPARTMENT


AYALA BOULEVARD, ERMITA MANILA

ASSIGNMENT NUMBER 4

SUBMITTED BY:
MANAOIS, ETHAN ZACHARY A.

COURSE / YEAR AND SECTION:


PEE3-M / BSEE – 3D

DATE SUBMITTED:
JANUARY 20, 2023

SUBMITTED TO:
ENGR. SEIGIE B. LLADONES
(INSTRUCTOR)

RATING

Problem 368: EE Board April 1980


A factory is supplied by a three-phase, 3-wire system with the following characteristics:
Vab=230∠ 20° V Voc=230 ∠ 240° V
Ia = 110∠ -36.87° A Ic = 125∠ 53.13° A
Determine the power consumed by the load.

Problem 369:
A 3-phase, 3-wire feeder has the following line currents and line voltages:
Vab =220∠0° V la = 30-j30 A
Vbc=220∠240° V lbc = 29+j39.8 A
Determine the reactive power supplied by the feeder.

Problem 371:
Given a balanced 3-wire, three-phase system serving the following loads:
Vab= 220∠20° V Vbc= 220∠240 V
Vac = 220∠120° V Zab= 11∠0°
Zbc - 11∠45° Zac= 11∠30°
Determine the reading of the two wattmeters with line b as common.

Problem 372: EE Board April


The following voltages and line currents were measured to a 3-phase, 3-wire feeder serving a commercial building:
Vab = 2,400∠0° V Ia = 85∠330° A
Vbc = 2400∠240° V Ic = 100∠80° A
Solve for the real power in kW drawn by the commercial building.

Problem 373: EE Board October 1981


A 3-phase, 3-wire load draws the following line currents:
Ia = 60∠330° A Ib = 78.4∠214 A Ic = 75∠80° A
If the voltages impressed on the load are balanced 3-phase, having a magnitude of 4140 volts line to line, solve for the
total power in kW.
Problem 374:
Given the following voltages and load impedances:
V = 220∠0° V Vbc=220∠240° V
Zab = 10∠36.87° Zbc = 10∠0°
Vca =220∠120° V Za = 10∠45° Ω
Determine the reading of a kW meter connected with its current coil connected in line b while the potential coil connected
across lines b and c.

Problem 375: EE Board October 1983


Given the following load impedances in delta and the impressed voltages as follows:
Vab=220∠0° V Zab = 8+16
Vbc=220∠240° V Zbc = 8.66-j5
Vca=220∠120° V Zca = 10+j0
What will be the reading of the two wattmeters connected to measure total power. Use line a as the common potential
point.
Problem 376: EE Board October 1984
The 3-phase power supply to a factory has the following measurements:
Vab = 240∠0° V Vbc = 240∠240° V
Ia = 120∠330° A Ib = 157∠214° A
Vca = 240∠120° V Ic = 150/80° A
Solve for the total power drawn.
Problem 381: EE Board April 1992
A 460 volt, three-phase motor draws 208 A with a power factor of 0.91 lagging- Calculate the indications of W, and W2
for the given condition.

Problem 382:
Two wattmeters are used to measure the power delivered to a balanced delta connected load. Wattmeter 1 reads 1000 W
and wattmeter 2 reads 500 W after the current coil terminals are reversed. If the line-to-line voltage is 208 V, solve for the
line current drawn by the load.
Problem 383:
The power drawn by a three-phase balanced load is measured using two wattmeters properly connected. At what power
factor will the reading of one of the wattmeters be zero?

Problem 384:
Two wattmeters connected to a three-phase 440 V squirrel cage induction motor indicate a total of 12 kW. If the operating
power factor of the motor is 0.4, determine the individual reading of the wattmeters.
Problem 386:
Two wattmeters used to measure the total power drawn by a three-phase circuit and are connected properly. The first
wattmeter reads 4800 watts while the other reads 400 watts after reversing its current coil. Solve for the load power factor.

Problem 387: EE Board June 1990


Two-wattmeter method is used to test a 25 HP, 230-volt, 1800 rpm, 60 cycle, 3 phase induction motor. When the line
voltages are 230 volts, one wattmeter reads +13,400 watts and the other +7,400 watts. Determine motor power factor.