Nec Tables
Nec Tables
Nec Tables
This section lists excerpts from industry, national, and international standards. The excerpts are for illustration and
educational purposes. There are often several related tables and information for other configurations and applications.
In addition, the standards have added detail and information that applies to all these excerpts. Therefore, any
application should refer to the standard, rather than the excerpts.
NEC 240.6(A) Standard Ampere Ratings for Fuses & Circuit Breakers
Amperes
15 20 25 30 35 40 45 50 60 70 80 90 100 110
125 150 175 200 225 250 300 350 400 450 500 - - -
600 700 800 1000 1200 1600 2000 2500 3000 4000 5000 6000 - -
Chapter 4 NEC & NEMA Standards 3
Table 310.16 Allowable Ampacities of Insulated Conductors Rated 0 Through 2000 Volts, 60°C
Through 90°C (140°F Through 194°F), Not More Than Three Current-Carrying Conductors in
Raceway, Cable, or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)
Temperature Rating of Conductor (See Table 310.13.)
60°C 75°C 90°C 60°C 75°C 90°C
(140°F) (167°F) (194°F) (140°F) (167°F) (194°F)
Size AWG Types Types RHW, Types TBS, SA, SIS, Types Types RHW, Types TBS, SA, Size
or kcmil TW, UF THHW, THW, FEP, FEPB, MI, RHH, TW, UF THHW, SIS, THHN, THHW, AWG or
THWN, RHW-2, THHN, THHW, THW, THW-2, THWN-2,
XHHW, USE, THW-2, THWN-2, THWN, RHH, RHW-2, USE-
kcmil
ZW USE-2, XHH, XHHW, XHHW, USE 2, XHH, XHHW,
XHHW-2, ZW-2 XHHW-2, ZW-2
COPPER ALUMINUM OR COPPER-CLAD ALUM
18 — — 14 — — — —
16 — — 18 — — — —
14* 20 20 25 — — — —
12* 25 25 30 20 20 25 12*
10* 30 35 40 25 30 35 10*
8 40 50 55 30 40 45 8
6 55 65 75 40 50 60 6
4 70 85 95 55 65 75 4
3 85 100 110 65 75 85 3
2 95 115 130 75 90 100 2
1 110 130 150 85 100 115 1
1/0 125 150 170 100 120 135 1/0
2/0 145 175 195 115 135 150 2/0
3/0 165 200 225 130 155 175 3/0
4/0 195 230 260 150 180 205 4/0
250 215 255 290 170 205 230 250
300 240 285 320 190 230 255 300
350 260 310 350 210 250 280 350
400 280 335 380 225 270 305 400
500 320 380 430 260 310 350 500
600 355 420 475 285 340 385 600
700 385 460 520 310 375 420 700
750 400 475 535 320 385 435 750
800 410 490 555 330 395 450 800
900 435 520 585 355 425 480 900
1000 455 545 615 375 445 500 1000
1250 495 590 665 405 485 545 1250
1500 520 625 705 435 520 585 1500
1750 545 650 735 455 545 615 1750
2000 560 665 750 470 560 630 2000
CORRECTION FACTORS
Ambient For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities Ambient
Temp. shown above by the appropriate factor shown below. Temp.
(°C) (°F)
21–25 1.08 1.05 1.04 1.08 1.05 1.04 70–77
26–30 1.00 1.00 1.00 1.00 1.00 1.00 78–86
31–35 0.91 0.94 0.96 0.91 0.94 0.96 87–95
36–40 0.82 0.88 0.91 0.82 0.88 0.91 96–104
41–45 0.71 0.82 0.87 0.71 0.82 0.87 105–113
46–50 0.58 0.75 0.82 0.58 0.75 0.82 114–122
51–55 0.41 0.67 0.76 0.41 0.67 0.76 123–131
56–60 — 0.58 0.71 — 0.58 0.71 132–140
61–70 — 0.33 0.58 — 0.33 0.58 141–158
71–80 — — 0.41 — — 0.41 159–176
* See 240.4(D).
4 Electric Power Systems Durham
These tables for use only with 430.110, 440.12, 440.41 and 455.8(C).
10 Electric Power Systems Durham
Table 9 Alternating-Current Resistance and Reactance for 600-Volt Cables, 3-Phase, 60 Hz, 75°C
(167°F) — Three Single Conductors in Conduit
Ohms to Neutral per Kilometer
Ohms to Neutral per 1000 Feet6
XL Alternating-Current Alternating-Current Effective Z Effective Z
(Reactance) for Resistance for Resistance for at 0.85 PF for at 0.85 PF for
Size All Wires Uncoated Copper Wires Aluminum Wires Uncoated Copper Wires Aluminum Wires Size
(AWG PVC, Steel PVC Aluminum Steel PVC Aluminum Steel PVC Aluminum Steel PVC Aluminum Steel (AWG
or Aluminum Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit Conduit or
kcmil) Conduits kcmil)
14 0.190 0.240 10.2 10.2 10.2 — — — 8.9 8.9 8.9 — — — 14
0.058 0.073 3.1 3.1 3.1 — — — 2.7 2.7 2.7 — — —
12 0.177 0.223 6.6 6.6 6.6 10.5 10.5 10.5 5.6 5.6 5.6 9.2 9.2 9.2 12
0.054 0.068 2.0 2.0 2.0 3.2 3.2 3.2 1.7 1.7 1.7 2.8 2.8 2.8
10 0.164 0.207 3.9 3.9 3.9 6.6 6.6 6.6 3.6 3.6 3.6 5.9 5.9 5.9 10
0.050 0.063 1.2 1.2 1.2 2.0 2.0 2.0 1.1 1.1 1.1 1.8 1.8 1.8
8 0.171 0.213 2.56 2.56 2.56 4.3 4.3 4.3 2.26 2.26 2.30 3.6 3.6 3.6 8
0.052 0.065 0.78 0.78 0.78 1.3 1.3 1.3 0.69 0.69 0.70 1.1 1.1 1.1
6 0.167 0.210 1.61 1.61 1.61 2.66 2.66 2.66 1.44 1.48 1.48 2.33 2.36 2.36 6
0.051 0.064 0.49 0.49 0.49 0.81 0.81 0.81 0.44 0.45 0.45 0.71 0.72 0.72
4 0.157 0.197 1.02 1.02 1.02 1.67 1.67 1.67 0.95 0.95 0.98 1.51 1.51 1.51 4
0.048 0.060 0.31 0.31 0.31 0.51 0.51 0.51 0.29 0.29 0.30 0.46 0.46 0.46
3 0.154 0.194 0.82 0.82 0.82 1.31 1.35 1.31 0.75 0.79 0.79 1.21 1.21 1.21 3
0.047 0.059 0.25 0.25 0.25 0.40 0.41 0.40 0.23 0.24 0.24 0.37 0.37 0.37
2 0.148 0.187 0.62 0.66 0.66 1.05 1.05 1.05 0.62 0.62 0.66 0.98 0.98 0.98 2
0.045 0.057 0.19 0.20 0.20 0.32 0.32 0.32 0.19 0.19 0.20 0.30 0.30 0.30
1 0.151 0.187 0.49 0.52 0.52 0.82 0.85 0.82 0.52 0.52 0.52 0.79 0.79 0.82 1
0.046 0.057 0.15 0.16 0.16 0.25 0.26 0.25 0.16 0.16 0.16 0.24 0.24 0.25
1/0 0.144 0.180 0.39 0.43 0.39 0.66 0.69 0.66 0.43 0.43 0.43 0.62 0.66 0.66 1/0
0.044 0.055 0.12 0.13 0.12 0.20 0.21 0.20 0.13 0.13 0.13 0.19 0.20 0.20
2/0 0.141 0.177 0.33 0.33 0.33 0.52 0.52 0.52 0.36 0.36 0.36 0.52 0.52 0.52 2/0
0.043 0.054 0.10 0.10 0.10 0.16 0.16 0.16 0.11 0.11 0.11 0.16 0.16 0.16
3/0 0.138 0.171 0.253 0.269 0.259 0.43 0.43 0.43 0.289 0.302 0.308 0.43 0.43 0.46 3/0
0.042 0.052 0.077 0.082 0.079 0.13 0.13 0.13 0.088 0.092 0.094 0.13 0.13 0.14
4/0 0.135 0.167 0.203 0.220 0.207 0.33 0.36 0.33 0.243 0.256 0.262 0.36 0.36 0.36 4/0
0.041 0.051 0.062 0.067 0.063 0.10 0.11 0.10 0.074 0.078 0.080 0.11 0.11 0.11
250 0.135 0.171 0.171 0.187 0.177 0.279 0.295 0.282 0.217 0.230 0.240 0.308 0.322 0.33 250
0.041 0.052 0.052 0.057 0.054 0.085 0.090 0.086 0.066 0.070 0.073 0.094 0.098 0.10
300 0.135 0.167 0.144 0.161 0.148 0.233 0.249 0.236 0.194 0.207 0.213 0.269 0.282 0.289 300
0.041 0.051 0.044 0.049 0.045 0.071 0.076 0.072 0.059 0.063 0.065 0.082 0.086 0.088
350 0.131 0.164 0.125 0.141 0.128 0.200 0.217 0.207 0.174 0.190 0.197 0.240 0.253 0.262 350
0.040 0.050 0.038 0.043 0.039 0.061 0.066 0.063 0.053 0.058 0.060 0.073 0.077 0.080
400 0.131 0.161 0.108 0.125 0.115 0.177 0.194 0.180 0.161 0.174 0.184 0.217 0.233 0.240 400
0.040 0.049 0.033 0.038 0.035 0.054 0.059 0.055 0.049 0.053 0.056 0.066 0.071 0.073
500 0.128 0.157 0.089 0.105 0.095 0.141 0.157 0.148 0.141 0.157 0.164 0.187 0.200 0.210 500
0.039 0.048 0.027 0.032 0.029 0.043 0.048 0.045 0.043 0.048 0.050 0.057 0.061 0.064
600 0.128 0.157 0.075 0.092 0.082 0.118 0.135 0.125 0.131 0.144 0.154 0.167 0.180 0.190 600
0.039 0.048 0.023 0.028 0.025 0.036 0.041 0.038 0.040 0.044 0.047 0.051 0.055 0.058
750 0.125 0.157 0.062 0.079 0.069 0.095 0.112 0.102 0.118 0.131 0.141 0.148 0.161 0.171 750
0.038 0.048 0.019 0.024 0.021 0.029 0.034 0.031 0.036 0.040 0.043 0.045 0.049 0.052
1000 0.121 0.151 0.049 0.062 0.059 0.075 0.089 0.082 0.105 0.118 0.131 0.128 0.138 0.151 1000
0.037 0.046 0.015 0.019 0.018 0.023 0.027 0.025 0.032 0.036 0.040 0.039 0.042 0.046
Notes:
1. These values are based on the following constants: UL-Type RHH wires with Class B stranding, in cradled
configuration. Wire conductivities are 100 percent IACS copper and 61 percent IACS aluminum, and aluminum conduit is
45 percent IACS. Capacitive reactance is ignored, since it is negligible at these voltages. These resistance values are
valid only at 75°C (167°F) and for the parameters as given, but are representative for 600-volt wire types operating at 60
Hz.
2. Effective Z is defined as R cos(θ) + X sin(θ), where θ is the power factor angle of the circuit. Multiplying current by
effective impedance gives a good approximation for line-to-neutral voltage drop. Effective impedance values shown in
this table are valid only at 0.85 power factor. For another circuit power factor (PF), effective impedance (Ze) can be
calculated from R and XL values given in this table as follows: Ze = R × PF + XL sin[arccos(PF)].
12 Electric Power Systems Durham
Table C.4 Maximum Number of Conductors or Fixture Wires in Intermediate Metal Conduit
(IMC) (Based on Table 1, Chapter 9)
CONDUCTORS
Size Metric Designator (Trade Size)
Type (AWG/ 16 21 27 35 41 53 63 78 91 103
kcmil) (½) (¾) (1) (1¼) (1½) (2) (2½) (3) (3½) (4)
RHH, RHW, 14 4 8 13 22 30 49 70 108 144 186
RHW-2 12 4 6 11 18 25 41 58 89 120 154
10 3 5 8 15 20 33 47 72 97 124
8 1 3 4 8 10 17 24 38 50 65
6 1 1 3 6 8 14 19 30 40 52
4 1 1 3 5 6 11 15 23 31 41
3 1 1 2 4 6 9 13 21 28 36
2 1 1 1 3 5 8 11 18 24 31
1 0 1 1 2 3 5 7 12 16 20
1/0 0 1 1 1 3 4 6 10 14 18
2/0 0 1 1 1 2 4 6 9 12 15
3/0 0 0 1 1 1 3 5 7 10 13
4/0 0 0 1 1 1 3 4 6 9 11
250 0 0 1 1 1 1 3 5 6 8
300 0 0 0 1 1 1 3 4 6 7
350 0 0 0 1 1 1 2 4 5 7
400 0 0 0 1 1 1 2 3 5 6
500 0 0 0 1 1 1 1 3 4 5
600 0 0 0 0 1 1 1 2 3 4
700 0 0 0 0 1 1 1 2 3 4
750 0 0 0 0 1 1 1 1 3 4
800 0 0 0 0 0 1 1 1 3 3
900 0 0 0 0 0 1 1 1 2 3
1000 0 0 0 0 0 1 1 1 2 3
1250 0 0 0 0 0 1 1 1 1 2
1500 0 0 0 0 0 0 1 1 1 1
1750 0 0 0 0 0 0 1 1 1 1
2000 0 0 0 0 0 0 1 1 1 1
TW 14 10 17 27 47 64 104 147 228 304 392
12 7 13 21 36 49 80 113 175 234 301
10 5 9 15 27 36 59 84 130 174 224
8 3 5 8 15 20 33 47 72 97 124
RHH*, RHW*, 14 6 11 18 31 42 69 98 151 202 261
RHW-2*, 12 5 9 14 25 34 56 79 122 163 209
THHW, THW, 10 4 7 11 19 26 43 61 95 127 163
THW-2 8 2 4 7 12 16 26 37 57 76 98
6 1 3 5 9 12 20 28 43 58 75
4 1 2 4 6 9 15 21 32 43 56
3 1 1 3 6 8 13 18 28 37 48
2 1 1 3 5 6 11 15 23 31 41
1 1 1 1 3 4 7 11 16 22 28
1/0 1 1 1 3 4 6 9 14 19 24
2/0 0 1 1 2 3 5 8 12 16 20
3/0 0 1 1 1 3 4 6 10 13 17
4/0 0 1 1 1 2 4 5 8 11 14
250 0 0 1 1 1 3 4 7 9 12
300 0 0 1 1 1 2 4 6 8 10
350 0 0 1 1 1 2 3 5 7 9
400 0 0 0 1 1 1 3 4 6 8
500 0 0 0 1 1 1 2 4 5 7
600 0 0 0 1 1 1 1 3 4 5
700 0 0 0 0 1 1 1 3 4 5
750 0 0 0 0 1 1 1 2 3 4
Chapter 4 NEC & NEMA Standards 13
800 0 0 0 0 1 1 1 2 3 4
900 0 0 0 0 1 1 1 2 3 4
1000 0 0 0 0 0 1 1 1 3 3
1250 0 0 0 0 0 1 1 1 1 3
1500 0 0 0 0 0 1 1 1 1 2
1750 0 0 0 0 0 0 1 1 1 1
2000 0 0 0 0 0 0 1 1 1 1
THHN, THWN, 14 14 24 39 68 91 149 211 326 436 562
THWN-2 12 10 17 29 49 67 109 154 238 318 410
10 6 11 18 31 42 68 97 150 200 258
8 3 6 10 18 24 39 56 86 115 149
6 2 4 7 13 17 28 40 62 83 107
4 1 3 4 8 10 17 25 38 51 66
3 1 2 4 6 9 15 21 32 43 56
2 1 1 3 5 7 12 17 27 36 47
1 1 1 2 4 5 9 13 20 27 35
1/0 1 1 1 3 4 8 11 17 23 29
2/0 1 1 1 3 4 6 9 14 19 24
3/0 0 1 1 2 3 5 7 12 16 20
4/0 0 1 1 1 2 4 6 9 13 17
250 0 0 1 1 1 3 5 8 10 13
300 0 0 1 1 1 3 4 7 9 12
350 0 0 1 1 1 2 4 6 8 10
400 0 0 1 1 1 2 3 5 7 9
500 0 0 0 1 1 1 3 4 6 7
600 0 0 0 1 1 1 2 3 5 6
700 0 0 0 1 1 1 1 3 4 5
750 0 0 0 1 1 1 1 3 4 5
800 0 0 0 0 1 1 1 3 4 5
900 0 0 0 0 1 1 1 2 3 4
1000 0 0 0 0 1 1 1 2 3 4
FEP, FEPB, 14 13 23 38 66 89 145 205 317 423 545
PFA, PFAH, 12 10 17 28 48 65 106 150 231 309 398
TFE 10 7 12 20 34 46 76 107 166 221 285
8 4 7 11 19 26 43 61 95 127 163
6 3 5 8 14 19 31 44 67 90 116
4 1 3 5 10 13 21 30 47 63 81
3 1 3 4 8 11 18 25 39 52 68
2 1 2 4 6 9 15 21 32 43 56
PFA, PFAH, 1 1 1 2 4 6 10 14 22 30 39
TFE 1/0 1 1 1 4 5 8 12 19 25 32
2/0 1 1 1 3 4 7 10 15 21 27
3/0 0 1 1 2 3 6 8 13 17 22
4/0 0 1 1 1 3 5 7 10 14 18
Z 14 16 28 46 79 107 175 247 381 510 657
12 11 20 32 56 76 124 175 271 362 466
10 7 12 20 34 46 76 107 166 221 285
8 4 7 12 21 29 48 68 105 140 180
6 3 5 9 15 20 33 47 73 98 127
4 1 3 6 10 14 23 33 50 67 87
3 1 2 4 7 10 17 24 37 49 63
2 1 1 3 6 8 14 20 30 41 53
1 1 1 3 5 7 11 16 25 33 43
XHH, XHHW, 14 10 17 27 47 64 104 147 228 304 392
XHHW-2, ZW 12 7 13 21 36 49 80 113 175 234 301
10 5 9 15 27 36 59 84 130 174 224
8 3 5 8 15 20 33 47 72 97 124
6 1 4 6 11 15 24 35 53 71 92
4 1 3 4 8 11 18 25 39 52 67
3 1 2 4 7 9 15 21 33 44 56
14 Electric Power Systems Durham
2 1 1 3 5 7 12 18 27 37 47
1 1 1 2 4 5 9 13 20 27 35
1/0 1 1 1 3 5 8 11 17 23 30
2/0 1 1 1 3 4 6 9 14 19 25
3/0 0 1 1 2 3 5 7 12 16 20
4/0 0 1 1 1 2 4 6 10 13 17
250 0 0 1 1 1 3 5 8 11 14
300 0 0 1 1 1 3 4 7 9 12
350 0 0 1 1 1 3 4 6 8 10
400 0 0 1 1 1 2 3 5 7 9
500 0 0 0 1 1 1 3 4 6 8
600 0 0 0 1 1 1 2 3 5 6
700 0 0 0 1 1 1 1 3 4 5
750 0 0 0 1 1 1 1 3 4 5
800 0 0 0 0 1 1 1 3 4 5
900 0 0 0 0 1 1 1 2 3 4
1000 0 0 0 0 1 1 1 2 3 4
1250 0 0 0 0 0 1 1 1 2 3
1500 0 0 0 0 0 1 1 1 1 2
1750 0 0 0 0 0 1 1 1 1 2
2000 0 0 0 0 0 0 1 1 1 1
Chapter 4 NEC & NEMA Standards 15
Service-Limit Current Ratings - The service-limit current ratings shown represent the maximum rms current, in amperes, which the controller
shall be permitted to carry for protracted periods in normal service. At service-limit current ratings, temperature rises shall be permitted to exceed
those obtained by testing the controller at its continuous current rating. The current rating of overload relays or the trip current of other motor
protective devices used shall not exceed the service-limit current rating of the controller.
Plugging or Jogging Service - The listed horsepower ratings are recommended for those applications requiring repeated interruption of stalled
motor current encountered in rapid motor reversal in excess of five openings or closings per minute and shall not be more than ten in a ten minute
period.
Capacitor terminals - If maximum available current is greater than 3,000 amperes, consult NEMA ICS-2 Standard.
Chapter 4 NEC & NEMA Standards 17
NEMA Table 11 Typical Characteristics and Applications of Fixed Frequency Small and
Medium AC Squirrel-Cage Induction Motors
Design Letter Locked Pull- Break- Locked Slip Typical Applications Relative
Rotor up down Rotor Efficiency
Torque Torque Torque Current
Polyphase Percent Percent Percent Percent Percent
Characteristics Rated Rated Rated Rated Sync
Load Load Load Load Speed
Torque* Torque Torque Current
Design A 70-275 65-190 175-300 Not 0.5-5% Fans, blowers, centrifugal pumps Medium or
defined and compressors, motor-generator high
High locked rotor sets, etc., where starting torque
torque requirements are relatively low.
High locked rotor
current
Design B 70-275 65-190 175-300 600-700 0.5-5% Fans, blowers, centrifugal pumps Medium or
and compressors, motor-generator high
Normal locked sets, etc., where starting torque
rotor torque requirements are relatively low.
Normal locked
rotor current
Design C 200-285 140-195 190-225 600-700 1-5% Conveyors, crushers, stirring motors, Medium
agitators, reciprocating pumps and
High locked rotor compressors, etc., where starting
torque under load is required
Normal locked
rotor current
Design D 275 NA 275 600-700 5-8% High peak loads with or without Low
flywheels such as punch presses,
High locked rotor shears, elevators, extractors,
torque winches, hoists, oil-well pumping
High slip and wire-drawing motors
Design N - NA - - - Centrifugal loads where starting Low
torque requirements are relatively
Small motor low.
Design 0 - NA - - NA
Small motor
Design L - 100% - - NA Fans, blowers, centrifugal pumps Medium or
and compressors, motor-generator low
Medium motor sets, etc., where starting torque
requirements are relatively low.
Design M - 100% - - NA Fans, blowers, centrifugal pumps Medium or
and compressors, motor-generator low
Medium motor sets, etc., where starting torque
requirements are relatively low.
*Higher values are for motors having lower horsepower ratings.
18 Electric Power Systems Durham
Pre-NEMA Dimensions
FRAME U V D 2F E FRAME U V D 2F E
203 3/4 2 5 5-1/2 4 404 2-1/8 6-1/8 10 12-1/4 8
204 3/4 2 5 6-1/2 4 404S 1-7/8 3-1/2 10 12-1/4 8
224 1 2-3/4 5-1/2 6-3/4 4-1/2 405 2-1/8 6-1/8 10 13-3/4 8
225 1 2-3/4 5-1/2 7-1/2 4-1/2 405S 1-7/8 3-/2 10 13-3/4 8
254 1-1/8 3-1/8 6-1/4 8-1/14 5 444 2-3/8 6-7/8 11 14-1/2 9
284 1-1/4 3-3/4 7 9-1/2 5-1/2 444S 2-1/8 4 11 14-1/2 9
324 1-5/8 4-5/8 8 10-1/2 6-1/4 445 2-3/8 6-7/8 11 16-1/2 9
324S 1-5/8 3 8 10-1/2 6-1/4 445S 2-1/8 4 11 16-1/2 9
326 1-5/8 4-5/8 8 12 6-1/4 504 2-5/8 7-5/8 12-1/2 16 8
326S 1-5/8 3 8 12 6-1/4 504S 2-1/8 4 12-1/2 16 8
364 1-7/8 5-3/8 9 11-1/4 7 505 2-7/8 8-3/8 12-1/2 18 9
364S 1-7/8 3-1/2 9 11-1/4 7 505S 2-1/8 4 12-1/2 18 9
356 1-7/8 5-3/8 9 12-1/4 7 584 2-7/8 11-5/8 14-1/2 18 9
365S 1-5/8 3-1/2 9 12-1/4 7 584S 2-3/8 4-3/4 14-1/2 18 9