1VDD005976 GB
Contents
1. General description 3
1.1 Table of locations 4
1.2 Dimensional drawings 5
2. Transport and handling 6
2.1 By receiving Inspection 6
2.2 Storage 6
3. Technical data 7
3.1 Electrical data 7
3.2 Fuse table for modules 9
4. Installation 10
4.1 Cable compartment 11
4.2 Cable connection 12
4.3 Current transformers for relay protection 13
4.4 Gas pressure 14
5. Operation 15
5.1 Operating conditions 15
5.2 Operation 16
5.3 Installation and replacement of fuses 18
6. Additional equipment 20
6.1 Low-voltage connections auxiliary contacts 20
6.2 Remote control and monitoring unit 20
6.3 Capacitive voltage indicator 20
6.4 Short circuit indicator 20
6.5 Motor operation 21
6.6 Cable testing 21
6.7 External busbar 22
6.8 Arc-suppressor 22
6.9 Pressure indicator 22
6.10 Base frame 22
6.11 Ronis key interlock 22
6.12 Top entry box for low voltage cables 22
6.13 Low voltage compartment 22
7. Maintenance 22
7.1 Control and monitoring the gas 22
7.2 Environmental certification 23
2
DOC ID: 13-2016-0401-04
1. GENERAL DESCRIPTION
SafeRing is a SF6-insulated ring main unit and SafePlus is a
compact switchgear for applications in medium voltage distri-
bution networks. SafeRing can be supplied as a 2, 3 or 4-way
standard configurations with additional equipment according
to customer specification.
Available configuraitons:
DeF, CCF, CCC, CCCF, CCFF, DeV, CCV, CCCC, CCCV,
CCVV.
Available modules:
Be - SL - Sv - M - C - De - D - F - V.
The units / modules are delivered from the factory ready for
installation.
SafeRing 3-way unit CCV Routine tests are carried out on all units/ modules before
dispatch.
3
DOC ID: 13-2016-0401-04
1.1 TABLE OF LOCATIONS
1. Lifting lugs
2. Capacitive voltage indication (additional equipment)
3. Short circuit indicator (additional equipment)
4. Pressure indicator (additional equipment)
5. Legend plate with serial number
6. Mimic diagram
7. Relay protection
8. Blown fuse indicator
9. Padlock device
10. Cable compartment
11. Test bushings (additional equipment)
12. Ronis key interlock (additional equipment)
13. Circuit breaker
14. Fuse switch disconnector
15. Earthing switch
16. Isolator
17. Circuit breaker open/ emergency stop
18. Circuit breaker close
19. Fuses
4
DOC ID: 13-2016-0401-04
1.2 DIMENSIONAL DRAWINGS
Unit mm
1-way 371
2-way 696
3-way 1021
4-way 1346
5-way 1671
5
DOC ID: 13-2016-0401-04
2. TRANSPORT AND HANDLING
The units are delivered from the factory ready for installation.
SafePlus
Standard 1-way 150 kg
2-, 3 and 4-way as for SafeRing
5-way approx. 750 kg
M-metering cubicle approx. 250 kg
2.2 STORAGE
SafeRing / SafePlus must be stored under cover in a dry and
well ventilated area until it is installed and put into operation.
6
DOC ID: 13-2016-0401-04
3. TECHNICAL DATA
3.1 ELECTRICAL DATA
1)
Depending on the current rating of the fuse-link
2)
Limited by high voltage fuse-links
3)
Maximum rating for bushings Interface A (200 series plug-in)
4)
Maximum rating for bushings Interface B (400 series plug-in)
5)
Maximum rating for bushings Interface C (400 series bolted)
SafeRing is tested according to IEC Publications IEC 60265, IEC 60694 and IEC 62271, parts 100, 102, 105, 200
1)
Depending on the current rating of the fuse-link
2)
Limited by high voltage fuse-links
3)
Maximum rating for bushings Interface A (200 series plug-in) with rated current 200A
4)
Maximum rating for bushings Interface B (400 series plug-in)
5)
Maximum rating for bushings Interface C (400 series bolted)
6)
Data for V-module 12kV/25kA, 24kV/20kA, see next page
SafePlus is tested according to IEC Publications IEC 60265, IEC 60694 and IEC 62271, parts 100, 102, 105, 200
7
DOC ID: 13-2016-0401-04
Technical data Vacuum circuit-breaker 24kV/20kA
Rated voltage kV 24
Power frequency withstand voltage kV 50
Impulse withstand voltage kV 125
Rated normal current A 630
Breaking capacities:
- short-circuit breaking current kA 20
Making capacity kA 50
Short time current 1 sec. 1) kA 21
Short time current 3 sec. kA 21
Number of mechanical operations 2000 close / open manual
Earthing switch downstream
Rated voltage kV 24
Power frequency withstand voltage kV 50
Impulse withstand voltage kV 125
Making capacity kA 50
Short time current 1 sec. A 21
Number of mechanical operations 1000 close / open manual
1)
Maximum rating for bushings Interface B (400 series plug-in): 16kA
8
DOC ID: 13-2016-0401-04
3.2 FUSE TABLE FOR MODULES
7,2 kV
5 10 16 25 25 25 40 40 50 50 63 80 100 160 160
5,5 6 16 16 25 25 25 40 50 50 63 80 100 125 160
6 6 16 16 25 25 25 40 40 50 50 80 100 125 160 160
6,6 6 16 16 25 25 25 40 40 50 50 63 80 100 125 160
10 6 10 10 16 16 25 25 25 40 40 50 50 80 80 125 125
12 kV
11 6 6 10 16 16 25 25 25 25 40 50 50 63 80 100 125
12 6 6 10 16 16 16 25 25 25 40 40 50 63 80 100 125
13,8 6 6 10 10 16 16 25 25 25 25 40 50 50 63 80 100
17,5 kV
15 6 6 10 10 16 16 16 25 25 25 40 40 50 63 80 100
17,5 6 6 6 10 10 16 16 16 25 25 25 40 50 50 63 80
20 6 6 6 10 10 16 16 16 25 25 25 40 40 50 63 63
24 kV
22 6 6 6 6 10 10 16 16 16 25 25 25 40 50 50 63
24 6 6 6 6 10 10 16 16 16 25 25 25 40 40 50 63
7,2 kV
5 10 16 25 25 25 40 40 50 63 80 80 100 160 160
5,5 6 16 16 25 25 25 40 50 50 80 80 100 125 160
6 6 16 16 25 25 25 40 40 50 63 80 100 125 160 160
6,6 6 16 16 25 25 25 40 40 50 63 80 80 100 125 160
10 6 10 10 16 16 25 25 25 40 40 50 50 80 80 125 125
12 kV
11 6 6 10 16 16 25 25 25 25 40 50 50 63 80 100 125
12 6 6 10 16 16 16 25 25 25 40 40 50 63 80 100 125
13,8 6 6 10 10 16 16 25 25 25 25 40 50 50 63 80 100
17,5 kV
15 6 6 10 10 16 16 16 25 25 25 40 40 50 63 80 100
17,5 6 6 6 10 10 16 16 16 25 25 25 40 50 50 63 80
20 6 6 6 10 10 16 16 16 25 25 25 40 40 50 63 63
24 kV
22 6 6 6 6 10 10 16 16 16 25 25 25 40 50 50 63
24 6 6 6 6 10 10 16 16 16 25 25 25 40 40 50 63
−− Both tables above are based on using ABB CEF hihg-voltage current-limiting back-up fuse-links
−− Normal operating conditions with no overlaod of transformer (table 1) and with 20% overlaod of transformer (table 2)
−− Ambient air temperature -25oC to +40oC
9
DOC ID: 13-2016-0401-04
4. INSTALLATION
The floor must be well leveled and the unit must be fixed by
means of anchor bolts in accordance with the dimensional Distance between wall fixtures
drawing for the number of modules or units as appropriate.
Removable
− − Distance from floor to roof must be minimum 2400 mm 1-way 271 297 336 371
− − Distance from back of unit to wall must be 100 mm. 2-way 696 622 661 696
− − Distance from side wall of unit to wall should preferably be 3-way 1021 947 986 1021
20 mm. 4-way 1346 1272 1313 1346
− − Protection cover(s) with height 650 mm must be mounted 5-way 1581 1597 1636 1671
on the side(s) of the unit when distance exceeds 20 mm.
− − If unit is freestanding (i.e. distance from back of unit to wall
exceeds 100 mm), the area behind the unit must be restric-
ted and not accessible.
− − Minimum dimensions of cable trench are 230 x 355 mm.
10
DOC ID: 13-2016-0401-04
4.1 CABLE COMPARTMENT NB!
Removal of cable cover:
The cable cover can be supplied with interlocking to earthing
switches. When interlocking is fitted, the cable cabinet can
only be accessed when the earthing switch is in the closed
position.
1. Loosen the screws on the cable cover, pull out and lift 3. Front section removed.
cover off.
11
DOC ID: 13-2016-0401-04
4.2 CABLE CONNECTION
SafeRing/SafePlus is equipped with external bushings which
comply with DIN47636T1 & T2/EDF HN 525-61 for termina-
tion of cables.
All bushings are situated in the same height from the floor and
are protected by the cable cover.
Type of module
Bushings C F V
200 series plug-in X X
400 series plug-in X X X
400 series bolted X X X
600 series bolted X
Cable adapters
The following types are recommended:
ABB Kabeldon
ABB Kabel und Draht
Elastimold
Raychem
Cooper
3M
NB!
Where cables are not connected, the earthing switch must be
locked in closed position or the bushings must be fitted with
deadend recepticals before the unit is put into operation.
12
DOC ID: 13-2016-0401-04
4.3 RELAY AND CURRENT TRANSFORMERS
A protection relay is installed in each vacuum circuit-breaker
module. The cables from the protection relay to the current
transformers are installed from the factory, and end up in the
cable compartment, ready for connection to the three current
transformers supplied.
Before installation:
− − Check that the three current transformers have been
delivered and that they are all of the same type.
− − Check that the current transformers are of the correct type,
75
13
DOC ID: 13-2016-0401-04
4.4 GAS PRESSURE
SafeRing / SafePlus contain SF6 gas with a nominal pressure
Green area
of 1,4 bar at 20o C.
SF 6 Air
Topping up of SF6 gas in SafeRing/SafePlus
Potensial risk!
Operators must be trained and qualified for SF6 gas
handling
Following equipment is needed: SF6 gas bottle with mano-
meter and reduction valve, bottle for recovery of SF6/air mix-
ture, adapter and pressure measuring device. It is important
that the pressure measuring device shows absolute pressure. Note! Screw/unscrew on this hexagonal
Spring-loaded nut only. The pressure indicator can be
If you have a pressure measuring device showing over- valve dismounted from the switchgear with-
pressure, please contact ABB for instructions (NHP 408025). out SF6 leakage from the SF6 tank
1,45
SF6-gas temp Absolute filling
pressure
1,4
o
C mbar
0 1305
1,35
Filing pressure Bar abs
5 1328
10 1352
1,3
15 1376
20 1400
1,25
30 o 25 1424
30 1448
1,2
20 o 35 1472
1,15
40 1496
10o
1,1
1,05
1
0
500
1000
1500
2000
2500
3000
3500
4000
Altitude
14
DOC ID: 13-2016-0401-04
5. OPERATION Application of the X-ray regulations
5.1 OPERATING CONDITIONS One of the physical properties of vacuum insulation is the
Normal ambient conditions possibility of X-ray emissions when the contact gap is open.
SafeRing / SafePlus is generally equipped for operation/ The specified type test performed by the Physikalisch-
service in normal indoor conditions in accordance with Technische Bundesanstalt (PTB) in Brunswick demonstrates
IEC 62271-1. that the local dosage output of 1 µSv/h at a distance of 10 cm
from the touchable surface is not exceeded.
Special conditions
In accordance with IEC 62271-1, the manufacturer and end-
user must agree about special operating conditions which
deviate from operation under normal conditions.
Airfreight
Units / modules transported by airfreight are delivered with
reduced overpressure. For topping up, please see procedure
for topping up of SF6 gas.
15
DOC ID: 13-2016-0401-04
5.2 OPERATION
All switches can be operated with the included operating
handle.
Internal mechanical interlocking between the switch discon-
nector/isolator and the associated earthing switches prevents
incorrect operation.
The isolator in the V-Module can only be opened after the cir-
cuit breaker is opened. Then the circuit breaker can be closed
for testing purpose.
Earthing switch:
C
Close: Turn the operating handle clockwise.
Open: Turn the operating handle anti-clockwise.
F-Module
D
Switch fuse disconnector:
Close: Turn the operating handle clockwise to charge
the close/open spring. Then push the green button. (A)
Open: Push the red button. (B)
16
DOC ID: 13-2016-0401-04
OPERATION OF VACUUM CIRCUIT-BREAKER - 24kV/20kA
Indication -
spring charged /( discharged
17
DOC ID: 13-2016-0401-04
5.3 INSTALLATION AND REPLACEMENT OF FUSE-LINKS
A red indicator below the fuse symbol on the lower front panel
indicates that at least one fuse-link has blown. Fuse links are
replaced as shown in the sequence of illustrations. Switch-
fuse configurations are supplied without fuse-links installed.
18
DOC ID: 13-2016-0401-04
7. Fix the fuses to the fuse cover using the contact 8.Turn the handle on the fuse cover clockwise to
screw lose and seal the fuse canister.
Use the operating handle.
- The striker must point out from the fuse canister
for the fuse to function properly. 9. Close the fuse panel.
Striker
19
DOC ID: 13-2016-0401-04
6. ADDITIONAL EQUIPMENT
6.1 LOW-VOLTAGE CONNECTIONS
Auxiliary contacts (2NO+2NC) can be supplied to indicate
switch positions on all switches/breakers. Access to the low-
voltage connections is gained by removing the top front panel.
A shunt trip coil (AC or DC) can be fitted on the transformer
switch/breaker.
VIM 1 VIM 3
Voltage indicators
20
DOC ID: 13-2016-0401-04
6.5 MOTOR OPERATION 6.6 CABLE TESTING
Cable switches, vacuum circuit-breakers and earthing swit- Voltage testing and locating cable faults can be performed in
chesare operated by mechanisms located behind the front two ways:
panel.The mechanisms for all the switches and breakers are
operated manually with the operating level (standard), or 1. Directly at the testing points (A) if they are fitted on the
are fitted with motor operation (additional equipment). The unit. Proceed as follows: engage the earthing switch.
earthing switch can only be operated manually and is fitted Connect the testing equipment on top of the testing
with mechanisms to achieve fault making capabilities. points which hold the earth bar (B). Remove the earth
bar and perform the test. Refit the earth strip before the
Motor operation can be easily retrofitted. testing equipment is disconnected
2. Directly at the cable connectors which are designed for
testing the voltage of the cable.
Follow the supplier’s instructions.
21
DOC ID: 13-2016-0401-04
6.7 EXTERNAL BUSBAR
SafeRing and SafePlus can be equipped with an external bus-
bar. See seperate instruction manual NOPOWSP 6006 GB.
6.8 ARC-SUPPRESSOR
An arc-suppressor can be fitted on all cable modules for Safe-
Ring and C, D, De and V-modules on SafePlus. They must be
ordered together with the unit and cannot be retrofitted.
The tripped of an arc-suppressor is indicated by means of a
electric contact in the SF6 tank, wired to the terminal strip
behind the top front panel. (This requires aux. voltage supply.)
7. MAINTENANCE
All components in the SF6 tank are maintenance-free for the
declared life expectancy of the product. The tank is made of
stainless steel.
If the panels substain any scratches or damage, these must
be repaired with paint to prevent corrosion.
22
DOC ID: 13-2016-0401-04
7.2 ENVIRONMENTAL CERTIFICATION
1. LIFE EXPECTANCY OF PRODUCT
The switchgear is gas-tight with an expected diffusion rate of
The product is developed in compliance with the requirements
less than 0.1 % per annum. Referring to the reference-pressu-
denoted by IEC 298. The design incorporates a life span
re of 1.4 bar, the switchgear will maintain gas-tightness and a
under indoor serviceconditions exceeding 30 years (IEC 298
gas-pressure better than 1.3 bar* throughout its designed life
annex GG).
span.
*) at 20oC.
RECYCLING CAPABILITY
Raw Material Weight (kg) % of total Recycle Environmental effects & recycle/reuse processes
weight
Iron 132,80 42,53 Yes Separate, utilise in favour of new source (ore)
Stainless steel 83,20 24,93 Yes Separate, utilise in favour of new source (ore)
Copper 43,98 14,09 Yes Separate, utilise in favour of new source (ore)
Brass 2,30 0,74 Yes Separate, utilise in favour of new source (ore)
Aluminium 8,55 2,74 Yes Separate, utilise in favour of new source (ore)
Zinc 3,90 1,25 Yes Separate, utilise in favour of new source (ore)
Silver 0,075 0,024 Yes Electrolysis, utilise in favour of new source
Thermoplastic 5,07 1,63 Yes Make granulate, re-use or apply as energy superior
additive in refuse inccineration
Epoxy incl. 60% quartz 26,75 8,35 Yes Grind to powder and use as high-grade energy additive in cement mill
Rubber 1,35 0,42 Yes High-grade energy additive in refuse incineration
Dielectric oil 0,21 0,066 Yes Reclaim or use as high-grade energy additive in refuse incineration
SF6 gas 3,24 1,04 Yes ABB AS in Skien reclaims used SF6 gas
Total recycleables 311,42 97,81
Unspecified* 9,00 No *Stickers, film foils, powder coating, screws, nuts, grease....
Total weight ** 320 100
Packing foil 0,20 Yes High-grade energy additive in refuse incineration
Wooden pallet 21,50 Yes Re-use or use as energy additive in refuse incineration
**) All figures are collected from CCF 3-way unit with fuse canisters
3. END-OF-LIFE
ABB AS, Power Products Division, is committed to the pro- We also recommend ABB’s website : http://www.abb.com/sf6
tection of the environment and adhere to ISO 14001 stan-
dards. It is our obligation to facilitate end-of-life recycling for ABB AS, Power Products Division in Skien is equipped to rec-
our products. laim SF6 gas from discarded switchgears.
23
DOC ID: 13-2016-0401-04