Final Structural DWG of Public Toilet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

1 2 3

CORNER
2545 2545
BARS

GENERAL NOTES:

350
B

700
1. USE M20 GRADE CONCRETE FOR BEAM AND SLAB .
ALL OTHER RCC AND PCC WORKS SHALL BE AS PER SPECIFIED IN THE DRAWINGS.
2. USE Fe500 GRADE STEEL
350
3. CLEAR COVER TO BARS FOOTING LINE FOOTING LINE
350
a. FOR BEAMS (FROM FACE TO LATERAL STIRRUPS) = 25mm
b. FOR OUTER BARS IN SLAB = 15mm

3470
350mm BRICK
c. FOR BANDS = 25mm WALL IN 1:4
4. BRICK SHALL HAVE ATLEAST 8MPA COMPRESSIVE STRENGTH C/S RATIO
700 700
5. MORTAR SHALL BE OF 1:4 RATIO (CEMENT/SAND RATION) AND THICKNESS SHALL NOT EXCEED 12mm DETAIL 2 DETAIL AT 1
AND VERTICAL JOINT SHALL BE PROPERLY CHECKED DURING THE MASONRY WORK
6. BACKFILL SHALL BE IN LAYERS OF 150mm THK. WITH PROPER MECHANICAL
COMPACTION AND WATERING AFTER EACH LAYER

350

700

700
A
7. SOLING SHAL BE OF GRADE B BRICK AND VOIDS ARE TO BE FILLED WITH EITHER
GRANULAR MATERIAL OR SAND FILL
8. AFTER CONCRETING RCC OR PCC, IT SHALL BE PROTECTED FROM RAIN FOR AT LEAST VERTICAL BAND FOOTING LAYOUT PLAN
10 HRS [ 1: 50 ] A
9. CURING SHALL BE DONE FOR AT LEAST 10DAYS FOR RCC AND PCC PART WHILE 7 DAYS FOR MASONRY TYP.
AND PLASTER WORK

10.BRICK SHALL BE WETTED IN A CONTAINER FOR AT LEAST ONE HOUR BEFORE


USE
SCALE: 1:10
11.CEMENT SHALL BE USED WITHIN 90DAYS OF ITS MANUFACTURE DATE AND SHALL
BE STORED IN DRY PLACES WITH REGULAR PILES NOT EXCEEDING 10 BAGS

12.AGGREGATE SIZE SHALL BE 12mm (DOWN) WELL GRADED CRUSHED FOR 50 TO 100 mm THK. 2 NOS. 10Ø
THAT CONTINUES TO THE TOP
CONCRETE WORK AND 20mm DOWN (WELL GRADED CRUSHED)FOR 100mm TO 300mm THK. CONCRETE WORK
16Ø
25 230
13.REBAR SHALL BE RUST FREE; IF RUST IS OBSERVED DURING CASTING SHALL BE REMOVED WITH CHEMICALS VERTICAL BARS
10Ø

75
14.CURING IS RECOMMENDED FOR 4 TIMES A DAY WITH PROPER MEANS.
M20 MICRO-CONCRETE
15.TOOTHING SHALL BE IN STEPS 8Ø@200 mm
10Ø
C.C LINKS VERTICAL BAR DETAILS
350

DETAIL AT 2 DETAIL 1

SCALE: 1:10 SCALE: 1:10

CLIENT: SILT CONSULTANTS (P) LTD. TEAM LEADER : ER. BUDDHI SAGAR THAPA SCALE : AS SHOWN STAGE: JOB TITLE: SHEET TITLE: SHEET NO.
JV DATE : MARCH ,2023 FINAL DRAWINGS PUBLIC TOILET DRAWINGS. TRENCH LAYOUT
ARCHITECT : AR. RAJESH KUMAR DAS
MEDICAL COLLEGE INFRASTRUCTURE CONSTRUCTION DEVELOPMENT COMMITTEE (MCICDC), GETA, MOONLIGHT CIVIL SOLUTION (P) LTD. ST
KAILALI, NEPAL EVERSAFE ENGINEERING CONSULTANCY (P) LTD. ENGINEER : ER. GOVIND RAJ BHATTA APPROVED BY :
1
KATHMANDU, NEPAL CAD BY : ER. SALIN SHRESTHA CHECKED BY :
BAND 3

PLINTH BEAM
8Ø@150 mm C.C BOTHWAYS 8Ø@150 mm C.C BOTHWAYS
[THESE BARS SHALL BE CUT OFF AT THE [THESE BARS SHALL BE CUT OFF AT THE
175 POINT OF SANITARY FIXTURES] PLINTH BEAM 175 POINT OF SANITARY FIXTURES]
BAND 2
SEE ARCHITECTURAL

150

SEE ARCHITECTURAL

150
DRAWING

DRAWING
ORIGINAL GROUND LEVEL
ORIGINAL GROUND LEVEL

BAND 1
350
350

125 125
900

125 125

900
250

50 50
50

250

750
50 8Ø@150 mm C.C
50 100

600 JUST BELOW THE 115mm WALL

50 100
75

100 PLINTH LEVEL


M10 PCC
M10 PCC 150
200

75
700
700
RAMMED EARTH ONE LAYER FLAT BRICK SOLING
RAMMED EARTH ONE LAYER FLAT BRICK SOLING

TYPICAL FOOTING DETAIL WITH VERTICAL BARS


TYPICAL FOOTING DETAIL 3 NOS. 10Ø

100
SCALE: 1:20 DETAIL A [TYP.]
SCALE: 1:20
TYPICAL FOOTING DETAIL FOR HALF BRICK WALL
SCALE: 1:20

CLIENT: SILT CONSULTANTS (P) LTD. TEAM LEADER : ER. BUDDHI SAGAR THAPA SCALE : AS SHOWN STAGE: JOB TITLE: SHEET TITLE: SHEET NO.
JV DATE : MARCH ,2023 FINAL DRAWINGS PUBLIC TOILET DRAWINGS. FOOTING DETAILS
ARCHITECT : AR. RAJESH KUMAR DAS
MEDICAL COLLEGE INFRASTRUCTURE CONSTRUCTION DEVELOPMENT COMMITTEE (MCICDC), GETA, MOONLIGHT CIVIL SOLUTION (P) LTD. ST
KAILALI, NEPAL EVERSAFE ENGINEERING CONSULTANCY (P) LTD. ENGINEER : ER. GOVIND RAJ BHATTA APPROVED BY :
2
KATHMANDU, NEPAL CAD BY : ER. SALIN SHRESTHA CHECKED BY :
1 2 3

2545 2545
1 2 3
THIS CORNER BAR
TERMINATES AT SLAB LEVEL 2545 2545
B
B 3 NOS. 12Ø

PB 230X300 PB 230X300 230

8Ø@200mm
C.C LINKS

300
3470

PB 230X300

PB 230X300
3470

PB 230X300
THIS CORNER BAR BRICK MASONRY
TERMINATES AT SLAB LEVEL IN 1:4 C/S

3 NOS. 12Ø
BRICK MASONRY PLINTH BEAM DETAILS
IN 1:4 C/S
SCALE: 1:10
SEE DETAIL 1
PB 230X300 PB 230X300
A
A

SEE DETAIL "3"


REDUCED BAND FROM 350X75
TO 230X75 PLINTH BEAM LAYOUT PLAN
[ 1: 50 ]
WALL LAYOUT PLAN AT PLINTH LEVEL
1 2 3
[ 1: 50 ]
2545 2545

1 2 3

2545 2545
B

8Ø@150C.C
MB 230X300 MB 230X300

125 mm
3470
MB 230X300

MB 230X300

8Ø@150C.C
MB 230X300
3470

125 mm

MB 230X300 MB 230X300 A

FIRST FLOOR BEAM LAYOUT PLAN


[ 1: 50 ]
BOTTOM REINFORCEMENT DETAIL FOR SLAB
[ 1: 50 ]

CLIENT: SILT CONSULTANTS (P) LTD. TEAM LEADER : ER. BUDDHI SAGAR THAPA SCALE : AS SHOWN STAGE: JOB TITLE: SHEET TITLE: SHEET NO.
JV DATE : MARCH ,2023 FINAL DRAWINGS PUBLIC TOILET DRAWINGS. WALL DETAIL
ARCHITECT : AR. RAJESH KUMAR DAS
MEDICAL COLLEGE INFRASTRUCTURE CONSTRUCTION DEVELOPMENT COMMITTEE (MCICDC), GETA, MOONLIGHT CIVIL SOLUTION (P) LTD. ST
KAILALI, NEPAL EVERSAFE ENGINEERING CONSULTANCY (P) LTD. ENGINEER : ER. GOVIND RAJ BHATTA APPROVED BY :
3
KATHMANDU, NEPAL CAD BY : ER. SALIN SHRESTHA CHECKED BY :
1 2 3

2545 2545
3-12Ø TH. 3-12Ø TH.
1 1

B 1 1
3-12Ø TH. 3-12Ø TH.
600 600 600 600

8Ø@150C.C
600

600
8Ø@150C.C
2L-8Ø@100c.c 2L-8Ø@150c.c 2L-8Ø@100c.c 2L-8Ø@100c.c 2L-8Ø@150c.c 2L-8Ø@100c.c

125 mm
3-12Ø TH.
L-SECTION
1 OF BEAM ALONG AA AND BB

500
3470

800 800 500

1
3-12Ø TH.
600 600
125 mm
2L-8Ø@100c.c 2L-8Ø@100c.c 2L-8Ø@100c.c
600

600
8Ø@150C.C
L-SECTION OF BEAM ALONG 11, 22 ,AND 33
A

3 NOS. 12Ø
STRUCTURAL SLAB LEVEL
230
TOP REINFORCEMENT DETAIL FOR SLAB
[ 1: 50 ]

125
300
2 NOS. 10Ø 3 NOS. 10Ø

230 305
3 NOS. 12Ø
BEAM SECTION AT 1
75

75

SCALE: 1:10
8Ø@200 mm 8Ø@200 mm
C.C LINKS C.C LINKS
VERTICAL BAND DETAIL SILL BAND DETAIL
DETAIL 3 9" WALL

SCALE: 1:10 2 NOS. 10Ø


SCALE: 1:10
THAT CONTINUES TO THE TOP

2 NOS. 10Ø 16Ø


25 230 VERTICAL BARS
10Ø
2 NOS. 10Ø
75

115
230
M20 MICRO-CONCRETE
8Ø@200 mm
75
75

10Ø
C.C LINKS VERTICAL BAR DETAILS
350
8Ø@200 mm 8Ø@200 mm DETAIL 1
C.C LINKS C.C S LINKS DETAIL AT 2

LINTEL BAND DETAIL SILL BAND DETAIL SCALE: 1:10 SCALE: 1:10
DETAIL 3 4" WALL
SCALE: 1:10
SCALE: 1:10

CLIENT: SILT CONSULTANTS (P) LTD. TEAM LEADER : ER. BUDDHI SAGAR THAPA SCALE : AS SHOWN STAGE: JOB TITLE: SHEET TITLE: SHEET NO.
JV DATE : MARCH ,2023 FINAL DRAWINGS PUBLIC TOILET DRAWINGS. BEAM DETAIL
ARCHITECT : AR. RAJESH KUMAR DAS
MEDICAL COLLEGE INFRASTRUCTURE CONSTRUCTION DEVELOPMENT COMMITTEE (MCICDC), GETA, MOONLIGHT CIVIL SOLUTION (P) LTD. ST
KAILALI, NEPAL EVERSAFE ENGINEERING CONSULTANCY (P) LTD. ENGINEER : ER. GOVIND RAJ BHATTA APPROVED BY :
4
KATHMANDU, NEPAL CAD BY : ER. SALIN SHRESTHA CHECKED BY :
FOLLOW LINTEL BAND DETAILS

FOLLOW VERTICAL BAND DETAILS

SILL BAND

VERTICAL BAND VERTICAL BAND


FOLLOW DETAIL 3 FOLLOW DETAIL 3

SILL BAND

BAND DETAILS

CLIENT: SILT CONSULTANTS (P) LTD. TEAM LEADER : ER. BUDDHI SAGAR THAPA SCALE : AS SHOWN STAGE: JOB TITLE: SHEET TITLE: SHEET NO.
JV DATE : MARCH ,2023 FINAL DRAWINGS PUBLIC TOILET DRAWINGS. SLAB REINFORCEMENT DETAILS
ARCHITECT : AR. RAJESH KUMAR DAS
MEDICAL COLLEGE INFRASTRUCTURE CONSTRUCTION DEVELOPMENT COMMITTEE (MCICDC), GETA, MOONLIGHT CIVIL SOLUTION (P) LTD. ST
KAILALI, NEPAL EVERSAFE ENGINEERING CONSULTANCY (P) LTD. ENGINEER : ER. GOVIND RAJ BHATTA APPROVED BY :
5
KATHMANDU, NEPAL CAD BY : ER. SALIN SHRESTHA CHECKED BY :