Design Calculations Columns
Design Calculations Columns
Design Calculations Columns
Definitions Of Terms:
All forces in units kN and m
All reinforcement details like area, spacing in mm
Neutral axis angle for resultant design moment is with respect to local major axis.
Ratio to account for reduction of stiffness of columns
1 βdns =
due to sustained axial loads
Moment magnification factor for frames not braced
2 δns =
against sidesway
First-order relative deflection between the top and
3 Δo =
bottom of the story due to Vu in mm
4 ∑Pu = Total factored vertical load in kN. (Clause 10.10.5.2)
5 δu = Design displacement in mm
Modification factor reflecting the reduced mechanical
6 λ =
properties of concrete
Coefficient defining the relative contribution of
7 ac =
concrete strength to nominal wall shear strength
Cross-sectional area of a structural member measured
8 Ach = to the outside edges of transverse reinforcement in
sqmm
Gross area of concrete section bounded by web
9 Acv = thickness and length of section in the direction of
shear force considered in sqmm
Effective cross-sectional area within a joint in a plane
10 Aj = parallel to plane of reinforcement generating shear in
the joint in sqmm
Area of non-prestressed longitudinal tension
11 As =
reinforcement in sqmm
Minimum area of shear reinforcement within spacing
12 Avmin =
's' in sqmm
13 B = Width of column/ wall in mm
Cross-sectional dimension of member core measured
14 bc = to the outside edges of the transverse reinforcement
composing area Ash in mm
Distance from extreme compression fiber to neutral
15 c =
axis in mm
16 Cc = Clear cover to longitudinal reinforcement in mm
Factor relating actual moment diagram to an
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 2 of 227
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 3 of 227
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 4 of 227
71 Vuy1 = depth, kN
Shear due to enhanced earthquake factor along depth,
72 Vuy2 =
kN
73 y = Neutral axis depth.
It is a Neutral Axis angle corresponding to load angle
74 β =
to find out MCap
Code References:
ACI 318M - 2011
Sr.No Element Clause / table
Minimum area of longitudinal reinforcement
1 : 21.6.3
for column
Maximum area of longitudinal
2 : 21.6.3
reinforcement for column
Minimum longitudinal and transverse
3 : 21.9.2.1
reinforcement for wall
4 Minimum diameter of transverse ties : 7.10.5
5 Minimum spacing of transverse ties : 7.10.5
Maximum spacing of longitudinal and
6 : 21.9.2.1
transverse reinforcement for wall
7 Applicability of boundary element : 21.9.6
Area and spacing of special confining
8 : 21.6.4
reinforcement
9 Slenderness Moments : 10.10
Shear Strength provided by concrete for
10 : 11.2
column
11 Design of shear for non-ductile wall : 11.9
12 Design of shear for ductile wall : 21.9.4
13 Minimum Flexural Strength of Columns : 21.6.2.2
14 Shear Check at Column Joint : 21.7.4.1
15 Shear Strength of Column : 21.3.3 & 21.5.4
16 fs,perm : 10.6.4
17 fc,perm : 10.2.7.1
18 Wcr : Eq 4.2(a)
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 5 of 227
3m to
216 2.8 2873.471 2.758 396.298 0.007 Non Sway
5.8m
5.8m to
216 2.8 119.534 1.702 28.583 0.003 Non Sway
8.6m
General Data
Column No. : C1
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1102
Critical Analysis Load Combination : 110
[10] : 1.2 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 2: EQ +X -E)
Critical Location = Bottom Joint
Put = 291.72 kN
Muxt = -53.59 kNm
Muyt = 4.73 kNm
Vuxt = 6.6 kN
Vuyt = 43.01 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 6 of 227
Pub = 305.55 kN
Muxb = 75.4 kNm
Muyb = -15.06 kNm
Vuxb = 6.6 kN
Vuyb = 43.01 kN
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 7 of 227
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 19.59
M1 = -53.59 kNm
M2 = 75.4 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 19.59
M1 = 4.73 kNm
M2 = -15.06 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.77
19.59 < 37.77, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 8 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 110
[10] : 1.2 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 2: EQ +X -E)
Nu = 305.55 kN
Muy = 75.4 kNm
Vuy = 43.009 kN
λ = 1
φ = 0.75
deff = 340.5 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 9 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 10 of 227
General Data
Column No. : C1
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
Clear Floor Height @ luy = 2450 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 2102
Critical Analysis Load Combination : 223
[51] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 8: EQ -Z -E)
Critical Location = Top Joint
Put = 139.18 kN
Muxt = 31.61 kNm
Muyt = 45.78 kNm
Vuxt = 35.51 kN
Vuyt = -14.78 kN
Pub = 157.25 kN
Muxb = -9.76 kNm
Muyb = -53.61 kNm
Vuxb = 35.51 kN
Vuyb = -14.78 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 11 of 227
350
Sway Condition (as per Stability
= Non Sway
Index)
Effective Length Factor along Major
= 1
Axis
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 21.22
M1 = -9.76 kNm
M2 = 31.61 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.71
21.22 < 37.71, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.74
r = 115.47 mm
Klux /r = 15.7
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 12 of 227
M1 = 45.78 kNm
M2 = -53.61 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.7 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 13 of 227
φ Pn = 274.26 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 218
[46] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 3: EQ -X +E)
Nu = 209.98 kN
Muy = 60.92 kNm
Vuy = -34.304 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 27.86 kNm
φVcy = 92.09 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 14 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C2
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 15 of 227
Load Data
Analysis Reference No. = 1110
Critical Analysis Load Combination : 110
[10] : 1.2 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 2: EQ +X -E)
Critical Location = Bottom Joint
Put = 470.18 kN
Muxt = -69.62 kNm
Muyt = -2.72 kNm
Vuxt = -0.66 kN
Vuyt = 50.93 kN
Pub = 484.01 kN
Muxb = 83.13 kNm
Muyb = -0.73 kNm
Vuxb = -0.66 kN
Vuyb = 50.93 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 16 of 227
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 19.59
M1 = -69.62 kNm
M2 = 83.13 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.73
r = 115.47 mm
Klux /r = 16.75
M1 = -0.73 kNm
M2 = -2.72 kNm
Min (40, 34 - 12 x (M1/M2)) = 30.76
16.75 < 30.76, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 17 of 227
Design Of Shear
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 18 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 19 of 227
General Data
Column No. : C2
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
Clear Floor Height @ luy = 2450 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 2109
Critical Analysis Load Combination : 217
[45] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 2: EQ +X -E)
Critical Location = Top Joint
Put = 263.26 kN
Muxt = -66.63 kNm
Muyt = 30.68 kNm
Vuxt = 19.64 kN
Vuyt = 45.62 kN
Pub = 281.33 kN
Muxb = 61.07 kNm
Muyb = -24.29 kNm
Vuxb = 19.64 kN
Vuyb = 45.62 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 20 of 227
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.86
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 21 of 227
r = 115.47 mm
Kluy /r = 18.25
M1 = 61.07 kNm
M2 = -66.63 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.25 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.68
r = 115.47 mm
Klux /r = 14.72
M1 = -24.29 kNm
M2 = 30.68 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.72 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 22 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 225
[53] : 1.38 (LOAD 9: DL) +(LOAD 2:
Critical Load Combination = kN
EQ +X -E)
Nu = 210.53 kN
Muy = 62.99 kNm
Vuy = 42.9381 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 29.84 kNm
φVcy = 93.84 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 23 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C3
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 24 of 227
Load Data
Analysis Reference No. = 1115
Critical Analysis Load Combination : 110
[10] : 1.2 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 2: EQ +X -E)
Critical Location = Bottom Joint
Put = 222.36 kN
Muxt = -71.12 kNm
Muyt = 4.58 kNm
Vuxt = 0.64 kN
Vuyt = 51.67 kN
Pub = 236.19 kN
Muxb = 83.85 kNm
Muyb = 2.67 kNm
Vuxb = 0.64 kN
Vuyb = 51.67 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 25 of 227
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.77
r = 115.47 mm
Kluy /r = 17.34
M1 = -71.12 kNm
M2 = 83.85 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.34 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.73
r = 115.47 mm
Klux /r = 16.75
M1 = 2.67 kNm
M2 = 4.58 kNm
Min (40, 34 - 12 x (M1/M2)) = 27.01
16.75 < 27.01, Column not slender along B
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 26 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 27 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 110
[10] : 1.2 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 2: EQ +X -E)
Nu = 236.19 kN
Muy = 83.85 kNm
Vuy = 51.6692 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 46.66 kNm
φVcy = 91.05 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 28 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C3
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
Clear Floor Height @ luy = 2450 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 2113
Critical Analysis Load Combination : 217
[45] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 2: EQ +X -E)
Critical Location = Top Joint
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 29 of 227
Put = 127.49 kN
Muxt = -70.32 kNm
Muyt = 46.47 kNm
Vuxt = 33.33 kN
Vuyt = 48.13 kN
Pub = 145.56 kN
Muxb = 64.42 kNm
Muyb = -46.81 kNm
Vuxb = 33.33 kN
Vuyb = 48.13 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 30 of 227
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.75
r = 115.47 mm
Kluy /r = 15.91
M1 = 64.42 kNm
M2 = -70.32 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.91 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.68
r = 115.47 mm
Klux /r = 14.72
M1 = 46.47 kNm
M2 = -46.81 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14.72 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 31 of 227
Pu = 127.49 kN
Mux = -70.32 kNm
Muy = 46.47 kNm
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 217
Critical Load Combination = [45] : 1.68 (LOAD 9: DL) +0.5 (LOAD kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 32 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 33 of 227
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---
General Data
Column No. : C4
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1120
Critical Analysis Load Combination : 111
[11] : 1.2 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 3: EQ -X +E)
Critical Location = Bottom Joint
Put = 50 kN
Muxt = 52.72 kNm
Muyt = 19.97 kNm
Vuxt = 13.48 kN
Vuyt = -41.06 kN
Pub = 63.83 kN
Muxb = -70.41 kNm
Muyb = -20.47 kNm
Vuxb = 13.48 kN
Vuyb = -41.06 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 34 of 227
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 19.59
M1 = 52.72 kNm
M2 = -70.41 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.59 < 40, Column not slender along D
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 35 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 36 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 111
[11] : 1.2 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 3: EQ -X +E)
Nu = 63.83 kN
Muy = 70.41 kNm
Vuy = -41.0556 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 60.37 kNm
φVcy = 87.45 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 37 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C4
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 38 of 227
Load Data
Analysis Reference No. = 2117
Critical Analysis Load Combination : 222
[50] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 7: EQ -Z +E)
Critical Location = Top Joint
Put = 88.04 kN
Muxt = -22.03 kNm
Muyt = 67.23 kNm
Vuxt = 47.2 kN
Vuyt = 15.29 kN
Pub = 106.11 kN
Muxb = 20.77 kNm
Muyb = -64.9 kNm
Vuxb = 47.2 kN
Vuyb = 15.29 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 39 of 227
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 21.22
M1 = 20.77 kNm
M2 = -22.03 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.22 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.8
r = 115.47 mm
Klux /r = 17.32
M1 = -64.9 kNm
M2 = 67.23 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.32 < 40, Column not slender along B
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 40 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 41 of 227
= 71.86 deg
MRes = 70.75 kNm
( φ ) MCap = 129.49 kNm
Capacity Ratio = MRes/ MCap
= 0.546 < 1
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 217
[45] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 2: EQ +X -E)
Nu = 138.14 kN
Muy = 54.55 kNm
Vuy = 36.7546 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 32.8 kNm
φVcy = 91.16 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 42 of 227
General Data
Column No. : C5
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1103
Critical Analysis Load Combination : 110
[10] : 1.2 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 2: EQ +X -E)
Critical Location = Bottom Joint
Put = 247.3 kN
Muxt = -43.57 kNm
Muyt = 12.93 kNm
Vuxt = 10.65 kN
Vuyt = 34.79 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 43 of 227
Pub = 261.13 kN
Muxb = 60.76 kNm
Muyb = -19.01 kNm
Vuxb = 10.65 kN
Vuyb = 34.79 kN
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 44 of 227
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 19.59
M1 = -43.57 kNm
M2 = 60.76 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 19.59
M1 = 12.93 kNm
M2 = -19.01 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.59 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 45 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 110
[10] : 1.2 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 2: EQ +X -E)
Nu = 261.13 kN
Muy = 60.76 kNm
Vuy = 34.7874 kN
λ = 1
φ = 0.75
deff = 340.5 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 46 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 47 of 227
General Data
Column No. : C5
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
Clear Floor Height @ luy = 2450 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 2103
Critical Analysis Load Combination : 220
[48] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 5: EQ +Z +E)
Critical Location = Top Joint
Put = 282.62 kN
Muxt = 28.07 kNm
Muyt = -67.96 kNm
Vuxt = -39.44 kN
Vuyt = -14.11 kN
Pub = 300.69 kN
Muxb = -11.43 kNm
Muyb = 42.43 kNm
Vuxb = -39.44 kN
Vuyb = -14.11 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 48 of 227
350
Sway Condition (as per Stability
= Non Sway
Index)
Effective Length Factor along Major
= 1
Axis
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 21.22
M1 = -11.43 kNm
M2 = 28.07 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.89
21.22 < 38.89, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 21.22
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 49 of 227
M1 = 42.43 kNm
M2 = -67.96 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.22 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 50 of 227
φ Pn = 321.58 kN
Pt min for φ Pn = 0.5 %
Pt min (User Defined) = 1 %
Final Pt = 1 %
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 112
[12] : 1.2 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 4: EQ -X -E)
Nu = 222.29 kN
Muy = 48.61 kNm
Vuy = -31.3604 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 13.61 kNm
φVcy = 101.13 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 51 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C5
Level : 5.8m To 8.6m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
Clear Floor Height @ luy = 2500 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 52 of 227
Load Data
Analysis Reference No. = 3101
Critical Analysis Load Combination : 223
[51] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 8: EQ -Z -E)
Critical Location = Top Joint
Put = 23.44 kN
Muxt = 10.67 kNm
Muyt = 20.63 kNm
Vuxt = 10.03 kN
Vuyt = -7.62 kN
Pub = 33.6 kN
Muxb = -10.66 kNm
Muyb = -7.46 kNm
Vuxb = 10.03 kN
Vuyb = -7.62 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 53 of 227
Along B
Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 28.87
M1 = -10.66 kNm
M2 = 10.67 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
28.87 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 28.87
M1 = -7.46 kNm
M2 = 20.63 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.34
28.87 < 38.34, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 54 of 227
Design Of Shear
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 55 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 56 of 227
General Data
Column No. : C6
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1111
Critical Analysis Load Combination : 110
[10] : 1.2 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 2: EQ +X -E)
Critical Location = Bottom Joint
Put = 457.82 kN
Muxt = -52.32 kNm
Muyt = -0.3 kNm
Vuxt = 0.53 kN
Vuyt = 39.11 kN
Pub = 471.65 kN
Muxb = 64.97 kNm
Muyb = -1.9 kNm
Vuxb = 0.53 kN
Vuyb = 39.11 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 57 of 227
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 19.59
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 58 of 227
M1 = -52.32 kNm
M2 = 64.97 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 19.59
M1 = -0.3 kNm
M2 = -1.9 kNm
Min (40, 34 - 12 x (M1/M2)) = 32.11
19.59 < 32.11, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 59 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 111
[11] : 1.2 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 3: EQ -X +E)
Nu = 401.74 kN
Muy = 42.98 kNm
Vuy = -33.0722 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = -20.27 kNm
φVcy = 194.71 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 60 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C6
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 61 of 227
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
Clear Floor Height @ luy = 2450 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 2110
Critical Analysis Load Combination : 230
Load Combination = [58] : 1.38 (LOAD 9: DL) +(LOAD 7: EQ -Z +E)
Critical Location = Bottom Joint
Put = 229.59 kN
Muxt = -0.43 kNm
Muyt = 48.55 kNm
Vuxt = 37.31 kN
Vuyt = 0.6 kN
Pub = 244.43 kN
Muxb = 1.24 kNm
Muyb = -55.88 kNm
Vuxb = 37.31 kN
Vuyb = 0.6 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 62 of 227
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 21.22
M1 = -0.43 kNm
M2 = 1.24 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.15
21.22 < 38.15, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 21.22
M1 = 48.55 kNm
M2 = -55.88 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.22 < 40, Column not slender along B
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 63 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 64 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 112
[12] : 1.2 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 4: EQ -X -E)
Nu = 194.92 kN
Muy = 41.62 kNm
Vuy = -28.3782 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 10.94 kNm
φVcy = 103.58 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 65 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C6
Level : 5.8m To 8.6m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
Clear Floor Height @ luy = 2500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 3103
Critical Analysis Load Combination : 108
[8] : 1.2 (LOAD 9: DL) +0.5 (LOAD 10: LL) +(LOAD
Load Combination =
14: WL -Z)
Critical Location = Bottom Joint
Put = 26.04 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 66 of 227
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 67 of 227
Along B
Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 28.87
M1 = 3.05 kNm
M2 = -4.75 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
28.87 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 28.87
M1 = 24.48 kNm
M2 = -25.74 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
28.87 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 68 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 216
[44] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 1: EQ +X +E)
Nu = 26.82 kN
Muy = 16.49 kNm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 69 of 227
Vuy = 10.6009 kN
λ = 1
φ = 0.75
deff = 240.5 mm
ρw (50% of As provided) = 0.016
Mm = 13.28 kNm
φVcy = 46.1 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 70 of 227
General Data
Column No. : C7
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1116
Critical Analysis Load Combination : 110
[10] : 1.2 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 2: EQ +X -E)
Critical Location = Bottom Joint
Put = 316.5 kN
Muxt = -58.34 kNm
Muyt = -8.11 kNm
Vuxt = -5.63 kN
Vuyt = 42.08 kN
Pub = 330.33 kN
Muxb = 67.88 kNm
Muyb = 8.78 kNm
Vuxb = -5.63 kN
Vuyb = 42.08 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 71 of 227
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.77
r = 115.47 mm
Kluy /r = 17.34
M1 = -58.34 kNm
M2 = 67.88 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.34 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 72 of 227
K = 0.87
r = 115.47 mm
Klux /r = 19.59
M1 = -8.11 kNm
M2 = 8.78 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.59 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 73 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 110
[10] : 1.2 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 2: EQ +X -E)
Nu = 330.33 kN
Muy = 67.88 kNm
Vuy = 42.0844 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 15.87 kNm
φVcy = 104.06 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 74 of 227
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = -31.95 kNm
φVcx = 193.69 kN
Vux < φVcx
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C7
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
Clear Floor Height @ luy = 2450 mm
No Of Floors = 1
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 75 of 227
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 2114
Critical Analysis Load Combination : 216
[44] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 1: EQ +X +E)
Critical Location = Top Joint
Put = 193.56 kN
Muxt = -63.18 kNm
Muyt = 2.98 kNm
Vuxt = 5.89 kN
Vuyt = 43.84 kN
Pub = 211.63 kN
Muxb = 59.54 kNm
Muyb = -13.5 kNm
Vuxb = 5.89 kN
Vuyb = 43.84 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 76 of 227
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.77
r = 115.47 mm
Kluy /r = 16.34
M1 = 59.54 kNm
M2 = -63.18 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.34 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 21.22
M1 = 2.98 kNm
M2 = -13.5 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.65
21.22 < 36.65, Column not slender along B
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 77 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 78 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 216
[44] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 1: EQ +X +E)
Nu = 193.56 kN
Muy = 63.18 kNm
Vuy = 43.8411 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 32.71 kNm
φVcy = 93.01 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 79 of 227
General Data
Column No. : C7
Level : 5.8m To 8.6m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
Clear Floor Height @ luy = 2500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 3105
Critical Analysis Load Combination : 222
[50] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 7: EQ -Z +E)
Critical Location = Top Joint
Put = 17.05 kN
Muxt = -4.5 kNm
Muyt = 17.68 kNm
Vuxt = 10.11 kN
Vuyt = 4.03 kN
Pub = 27.21 kN
Muxb = 6.79 kNm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 80 of 227
Along B
Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 81 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 82 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 216
[44] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 1: EQ +X +E)
Nu = 28.07 kN
Muy = 14.34 kNm
Vuy = 9.373 kN
λ = 1
φ = 0.75
deff = 240.5 mm
ρw (50% of As provided) = 0.016
Mm = 10.97 kNm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 83 of 227
φVcy = 46.29 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
General Data
Column No. : C8
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 84 of 227
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1121
Critical Analysis Load Combination : 111
[11] : 1.2 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 3: EQ -X +E)
Critical Location = Bottom Joint
Put = 66.57 kN
Muxt = 37.4 kNm
Muyt = 14.44 kNm
Vuxt = 10.75 kN
Vuyt = -30.32 kN
Pub = 80.4 kN
Muxb = -53.53 kNm
Muyb = -17.8 kNm
Vuxb = 10.75 kN
Vuyb = -30.32 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 85 of 227
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 19.59
M1 = 37.4 kNm
M2 = -53.53 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 19.59
M1 = 14.44 kNm
M2 = -17.8 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 86 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 87 of 227
Final Pt = 1 %
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 111
[11] : 1.2 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 3: EQ -X +E)
Nu = 80.4 kN
Muy = 53.53 kNm
Vuy = -30.3158 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 40.87 kNm
φVcy = 87.97 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 88 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C8
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
Clear Floor Height @ luy = 2450 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 2118
Critical Analysis Load Combination : 221
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 89 of 227
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 90 of 227
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 21.22
M1 = 12.97 kNm
M2 = -15.04 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.22 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 21.22
M1 = 45.49 kNm
M2 = -62.43 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.22 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 91 of 227
Design Of Shear
Design for shear along D
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 92 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 93 of 227
General Data
Column No. : C9
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1104
Critical Analysis Load Combination : 220
[48] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 5: EQ +Z +E)
Critical Location = Top Joint
Put = 338.94 kN
Muxt = 56.76 kNm
Muyt = -72.11 kNm
Vuxt = -50.83 kN
Vuyt = -25.33 kN
Pub = 358.3 kN
Muxb = -19.2 kNm
Muyb = 80.34 kNm
Vuxb = -50.83 kN
Vuyb = -25.33 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 94 of 227
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 19.59
M1 = -19.2 kNm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 95 of 227
M2 = 56.76 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.06
19.59 < 38.06, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 19.59
M1 = -72.11 kNm
M2 = 80.34 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.59 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 96 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 219
[47] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 4: EQ -X -E)
Nu = 411.03 kN
Muy = 86.34 kNm
Vuy = -52.7736 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 21.63 kNm
φVcy = 102.27 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 97 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C9
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 98 of 227
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
Clear Floor Height @ luy = 2450 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 2104
Critical Analysis Load Combination : 223
[51] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 8: EQ -Z -E)
Critical Location = Bottom Joint
Put = 132.26 kN
Muxt = 72.65 kNm
Muyt = 18.8 kNm
Vuxt = 29.77 kN
Vuyt = -60.41 kN
Pub = 150.33 kN
Muxb = -96.46 kNm
Muyb = -64.54 kNm
Vuxb = 29.77 kN
Vuyb = -60.41 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 99 of 227
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 21.22
M1 = 72.65 kNm
M2 = -96.46 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.22 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 21.22
M1 = 18.8 kNm
M2 = -64.54 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.5
21.22 < 37.5, Column not slender along B
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 100 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 101 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 219
[47] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 4: EQ -X -E)
Nu = 173.13 kN
Muy = 114.76 kNm
Vuy = -71.8094 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 87.5 kNm
φVcy = 88.63 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 102 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C9
Level : 5.8m To 8.6m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
Clear Floor Height @ luy = 2500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 3102
Critical Analysis Load Combination : 219
[47] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 4: EQ -X -E)
Critical Location = Top Joint
Put = 18.8 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 103 of 227
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 104 of 227
Along B
Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 28.87
M1 = -13.73 kNm
M2 = 16.46 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
28.87 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 28.87
M1 = -4.18 kNm
M2 = 8.04 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
28.87 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 105 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 218
[46] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 3: EQ -X +E)
Nu = 18.84 kN
Muy = 16.13 kNm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 106 of 227
Vuy = -11.0293 kN
λ = 1
φ = 0.75
deff = 240.5 mm
ρw (50% of As provided) = 0.016
Mm = 13.87 kNm
φVcy = 46.08 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 107 of 227
General Data
Column No. : C10
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1112
Critical Analysis Load Combination : 220
[48] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 5: EQ +Z +E)
Critical Location = Top Joint
Put = 456.92 kN
Muxt = -30.35 kNm
Muyt = -64.75 kNm
Vuxt = -44.79 kN
Vuyt = 17.71 kN
Pub = 476.28 kN
Muxb = 22.78 kNm
Muyb = 69.59 kNm
Vuxb = -44.79 kN
Vuyb = 17.71 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 108 of 227
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 19.59
M1 = 22.78 kNm
M2 = -30.35 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 109 of 227
K = 0.87
r = 115.47 mm
Klux /r = 19.59
M1 = -64.75 kNm
M2 = 69.59 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.59 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 110 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 109
[9] : 1.2 (LOAD 9: DL) +0.5 (LOAD 10:
Critical Load Combination = kN
LL) +(LOAD 1: EQ +X +E)
Nu = 362.88 kN
Muy = 61.79 kNm
Vuy = 39.1348 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 4.66 kNm
φVcy = 152.47 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 111 of 227
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 15.74 kNm
φVcx = 104.76 kN
Vux < φVcx
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C10
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
Clear Floor Height @ luy = 2450 mm
No Of Floors = 1
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 112 of 227
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 2111
Critical Analysis Load Combination : 220
[48] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 5: EQ +Z +E)
Critical Location = Bottom Joint
Put = 231.32 kN
Muxt = -32.61 kNm
Muyt = -70.48 kNm
Vuxt = -50.56 kN
Vuyt = 24.58 kN
Pub = 249.39 kN
Muxb = 36.2 kNm
Muyb = 71.04 kNm
Vuxb = -50.56 kN
Vuyb = 24.58 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 113 of 227
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 21.22
M1 = -32.61 kNm
M2 = 36.2 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.22 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 21.22
M1 = -70.48 kNm
M2 = 71.04 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.22 < 40, Column not slender along B
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 114 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 115 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 216
[44] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 1: EQ +X +E)
Nu = 224.05 kN
Muy = 64.15 kNm
Vuy = 43.6137 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 28.88 kNm
φVcy = 94.44 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 116 of 227
General Data
Column No. : C10
Level : 5.8m To 8.6m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
Clear Floor Height @ luy = 2500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 3104
Critical Analysis Load Combination : 217
[45] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 2: EQ +X -E)
Critical Location = Bottom Joint
Put = 24.75 kN
Muxt = -16.47 kNm
Muyt = -8.62 kNm
Vuxt = -7.24 kN
Vuyt = 11.41 kN
Pub = 34.91 kN
Muxb = 15.46 kNm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 117 of 227
Along B
Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 118 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 119 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 216
[44] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 1: EQ +X +E)
Nu = 24.6 kN
Muy = 17.32 kNm
Vuy = 11.6646 kN
λ = 1
φ = 0.75
deff = 240.5 mm
ρw (50% of As provided) = 0.016
Mm = 14.37 kNm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 120 of 227
φVcy = 46.14 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
General Data
Column No. : C11
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 121 of 227
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1117
Critical Analysis Load Combination : 114
[14] : 1.2 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 6: EQ +Z -E)
Critical Location = Bottom Joint
Put = 202.36 kN
Muxt = -11.57 kNm
Muyt = -62.14 kNm
Vuxt = -43.09 kN
Vuyt = 7.03 kN
Pub = 216.19 kN
Muxb = 9.52 kNm
Muyb = 67.09 kNm
Vuxb = -43.09 kN
Vuyb = 7.03 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 122 of 227
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.77
r = 115.47 mm
Kluy /r = 17.34
M1 = 9.52 kNm
M2 = -11.57 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
17.34 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 19.59
M1 = -62.14 kNm
M2 = 67.09 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 123 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 124 of 227
Final Pt = 1 %
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 109
[9] : 1.2 (LOAD 9: DL) +0.5 (LOAD 10:
Critical Load Combination = kN
LL) +(LOAD 1: EQ +X +E)
Nu = 235.77 kN
Muy = 60.12 kNm
Vuy = 37.4185 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 23 kNm
φVcy = 95.43 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 125 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C11
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
Clear Floor Height @ luy = 2450 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 2115
Critical Analysis Load Combination : 221
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 126 of 227
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 127 of 227
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.86
r = 115.47 mm
Kluy /r = 18.25
M1 = 13.14 kNm
M2 = -17.52 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.25 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 21.22
M1 = -68.7 kNm
M2 = 78.38 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.22 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 128 of 227
Design Of Shear
Design for shear along D
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 129 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 130 of 227
General Data
Column No. : C11
Level : 5.8m To 8.6m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
Clear Floor Height @ luy = 2500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 3106
Critical Analysis Load Combination : 221
[49] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 6: EQ +Z -E)
Critical Location = Top Joint
Put = 15.35 kN
Muxt = -3.98 kNm
Muyt = -13.38 kNm
Vuxt = -8.23 kN
Vuyt = 3.5 kN
Pub = 25.51 kN
Muxb = 5.81 kNm
Muyb = 9.65 kNm
Vuxb = -8.23 kN
Vuyb = 3.5 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 131 of 227
Along B
Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 28.87
M1 = -3.98 kNm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 132 of 227
M2 = 5.81 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
28.87 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 28.87
M1 = 9.65 kNm
M2 = -13.38 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
28.87 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 133 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 216
[44] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 1: EQ +X +E)
Nu = 15.89 kN
Muy = 11.19 kNm
Vuy = 7.7589 kN
λ = 1
φ = 0.75
deff = 240.5 mm
ρw (50% of As provided) = 0.016
Mm = 9.28 kNm
φVcy = 46.23 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 134 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
General Data
Column No. : C12
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 300 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 135 of 227
Column D = 300 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1101
Critical Analysis Load Combination : 218
[46] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 3: EQ -X +E)
Critical Location = Top Joint
Put = 93.91 kN
Muxt = 35.33 kNm
Muyt = 1.08 kNm
Vuxt = -0.4 kN
Vuyt = -22.81 kN
Pub = 104.8 kN
Muxb = -33.08 kNm
Muyb = 2.29 kNm
Vuxb = -0.4 kN
Vuyb = -22.81 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 136 of 227
(Length x (Length x
Width x Depth) Width x Depth)
N-M mm mm N-M N-M
Bottom 22.5 No Beam No Beam - - 1
2786 x 300 x
Top 22.5 No Beam 57.43 - 1.139
400
Sway Condition (as per Stability
= Non Sway
Index)
Effective Length Factor along Minor
= 0.87
axis
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.71
r = 86.6 mm
Kluy /r = 21.73
M1 = -33.08 kNm
M2 = 35.33 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.73 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 86.6 mm
Klux /r = 26.12
M1 = 1.08 kNm
M2 = 2.29 kNm
Min (40, 34 - 12 x (M1/M2)) = 28.31
26.12 < 28.31, Column not slender along B
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 137 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 138 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 218
[46] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 3: EQ -X +E)
Nu = 93.91 kN
Muy = 35.33 kNm
Vuy = -22.8108 kN
λ = 1
φ = 0.75
deff = 240.5 mm
ρw (50% of As provided) = 0.016
Mm = 24.07 kNm
φVcy = 46.62 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 139 of 227
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
General Data
Column No. : C13
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 3000 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1109
Critical Analysis Load Combination : 110
[10] : 1.2 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 2: EQ +X -E)
Critical Location = Bottom Joint
Put = 76.98 kN
Muxt = -24.31 kNm
Muyt = -0.33 kNm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 140 of 227
Vuxt = 0.05 kN
Vuyt = 17.87 kN
Pub = 84.76 kN
Muxb = 29.29 kNm
Muyb = -0.49 kNm
Vuxb = 0.05 kN
Vuyb = 17.87 kN
Along B
Q = 0.009
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 141 of 227
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.74
r = 86.6 mm
Kluy /r = 22.64
M1 = -24.31 kNm
M2 = 29.29 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.64 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.78
r = 86.6 mm
Klux /r = 27.02
M1 = -0.33 kNm
M2 = -0.49 kNm
Min (40, 34 - 12 x (M1/M2)) = 25.97
27.02 > 25.97, Column slender along B
Moment Magnification:
For Non-sway frame:
Along B
βdns = 0.6
Ec = 23500 N/sqmm
9 = 0.675 mm^4
Ig ( x 10 )
EI ( x 10 6) = 4579107.188 N-sqmm
M2min = 2.03 kNm
Cm = 1
Pc = 8253.7 kN
δns = 1.01
Mc1 = -2.06 kNm
1.4 MuyB = -0.68 kNm
Mc1 = Min (-2.06, -0.68) kNm
= -0.68 kNm
Mc2 = -2.06 kNm
1.4 MuyT = -0.46 kNm
Mc2 = Min (-2.06, -0.46) kNm
= -0.46 kNm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 142 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 143 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 110
[10] : 1.2 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 2: EQ +X -E)
Nu = 84.76 kN
Muy = 29.29 kNm
Vuy = 17.8709 kN
λ = 1
φ = 0.75
deff = 240.5 mm
ρw (50% of As provided) = 0.016
Mm = 19.13 kNm
φVcy = 46.57 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 144 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
General Data
Column No. : C14
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1119
Critical Analysis Load Combination : 217
[45] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 2: EQ +X -E)
Critical Location = Top Joint
Put = 67.21 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 145 of 227
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 146 of 227
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.72
r = 86.6 mm
Kluy /r = 22.03
M1 = 35.44 kNm
M2 = -36.66 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
22.03 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 86.6 mm
Klux /r = 26.62
M1 = -0.78 kNm
M2 = 2.85 kNm
Min (40, 34 - 12 x (M1/M2)) = 37.26
26.62 < 37.26, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 147 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 217
[45] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 2: EQ +X -E)
Nu = 67.21 kN
Muy = 36.66 kNm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 148 of 227
Vuy = 24.0401 kN
λ = 1
φ = 0.75
deff = 240.5 mm
ρw (50% of As provided) = 0.016
Mm = 28.6 kNm
φVcy = 46.24 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 149 of 227
General Data
Column No. : C15
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1107
Critical Analysis Load Combination : 218
[46] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 3: EQ -X +E)
Critical Location = Top Joint
Put = 671.99 kN
Muxt = 109.59 kNm
Muyt = -6.13 kNm
Vuxt = -4.59 kN
Vuyt = -68.86 kN
Pub = 691.35 kN
Muxb = -96.94 kNm
Muyb = 7.63 kNm
Vuxb = -4.59 kN
Vuyb = -68.86 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 150 of 227
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.73
r = 115.47 mm
Kluy /r = 16.44
M1 = -96.94 kNm
M2 = 109.59 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.44 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 151 of 227
K = 0.69
r = 115.47 mm
Klux /r = 15.84
M1 = -6.13 kNm
M2 = 7.63 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
15.84 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 152 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 111
[11] : 1.2 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 3: EQ -X +E)
Nu = 486.84 kN
Muy = 98.99 kNm
Vuy = -63.9214 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 22.35 kNm
φVcy = 105.82 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 153 of 227
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = -47.83 kNm
φVcx = 200.38 kN
Vux < φVcx
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C16
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 154 of 227
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1108
Critical Analysis Load Combination : 219
[47] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 4: EQ -X -E)
Critical Location = Top Joint
Put = 562.24 kN
Muxt = 85.51 kNm
Muyt = 12.6 kNm
Vuxt = 6.08 kN
Vuyt = -53.48 kN
Pub = 581.6 kN
Muxb = -74.89 kNm
Muyb = -5.63 kNm
Vuxb = 6.08 kN
Vuyb = -53.48 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 155 of 227
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.73
r = 115.47 mm
Kluy /r = 16.44
M1 = -74.89 kNm
M2 = 85.51 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.44 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 19.59
M1 = -5.63 kNm
M2 = 12.6 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.36
19.59 < 39.36, Column not slender along B
Where
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 156 of 227
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 157 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 111
[11] : 1.2 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 3: EQ -X +E)
Nu = 408.45 kN
Muy = 79.07 kNm
Vuy = -50.9081 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 14.77 kNm
φVcy = 110.76 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 158 of 227
General Data
Column No. : C17
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1122
Critical Analysis Load Combination : 114
[14] : 1.2 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 6: EQ +Z -E)
Critical Location = Bottom Joint
Put = 35.18 kN
Muxt = -10.19 kNm
Muyt = -62.29 kNm
Vuxt = -42.89 kN
Vuyt = 6.35 kN
Pub = 49.01 kN
Muxb = 8.86 kNm
Muyb = 66.35 kNm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 159 of 227
Vuxb = -42.89 kN
Vuyb = 6.35 kN
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 160 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 161 of 227
Pu = 168.24 kN
Mux = 63.13 kNm
Muy = 9.01 kNm
Pt Calculated = 1.21
φ Pn, Max = 2170.33 kN
Pu < φ Pn, Max Hence, OK
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 216
[44] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 1: EQ +X +E)
Nu = 168.24 kN
Muy = 63.13 kNm
Vuy = 40.0092 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 36.64 kNm
φVcy = 90.92 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 162 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C18
Level : 0m To 3m
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 163 of 227
Load Data
Analysis Reference No. = 1105
Critical Analysis Load Combination : 223
[51] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 8: EQ -Z -E)
Critical Location = Top Joint
Put = 80.83 kN
Muxt = 57.05 kNm
Muyt = 75.28 kNm
Vuxt = 53.94 kN
Vuyt = -29.94 kN
Pub = 100.19 kN
Muxb = -32.74 kNm
Muyb = -86.51 kNm
Vuxb = 53.94 kN
Vuyb = -29.94 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 164 of 227
Axis = 0.87
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 19.59
M1 = -32.74 kNm
M2 = 57.05 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.59 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.73
r = 115.47 mm
Klux /r = 16.75
M1 = 75.28 kNm
M2 = -86.51 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.75 < 40, Column not slender along B
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 165 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 166 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 219
[47] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 4: EQ -X -E)
Nu = 163.07 kN
Muy = 84.42 kNm
Vuy = -51.4137 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 58.74 kNm
φVcy = 89.09 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 167 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C19
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1113
Critical Analysis Load Combination : 116
[16] : 1.2 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 168 of 227
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 169 of 227
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.77
r = 115.47 mm
Kluy /r = 17.34
M1 = 0.22 kNm
M2 = -6.04 kNm
Min (40, 34 - 12 x (M1/M2)) = 34.44
17.34 < 34.44, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.73
r = 115.47 mm
Klux /r = 16.75
M1 = 63.06 kNm
M2 = -72.25 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.75 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 170 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 224
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 171 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 172 of 227
General Data
Column No. : C20
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1118
Critical Analysis Load Combination : 230
Load Combination = [58] : 1.38 (LOAD 9: DL) +(LOAD 7: EQ -Z +E)
Critical Location = Bottom Joint
Put = -9.21 kN
Muxt = -4.07 kNm
Muyt = 51.84 kNm
Vuxt = 38.99 kN
Vuyt = 1.73 kN
Pub = 6.69 kN
Muxb = 1.12 kNm
Muyb = -65.1 kNm
Vuxb = 38.99 kN
Vuyb = 1.73 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 173 of 227
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.72
r = 115.47 mm
Kluy /r = 16.21
M1 = 0 kNm
M2 = 0 kNm
Min (40, 34 - 12 x (M1/M2)) = 0
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 174 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 175 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 216
[44] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 1: EQ +X +E)
Nu = 64.13 kN
Muy = 63.26 kNm
Vuy = 41.105 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 53.16 kNm
φVcy = 88.23 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 176 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C21
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 177 of 227
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1123
Critical Analysis Load Combination : 230
Load Combination = [58] : 1.38 (LOAD 9: DL) +(LOAD 7: EQ -Z +E)
Critical Location = Bottom Joint
Put = 4.9 kN
Muxt = -0.72 kNm
Muyt = 61.87 kNm
Vuxt = 43.63 kN
Vuyt = 0.07 kN
Pub = 20.8 kN
Muxb = -0.5 kNm
Muyb = -68.99 kNm
Vuxb = 43.63 kN
Vuyb = 0.07 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 178 of 227
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.74
r = 115.47 mm
Kluy /r = 16.66
M1 = -0.5 kNm
M2 = -0.72 kNm
Min (40, 34 - 12 x (M1/M2)) = 25.67
16.66 < 25.67, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.73
r = 115.47 mm
Klux /r = 16.75
M1 = 61.87 kNm
M2 = -68.99 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
16.75 < 40, Column not slender along B
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 179 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 180 of 227
= 89.59 deg
MRes = 68.99 kNm
( φ ) MCap = 119.34 kNm
Capacity Ratio = MRes/ MCap
= 0.578 < 1
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 216
[44] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 1: EQ +X +E)
Nu = 129.99 kN
Muy = 59.2 kNm
Vuy = 36.9421 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 38.73 kNm
φVcy = 89.75 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 181 of 227
General Data
Column No. : C22
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 3000 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1106
Critical Analysis Load Combination : 113
[13] : 1.2 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 5: EQ +Z +E)
Critical Location = Bottom Joint
Put = 31.68 kN
Muxt = 0.74 kNm
Muyt = -26.31 kNm
Vuxt = -17.98 kN
Vuyt = 1.2 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 182 of 227
Pub = 39.46 kN
Muxb = 4.34 kNm
Muyb = 27.62 kNm
Vuxb = -17.98 kN
Vuyb = 1.2 kN
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 183 of 227
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.78
r = 86.6 mm
Kluy /r = 27.02
M1 = 0.74 kNm
M2 = 4.34 kNm
Min (40, 34 - 12 x (M1/M2)) = 31.96
27.02 < 31.96, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.76
r = 86.6 mm
Klux /r = 23.26
M1 = -26.31 kNm
M2 = 27.62 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
23.26 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 184 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 112
[12] : 1.2 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 4: EQ -X -E)
Nu = 31.18 kN
Muy = 10.39 kNm
Vuy = -4.6699 kN
λ = 1
φ = 0.75
deff = 240.5 mm
ρw (50% of As provided) = 0.016
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 185 of 227
Mm = 6.65 kNm
φVcy = 45.76 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 186 of 227
General Data
Column No. : C23
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1114
Critical Analysis Load Combination : 221
[49] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 6: EQ +Z -E)
Critical Location = Top Joint
Put = 84.67 kN
Muxt = 16.54 kNm
Muyt = -23.73 kNm
Vuxt = -15.83 kN
Vuyt = -7.47 kN
Pub = 95.56 kN
Muxb = -5.85 kNm
Muyb = 23.75 kNm
Vuxb = -15.83 kN
Vuyb = -7.47 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 187 of 227
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 86.6 mm
Kluy /r = 26.62
M1 = -5.85 kNm
M2 = 16.54 kNm
Min (40, 34 - 12 x (M1/M2)) = 38.24
26.62 < 38.24, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.76
r = 86.6 mm
Klux /r = 23.26
M1 = -23.73 kNm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 188 of 227
M2 = 23.75 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
23.26 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 189 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 219
[47] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 4: EQ -X -E)
Nu = 81.33 kN
Muy = 29.12 kNm
Vuy = -17.2714 kN
λ = 1
φ = 0.75
deff = 240.5 mm
ρw (50% of As provided) = 0.016
Mm = 19.36 kNm
φVcy = 46.43 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 190 of 227
Mm = 15.17 kNm
φVcx = 46.87 kN
Vux < φVcx
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
General Data
Column No. : C24
Level : 0m To 3m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2650 mm
Clear Floor Height @ luy = 2650 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 191 of 227
Load Data
Analysis Reference No. = 1124
Critical Analysis Load Combination : 220
[48] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 5: EQ +Z +E)
Critical Location = Top Joint
Put = 94.75 kN
Muxt = -24.41 kNm
Muyt = -21.92 kNm
Vuxt = -14.22 kN
Vuyt = 13.76 kN
Pub = 105.64 kN
Muxb = 16.86 kNm
Muyb = 20.73 kNm
Vuxb = -14.22 kN
Vuyb = 13.76 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 192 of 227
Along B
Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 86.6 mm
Kluy /r = 26.62
M1 = 16.86 kNm
M2 = -24.41 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
26.62 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.76
r = 86.6 mm
Klux /r = 23.26
M1 = 20.73 kNm
M2 = -21.92 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
23.26 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 193 of 227
Design Of Shear
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 194 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 195 of 227
General Data
Column No. : C25
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
Clear Floor Height @ luy = 2450 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 2101
Critical Analysis Load Combination : 220
[48] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 5: EQ +Z +E)
Critical Location = Top Joint
Put = 162.59 kN
Muxt = 42.3 kNm
Muyt = -63.6 kNm
Vuxt = -42.75 kN
Vuyt = -22.77 kN
Pub = 180.66 kN
Muxb = -21.44 kNm
Muyb = 56.07 kNm
Vuxb = -42.75 kN
Vuyb = -22.77 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 196 of 227
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 18.46
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 197 of 227
M1 = -21.44 kNm
M2 = 42.3 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
18.46 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.66
r = 115.47 mm
Klux /r = 14
M1 = 56.07 kNm
M2 = -63.6 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
14 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 198 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 218
[46] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 3: EQ -X +E)
Nu = 242.75 kN
Muy = 62.56 kNm
Vuy = -35.4543 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 24.35 kNm
φVcy = 93.99 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 199 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C26
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 200 of 227
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
Clear Floor Height @ luy = 2500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 2105
Critical Analysis Load Combination : 217
[45] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 2: EQ +X -E)
Critical Location = Top Joint
Put = 139.19 kN
Muxt = -58.16 kNm
Muyt = -28.27 kNm
Vuxt = -9.59 kN
Vuyt = 29.94 kN
Pub = 157.26 kN
Muxb = 25.64 kNm
Muyb = -1.42 kNm
Vuxb = -9.59 kN
Vuyb = 29.94 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 201 of 227
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 18.84
M1 = 25.64 kNm
M2 = -58.16 kNm
Min (40, 34 - 12 x (M1/M2)) = 39.29
18.84 < 39.29, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.66
r = 115.47 mm
Klux /r = 14
M1 = -1.42 kNm
M2 = -28.27 kNm
Min (40, 34 - 12 x (M1/M2)) = 33.4
14 < 33.4, Column not slender along B
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 202 of 227
A B C
Major Axis Mux (top) -58.16 - -58.16
Major Axis Mux (bottom) 25.64 - 25.64
Minor Axis Muy (top) -28.27 - -28.27
Minor Axis Muy (bottom) -1.42 - -1.42
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 203 of 227
Pt Calculated = 1.21
Reinforcement Provided = 4-#19 + 4-#16
Load Angle = Tan-1(Muy/Mux)
= 25.92 deg
MRes = 64.66 kNm
( φ ) MCap = 135.08 kNm
Capacity Ratio = MRes/ MCap
= 0.479 < 1
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 225
[53] : 1.38 (LOAD 9: DL) +(LOAD 2:
Critical Load Combination = kN
EQ +X -E)
Nu = 112.66 kN
Muy = 55.14 kNm
Vuy = 29.9941 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 37.4 kNm
φVcy = 88.48 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 204 of 227
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C27
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
Clear Floor Height @ luy = 2500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 2108
Critical Analysis Load Combination : 217
[45] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 2: EQ +X -E)
Critical Location = Top Joint
Put = 0.4 kN
Muxt = -25.3 kNm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 205 of 227
Along B
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 206 of 227
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.75
r = 86.6 mm
Kluy /r = 21.65
M1 = -25.3 kNm
M2 = 25.42 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.65 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.67
r = 86.6 mm
Klux /r = 19.34
M1 = 5.25 kNm
M2 = -5.25 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.34 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 207 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 217
[45] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 2: EQ +X -E)
Nu = 0.4 kN
Muy = 25.3 kNm
Vuy = 18.1203 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 208 of 227
λ = 1
φ = 0.75
deff = 240.5 mm
ρw (50% of As provided) = 0.016
Mm = 25.25 kNm
φVcy = 45.81 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 209 of 227
General Data
Column No. : C28
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
Clear Floor Height @ luy = 2500 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 2112
Critical Analysis Load Combination : 217
[45] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 2: EQ +X -E)
Critical Location = Top Joint
Put = 15.77 kN
Muxt = -25.98 kNm
Muyt = 11.2 kNm
Vuxt = 8.21 kN
Vuyt = 18.06 kN
Pub = 25.94 kN
Muxb = 24.57 kNm
Muyb = -11.79 kNm
Vuxb = 8.21 kN
Vuyb = 18.06 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 210 of 227
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.74
r = 86.6 mm
Kluy /r = 21.36
M1 = 24.57 kNm
M2 = -25.98 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.36 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.67
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 211 of 227
r = 86.6 mm
Klux /r = 19.34
M1 = 11.2 kNm
M2 = -11.79 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.34 < 40, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 212 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 217
[45] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 2: EQ +X -E)
Nu = 15.77 kN
Muy = 25.98 kNm
Vuy = 18.0612 kN
λ = 1
φ = 0.75
deff = 240.5 mm
ρw (50% of As provided) = 0.016
Mm = 24.09 kNm
φVcy = 45.92 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 213 of 227
φ = 0.75
deff = 240.5 mm
ρw (50% of As provided) = 0.016
Mm = 15.65 kNm
φVcx = 46.2 kN
Vux < φVcx
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 300 mm
General Data
Column No. : C29
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2500 mm
Clear Floor Height @ luy = 2500 mm
No Of Floors = 1
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 214 of 227
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 2116
Critical Analysis Load Combination : 222
[50] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 7: EQ -Z +E)
Critical Location = Bottom Joint
Put = 29.38 kN
Muxt = -9.25 kNm
Muyt = 19.85 kNm
Vuxt = 14.64 kN
Vuyt = 6.43 kN
Pub = 39.54 kN
Muxb = 8.75 kNm
Muyb = -21.13 kNm
Vuxb = 14.64 kN
Vuyb = 6.43 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 215 of 227
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.76
r = 86.6 mm
Kluy /r = 21.94
M1 = 8.75 kNm
M2 = -9.25 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
21.94 < 40, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.67
r = 86.6 mm
Klux /r = 19.34
M1 = 19.85 kNm
M2 = -21.13 kNm
Min (40, 34 - 12 x (M1/M2)) = 40
19.34 < 40, Column not slender along B
Where
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 216 of 227
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 217 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 217
[45] : 1.68 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 2: EQ +X -E)
Nu = 6.26 kN
Muy = 19.44 kNm
Vuy = 13.1061 kN
λ = 1
φ = 0.75
deff = 240.5 mm
ρw (50% of As provided) = 0.016
Mm = 18.69 kNm
φVcy = 45.75 kN
Vuy < φVcy
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 218 of 227
General Data
Column No. : C30
Level : 3m To 5.8m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy420 N/sqmm
Consider Ductile = No
Column B = 400 mm
Column D = 400 mm
Clear Cover, Cc = 50 mm
Clear Floor Height @ lux = 2450 mm
Clear Floor Height @ luy = 2450 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 2106
Critical Analysis Load Combination : 225
Load Combination = [53] : 1.38 (LOAD 9: DL) +(LOAD 2: EQ +X -E)
Critical Location = Top Joint
Put = 196.76 kN
Muxt = -59.31 kNm
Muyt = -4.66 kNm
Vuxt = 0.53 kN
Vuyt = 34.04 kN
Pub = 211.61 kN
Muxb = 35.97 kNm
Muyb = -6.16 kNm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 219 of 227
Vuxb = 0.53 kN
Vuyb = 34.04 kN
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 220 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 221 of 227
Pu = 284.94 kN
Mux = -62.49 kNm
Muy = -9.63 kNm
Pt Calculated = 1.21
φ Pn, Max = 2170.33 kN
Pu < φ Pn, Max Hence, OK
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 110
[10] : 1.2 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 2: EQ +X -E)
Nu = 175.99 kN
Muy = 57.48 kNm
Vuy = 33.6451 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 29.77 kNm
φVcy = 91.24 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 222 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
General Data
Column No. : C31
Level : 3m To 5.8m
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 223 of 227
Load Data
Analysis Reference No. = 2107
Critical Analysis Load Combination : 220
[48] : 1.68 (LOAD 9: DL) +0.5 (LOAD 10: LL) +
Load Combination =
(LOAD 5: EQ +Z +E)
Critical Location = Top Joint
Put = 199.09 kN
Muxt = -10.69 kNm
Muyt = -104.74 kNm
Vuxt = -46.71 kN
Vuyt = -2.21 kN
Pub = 217.17 kN
Muxb = -16.87 kNm
Muyb = 26.01 kNm
Vuxb = -46.71 kN
Vuyb = -2.21 kN
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 224 of 227
Axis = 0.76
Along B
Q = 0.007
0.007< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.76
r = 115.47 mm
Kluy /r = 16.13
M1 = -10.69 kNm
M2 = -16.87 kNm
Min (40, 34 - 12 x (M1/M2)) = 26.39
16.13 < 26.39, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 18.46
M1 = 26.01 kNm
M2 = -104.74 kNm
Min (40, 34 - 12 x (M1/M2)) = 36.98
18.46 < 36.98, Column not slender along B
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 225 of 227
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 226 of 227
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 112
[12] : 1.2 (LOAD 9: DL) +0.5 (LOAD
Critical Load Combination = kN
10: LL) +(LOAD 4: EQ -X -E)
Nu = 162.99 kN
Muy = 65.38 kNm
Vuy = -39.0206 kN
λ = 1
φ = 0.75
deff = 340.5 mm
ρw (50% of As provided) = 0.014
Mm = 39.72 kNm
φVcy = 90 kN
Vuy < φVcy
Link For Shear Design Along D are not required
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024
Column Design: Design Calculations Page 227 of 227
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm
file:///C:/Users/Acer/AppData/Local/Temp/tmp4214.tmp 02/03/2024