Column Design: Design Calculations Page 1 of 198

COLUMN DESIGN CALCULATIONS


Project Name : IFSU
Client Name : IFSU
Engineer Name : ANMJR
Design File : C:\Users\63917\Documents\ANMJR\PROJECTS\ANMJR-2023-
IFSU\RCDC\cOLUMNS.rcdx
Analysis File : C:\Users\63917\Documents\ANMJR\PROJECTS\ANMJR-2023-
IFSU\STAAD ANALYSIS\IFSU.std
Analysis Last Modified : 19/01/2023 10:42:40 pm

Definitions Of Terms:
All forces in units kN and m
All reinforcement details like area, spacing in mm
Neutral axis angle for resultant design moment is with respect to local major axis.
Ratio to account for reduction of stiffness of columns
1 βdns =
due to sustained axial loads
Moment magnification factor for frames not braced
2 δns =
against sidesway
First-order relative deflection between the top and
3 Δo =
bottom of the story due to Vu in mm
4 ∑Pu = Total factored vertical load in kN. (Clause 10.10.5.2)
5 δu = Design displacement in mm
Modification factor reflecting the reduced mechanical
6 λ =
properties of concrete
Coefficient defining the relative contribution of
7 ac =
concrete strength to nominal wall shear strength
Cross-sectional area of a structural member measured
8 Ach = to the outside edges of transverse reinforcement in
sqmm
Gross area of concrete section bounded by web
9 Acv = thickness and length of section in the direction of
shear force considered in sqmm
Effective cross-sectional area within a joint in a plane
10 Aj = parallel to plane of reinforcement generating shear in
the joint in sqmm
Area of non-prestressed longitudinal tension
11 As =
reinforcement in sqmm
Minimum area of shear reinforcement within spacing
12 Avmin =
's' in sqmm
13 B = Width of column/ wall in mm
Cross-sectional dimension of member core measured
14 bc = to the outside edges of the transverse reinforcement
composing area Ash in mm
Distance from extreme compression fiber to neutral
15 c =
axis in mm
16 Cc = Clear cover to longitudinal reinforcement in mm
Factor relating actual moment diagram to an

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 2 of 198

17 Cm = equivalent uniform moment diagram


18 D = Depth / diameter of column in mm
Distance from extreme compression fiber to centroid
19 d =
of longitudinal tension reinforcement in mm
Distance from extreme compression fiber to centroid
20 d' =
of longitudinal compression reinforcement,mm
21 Ec = Modulus of elasticity of concrete in N/sqmm
22 EI = Flexural stiffness of compression member in N-sqmm
Specified compressive strength of concrete cylinder in
23 f'c =
N/sqmm
24 fy = Specified yield strength of reinforcement in N/sqmm
Specified yield strength fy of transverse
25 fyt =
reinforcement in N/sqmm
Height of entire wall from base to top of wall segment
26 hw =
considered in mm
27 k = Effective length factor for compression member
Length of compression member in a frame, measured
28 lc =
center-to-center of the joints in the frame in mm
Moment of inertia of gross concrete section about
29 lg =
centroidal axis neglecting reinforcement in mm4
30 lw = Length of entire wall in mm
Un-supported length for compression member along
31 lux =
D in mm
Un-supported length for compression member along
32 luy =
B in mm
Moment capacity of section for a given NA angle at
33 MCap =
design Pu in kNm
Resultant design moment at a given load angle to
34 MRes =
local major axis in kNm
Factored moment amplified for the effects of member
35 Mc = curvature used for design of compression member in
kNm
Factored moment modified to account for effect of
36 Mm =
axial compression in kNm
Factored moment acting on a section along D in kNm
37 Mux =
(From Analysis)
Factored moment acting on a section along B in kNm
38 Muy =
(From Analysis)
Smaller factored end moment on a compression
39 M1 =
member in kNm
Factored end moment on a compression member at
40 M1ns = the end at which M1 acts, due to loads that cause no
appreciable sidesway in kNm
Factored end moment on compression member at the
41 M1s = end at which M1 acts, due to loads that cause
appreciable sidesway in kNm
Smaller factored end moment on a compression
42 M1sldr =
member due to slenderness effect in kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 3 of 198

Larger factored end moment on compression member


43 M2 =
in kNm
Minimum value of moment M2 as per minimum
44 M2min =
eccentricity of column
Factored end moment on compression member at the
45 M2ns = end at which M2 acts, due to loads that cause no
appreciable sidesway in kNm
Factored end moment on compression member at the
46 M2s = end at which M2 acts, due to loads that cause
appreciable sidesway in kNm
Largest factored end moment on a compression
47 M2sldr =
member due to slenderness effect in kNm
48 Mnb = Flexure Capacity for Beam
49 Mnc = Flexure Capacity for Column
Nominal Flexure strength of column at top along
50 Mnty =
depth in kNm
Nominal Flexure strength of column at bottom along
51 Mnby =
depth in kNm
Nominal Flexure strength of column at top along
52 Mntx =
width in kNm
Nominal Flexure strength of column at bottom along
53 Mnbx =
width in kNm
Factored axial force normal to cross section occurring
54 Nu =
simultaneously with Vu in kN
55 Pc = Critical buckling load in kN
Ratio of area of distributed transverse reinforcement
56 pt = to gross concrete area perpendicular to that
reinforcement
57 Pω = Ratio of As to B x d
58 Q = Stability index for storey
Radius of gyration of cross section of a compression
59 r =
member in mm
60 Vc = Nominal shear strength provided by concrete in kN
61 Vj = Shear Force acting at the joint in kN
62 Vn = Nominal shear strength in kN
63 Vn' = Nominal shear strength at joint in kN
64 Vus = Factored horizontal shear in a storey in kN
Factored shear at section along D in kN (From
65 Vux =
Analysis)
Shear induced due to column flexural capacity along
66 Vux1 =
width, kN
Shear due to enhanced earthquake factor along
67 Vux2 =
width, kN
Factored shear at section along B in kN (From
68 Vuy =
Analysis)
Shear induced due to column flexural capacity along
69 Vuy1 =
depth, kN
Shear due to enhanced earthquake factor along depth,

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 4 of 198

70 Vuy2 = kN
It is a Neutral Axis angle corresponding to load angle
71 β =
to find out MCap

Code References:
ACI 318M-2011
Sr.No Element Clause / table
Minimum area of longitudinal reinforcement
1 : 21.6.3
for column
Maximum area of longitudinal
2 : 21.6.3
reinforcement for column
Minimum longitudinal and transverse
3 : 21.9.2.1
reinforcement for wall
4 Minimum diameter of transverse ties : 7.10.5
5 Minimum spacing of transverse ties : 7.10.5
Maximum spacing of longitudinal and
6 : 21.9.2.1
transverse reinforcement for wall
7 Applicability of boundary element : 21.9.6
Area and spacing of special confining
8 : 21.6.4
reinforcement
9 Slenderness Moments : 10.10
Shear Strength provided by concrete for
10 : 11.2
column
11 Design of shear for non-ductile wall : 11.9
12 Design of shear for ductile wall : 21.9.4
13 Minimum Flexural Strength of Columns : 21.6.2.2
14 Shear Check at Column Joint : 21.7.4.1
15 Shear Strength of Column : 21.3.3 & 21.5.4

Lateral Load case is not been considered in analysis

General Data
Column No. : C1
Level : -1.5m To 0m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 5 of 198

Clear Floor Height @ lux = 1500 mm


Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 54
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 235.83 kN
Muxt = -14.09 kNm
Muyt = 2.01 kNm
Vuxt = -3.12 kN
Vuyt = -17.44 kN
Pub = 240.28 kN
Muxb = 12.05 kNm
Muyb = -2.66 kNm
Vuxb = -3.12 kN
Vuyb = -17.44 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 17.32
M1 = 12.05 kNm
M2 = -14.09 kNm
34 - 12 x (M1/M2) = 44.26

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 6 of 198

17.32 < 44.26, Column not slender along D


Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 17.32
M1 = 2.01 kNm
M2 = -2.66 kNm
34 - 12 x (M1/M2) = 43.04
17.32 < 43.04, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -14.09 - -14.09
Major Axis Mux (bottom) 12.05 - 12.05
Minor Axis Muy (top) 2.01 - 2.01
Minor Axis Muy (bottom) -2.66 - -2.66

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 235.83 kN
Mux = -14.09 kNm
Muy = 2.01 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 8.11 deg
MRes = 14.24 kNm
( φ ) MCap = 69.85 kNm
Capacity Ratio = MRes/ MCap
= 0.204 < 1

Design Of Shear

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 7 of 198

Design for shear along D


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 202.14 kN
Muy = 12.08 kNm
Vuy = -14.9453 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -11.82 kNm
φVcy = 106.49 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 202.14 kN
Mux = 1.72 kNm
Vux = -2.6704 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -22.18 kNm
φVcx = 106.49 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 8 of 198

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C1
Level : 0m To 0.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 72
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 233.75 kN
Muxt = 26.3 kNm
Muyt = 4.19 kNm
Vuxt = 3.12 kN
Vuyt = -17.44 kN
Pub = 235.83 kN
Muxb = 14.09 kNm
Muyb = 2.01 kNm
Vuxb = 3.12 kN
Vuyb = -17.44 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 9 of 198

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 3.46
M1 = 14.09 kNm
M2 = 26.3 kNm
34 - 12 x (M1/M2) = 27.57
3.46 < 27.57, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 3.46
M1 = 2.01 kNm
M2 = 4.19 kNm
34 - 12 x (M1/M2) = 28.25
3.46 < 28.25, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 26.3 - 26.3
Major Axis Mux (bottom) 14.09 - 14.09
Minor Axis Muy (top) 4.19 - 4.19
Minor Axis Muy (bottom) 2.01 - 2.01

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 10 of 198

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 233.75 kN
Mux = 26.3 kNm
Muy = 4.19 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 9.05 deg
MRes = 26.63 kNm
( φ ) MCap = 69.28 kNm
Capacity Ratio = MRes/ MCap
= 0.384 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 200.36 kN
Muy = 22.54 kNm
Vuy = -14.9453 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -1.15 kNm
φVcy = 106.3 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 200.36 kN
Mux = 3.59 kNm
Vux = 2.6704 kN
λ = 1
φ = 0.75
deff = 254 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 11 of 198

ρw (50% of As provided) = 0.021


Mm = -20.1 kNm
φVcx = 106.3 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C1
Level : 0.7m To 4.65m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 3450 mm
Clear Floor Height @ luy = 3450 mm
No Of Floors = 1
No Of Columns In Group = 1

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 12 of 198

Load Data
Analysis Reference No. = 114
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 132.13 kN
Muxt = 22.37 kNm
Muyt = 3.48 kNm
Vuxt = 1.87 kN
Vuyt = -11.41 kN
Pub = 143.86 kN
Muxb = -22.67 kNm
Muyb = -3.92 kNm
Vuxb = 1.87 kN
Vuyb = -11.41 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 39.84
M1 = 22.37 kNm
M2 = -22.67 kNm
34 - 12 x (M1/M2) = 45.84
39.84 < 45.84, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 39.84

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 13 of 198

M1 = 3.48 kNm
M2 = -3.92 kNm
34 - 12 x (M1/M2) = 44.65
39.84 < 44.65, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 22.37 - 22.37
Major Axis Mux (bottom) -22.67 - -22.67
Minor Axis Muy (top) 3.48 - 3.48
Minor Axis Muy (bottom) -3.92 - -3.92

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 132.13 kN
Mux = 22.37 kNm
Muy = 3.48 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 8.84 deg
MRes = 22.64 kNm
( φ ) MCap = 61.28 kNm
Capacity Ratio = MRes/ MCap
= 0.369 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 117.09 kN
Muy = 20.93 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 14 of 198

Vuy = -10.4001 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 7.08 kNm
φVcy = 53.37 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 113.25 kN
Mux = 2.98 kNm
Vux = 1.6051 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -10.41 kNm
φVcx = 96.81 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 15 of 198

General Data
Column No. : C1
Level : 4.65m To 7.51m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 2360 mm
Clear Floor Height @ luy = 2460 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 156
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Bottom Joint
Put = 30.15 kN
Muxt = 17.23 kNm
Muyt = 2.34 kNm
Vuxt = 1.94 kN
Vuyt = -14.03 kN
Pub = 38.64 kN
Muxb = -22.88 kNm
Muyb = -3.2 kNm
Vuxb = 1.94 kN
Vuyb = -14.03 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 16 of 198

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 28.41
M1 = 17.23 kNm
M2 = -22.88 kNm
34 - 12 x (M1/M2) = 43.03
28.41 < 43.03, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 27.25
M1 = 2.34 kNm
M2 = -3.2 kNm
34 - 12 x (M1/M2) = 42.76
27.25 < 42.76, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 17.23 - 17.23
Major Axis Mux (bottom) -22.88 - -22.88
Minor Axis Muy (top) 2.34 - 2.34
Minor Axis Muy (bottom) -3.2 - -3.2

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 38.64 kN
Mux = -22.88 kNm
Muy = -3.2 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 17 of 198

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 7.97 deg
MRes = 23.1 kNm
( φ ) MCap = 51.87 kNm
Capacity Ratio = MRes/ MCap
= 0.445 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 3
Critical Load Combination = [1] : 1.4 (LOAD 1: DL) kN
Nu = 38.64 kN
Muy = 22.88 kNm
Vuy = -14.0275 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 18.31 kNm
φVcy = 49.71 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 25.84 kN
Mux = 2.01 kNm
Vux = 1.6617 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -1.05 kNm
φVcx = 86.25 kN
Vux < φVcx
Link For Shear Design Along B are not required

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 18 of 198

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C2
Level : -1.5m To 0m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 53
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Bottom Joint
Put = 388.48 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 19 of 198

Muxt = 6.58 kNm


Muyt = 1.53 kNm
Vuxt = -2.89 kN
Vuyt = 8.72 kN
Pub = 392.93 kN
Muxb = -6.49 kNm
Muyb = -2.8 kNm
Vuxb = -2.89 kN
Vuyb = 8.72 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 17.32
M1 = -6.49 kNm
M2 = 6.58 kNm
34 - 12 x (M1/M2) = 45.84
17.32 < 45.84, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 17.32
M1 = 1.53 kNm
M2 = -2.8 kNm
34 - 12 x (M1/M2) = 40.57
17.32 < 40.57, Column not slender along B

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 20 of 198

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 6.58 - 6.58
Major Axis Mux (bottom) -6.49 - -6.49
Minor Axis Muy (top) 1.53 - 1.53
Minor Axis Muy (bottom) -2.8 - -2.8

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 392.93 kN
Mux = -6.49 kNm
Muy = -2.8 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 23.29 deg
MRes = 7.07 kNm
( φ ) MCap = 65.04 kNm
Capacity Ratio = MRes/ MCap
= 0.109 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 332.98 kN
Muy = 5.64 kNm
Vuy = 7.4729 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -33.73 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 21 of 198

φVcy = 119.31 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 332.98 kN
Mux = 1.31 kNm
Vux = -2.4736 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -38.06 kNm
φVcx = 119.31 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C2

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 22 of 198

Level : 0m To 0.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 71
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 386.4 kN
Muxt = -12.68 kNm
Muyt = 3.55 kNm
Vuxt = 2.89 kN
Vuyt = 8.72 kN
Pub = 388.48 kN
Muxb = -6.58 kNm
Muyb = 1.53 kNm
Vuxb = 2.89 kN
Vuyb = 8.72 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 23 of 198

Column Is Braced Along D


Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 3.46
M1 = -6.58 kNm
M2 = -12.68 kNm
34 - 12 x (M1/M2) = 27.77
3.46 < 27.77, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 3.46
M1 = 1.53 kNm
M2 = 3.55 kNm
34 - 12 x (M1/M2) = 28.82
3.46 < 28.82, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -12.68 - -12.68
Major Axis Mux (bottom) -6.58 - -6.58
Minor Axis Muy (top) 3.55 - 3.55
Minor Axis Muy (bottom) 1.53 - 1.53

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 386.4 kN
Mux = -12.68 kNm
Muy = 3.55 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 24 of 198

Load Angle = Tan-1(Muy/Mux)


= 15.64 deg
MRes = 13.17 kNm
( φ ) MCap = 68.39 kNm
Capacity Ratio = MRes/ MCap
= 0.193 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 331.2 kN
Muy = 10.87 kNm
Vuy = 7.4729 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -28.29 kNm
φVcy = 119.14 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 331.2 kN
Mux = 3.04 kNm
Vux = 2.4736 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -36.12 kNm
φVcx = 119.14 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 25 of 198

> Max. longitudinal bar dia / 4


= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C2
Level : 0.7m To 4.65m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 3450 mm
Clear Floor Height @ luy = 3450 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 113
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Top Joint
Put = 246.41 kN
Muxt = -8.79 kNm
Muyt = 6.18 kNm
Vuxt = 2.71 kN
Vuyt = 4.49 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 26 of 198

Pub = 256.47 kN
Muxb = 8.96 kNm
Muyb = -4.52 kNm
Vuxb = 2.71 kN
Vuyb = 4.49 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 39.84
M1 = -8.79 kNm
M2 = 8.96 kNm
34 - 12 x (M1/M2) = 45.77
39.84 < 45.77, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 39.84
M1 = -4.52 kNm
M2 = 6.18 kNm
34 - 12 x (M1/M2) = 42.77
39.84 < 42.77, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -8.79 - -8.79

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 27 of 198

Major Axis Mux (bottom) 8.96 - 8.96


Minor Axis Muy (top) 6.18 - 6.18
Minor Axis Muy (bottom) -4.52 - -4.52

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 246.41 kN
Mux = -8.79 kNm
Muy = 6.18 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 35.14 deg
MRes = 10.74 kNm
( φ ) MCap = 60.16 kNm
Capacity Ratio = MRes/ MCap
= 0.179 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 202.66 kN
Muy = 8.35 kNm
Vuy = 4.3458 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -15.62 kNm
φVcy = 106.54 kN
Vuy < φVcy
Link For Shear Design Along D are not required

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 28 of 198

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 202.66 kN
Mux = 4.24 kNm
Vux = 1.8627 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -19.72 kNm
φVcx = 106.54 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C2
Level : 4.65m To 7.51m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 29 of 198

Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 2360 mm
Clear Floor Height @ luy = 2460 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 155
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Bottom Joint
Put = 38.7 kN
Muxt = -7.72 kNm
Muyt = 5.4 kNm
Vuxt = 4.64 kN
Vuyt = 6.25 kN
Pub = 45.98 kN
Muxb = 10.14 kNm
Muyb = -7.87 kNm
Vuxb = 4.64 kN
Vuyb = 6.25 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 30 of 198

Kluy /r = 28.41
M1 = -7.72 kNm
M2 = 10.14 kNm
34 - 12 x (M1/M2) = 43.14
28.41 < 43.14, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 27.25
M1 = 5.4 kNm
M2 = -7.87 kNm
34 - 12 x (M1/M2) = 42.23
27.25 < 42.23, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -7.72 - -7.72
Major Axis Mux (bottom) 10.14 - 10.14
Minor Axis Muy (top) 5.4 - 5.4
Minor Axis Muy (bottom) -7.87 - -7.87

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 45.98 kN
Mux = 10.14 kNm
Muy = -7.87 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 37.8 deg
MRes = 12.84 kNm
( φ ) MCap = 53.43 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 31 of 198

Capacity Ratio = MRes/ MCap


= 0.24 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 3
Critical Load Combination = [1] : 1.4 (LOAD 1: DL) kN
Nu = 50.95 kN
Muy = 11.34 kNm
Vuy = 7.1565 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 5.32 kNm
φVcy = 52.73 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 45.98 kN
Mux = 7.87 kNm
Vux = 4.6396 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 2.43 kNm
φVcx = 55.66 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 32 of 198

48 x diameter of links = 480 mm


Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C3
Level : -1.5m To 0m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 45
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Bottom Joint
Put = 290.45 kN
Muxt = 1.17 kNm
Muyt = 2.45 kNm
Vuxt = -3.9 kN
Vuyt = 1.79 kN
Pub = 294.9 kN
Muxb = -1.51 kNm
Muyb = -3.4 kNm
Vuxb = -3.9 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 33 of 198

Vuyb = 1.79 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 17.32
M1 = 1.17 kNm
M2 = -1.51 kNm
34 - 12 x (M1/M2) = 43.32
17.32 < 43.32, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 17.32
M1 = 2.45 kNm
M2 = -3.4 kNm
34 - 12 x (M1/M2) = 42.65
17.32 < 42.65, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 1.17 - 1.17
Major Axis Mux (bottom) -1.51 - -1.51
Minor Axis Muy (top) 2.45 - 2.45
Minor Axis Muy (bottom) -3.4 - -3.4

Where

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 34 of 198

A = Moments from analysis


B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 294.9 kN
Mux = -1.51 kNm
Muy = -3.4 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 66.05 deg
MRes = 3.72 kNm
( φ ) MCap = 64.81 kNm
Capacity Ratio = MRes/ MCap
= 0.057 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 248.95 kN
Muy = 1.01 kNm
Vuy = 1.5348 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -28.43 kNm
φVcy = 111.25 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 248.95 kN
Mux = 2.1 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 35 of 198

Vux = -3.347 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -27.34 kNm
φVcx = 111.25 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C3
Level : 0m To 0.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 36 of 198

No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 63
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 288.37 kN
Muxt = -2.43 kNm
Muyt = 5.19 kNm
Vuxt = 3.9 kN
Vuyt = 1.79 kN
Pub = 290.45 kN
Muxb = -1.17 kNm
Muyb = 2.45 kNm
Vuxb = 3.9 kN
Vuyb = 1.79 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 3.46
M1 = -1.17 kNm
M2 = -2.43 kNm
34 - 12 x (M1/M2) = 28.2
3.46 < 28.2, Column not slender along D
Column Is Braced Along B

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 37 of 198

Slenderness Check along B


K = 1
r = 86.6 mm
Klux /r = 3.46
M1 = 2.45 kNm
M2 = 5.19 kNm
34 - 12 x (M1/M2) = 28.32
3.46 < 28.32, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -2.43 - -2.43
Major Axis Mux (bottom) -1.17 - -1.17
Minor Axis Muy (top) 5.19 - 5.19
Minor Axis Muy (bottom) 2.45 - 2.45

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 288.37 kN
Mux = -2.43 kNm
Muy = 5.19 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 64.92 deg
MRes = 5.73 kNm
( φ ) MCap = 64.25 kNm
Capacity Ratio = MRes/ MCap
= 0.089 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 38 of 198

Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN


Nu = 247.17 kN
Muy = 2.08 kNm
Vuy = 1.5348 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -27.15 kNm
φVcy = 111.07 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 247.17 kN
Mux = 4.44 kNm
Vux = 3.347 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -24.78 kNm
φVcx = 111.07 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 39 of 198

Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C3
Level : 0.7m To 4.65m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 3450 mm
Clear Floor Height @ luy = 3450 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 105
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Top Joint
Put = 186.37 kN
Muxt = -2.64 kNm
Muyt = 6.4 kNm
Vuxt = 2.93 kN
Vuyt = 1.24 kN
Pub = 196.43 kN
Muxb = 2.25 kNm
Muyb = -5.17 kNm
Vuxb = 2.93 kN
Vuyb = 1.24 kN

Check For Stability Index


Along D

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 40 of 198

       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 39.84
M1 = 2.25 kNm
M2 = -2.64 kNm
34 - 12 x (M1/M2) = 44.27
39.84 < 44.27, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 39.84
M1 = -5.17 kNm
M2 = 6.4 kNm
34 - 12 x (M1/M2) = 43.71
39.84 < 43.71, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -2.64 - -2.64
Major Axis Mux (bottom) 2.25 - 2.25
Minor Axis Muy (top) 6.4 - 6.4
Minor Axis Muy (bottom) -5.17 - -5.17

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 41 of 198

Critical Case - Axial Load & BiAxial Bending


Pu = 186.37 kN
Mux = -2.64 kNm
Muy = 6.4 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 67.6 deg
MRes = 6.92 kNm
( φ ) MCap = 62.04 kNm
Capacity Ratio = MRes/ MCap
= 0.111 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 150.74 kN
Muy = 1.98 kNm
Vuy = 0.9868 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -15.85 kNm
φVcy = 101.01 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 150.74 kN
Mux = 4.81 kNm
Vux = 2.2014 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 42 of 198

Mm = -13.01 kNm
φVcx = 101.01 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C3
Level : 4.65m To 7.51m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 2360 mm
Clear Floor Height @ luy = 2460 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 43 of 198

Analysis Reference No. = 147


Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Bottom Joint
Put = 28.04 kN
Muxt = -3.86 kNm
Muyt = 6.49 kNm
Vuxt = 5.04 kN
Vuyt = 2.83 kN
Pub = 35.32 kN
Muxb = 4.23 kNm
Muyb = -7.91 kNm
Vuxb = 5.04 kN
Vuyb = 2.83 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 28.41
M1 = -3.86 kNm
M2 = 4.23 kNm
34 - 12 x (M1/M2) = 44.96
28.41 < 44.96, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 27.25
M1 = 6.49 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 44 of 198

M2 = -7.91 kNm
34 - 12 x (M1/M2) = 43.84
27.25 < 43.84, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -3.86 - -3.86
Major Axis Mux (bottom) 4.23 - 4.23
Minor Axis Muy (top) 6.49 - 6.49
Minor Axis Muy (bottom) -7.91 - -7.91

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 35.32 kN
Mux = 4.23 kNm
Muy = -7.91 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 61.88 deg
MRes = 8.97 kNm
( φ ) MCap = 53.1 kNm
Capacity Ratio = MRes/ MCap
= 0.169 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 28.04 kN
Muy = 3.86 kNm
Vuy = 2.83 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 45 of 198

λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 0.55 kNm
φVcy = 72.64 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 35.32 kN
Mux = 7.91 kNm
Vux = 5.0369 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 3.74 kNm
φVcx = 52.74 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 46 of 198

General Data
Column No. : C4
Level : -1.5m To 0m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 44
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Bottom Joint
Put = 170.78 kN
Muxt = 3.09 kNm
Muyt = 2.57 kNm
Vuxt = -3.63 kN
Vuyt = 4.21 kN
Pub = 175.23 kN
Muxb = -3.22 kNm
Muyb = -2.87 kNm
Vuxb = -3.63 kN
Vuyb = 4.21 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 47 of 198

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 17.32
M1 = 3.09 kNm
M2 = -3.22 kNm
34 - 12 x (M1/M2) = 45.51
17.32 < 45.51, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 17.32
M1 = 2.57 kNm
M2 = -2.87 kNm
34 - 12 x (M1/M2) = 44.75
17.32 < 44.75, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 3.09 - 3.09
Major Axis Mux (bottom) -3.22 - -3.22
Minor Axis Muy (top) 2.57 - 2.57
Minor Axis Muy (bottom) -2.87 - -2.87

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 175.23 kN
Mux = -3.22 kNm
Muy = -2.87 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 48 of 198

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 41.71 deg
MRes = 4.32 kNm
( φ ) MCap = 58.45 kNm
Capacity Ratio = MRes/ MCap
= 0.074 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 146.38 kN
Muy = 2.65 kNm
Vuy = 3.6103 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -14.66 kNm
φVcy = 100.53 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 146.38 kN
Mux = 2.21 kNm
Vux = -3.1127 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -15.1 kNm
φVcx = 100.53 kN
Vux < φVcx
Link For Shear Design Along B are not required

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 49 of 198

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C4
Level : 0m To 0.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 62
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 168.7 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 50 of 198

Muxt = -6.04 kNm


Muyt = 5.11 kNm
Vuxt = 3.63 kN
Vuyt = 4.21 kN
Pub = 170.78 kN
Muxb = -3.09 kNm
Muyb = 2.57 kNm
Vuxb = 3.63 kN
Vuyb = 4.21 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 3.46
M1 = -3.09 kNm
M2 = -6.04 kNm
34 - 12 x (M1/M2) = 27.86
3.46 < 27.86, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 3.46
M1 = 2.57 kNm
M2 = 5.11 kNm
34 - 12 x (M1/M2) = 27.96
3.46 < 27.96, Column not slender along B

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 51 of 198

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -6.04 - -6.04
Major Axis Mux (bottom) -3.09 - -3.09
Minor Axis Muy (top) 5.11 - 5.11
Minor Axis Muy (bottom) 2.57 - 2.57

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 168.7 kN
Mux = -6.04 kNm
Muy = 5.11 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 40.25 deg
MRes = 7.91 kNm
( φ ) MCap = 58.45 kNm
Capacity Ratio = MRes/ MCap
= 0.135 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 144.6 kN
Muy = 5.18 kNm
Vuy = 3.6103 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -11.92 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 52 of 198

φVcy = 100.33 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 144.6 kN
Mux = 4.38 kNm
Vux = 3.1127 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -12.72 kNm
φVcx = 100.33 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C4

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 53 of 198

Level : 0.7m To 4.65m


Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 3450 mm
Clear Floor Height @ luy = 3450 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 104
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Top Joint
Put = 99.14 kN
Muxt = -5.29 kNm
Muyt = 4.52 kNm
Vuxt = 2.25 kN
Vuyt = 2.58 kN
Pub = 109.2 kN
Muxb = 4.89 kNm
Muyb = -4.35 kNm
Vuxb = 2.25 kN
Vuyb = 2.58 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 54 of 198

Column Is Braced Along D


Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 39.84
M1 = 4.89 kNm
M2 = -5.29 kNm
34 - 12 x (M1/M2) = 45.1
39.84 < 45.1, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 39.84
M1 = -4.35 kNm
M2 = 4.52 kNm
34 - 12 x (M1/M2) = 45.55
39.84 < 45.55, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -5.29 - -5.29
Major Axis Mux (bottom) 4.89 - 4.89
Minor Axis Muy (top) 4.52 - 4.52
Minor Axis Muy (bottom) -4.35 - -4.35

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 99.14 kN
Mux = -5.29 kNm
Muy = 4.52 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 55 of 198

Load Angle = Tan-1(Muy/Mux)


= 40.48 deg
MRes = 6.96 kNm
( φ ) MCap = 56.24 kNm
Capacity Ratio = MRes/ MCap
= 0.124 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 86.21 kN
Muy = 4.48 kNm
Vuy = 2.2778 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -5.72 kNm
φVcy = 93.67 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 86.21 kN
Mux = 3.65 kNm
Vux = 1.824 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -6.54 kNm
φVcx = 93.67 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 56 of 198

> Max. longitudinal bar dia / 4


= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C4
Level : 4.65m To 7.51m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 2360 mm
Clear Floor Height @ luy = 2460 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 146
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Bottom Joint
Put = 19.77 kN
Muxt = -5.32 kNm
Muyt = 5.83 kNm
Vuxt = 4.1 kN
Vuyt = 4.22 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 57 of 198

Pub = 27.05 kN
Muxb = 6.75 kNm
Muyb = -5.91 kNm
Vuxb = 4.1 kN
Vuyb = 4.22 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 28.41
M1 = -5.32 kNm
M2 = 6.75 kNm
34 - 12 x (M1/M2) = 43.47
28.41 < 43.47, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 27.25
M1 = 5.83 kNm
M2 = -5.91 kNm
34 - 12 x (M1/M2) = 45.83
27.25 < 45.83, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -5.32 - -5.32

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 58 of 198

Major Axis Mux (bottom) 6.75 - 6.75


Minor Axis Muy (top) 5.83 - 5.83
Minor Axis Muy (bottom) -5.91 - -5.91

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 27.05 kN
Mux = 6.75 kNm
Muy = -5.91 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 41.2 deg
MRes = 8.97 kNm
( φ ) MCap = 52.58 kNm
Capacity Ratio = MRes/ MCap
= 0.171 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 27.05 kN
Muy = 6.75 kNm
Vuy = 4.2231 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 3.55 kNm
φVcy = 51.91 kN
Vuy < φVcy
Link For Shear Design Along D are not required

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 59 of 198

Design for shear along B


Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 19.77 kN
Mux = 5.83 kNm
Vux = 4.1043 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 3.49 kNm
φVcx = 51.85 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C5
Level : -1.5m To 0m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 60 of 198

Grade Of Steel (fy) = Fy275 N/sqmm


Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 56
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 144.26 kN
Muxt = -2.66 kNm
Muyt = -2.77 kNm
Vuxt = 2.95 kN
Vuyt = -3.2 kN
Pub = 148.72 kN
Muxb = 2.14 kNm
Muyb = 1.65 kNm
Vuxb = 2.95 kN
Vuyb = -3.2 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 61 of 198

r = 86.6 mm
Kluy /r = 17.32
M1 = 2.14 kNm
M2 = -2.66 kNm
34 - 12 x (M1/M2) = 43.65
17.32 < 43.65, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 17.32
M1 = 1.65 kNm
M2 = -2.77 kNm
34 - 12 x (M1/M2) = 41.17
17.32 < 41.17, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -2.66 - -2.66
Major Axis Mux (bottom) 2.14 - 2.14
Minor Axis Muy (top) -2.77 - -2.77
Minor Axis Muy (bottom) 1.65 - 1.65

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 144.26 kN
Mux = -2.66 kNm
Muy = -2.77 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 46.16 deg
MRes = 3.83 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 62 of 198

( φ ) MCap = 57.69 kNm


Capacity Ratio = MRes/ MCap
= 0.066 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 122.36 kN
Muy = 2.42 kNm
Vuy = -2.9445 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -12.05 kNm
φVcy = 97.85 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 122.36 kN
Mux = 2.39 kNm
Vux = 2.4753 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -12.08 kNm
φVcx = 97.85 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 63 of 198

Criterion for spacing of normal links


Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C5
Level : 0m To 0.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 74
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 142.19 kN
Muxt = 4.89 kNm
Muyt = -4.83 kNm
Vuxt = -2.95 kN
Vuyt = -3.2 kN
Pub = 144.26 kN
Muxb = 2.66 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 64 of 198

Muyb = -2.77 kNm


Vuxb = -2.95 kN
Vuyb = -3.2 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 3.46
M1 = 2.66 kNm
M2 = 4.89 kNm
34 - 12 x (M1/M2) = 27.49
3.46 < 27.49, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 3.46
M1 = -2.77 kNm
M2 = -4.83 kNm
34 - 12 x (M1/M2) = 27.13
3.46 < 27.13, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 4.89 - 4.89
Major Axis Mux (bottom) 2.66 - 2.66
Minor Axis Muy (top) -4.83 - -4.83
Minor Axis Muy (bottom) -2.77 - -2.77

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 65 of 198

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 142.19 kN
Mux = 4.89 kNm
Muy = -4.83 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 44.62 deg
MRes = 6.87 kNm
( φ ) MCap = 57.64 kNm
Capacity Ratio = MRes/ MCap
= 0.119 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 120.58 kN
Muy = 4.48 kNm
Vuy = -2.9445 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -9.78 kNm
φVcy = 97.65 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 4

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 66 of 198

[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:


Critical Load Combination = kN
LL)
Nu = 120.58 kN
Mux = 4.12 kNm
Vux = -2.4753 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -10.14 kNm
φVcx = 97.65 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C5
Level : 0.7m To 4.65m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 67 of 198

Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 3450 mm
Clear Floor Height @ luy = 3450 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 116
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Bottom Joint
Put = 77.31 kN
Muxt = 3.86 kNm
Muyt = -3.35 kNm
Vuxt = -1.7 kN
Vuyt = -2.01 kN
Pub = 89.04 kN
Muxb = -4.06 kNm
Muyb = 3.37 kNm
Vuxb = -1.7 kN
Vuyb = -2.01 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 39.84
M1 = 3.86 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 68 of 198

M2 = -4.06 kNm
34 - 12 x (M1/M2) = 45.42
39.84 < 45.42, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 39.84
M1 = -3.35 kNm
M2 = 3.37 kNm
34 - 12 x (M1/M2) = 45.93
39.84 < 45.93, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 3.86 - 3.86
Major Axis Mux (bottom) -4.06 - -4.06
Minor Axis Muy (top) -3.35 - -3.35
Minor Axis Muy (bottom) 3.37 - 3.37

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 89.04 kN
Mux = -4.06 kNm
Muy = 3.37 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 39.72 deg
MRes = 5.28 kNm
( φ ) MCap = 55.71 kNm
Capacity Ratio = MRes/ MCap
= 0.095 < 1

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 69 of 198

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 64.69 kN
Muy = 3.33 kNm
Vuy = -1.7472 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -4.32 kNm
φVcy = 91.1 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 64.69 kN
Mux = 2.76 kNm
Vux = -1.401 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -4.89 kNm
φVcx = 91.1 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 70 of 198

Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C5
Level : 4.65m To 7.51m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 2360 mm
Clear Floor Height @ luy = 2460 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 158
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Bottom Joint
Put = 17.16 kN
Muxt = 2.89 kNm
Muyt = -2.64 kNm
Vuxt = -2.2 kN
Vuyt = -2.17 kN
Pub = 25.65 kN
Muxb = -3.3 kNm
Muyb = 3.65 kNm
Vuxb = -2.2 kN
Vuyb = -2.17 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 71 of 198

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 28.41
M1 = 2.89 kNm
M2 = -3.3 kNm
34 - 12 x (M1/M2) = 44.54
28.41 < 44.54, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 27.25
M1 = -2.64 kNm
M2 = 3.65 kNm
34 - 12 x (M1/M2) = 42.69
27.25 < 42.69, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 2.89 - 2.89
Major Axis Mux (bottom) -3.3 - -3.3
Minor Axis Muy (top) -2.64 - -2.64
Minor Axis Muy (bottom) 3.65 - 3.65

Where
A = Moments from analysis
B = Moment due to slenderness effect

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 72 of 198

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 25.65 kN
Mux = -3.3 kNm
Muy = 3.65 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 47.88 deg
MRes = 4.92 kNm
( φ ) MCap = 52.55 kNm
Capacity Ratio = MRes/ MCap
= 0.094 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 15.2 kN
Muy = 2.93 kNm
Vuy = -2.0571 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 1.13 kNm
φVcy = 55.17 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 3
Critical Load Combination = [1] : 1.4 (LOAD 1: DL) kN
Nu = 25.65 kN
Mux = 3.65 kNm
Vux = -2.1994 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 73 of 198

λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 0.61 kNm
φVcx = 64.41 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C6
Level : -1.5m To 0m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 74 of 198

No Of Columns In Group = 1

Load Data
Analysis Reference No. = 58
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Bottom Joint
Put = 227.43 kN
Muxt = 0.95 kNm
Muyt = 0.79 kNm
Vuxt = -1.46 kN
Vuyt = 1.38 kN
Pub = 231.89 kN
Muxb = -1.12 kNm
Muyb = -1.39 kNm
Vuxb = -1.46 kN
Vuyb = 1.38 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 17.32
M1 = 0.95 kNm
M2 = -1.12 kNm
34 - 12 x (M1/M2) = 44.16
17.32 < 44.16, Column not slender along D
Column Is Braced Along B
Slenderness Check along B

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 75 of 198

K = 1
r = 86.6 mm
Klux /r = 17.32
M1 = 0.79 kNm
M2 = -1.39 kNm
34 - 12 x (M1/M2) = 40.85
17.32 < 40.85, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 0.95 - 0.95
Major Axis Mux (bottom) -1.12 - -1.12
Minor Axis Muy (top) 0.79 - 0.79
Minor Axis Muy (bottom) -1.39 - -1.39

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 231.89 kN
Mux = -1.12 kNm
Muy = -1.39 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 51.1 deg
MRes = 1.79 kNm
( φ ) MCap = 59.49 kNm
Capacity Ratio = MRes/ MCap
= 0.03 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 76 of 198

Nu = 194.94 kN
Muy = 0.82 kNm
Vuy = 1.1861 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -22.24 kNm
φVcy = 105.74 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 194.94 kN
Mux = 0.68 kNm
Vux = -1.25 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -22.37 kNm
φVcx = 105.74 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 77 of 198

Link Dia. 10 --- --- 10 ---


Spacing 250 --- --- 250 ---

General Data
Column No. : C6
Level : 0m To 0.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 76
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 225.35 kN
Muxt = -1.92 kNm
Muyt = 1.81 kNm
Vuxt = 1.46 kN
Vuyt = 1.38 kN
Pub = 227.43 kN
Muxb = -0.95 kNm
Muyb = 0.79 kNm
Vuxb = 1.46 kN
Vuyb = 1.38 kN

Check For Stability Index


Along D
       Q = 0.01

0.01< 0.05, Column shall be designed as non-sway frame

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 78 of 198

(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 3.46
M1 = -0.95 kNm
M2 = -1.92 kNm
34 - 12 x (M1/M2) = 28.05
3.46 < 28.05, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 3.46
M1 = 0.79 kNm
M2 = 1.81 kNm
34 - 12 x (M1/M2) = 28.75
3.46 < 28.75, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -1.92 - -1.92
Major Axis Mux (bottom) -0.95 - -0.95
Minor Axis Muy (top) 1.81 - 1.81
Minor Axis Muy (bottom) 0.79 - 0.79

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 225.35 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 79 of 198

Mux = -1.92 kNm


Muy = 1.81 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 43.39 deg
MRes = 2.64 kNm
( φ ) MCap = 59.24 kNm
Capacity Ratio = MRes/ MCap
= 0.045 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 193.16 kN
Muy = 1.65 kNm
Vuy = 1.1861 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -21.2 kNm
φVcy = 105.55 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 193.16 kN
Mux = 1.56 kNm
Vux = 1.25 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -21.29 kNm
φVcx = 105.55 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 80 of 198

Vux < φVcx


Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C6
Level : 0.7m To 4.65m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 3450 mm
Clear Floor Height @ luy = 3450 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 118
Critical Analysis Load Combination : 4

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 81 of 198

Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)


Critical Location = Top Joint
Put = 154.56 kN
Muxt = 3.08 kNm
Muyt = 2.99 kNm
Vuxt = 1.46 kN
Vuyt = -0.99 kN
Pub = 164.62 kN
Muxb = -0.83 kNm
Muyb = -2.77 kNm
Vuxb = 1.46 kN
Vuyb = -0.99 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 39.84
M1 = -0.83 kNm
M2 = 3.08 kNm
34 - 12 x (M1/M2) = 37.22
39.84 > 37.22,Column slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 39.84
M1 = -2.77 kNm
M2 = 2.99 kNm
34 - 12 x (M1/M2) = 45.11

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 82 of 198

39.84 < 45.11, Column not slender along B


Moment Magnification:
For Non-sway frame:
Along D
βdns = 0.6
Ec = 23500 N/sqmm
9 = 0.675 mm^4
Ig ( x 10 )
6 = 4579107.188 >N-sqmm
EI ( x 10 )
M2min = 3.95 kNm
Cm = 1
Pc = 3797.02 kN
δns = 1.06
Mc1 = -4.19 kN
Mc2 = 4.19 kN

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 3.08 4.19 4.19
Major Axis Mux (bottom) -0.83 -4.19 -4.19
Minor Axis Muy (top) 2.99 - 2.99
Minor Axis Muy (bottom) -2.77 - -2.77

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 154.56 kN
Mux = 4.19 kNm
Muy = 2.99 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 35.46 deg
MRes = 5.15 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 83 of 198

( φ ) MCap = 58.59 kNm


Capacity Ratio = MRes/ MCap
= 0.088 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 121.05 kN
Muy = 0.97 kNm
Vuy = -0.1889 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -13.35 kNm
φVcy = 97.7 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 121.05 kN
Mux = 1.89 kNm
Vux = 1.0158 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -12.43 kNm
φVcx = 97.7 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 84 of 198

48 x diameter of links = 480 mm


Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C6
Level : 4.65m To 7.51m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 2360 mm
Clear Floor Height @ luy = 2460 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 160
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Bottom Joint
Put = 25.99 kN
Muxt = 3.37 kNm
Muyt = 1.47 kNm
Vuxt = 1 kN
Vuyt = -2.83 kN
Pub = 33.28 kN
Muxb = -4.71 kNm
Muyb = -1.39 kNm
Vuxb = 1 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 85 of 198

Vuyb = -2.83 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 28.41
M1 = 3.37 kNm
M2 = -4.71 kNm
34 - 12 x (M1/M2) = 42.59
28.41 < 42.59, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 27.25
M1 = -1.39 kNm
M2 = 1.47 kNm
34 - 12 x (M1/M2) = 45.3
27.25 < 45.3, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 3.37 - 3.37
Major Axis Mux (bottom) -4.71 - -4.71
Minor Axis Muy (top) 1.47 - 1.47
Minor Axis Muy (bottom) -1.39 - -1.39

Where

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 86 of 198

A = Moments from analysis


B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 33.28 kN
Mux = -4.71 kNm
Muy = -1.39 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 16.39 deg
MRes = 4.91 kNm
( φ ) MCap = 52.09 kNm
Capacity Ratio = MRes/ MCap
= 0.094 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 33.28 kN
Muy = 4.71 kNm
Vuy = -2.8276 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 0.78 kNm
φVcy = 64.69 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 87 of 198

Nu = 25.99 kN
Mux = 1.47 kNm
Vux = 0.999 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -1.6 kNm
φVcx = 86.27 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C7
Level : -1.5m To 0m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 88 of 198

Clear Floor Height @ lux = 1500 mm


Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 48
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Bottom Joint
Put = 379.89 kN
Muxt = -5.38 kNm
Muyt = 5.74 kNm
Vuxt = -8.26 kN
Vuyt = -6.68 kN
Pub = 384.34 kN
Muxb = 4.63 kNm
Muyb = -6.64 kNm
Vuxb = -8.26 kN
Vuyb = -6.68 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 17.32
M1 = 4.63 kNm
M2 = -5.38 kNm
34 - 12 x (M1/M2) = 44.31

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 89 of 198

17.32 < 44.31, Column not slender along D


Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 17.32
M1 = 5.74 kNm
M2 = -6.64 kNm
34 - 12 x (M1/M2) = 44.37
17.32 < 44.37, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -5.38 - -5.38
Major Axis Mux (bottom) 4.63 - 4.63
Minor Axis Muy (top) 5.74 - 5.74
Minor Axis Muy (bottom) -6.64 - -6.64

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 384.34 kN
Mux = 4.63 kNm
Muy = -6.64 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 55.14 deg
MRes = 8.1 kNm
( φ ) MCap = 61.55 kNm
Capacity Ratio = MRes/ MCap
= 0.132 < 1

Design Of Shear

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 90 of 198

Design for shear along D


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 325.62 kN
Muy = 4.61 kNm
Vuy = -5.7225 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -33.89 kNm
φVcy = 118.63 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 325.62 kN
Mux = 4.92 kNm
Vux = -7.0793 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -33.58 kNm
φVcx = 118.63 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 91 of 198

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C7
Level : 0m To 0.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 66
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 377.81 kN
Muxt = 10.06 kNm
Muyt = 11.52 kNm
Vuxt = 8.26 kN
Vuyt = -6.68 kN
Pub = 379.89 kN
Muxb = 5.38 kNm
Muyb = 5.74 kNm
Vuxb = 8.26 kN
Vuyb = -6.68 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 92 of 198

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 3.46
M1 = 5.38 kNm
M2 = 10.06 kNm
34 - 12 x (M1/M2) = 27.58
3.46 < 27.58, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 3.46
M1 = 5.74 kNm
M2 = 11.52 kNm
34 - 12 x (M1/M2) = 28.02
3.46 < 28.02, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 10.06 - 10.06
Major Axis Mux (bottom) 5.38 - 5.38
Minor Axis Muy (top) 11.52 - 11.52
Minor Axis Muy (bottom) 5.74 - 5.74

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 93 of 198

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 377.81 kN
Mux = 10.06 kNm
Muy = 11.52 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 48.88 deg
MRes = 15.29 kNm
( φ ) MCap = 60.47 kNm
Capacity Ratio = MRes/ MCap
= 0.253 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 323.83 kN
Muy = 8.62 kNm
Vuy = -5.7225 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -29.67 kNm
φVcy = 118.46 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 323.83 kN
Mux = 9.88 kNm
Vux = 7.0793 kN
λ = 1
φ = 0.75
deff = 254 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 94 of 198

ρw (50% of As provided) = 0.021


Mm = -28.42 kNm
φVcx = 118.46 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C7
Level : 0.7m To 4.65m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 3450 mm
Clear Floor Height @ luy = 3450 mm
No Of Floors = 1
No Of Columns In Group = 1

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 95 of 198

Load Data
Analysis Reference No. = 108
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Bottom Joint
Put = 322.71 kN
Muxt = 7.36 kNm
Muyt = 5.98 kNm
Vuxt = 3.27 kN
Vuyt = -3.71 kN
Pub = 332.77 kN
Muxb = -7.3 kNm
Muyb = -6.93 kNm
Vuxb = 3.27 kN
Vuyb = -3.71 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 39.84
M1 = -7.3 kNm
M2 = 7.36 kNm
34 - 12 x (M1/M2) = 45.89
39.84 < 45.89, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 39.84

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 96 of 198

M1 = 5.98 kNm
M2 = -6.93 kNm
34 - 12 x (M1/M2) = 44.36
39.84 < 44.36, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 7.36 - 7.36
Major Axis Mux (bottom) -7.3 - -7.3
Minor Axis Muy (top) 5.98 - 5.98
Minor Axis Muy (bottom) -6.93 - -6.93

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 332.77 kN
Mux = -7.3 kNm
Muy = -6.93 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 43.5 deg
MRes = 10.06 kNm
( φ ) MCap = 60.25 kNm
Capacity Ratio = MRes/ MCap
= 0.167 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 200.24 kN
Muy = 5.49 kNm
Vuy = -3.0298 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 97 of 198

λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -18.19 kNm
φVcy = 106.29 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 200.24 kN
Mux = 0.82 kNm
Vux = 1.3111 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -22.86 kNm
φVcx = 106.29 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 98 of 198

General Data
Column No. : C7
Level : 4.65m To 7.51m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 2460 mm
Clear Floor Height @ luy = 2460 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 150
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Bottom Joint
Put = 31.85 kN
Muxt = 4.41 kNm
Muyt = 5.23 kNm
Vuxt = 3.9 kN
Vuyt = -3.95 kN
Pub = 39.13 kN
Muxb = -6.89 kNm
Muyb = -5.91 kNm
Vuxb = 3.9 kN
Vuyb = -3.95 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 99 of 198

       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 28.41
M1 = 4.41 kNm
M2 = -6.89 kNm
34 - 12 x (M1/M2) = 41.69
28.41 < 41.69, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 28.41
M1 = 5.23 kNm
M2 = -5.91 kNm
34 - 12 x (M1/M2) = 44.62
28.41 < 44.62, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 4.41 - 4.41
Major Axis Mux (bottom) -6.89 - -6.89
Minor Axis Muy (top) 5.23 - 5.23
Minor Axis Muy (bottom) -5.91 - -5.91

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 39.13 kN
Mux = -6.89 kNm
Muy = -5.91 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 100 of 198

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 40.63 deg
MRes = 9.07 kNm
( φ ) MCap = 53.18 kNm
Capacity Ratio = MRes/ MCap
= 0.171 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 39.13 kN
Muy = 6.89 kNm
Vuy = -3.9518 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 2.26 kNm
φVcy = 54.83 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 31.85 kN
Mux = 5.23 kNm
Vux = 3.8953 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 1.46 kNm
φVcx = 59.59 kN
Vux < φVcx
Link For Shear Design Along B are not required

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 101 of 198

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C8
Level : -1.5m To 0m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 47
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Bottom Joint

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 102 of 198

Put = 450.09 kN
Muxt = 2.2 kNm
Muyt = 6.04 kNm
Vuxt = -8.5 kN
Vuyt = 2.92 kN
Pub = 454.54 kN
Muxb = -2.18 kNm
Muyb = -6.7 kNm
Vuxb = -8.5 kN
Vuyb = 2.92 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 17.32
M1 = -2.18 kNm
M2 = 2.2 kNm
34 - 12 x (M1/M2) = 45.92
17.32 < 45.92, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 17.32
M1 = 6.04 kNm
M2 = -6.7 kNm
34 - 12 x (M1/M2) = 44.82
17.32 < 44.82, Column not slender along B

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 103 of 198

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 2.2 - 2.2
Major Axis Mux (bottom) -2.18 - -2.18
Minor Axis Muy (top) 6.04 - 6.04
Minor Axis Muy (bottom) -6.7 - -6.7

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 454.54 kN
Mux = -2.18 kNm
Muy = -6.7 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 71.96 deg
MRes = 7.04 kNm
( φ ) MCap = 66.43 kNm
Capacity Ratio = MRes/ MCap
= 0.106 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 385.79 kN
Muy = 1.88 kNm
Vuy = 2.5027 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -43.74 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 104 of 198

φVcy = 124.11 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 385.79 kN
Mux = 5.18 kNm
Vux = -7.2822 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -40.44 kNm
φVcx = 124.11 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C8

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 105 of 198

Level : 0m To 0.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 65
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 448.01 kN
Muxt = -4.24 kNm
Muyt = 11.99 kNm
Vuxt = 8.5 kN
Vuyt = 2.92 kN
Pub = 450.09 kN
Muxb = -2.2 kNm
Muyb = 6.04 kNm
Vuxb = 8.5 kN
Vuyb = 2.92 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 106 of 198

Column Is Braced Along D


Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 3.46
M1 = -2.2 kNm
M2 = -4.24 kNm
34 - 12 x (M1/M2) = 27.78
3.46 < 27.78, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 3.46
M1 = 6.04 kNm
M2 = 11.99 kNm
34 - 12 x (M1/M2) = 27.95
3.46 < 27.95, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -4.24 - -4.24
Major Axis Mux (bottom) -2.2 - -2.2
Minor Axis Muy (top) 11.99 - 11.99
Minor Axis Muy (bottom) 6.04 - 6.04

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 448.01 kN
Mux = -4.24 kNm
Muy = 11.99 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 107 of 198

Load Angle = Tan-1(Muy/Mux)


= 70.52 deg
MRes = 12.72 kNm
( φ ) MCap = 66.02 kNm
Capacity Ratio = MRes/ MCap
= 0.193 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 384.01 kN
Muy = 3.63 kNm
Vuy = 2.5027 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -41.77 kNm
φVcy = 123.95 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 384.01 kN
Mux = 10.28 kNm
Vux = 7.2822 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -35.13 kNm
φVcx = 123.95 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 108 of 198

> Max. longitudinal bar dia / 4


= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C8
Level : 0.7m To 4.65m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 3450 mm
Clear Floor Height @ luy = 3450 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 107
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Top Joint
Put = 343.25 kN
Muxt = -4.37 kNm
Muyt = 9.08 kNm
Vuxt = 4.44 kN
Vuyt = 2.06 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 109 of 198

Pub = 353.3 kN
Muxb = 3.75 kNm
Muyb = -8.46 kNm
Vuxb = 4.44 kN
Vuyb = 2.06 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 39.84
M1 = 3.75 kNm
M2 = -4.37 kNm
34 - 12 x (M1/M2) = 44.29
39.84 < 44.29, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 39.84
M1 = -8.46 kNm
M2 = 9.08 kNm
34 - 12 x (M1/M2) = 45.19
39.84 < 45.19, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -4.37 - -4.37

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 110 of 198

Major Axis Mux (bottom) 3.75 - 3.75


Minor Axis Muy (top) 9.08 - 9.08
Minor Axis Muy (bottom) -8.46 - -8.46

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 343.25 kN
Mux = -4.37 kNm
Muy = 9.08 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 64.29 deg
MRes = 10.08 kNm
( φ ) MCap = 64.69 kNm
Capacity Ratio = MRes/ MCap
= 0.156 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 224.91 kN
Muy = 2.38 kNm
Vuy = 1.3023 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -24.22 kNm
φVcy = 108.83 kN
Vuy < φVcy
Link For Shear Design Along D are not required

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 111 of 198

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 224.91 kN
Mux = 3.16 kNm
Vux = 2.208 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -23.44 kNm
φVcx = 108.83 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C8
Level : 4.65m To 7.51m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 112 of 198

Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 2360 mm
Clear Floor Height @ luy = 2460 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 149
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Bottom Joint
Put = 28.47 kN
Muxt = -4.52 kNm
Muyt = 7.1 kNm
Vuxt = 5.88 kN
Vuyt = 3.67 kN
Pub = 35.75 kN
Muxb = 5.98 kNm
Muyb = -9.71 kNm
Vuxb = 5.88 kN
Vuyb = 3.67 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 113 of 198

Kluy /r = 28.41
M1 = -4.52 kNm
M2 = 5.98 kNm
34 - 12 x (M1/M2) = 43.07
28.41 < 43.07, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 27.25
M1 = 7.1 kNm
M2 = -9.71 kNm
34 - 12 x (M1/M2) = 42.77
27.25 < 42.77, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -4.52 - -4.52
Major Axis Mux (bottom) 5.98 - 5.98
Minor Axis Muy (top) 7.1 - 7.1
Minor Axis Muy (bottom) -9.71 - -9.71

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 35.75 kN
Mux = 5.98 kNm
Muy = -9.71 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 58.37 deg
MRes = 11.41 kNm
( φ ) MCap = 53.13 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 114 of 198

Capacity Ratio = MRes/ MCap


= 0.215 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 35.75 kN
Muy = 5.98 kNm
Vuy = 3.6742 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 1.76 kNm
φVcy = 56.62 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 35.75 kN
Mux = 9.71 kNm
Vux = 5.8796 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 5.49 kNm
φVcx = 51.3 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 115 of 198

Min. Longitudinal Bar dia X 16 = 256 mm


48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C9
Level : -1.5m To 0m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 46
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 343.94 kN
Muxt = 2.89 kNm
Muyt = 5.4 kNm
Vuxt = -7.26 kN
Vuyt = 3.78 kN
Pub = 348.39 kN
Muxb = -2.78 kNm
Muyb = -5.48 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 116 of 198

Vuxb = -7.26 kN
Vuyb = 3.78 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 17.32
M1 = -2.78 kNm
M2 = 2.89 kNm
34 - 12 x (M1/M2) = 45.55
17.32 < 45.55, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 17.32
M1 = 5.4 kNm
M2 = -5.48 kNm
34 - 12 x (M1/M2) = 45.83
17.32 < 45.83, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 2.89 - 2.89
Major Axis Mux (bottom) -2.78 - -2.78
Minor Axis Muy (top) 5.4 - 5.4
Minor Axis Muy (bottom) -5.48 - -5.48

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 117 of 198

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 343.94 kN
Mux = 2.89 kNm
Muy = 5.4 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 61.9 deg
MRes = 6.12 kNm
( φ ) MCap = 63.59 kNm
Capacity Ratio = MRes/ MCap
= 0.096 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 294.8 kN
Muy = 2.47 kNm
Vuy = 3.2359 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -32.39 kNm
φVcy = 115.72 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 294.8 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 118 of 198

Mux = 4.63 kNm


Vux = -6.2205 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -30.23 kNm
φVcx = 115.72 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C9
Level : 0m To 0.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 300 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 119 of 198

Clear Floor Height @ luy = 300 mm


No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 64
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 341.86 kN
Muxt = -5.53 kNm
Muyt = 10.48 kNm
Vuxt = 7.26 kN
Vuyt = 3.78 kN
Pub = 343.94 kN
Muxb = -2.89 kNm
Muyb = 5.4 kNm
Vuxb = 7.26 kN
Vuyb = 3.78 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 3.46
M1 = -2.89 kNm
M2 = -5.53 kNm
34 - 12 x (M1/M2) = 27.74
3.46 < 27.74, Column not slender along D

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 120 of 198

Column Is Braced Along B


Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 3.46
M1 = 5.4 kNm
M2 = 10.48 kNm
34 - 12 x (M1/M2) = 27.81
3.46 < 27.81, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -5.53 - -5.53
Major Axis Mux (bottom) -2.89 - -2.89
Minor Axis Muy (top) 10.48 - 10.48
Minor Axis Muy (bottom) 5.4 - 5.4

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 341.86 kN
Mux = -5.53 kNm
Muy = 10.48 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 62.2 deg
MRes = 11.85 kNm
( φ ) MCap = 63.74 kNm
Capacity Ratio = MRes/ MCap
= 0.186 < 1

Design Of Shear

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 121 of 198

Design for shear along D


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 293.02 kN
Muy = 4.74 kNm
Vuy = 3.2359 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -29.91 kNm
φVcy = 115.55 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 293.02 kN
Mux = 8.98 kNm
Vux = 6.2205 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -25.67 kNm
φVcx = 115.55 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 122 of 198

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C9
Level : 0.7m To 4.65m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 3450 mm
Clear Floor Height @ luy = 3450 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 106
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Top Joint
Put = 226.51 kN
Muxt = -6.01 kNm
Muyt = 9.92 kNm
Vuxt = 4.72 kN
Vuyt = 2.8 kN
Pub = 236.57 kN
Muxb = 5.04 kNm
Muyb = -8.7 kNm
Vuxb = 4.72 kN
Vuyb = 2.8 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 123 of 198

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 39.84
M1 = 5.04 kNm
M2 = -6.01 kNm
34 - 12 x (M1/M2) = 44.06
39.84 < 44.06, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 39.84
M1 = -8.7 kNm
M2 = 9.92 kNm
34 - 12 x (M1/M2) = 44.52
39.84 < 44.52, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -6.01 - -6.01
Major Axis Mux (bottom) 5.04 - 5.04
Minor Axis Muy (top) 9.92 - 9.92
Minor Axis Muy (bottom) -8.7 - -8.7

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 124 of 198

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 226.51 kN
Mux = -6.01 kNm
Muy = 9.92 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 58.8 deg
MRes = 11.6 kNm
( φ ) MCap = 60.91 kNm
Capacity Ratio = MRes/ MCap
= 0.19 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 178.73 kN
Muy = 3.83 kNm
Vuy = 1.9803 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -17.3 kNm
φVcy = 104.03 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 178.73 kN
Mux = 6.62 kNm
Vux = 3.4441 kN
λ = 1
φ = 0.75
deff = 254 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 125 of 198

ρw (50% of As provided) = 0.021


Mm = -14.51 kNm
φVcx = 104.03 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C9
Level : 4.65m To 7.51m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 2360 mm
Clear Floor Height @ luy = 2460 mm
No Of Floors = 1
No Of Columns In Group = 1

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 126 of 198

Load Data
Analysis Reference No. = 148
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Bottom Joint
Put = 32 kN
Muxt = -5.51 kNm
Muyt = 8.03 kNm
Vuxt = 6.83 kN
Vuyt = 4.65 kN
Pub = 39.28 kN
Muxb = 7.79 kNm
Muyb = -11.51 kNm
Vuxb = 6.83 kN
Vuyb = 4.65 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 28.41
M1 = -5.51 kNm
M2 = 7.79 kNm
34 - 12 x (M1/M2) = 42.49
28.41 < 42.49, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 27.25

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 127 of 198

M1 = 8.03 kNm
M2 = -11.51 kNm
34 - 12 x (M1/M2) = 42.37
27.25 < 42.37, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -5.51 - -5.51
Major Axis Mux (bottom) 7.79 - 7.79
Minor Axis Muy (top) 8.03 - 8.03
Minor Axis Muy (bottom) -11.51 - -11.51

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 39.28 kN
Mux = 7.79 kNm
Muy = -11.51 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 55.92 deg
MRes = 13.89 kNm
( φ ) MCap = 53.14 kNm
Capacity Ratio = MRes/ MCap
= 0.261 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 39.28 kN
Muy = 7.79 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 128 of 198

Vuy = 4.6496 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 3.14 kNm
φVcy = 53.43 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 39.28 kN
Mux = 11.51 kNm
Vux = 6.8317 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 6.86 kNm
φVcx = 50.91 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 129 of 198

Spacing 250 --- --- 250 ---

General Data
Column No. : C10
Level : -1.5m To 0m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 60
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Bottom Joint
Put = 221.45 kN
Muxt = 0.56 kNm
Muyt = 1.44 kNm
Vuxt = -2.28 kN
Vuyt = 0.55 kN
Pub = 225.91 kN
Muxb = -0.26 kNm
Muyb = -1.98 kNm
Vuxb = -2.28 kN
Vuyb = 0.55 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 130 of 198

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 17.32
M1 = -0.26 kNm
M2 = 0.56 kNm
34 - 12 x (M1/M2) = 39.68
17.32 < 39.68, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 17.32
M1 = 1.44 kNm
M2 = -1.98 kNm
34 - 12 x (M1/M2) = 42.72
17.32 < 42.72, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 0.56 - 0.56
Major Axis Mux (bottom) -0.26 - -0.26
Minor Axis Muy (top) 1.44 - 1.44
Minor Axis Muy (bottom) -1.98 - -1.98

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 225.91 kN
Mux = -0.26 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 131 of 198

Muy = -1.98 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 82.39 deg
MRes = 2 kNm
( φ ) MCap = 69.31 kNm
Capacity Ratio = MRes/ MCap
= 0.029 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 189.82 kN
Muy = 0.48 kNm
Vuy = 0.4699 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -21.97 kNm
φVcy = 105.2 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 189.82 kN
Mux = 1.23 kNm
Vux = -1.9521 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -21.21 kNm
φVcx = 105.2 kN
Vux < φVcx

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 132 of 198

Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C10
Level : 0m To 0.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 700 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 78
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 133 of 198

Critical Location = Top Joint


Put = 219.37 kN
Muxt = -0.94 kNm
Muyt = 3.03 kNm
Vuxt = 2.28 kN
Vuyt = 0.55 kN
Pub = 221.45 kN
Muxb = -0.56 kNm
Muyb = 1.44 kNm
Vuxb = 2.28 kN
Vuyb = 0.55 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 8.08
M1 = -0.56 kNm
M2 = -0.94 kNm
34 - 12 x (M1/M2) = 26.89
8.08 < 26.89, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 3.46
M1 = 1.44 kNm
M2 = 3.03 kNm
34 - 12 x (M1/M2) = 28.31
3.46 < 28.31, Column not slender along B

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 134 of 198

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -0.94 - -0.94
Major Axis Mux (bottom) -0.56 - -0.56
Minor Axis Muy (top) 3.03 - 3.03
Minor Axis Muy (bottom) 1.44 - 1.44

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 219.37 kN
Mux = -0.94 kNm
Muy = 3.03 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 72.74 deg
MRes = 3.17 kNm
( φ ) MCap = 64.95 kNm
Capacity Ratio = MRes/ MCap
= 0.049 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 188.03 kN
Muy = 0.81 kNm
Vuy = 0.4699 kN
λ = 1
φ = 0.75
deff = 254 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 135 of 198

ρw (50% of As provided) = 0.021


Mm = -21.43 kNm
φVcy = 105.01 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 188.03 kN
Mux = 2.6 kNm
Vux = 1.9521 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -19.64 kNm
φVcx = 105.01 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 136 of 198

General Data
Column No. : C10
Level : 0.7m To 4.65m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 3450 mm
Clear Floor Height @ luy = 3950 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 120
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 137.1 kN
Muxt = -1.37 kNm
Muyt = 3.92 kNm
Vuxt = 1.97 kN
Vuyt = 0.66 kN
Pub = 148.83 kN
Muxb = 1.25 kNm
Muyb = -3.85 kNm
Vuxb = 1.97 kN
Vuyb = 0.66 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 137 of 198

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 45.61
M1 = 1.25 kNm
M2 = -1.37 kNm
34 - 12 x (M1/M2) = 45
45.61 > 45,Column slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 39.84
M1 = -3.85 kNm
M2 = 3.92 kNm
34 - 12 x (M1/M2) = 45.79
39.84 < 45.79, Column not slender along B
Moment Magnification:
For Non-sway frame:
Along D
βdns = 0.6
Ec = 23500 N/sqmm
9 = 0.675 mm^4
Ig ( x 10 )
6 = 4579107.188 >N-sqmm
EI ( x 10 )
M2min = 3.57 kNm
Cm = 1
Pc = 2896.59 kN
δns = 1.07
Mc1 = 3.83 kN
Mc2 = -3.83 kN

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -1.37 -3.83 -3.83
Major Axis Mux (bottom) 1.25 3.83 3.83
Minor Axis Muy (top) 3.92 - 3.92
Minor Axis Muy (bottom) -3.85 - -3.85

Where
A = Moments from analysis

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 138 of 198

B = Moment due to slenderness effect


C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 137.1 kN
Mux = -3.83 kNm
Muy = 3.92 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 45.62 deg
MRes = 5.48 kNm
( φ ) MCap = 57.51 kNm
Capacity Ratio = MRes/ MCap
= 0.095 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 117.51 kN
Muy = 1.17 kNm
Vuy = 0.5686 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -12.72 kNm
φVcy = 97.3 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 117.51 kN
Mux = 3.36 kNm
Vux = 1.6857 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 139 of 198

λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -10.54 kNm
φVcx = 97.3 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C10
Level : 4.65m To 7.51m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 2360 mm
Clear Floor Height @ luy = 2860 mm
No Of Floors = 1

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 140 of 198

No Of Columns In Group = 1

Load Data
Analysis Reference No. = 162
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Bottom Joint
Put = 29.67 kN
Muxt = -0.32 kNm
Muyt = 0.66 kNm
Vuxt = 0.7 kN
Vuyt = 0.27 kN
Pub = 38.16 kN
Muxb = 0.46 kNm
Muyb = -1.33 kNm
Vuxb = 0.7 kN
Vuyb = 0.27 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 33.02
M1 = -0.32 kNm
M2 = 0.46 kNm
34 - 12 x (M1/M2) = 42.3
33.02 < 42.3, Column not slender along D
Column Is Braced Along B
Slenderness Check along B

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 141 of 198

K = 1
r = 86.6 mm
Klux /r = 27.25
M1 = 0.66 kNm
M2 = -1.33 kNm
34 - 12 x (M1/M2) = 39.91
27.25 < 39.91, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -0.32 - -0.32
Major Axis Mux (bottom) 0.46 - 0.46
Minor Axis Muy (top) 0.66 - 0.66
Minor Axis Muy (bottom) -1.33 - -1.33

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 38.16 kN
Mux = 0.46 kNm
Muy = -1.33 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 71.05 deg
MRes = 1.41 kNm
( φ ) MCap = 52.72 kNm
Capacity Ratio = MRes/ MCap
= 0.027 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 142 of 198

Critical Load Combination = LL) kN


Nu = 24.44 kN
Muy = 0.18 kNm
Vuy = -0.1742 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -2.71 kNm
φVcy = 86.07 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 25.43 kN
Mux = 0.56 kNm
Vux = 0.5965 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -2.44 kNm
φVcx = 86.2 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 143 of 198

Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C11
Level : -1.5m To 0m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 61
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 211.11 kN
Muxt = 4.05 kNm
Muyt = -0.54 kNm
Vuxt = -0.08 kN
Vuyt = 4.71 kN
Pub = 215.57 kN
Muxb = -3.02 kNm
Muyb = -0.66 kNm
Vuxb = -0.08 kN
Vuyb = 4.71 kN

Check For Stability Index


Along D

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 144 of 198

       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 17.32
M1 = -3.02 kNm
M2 = 4.05 kNm
34 - 12 x (M1/M2) = 42.93
17.32 < 42.93, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 17.32
M1 = -0.54 kNm
M2 = -0.66 kNm
34 - 12 x (M1/M2) = 24.26
17.32 < 24.26, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 4.05 - 4.05
Major Axis Mux (bottom) -3.02 - -3.02
Minor Axis Muy (top) -0.54 - -0.54
Minor Axis Muy (bottom) -0.66 - -0.66

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 145 of 198

Critical Case - Axial Load & BiAxial Bending


Pu = 211.11 kN
Mux = 4.05 kNm
Muy = -0.54 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 7.57 deg
MRes = 4.09 kNm
( φ ) MCap = 68.16 kNm
Capacity Ratio = MRes/ MCap
= 0.06 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 180.96 kN
Muy = 3.47 kNm
Vuy = 4.0397 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -17.92 kNm
φVcy = 104.26 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 180.96 kN
Mux = 0.46 kNm
Vux = -0.0715 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 146 of 198

Mm = -20.94 kNm
φVcx = 104.26 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C11
Level : 0m To 0.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 700 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 147 of 198

Analysis Reference No. = 79


Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 209.04 kN
Muxt = -7.35 kNm
Muyt = -0.48 kNm
Vuxt = 0.08 kN
Vuyt = 4.71 kN
Pub = 211.11 kN
Muxb = -4.05 kNm
Muyb = -0.54 kNm
Vuxb = 0.08 kN
Vuyb = 4.71 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 3.46
M1 = -4.05 kNm
M2 = -7.35 kNm
34 - 12 x (M1/M2) = 27.38
3.46 < 27.38, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 8.08
M1 = -0.48 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 148 of 198

M2 = -0.54 kNm
34 - 12 x (M1/M2) = 23.3
8.08 < 23.3, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -7.35 - -7.35
Major Axis Mux (bottom) -4.05 - -4.05
Minor Axis Muy (top) -0.48 - -0.48
Minor Axis Muy (bottom) -0.54 - -0.54

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 209.04 kN
Mux = -7.35 kNm
Muy = -0.48 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 3.73 deg
MRes = 7.37 kNm
( φ ) MCap = 68.41 kNm
Capacity Ratio = MRes/ MCap
= 0.108 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 179.17 kN
Muy = 6.3 kNm
Vuy = 4.0397 kN
λ = 1

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 149 of 198

φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -14.89 kNm
φVcy = 104.07 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 179.17 kN
Mux = 0.41 kNm
Vux = 0.0715 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -20.78 kNm
φVcx = 104.07 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 150 of 198

General Data
Column No. : C11
Level : 0.7m To 4.65m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 3950 mm
Clear Floor Height @ luy = 3450 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 121
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Bottom Joint
Put = 129.85 kN
Muxt = -5.96 kNm
Muyt = 0.98 kNm
Vuxt = 0.33 kN
Vuyt = 3.15 kN
Pub = 141.58 kN
Muxb = 6.47 kNm
Muyb = -0.34 kNm
Vuxb = 0.33 kN
Vuyb = 3.15 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 151 of 198

0.01< 0.05, Column shall be designed as non-sway frame


(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 39.84
M1 = -5.96 kNm
M2 = 6.47 kNm
34 - 12 x (M1/M2) = 45.06
39.84 < 45.06, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 45.61
M1 = -0.34 kNm
M2 = 0.98 kNm
34 - 12 x (M1/M2) = 38.22
45.61 > 38.22, Column slender along B
Moment Magnification:
For Non-sway frame:
Along B
βdns = 0.6
Ec = 23500 N/sqmm
9 = 0.675 mm^4
Ig ( x 10 )
EI ( x 10 6) = 4579107.188 N-sqmm
M2min = 3.4 kNm
Cm = 1
Pc = 2896.59 kN
δns = 1.07
Mc1 = -3.63 kN
Mc2 = 3.63 kN

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -5.96 - -5.96
Major Axis Mux (bottom) 6.47 - 6.47
Minor Axis Muy (top) 0.98 3.63 3.63
Minor Axis Muy (bottom) -0.34 -3.63 -3.63

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 152 of 198

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 141.58 kN
Mux = 6.47 kNm
Muy = -3.63 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 29.34 deg
MRes = 7.42 kNm
( φ ) MCap = 58.38 kNm
Capacity Ratio = MRes/ MCap
= 0.127 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 111.3 kN
Muy = 5.11 kNm
Vuy = 2.697 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -8.05 kNm
φVcy = 96.59 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 111.3 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 153 of 198

Mux = 0.84 kNm


Vux = 0.2866 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -12.32 kNm
φVcx = 96.59 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C11
Level : 4.65m To 7.51m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 2860 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 154 of 198

Clear Floor Height @ luy = 2460 mm


No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 163
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Bottom Joint
Put = 22.7 kN
Muxt = -2.31 kNm
Muyt = -0.3 kNm
Vuxt = -0.14 kN
Vuyt = 2.26 kN
Pub = 31.19 kN
Muxb = 4.16 kNm
Muyb = 0.09 kNm
Vuxb = -0.14 kN
Vuyb = 2.26 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 28.41
M1 = -2.31 kNm
M2 = 4.16 kNm
34 - 12 x (M1/M2) = 40.66
28.41 < 40.66, Column not slender along D

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 155 of 198

Column Is Braced Along B


Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 33.02
M1 = 0.09 kNm
M2 = -0.3 kNm
34 - 12 x (M1/M2) = 37.51
33.02 < 37.51, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -2.31 - -2.31
Major Axis Mux (bottom) 4.16 - 4.16
Minor Axis Muy (top) -0.3 - -0.3
Minor Axis Muy (bottom) 0.09 - 0.09

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 31.19 kN
Mux = 4.16 kNm
Muy = 0.09 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 1.22 deg
MRes = 4.16 kNm
( φ ) MCap = 50.64 kNm
Capacity Ratio = MRes/ MCap
= 0.082 < 1

Design Of Shear

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 156 of 198

Design for shear along D


Critical Analysis Load Combination : 3
Critical Load Combination = [1] : 1.4 (LOAD 1: DL) kN
Nu = 31.19 kN
Muy = 4.16 kNm
Vuy = 2.2613 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 0.47 kNm
φVcy = 70.81 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 21.21 kN
Mux = 0.31 kNm
Vux = -0.7761 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -2.19 kNm
φVcx = 85.65 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 157 of 198

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C12
Level : -1.5m To 0m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 51
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 283.13 kN
Muxt = -4.04 kNm
Muyt = -10.83 kNm
Vuxt = 12.65 kN
Vuyt = -5.58 kN
Pub = 287.58 kN
Muxb = 4.33 kNm
Muyb = 8.15 kNm
Vuxb = 12.65 kN
Vuyb = -5.58 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 158 of 198

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 17.32
M1 = -4.04 kNm
M2 = 4.33 kNm
34 - 12 x (M1/M2) = 45.22
17.32 < 45.22, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 17.32
M1 = 8.15 kNm
M2 = -10.83 kNm
34 - 12 x (M1/M2) = 43.03
17.32 < 43.03, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -4.04 - -4.04
Major Axis Mux (bottom) 4.33 - 4.33
Minor Axis Muy (top) -10.83 - -10.83
Minor Axis Muy (bottom) 8.15 - 8.15

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 159 of 198

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 283.13 kN
Mux = -4.04 kNm
Muy = -10.83 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 69.52 deg
MRes = 11.56 kNm
( φ ) MCap = 65.85 kNm
Capacity Ratio = MRes/ MCap
= 0.176 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 242.68 kN
Muy = 3.47 kNm
Vuy = -4.7836 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -25.23 kNm
φVcy = 110.62 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 242.68 kN
Mux = 9.28 kNm
Vux = 10.8457 kN
λ = 1
φ = 0.75
deff = 254 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 160 of 198

ρw (50% of As provided) = 0.021


Mm = -19.42 kNm
φVcx = 110.62 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C12
Level : 0m To 0.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 161 of 198

Load Data
Analysis Reference No. = 69
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 281.05 kN
Muxt = 7.95 kNm
Muyt = -19.68 kNm
Vuxt = -12.65 kN
Vuyt = -5.58 kN
Pub = 283.13 kN
Muxb = 4.04 kNm
Muyb = -10.83 kNm
Vuxb = -12.65 kN
Vuyb = -5.58 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 3.46
M1 = 4.04 kNm
M2 = 7.95 kNm
34 - 12 x (M1/M2) = 27.9
3.46 < 27.9, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 3.46

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 162 of 198

M1 = -10.83 kNm
M2 = -19.68 kNm
34 - 12 x (M1/M2) = 27.4
3.46 < 27.4, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 7.95 - 7.95
Major Axis Mux (bottom) 4.04 - 4.04
Minor Axis Muy (top) -19.68 - -19.68
Minor Axis Muy (bottom) -10.83 - -10.83

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 281.05 kN
Mux = 7.95 kNm
Muy = -19.68 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 68.01 deg
MRes = 21.23 kNm
( φ ) MCap = 65.19 kNm
Capacity Ratio = MRes/ MCap
= 0.326 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 240.9 kN
Muy = 6.81 kNm
Vuy = -4.7836 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 163 of 198

λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -21.67 kNm
φVcy = 110.44 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 240.9 kN
Mux = 16.87 kNm
Vux = -10.8457 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -11.61 kNm
φVcx = 110.44 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 164 of 198

General Data
Column No. : C12
Level : 0.7m To 4.65m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 3450 mm
Clear Floor Height @ luy = 3450 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 111
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Top Joint
Put = 193.27 kN
Muxt = 6.49 kNm
Muyt = -14.75 kNm
Vuxt = -7.23 kN
Vuyt = -3.12 kN
Pub = 203.33 kN
Muxb = -5.82 kNm
Muyb = 13.8 kNm
Vuxb = -7.23 kN
Vuyb = -3.12 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 165 of 198

       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 39.84
M1 = -5.82 kNm
M2 = 6.49 kNm
34 - 12 x (M1/M2) = 44.76
39.84 < 44.76, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 39.84
M1 = 13.8 kNm
M2 = -14.75 kNm
34 - 12 x (M1/M2) = 45.23
39.84 < 45.23, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 6.49 - 6.49
Major Axis Mux (bottom) -5.82 - -5.82
Minor Axis Muy (top) -14.75 - -14.75
Minor Axis Muy (bottom) 13.8 - 13.8

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 193.27 kN
Mux = 6.49 kNm
Muy = -14.75 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 166 of 198

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 66.24 deg
MRes = 16.12 kNm
( φ ) MCap = 62.11 kNm
Capacity Ratio = MRes/ MCap
= 0.26 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 132.27 kN
Muy = 4.85 kNm
Vuy = -2.5081 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -10.79 kNm
φVcy = 98.96 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 132.27 kN
Mux = 5.87 kNm
Vux = -4.1974 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -9.78 kNm
φVcx = 98.96 kN
Vux < φVcx
Link For Shear Design Along B are not required

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 167 of 198

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C12
Level : 4.65m To 7.51m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 2360 mm
Clear Floor Height @ luy = 2460 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 153
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Bottom Joint
Put = 29.46 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 168 of 198

Muxt = 7 kNm
Muyt = -10.04 kNm
Vuxt = -9.05 kN
Vuyt = -5.6 kN
Pub = 36.74 kN
Muxb = -9.02 kNm
Muyb = 15.83 kNm
Vuxb = -9.05 kN
Vuyb = -5.6 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 28.41
M1 = 7 kNm
M2 = -9.02 kNm
34 - 12 x (M1/M2) = 43.31
28.41 < 43.31, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 27.25
M1 = -10.04 kNm
M2 = 15.83 kNm
34 - 12 x (M1/M2) = 41.61
27.25 < 41.61, Column not slender along B

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 169 of 198

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 7 - 7
Major Axis Mux (bottom) -9.02 - -9.02
Minor Axis Muy (top) -10.04 - -10.04
Minor Axis Muy (bottom) 15.83 - 15.83

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 36.74 kN
Mux = -9.02 kNm
Muy = 15.83 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 60.34 deg
MRes = 18.22 kNm
( φ ) MCap = 53.28 kNm
Capacity Ratio = MRes/ MCap
= 0.342 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 36.74 kN
Muy = 9.02 kNm
Vuy = -5.6009 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 4.67 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 170 of 198

φVcy = 51.96 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 36.74 kN
Mux = 15.83 kNm
Vux = -9.0489 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 11.49 kNm
φVcx = 49.82 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C13

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 171 of 198

Level : -1.5m To 0m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 50
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 337.5 kN
Muxt = 1.75 kNm
Muyt = -11.05 kNm
Vuxt = 13.1 kN
Vuyt = 1.78 kN
Pub = 341.95 kN
Muxb = -0.91 kNm
Muyb = 8.58 kNm
Vuxb = 13.1 kN
Vuyb = 1.78 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 172 of 198

Column Is Braced Along D


Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 17.32
M1 = -0.91 kNm
M2 = 1.75 kNm
34 - 12 x (M1/M2) = 40.24
17.32 < 40.24, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 17.32
M1 = 8.58 kNm
M2 = -11.05 kNm
34 - 12 x (M1/M2) = 43.32
17.32 < 43.32, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 1.75 - 1.75
Major Axis Mux (bottom) -0.91 - -0.91
Minor Axis Muy (top) -11.05 - -11.05
Minor Axis Muy (bottom) 8.58 - 8.58

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 337.5 kN
Mux = 1.75 kNm
Muy = -11.05 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 173 of 198

Load Angle = Tan-1(Muy/Mux)


= 80.99 deg
MRes = 11.19 kNm
( φ ) MCap = 72.79 kNm
Capacity Ratio = MRes/ MCap
= 0.154 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 289.28 kN
Muy = 1.5 kNm
Vuy = 1.5229 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -32.7 kNm
φVcy = 115.19 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 289.28 kN
Mux = 9.47 kNm
Vux = 11.2243 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -24.73 kNm
φVcx = 115.19 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 174 of 198

> Max. longitudinal bar dia / 4


= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C13
Level : 0m To 0.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 68
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 335.42 kN
Muxt = -3 kNm
Muyt = -20.22 kNm
Vuxt = -13.1 kN
Vuyt = 1.78 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 175 of 198

Pub = 337.5 kN
Muxb = -1.75 kNm
Muyb = -11.05 kNm
Vuxb = -13.1 kN
Vuyb = 1.78 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 3.46
M1 = -1.75 kNm
M2 = -3 kNm
34 - 12 x (M1/M2) = 26.98
3.46 < 26.98, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 3.46
M1 = -11.05 kNm
M2 = -20.22 kNm
34 - 12 x (M1/M2) = 27.44
3.46 < 27.44, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -3 - -3

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 176 of 198

Major Axis Mux (bottom) -1.75 - -1.75


Minor Axis Muy (top) -20.22 - -20.22
Minor Axis Muy (bottom) -11.05 - -11.05

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 335.42 kN
Mux = -3 kNm
Muy = -20.22 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 81.57 deg
MRes = 20.44 kNm
( φ ) MCap = 73.17 kNm
Capacity Ratio = MRes/ MCap
= 0.279 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 287.5 kN
Muy = 2.57 kNm
Vuy = 1.5229 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -31.43 kNm
φVcy = 115.02 kN
Vuy < φVcy
Link For Shear Design Along D are not required

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 177 of 198

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 287.5 kN
Mux = 17.33 kNm
Vux = -11.2243 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -16.67 kNm
φVcx = 115.02 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C13
Level : 0.7m To 4.65m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 178 of 198

Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 3450 mm
Clear Floor Height @ luy = 3450 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 110
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Top Joint
Put = 230.33 kN
Muxt = -3.58 kNm
Muyt = -16.48 kNm
Vuxt = -7.95 kN
Vuyt = 1.72 kN
Pub = 240.39 kN
Muxb = 3.21 kNm
Muyb = 14.92 kNm
Vuxb = -7.95 kN
Vuyb = 1.72 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 179 of 198

Kluy /r = 39.84
M1 = 3.21 kNm
M2 = -3.58 kNm
34 - 12 x (M1/M2) = 44.78
39.84 < 44.78, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 39.84
M1 = 14.92 kNm
M2 = -16.48 kNm
34 - 12 x (M1/M2) = 44.87
39.84 < 44.87, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -3.58 - -3.58
Major Axis Mux (bottom) 3.21 - 3.21
Minor Axis Muy (top) -16.48 - -16.48
Minor Axis Muy (bottom) 14.92 - 14.92

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 230.33 kN
Mux = -3.58 kNm
Muy = -16.48 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 77.75 deg
MRes = 16.86 kNm
( φ ) MCap = 67.73 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 180 of 198

Capacity Ratio = MRes/ MCap


= 0.249 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 164.77 kN
Muy = 2.25 kNm
Vuy = 1.2084 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -17.24 kNm
φVcy = 102.53 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 164.77 kN
Mux = 7.51 kNm
Vux = -4.9012 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -11.97 kNm
φVcx = 102.53 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 181 of 198

Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C13
Level : 4.65m To 7.51m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 2360 mm
Clear Floor Height @ luy = 2460 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 152
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Bottom Joint
Put = 34.51 kN
Muxt = -2.25 kNm
Muyt = -11.48 kNm
Vuxt = -10.47 kN
Vuyt = 1.89 kN
Pub = 41.79 kN
Muxb = 3.15 kNm
Muyb = 18.45 kNm
Vuxb = -10.47 kN
Vuyb = 1.89 kN

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 182 of 198

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 28.41
M1 = -2.25 kNm
M2 = 3.15 kNm
34 - 12 x (M1/M2) = 42.58
28.41 < 42.58, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 27.25
M1 = -11.48 kNm
M2 = 18.45 kNm
34 - 12 x (M1/M2) = 41.47
27.25 < 41.47, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -2.25 - -2.25
Major Axis Mux (bottom) 3.15 - 3.15
Minor Axis Muy (top) -11.48 - -11.48
Minor Axis Muy (bottom) 18.45 - 18.45

Where
A = Moments from analysis
B = Moment due to slenderness effect

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 183 of 198

C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 41.79 kN
Mux = 3.15 kNm
Muy = 18.45 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 80.31 deg
MRes = 18.72 kNm
( φ ) MCap = 52.4 kNm
Capacity Ratio = MRes/ MCap
= 0.357 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 34.51 kN
Muy = 2.25 kNm
Vuy = 1.8897 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -1.83 kNm
φVcy = 87.35 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 41.79 kN
Mux = 18.45 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 184 of 198

Vux = -10.4677 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 13.51 kNm
φVcx = 49.76 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C14
Level : -1.5m To 0m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 1500 mm
Clear Floor Height @ luy = 1500 mm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 185 of 198

No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 49
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 232.63 kN
Muxt = 2.76 kNm
Muyt = -10.34 kNm
Vuxt = 12.67 kN
Vuyt = 3.05 kN
Pub = 237.09 kN
Muxb = -1.81 kNm
Muyb = 8.67 kNm
Vuxb = 12.67 kN
Vuyb = 3.05 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 17.32
M1 = -1.81 kNm
M2 = 2.76 kNm
34 - 12 x (M1/M2) = 41.86
17.32 < 41.86, Column not slender along D
Column Is Braced Along B

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 186 of 198

Slenderness Check along B


K = 1
r = 86.6 mm
Klux /r = 17.32
M1 = 8.67 kNm
M2 = -10.34 kNm
34 - 12 x (M1/M2) = 44.06
17.32 < 44.06, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 2.76 - 2.76
Major Axis Mux (bottom) -1.81 - -1.81
Minor Axis Muy (top) -10.34 - -10.34
Minor Axis Muy (bottom) 8.67 - 8.67

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 232.63 kN
Mux = 2.76 kNm
Muy = -10.34 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 75.03 deg
MRes = 10.7 kNm
( φ ) MCap = 66.61 kNm
Capacity Ratio = MRes/ MCap
= 0.161 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 187 of 198

Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN


Nu = 199.4 kN
Muy = 2.37 kNm
Vuy = 2.6154 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -21.21 kNm
φVcy = 106.2 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 199.4 kN
Mux = 8.86 kNm
Vux = 10.8633 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -14.72 kNm
φVcx = 106.2 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 188 of 198

Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C14
Level : 0m To 0.7m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 300 mm
Clear Floor Height @ luy = 300 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 67
Critical Analysis Load Combination : 3
Load Combination = [1] : 1.4 (LOAD 1: DL)
Critical Location = Top Joint
Put = 230.55 kN
Muxt = -4.9 kNm
Muyt = -19.21 kNm
Vuxt = -12.67 kN
Vuyt = 3.05 kN
Pub = 232.63 kN
Muxb = -2.76 kNm
Muyb = -10.34 kNm
Vuxb = -12.67 kN
Vuyb = 3.05 kN

Check For Stability Index


Along D

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 189 of 198

       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 3.46
M1 = -2.76 kNm
M2 = -4.9 kNm
34 - 12 x (M1/M2) = 27.23
3.46 < 27.23, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 3.46
M1 = -10.34 kNm
M2 = -19.21 kNm
34 - 12 x (M1/M2) = 27.54
3.46 < 27.54, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -4.9 - -4.9
Major Axis Mux (bottom) -2.76 - -2.76
Minor Axis Muy (top) -19.21 - -19.21
Minor Axis Muy (bottom) -10.34 - -10.34

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 190 of 198

Critical Case - Axial Load & BiAxial Bending


Pu = 230.55 kN
Mux = -4.9 kNm
Muy = -19.21 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 75.69 deg
MRes = 19.82 kNm
( φ ) MCap = 66.81 kNm
Capacity Ratio = MRes/ MCap
= 0.297 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 197.62 kN
Muy = 4.2 kNm
Vuy = 2.6154 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -19.17 kNm
φVcy = 106.02 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 197.62 kN
Mux = 16.46 kNm
Vux = -10.8633 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 191 of 198

Mm = -6.9 kNm
φVcx = 106.02 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

General Data
Column No. : C14
Level : 0.7m To 4.65m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 3450 mm
Clear Floor Height @ luy = 3450 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 192 of 198

Analysis Reference No. = 109


Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Top Joint
Put = 145.63 kN
Muxt = -4.63 kNm
Muyt = -17.76 kNm
Vuxt = -8.39 kN
Vuyt = 2.3 kN
Pub = 155.68 kN
Muxb = 4.46 kNm
Muyb = 15.37 kNm
Vuxb = -8.39 kN
Vuyb = 2.3 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 39.84
M1 = 4.46 kNm
M2 = -4.63 kNm
34 - 12 x (M1/M2) = 45.55
39.84 < 45.55, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 39.84
M1 = 15.37 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 193 of 198

M2 = -17.76 kNm
34 - 12 x (M1/M2) = 44.38
39.84 < 44.38, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -4.63 - -4.63
Major Axis Mux (bottom) 4.46 - 4.46
Minor Axis Muy (top) -17.76 - -17.76
Minor Axis Muy (bottom) 15.37 - 15.37

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 145.63 kN
Mux = -4.63 kNm
Muy = -17.76 kNm

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 75.38 deg
MRes = 18.35 kNm
( φ ) MCap = 61.94 kNm
Capacity Ratio = MRes/ MCap
= 0.296 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 119.02 kN
Muy = 3.47 kNm
Vuy = 1.8546 kN
λ = 1

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 194 of 198

φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -10.6 kNm
φVcy = 97.47 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 6
Critical Load Combination = [4] : 1.2 (LOAD 1: DL) kN
Nu = 119.02 kN
Mux = 13.24 kNm
Vux = -6.8867 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = -0.84 kNm
φVcx = 97.47 kN
Vux < φVcx
Link For Shear Design Along B are not required

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 195 of 198

General Data
Column No. : C14
Level : 4.65m To 7.51m
Design Code = ACI 318M - 2011
Grade Of Concrete (f'c) = C25 N/sqmm
Grade Of Steel (fy) = Fy275 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover, Cc = 38 mm
Clear Floor Height @ lux = 2360 mm
Clear Floor Height @ luy = 2460 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data
Analysis Reference No. = 151
Critical Analysis Load Combination : 4
Load Combination = [2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2: LL)
Critical Location = Bottom Joint
Put = 25.34 kN
Muxt = -3.66 kNm
Muyt = -12.31 kNm
Vuxt = -11.28 kN
Vuyt = 2.82 kN
Pub = 32.62 kN
Muxb = 4.41 kNm
Muyb = 19.95 kNm
Vuxb = -11.28 kN
Vuyb = 2.82 kN

Check For Stability Index


Along D
       Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)

Along B
       Q = 0.01

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 196 of 198

0.01< 0.05, Column shall be designed as non-sway frame


(Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 28.41
M1 = -3.66 kNm
M2 = 4.41 kNm
34 - 12 x (M1/M2) = 43.94
28.41 < 43.94, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 86.6 mm
Klux /r = 27.25
M1 = -12.31 kNm
M2 = 19.95 kNm
34 - 12 x (M1/M2) = 41.4
27.25 < 41.4, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -3.66 - -3.66
Major Axis Mux (bottom) 4.41 - 4.41
Minor Axis Muy (top) -12.31 - -12.31
Minor Axis Muy (bottom) 19.95 - 19.95

Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 32.62 kN
Mux = 4.41 kNm
Muy = 19.95 kNm

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 197 of 198

Resultant Moment (Combined Action)


Moment Capacity Check
Pt Calculated = 1.79
Reinforcement Provided = 8-#16
Load Angle = Tan-1(Muy/Mux)
= 77.52 deg
MRes = 20.44 kNm
( φ ) MCap = 51.75 kNm
Capacity Ratio = MRes/ MCap
= 0.395 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 25.34 kN
Muy = 3.66 kNm
Vuy = 2.8232 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 0.66 kNm
φVcy = 67.96 kN
Vuy < φVcy
Link For Shear Design Along D are not required

Design for shear along B


Critical Analysis Load Combination : 4
[2] : 1.2 (LOAD 1: DL) +1.6 (LOAD 2:
Critical Load Combination = kN
LL)
Nu = 32.62 kN
Mux = 19.95 kNm
Vux = -11.2833 kN
λ = 1
φ = 0.75
deff = 254 mm
ρw (50% of As provided) = 0.021
Mm = 16.1 kNm
φVcx = 49.37 kN
Vux < φVcx
Link For Shear Design Along B are not required

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023
Column Design: Design Calculations Page 198 of 198

Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 250 mm

Table For Links


Note: Ductile Design of Links is Applicable Only For Boundary Elements
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- --- 10 ---
Spacing 250 --- --- 250 ---

file:///C:/Users/63917/AppData/Local/Temp/tmp38E8.tmp 03/03/2023