InteliLite 4

MRS 16

Order code: IL4MRS16BAA, IL4MRS16BLA

Controller for single gen-set applications


Datasheet
Product description
Advanced single Gen-set controller for stand-by and Detailed history log with up to 350 records
prime-power applications Dual Mutual Standby application support
All-in-one intuitive & powerful PC tool for Remote display
configuration/monitoring/control, locally or remotely User setpoints and protections
Easy to install, configure and use 5 languages in the controller & Translator functionality
User Access Management
Key features
Cyber security improvement
Backlit symbols
Alternative configurations
8 binary outputs, 8 + 1 binary inputs, 4 analog inputs (U/I/R)
Multi-purpose schedulers
+5 V output reference for analog inputs
Modbus register mapping possibility
2 high-current E-Stop binary outputs
Load shedding, dummy load management
USB Host
User buttons
Inbuild RS485
Geofencing based on GPS position
2 slots for extension plug-in modules (Modbus, Internet,
Available also in low temperature version (Order code:
SMS, inputs/outputs)
IL4MRS16BLA)
Extension CAN modules
ECU support (Tier 4 Final, Stage V) Application overview
RTC with battery back-up (full calendar)
Power over USB for controller configuration
Zero power mode
True RMS measurement
In-built PLC, complemented with a PLC monitoring tool in
InteliConfig
Full remote communications support (AirGate 2.0, WSV)
Internet access using Ethernet / 4G, Modbus TCP/RTU,
SNMP v1/v2c
Active SMS and emails

| InteliLite 4 MRS 16 Datasheet | Related HW ver: 1.0 | Related SW ver: 1.0.0 | Date of issue: 4/29/2021
Dimensions, terminals and mounting

Note: The final depth of the controller depends on the selected plug-in module – it can vary between 41 mm
and 56 mm. Mind also the size of connectors and cables (e.g. in case of RS232 connector, add about 60 mm
more for standard RS232 connector and cable).

Note: The controller is to be mounted into panel doors as a standalone unit using provided holders. The
requested cutout size is 187 × 132 mm. Use the screw holders delivered with the controller to fix the controller
into the door.

InteliLite 4 MRS 16 Datasheet 2


Technical data

Power supply Current measurement


Power supply range 8-36 VDC Measurement inputs 3ph Gen current

Power consumption Measurement range 5A


3.5 W
(without modules) Max. allowed current 10 A
RTC battery Replaceable (3 V) Accuracy ±20 mA for 0-2 A; 1 % of value for 2-5 A
Fusing power 4 A w/o BOUT consumption Input impedance <0.1 Ω
E-Stop fusing 10 A
E-Stop
Max. Power Dissipation 9W
Dedicated terminal for safe E-Stop input.
Operating conditions Physical supply for binary outputs 1 & 2.

Protection degree (front Binary inputs


IP 65
panel)
Number 8
Operating temperature -20 ˚C to +70 ˚C
0-2 VDC close contact
Operating temperature Close/Open indication
-40 ˚C to +70 ˚C 6-36 VDC open contact
for Low Temp. version
Storage temperature -30 ˚C to +80 ˚C Binary outputs
95 % non-condensing Number 8
Operating humidity
(EN 60068-2-30) BO1,2 = 5 A; BO3-8 = 0.5 A
Max. current
5-25 Hz, ± 1.6 mm
Vibration Switching to positive supply terminal
25-100 Hz, a = 4 g

Shocks a = 500 m/s


2 Analog inputs
Surrounding air temperature rating 70 °C Number 4, switchable (R/U/I)
Suitable for pollution degree 2 Range R = 0-2500 Ω; U = 0-10 V; I = 0-20 mA

D+ R: ±2 % from value ±5 Ω in range 0-250 Ω


R: ±4 % from value in range 250 Ω-2500 Ω
Max. output current 250 mA Accuracy
U: 1 % from value ±100 mV
Charging fail threshold Adjustable
I: 1 % from value ±0.2 mA
Voltage measurement
+5 V Power supply output
Measurement inputs 3ph-n Gen voltage
Max. current 45 mA
10-277 V AC / 10-480 V AC (EU)
Measurement range 10-346 V AC / 10-600 V AC Magnetic pickup
(US/Canada) 4 Vpk-pk to 50 Vpk-pk in range 4 Hz to 1 kHz
Voltage input
Linear measurement 350 V AC Ph-N 6 Vpk-pk to 50 Vpk-pk in range 1 to 5 kHz
range
and protection range 660 V AC Ph-Ph 10 Vpk-pk to 50 Vpk-pk in range 5 to 10 kHz
Accuracy 1% Frequency input
4 Hz to 10 kHz
Frequency range 30-70 Hz (accuracy 0.1 Hz) range

Input impedance 0.72 MΩ ph-ph , 0.36 MΩ ph-n Frequency


measurement 0.2 % from measured value
Display tolerance
Type Build-in monochromatic 3.2"

Resolution 132 × 64 px

Communications
USB Device Non-isolated type B connector

USB Host Non-isolated type A connector

RS485 Isolated
Non-isolated, 250 / 50 kbps,
CAN 1
Terminator impedance 120 Ω

InteliLite 4 MRS 16 Datasheet 3


Available plug-in modules
Product Description Order code

CM-RS232-485 Dual port interface CM223248XBX


CM2-4G-GPS 4G & GPS plug-in communication module CM24GGPSXBX
CM3-Ethernet Internet / Ethernet plug-in communication module CM3ETHERXBX
EM-BIO8-EFCP 8 additional binary inputs/outputs EM2BIO8EXBX

Note: Controller has 2 slots for plug-in modules.

Available CAN modules


Product Description Order code

IGL-RA15 CAN remote annunciator with 15 LEDs EM2IGLRABAA


Inteli AIN8 CAN module with 8 analog inputs I-AIN8
Inteli IO8/8 CAN module with 8 binary inputs and 8 binary outputs I-IO8/8
IGS-PTM CAN module with 8 binary inputs, 8 binary outputs, 4 analog inputs and 1 analog output IGS-PTM
Inteli AIN8TC CAN module with 8 analog inputs dedicated for thermocouple sensors only. I-AIN8TC
Inteli AIO9/1 CAN module with analog inputs and outputs – designed for DC measurement. I-AIO9/1

Functions and protections


Support of functions and protections as defined by ANSI (American National Standards Institute):

Description ANSI code Description ANSI code


Voltage unbalance / Negative
Master unit 1 47
sequence voltage
Stopping device 5 Incomplete sequence relay 48
Multi-function device 11 Overcurrent 50/50TD
Overspeed 12 Earth fault** 50G
Underspeed 14 Breaker failure ANSI 50BF
Starting-to-running transition contactor 19 Overcurrent IDMT 51
Thermal relay 26 Overvoltage 59
Undervoltage 27 Aux Over Voltage 59X
Aux Battery Under Voltage 27X Pressure switch 63
Annunciator 30 Liquid level switch 71
Overload (real power) 32P Alarm relay*** 74
Reverse power 32R Reclosing relay 79
Master sequence device 34 Overfrequency 81O
Unit sequence starting* 44 Underfrequency 81U
Current unbalance 46

*Dual-operation **Extension module EM-BIO8-EFCP required *** extension module IGL-RA15 required

Certifications and standards


EN 61000-6-2 EN 60068-2-6 (2÷25 Hz / ±1,6 mm; 25÷100 Hz / 4.0 g)
2
EN 61000-6-4 EN 60068-2-27 (a=500 m/s ; T=6 ms)

EN 61010-1 EN 60068-2-30:2005 25/55°C, RH 95%, 48hours

EN 60068-2-1 (-20 °C/16 h for std, -40 °C/16 EN 60529 (front panel IP65, back side IP20)
h for LT version) UL 6200
EN 60068-2-2 (70 °C/16 h)

E-mail: info@comap-control.com
Web: www.comap-control.com

© ComAp. Features and specification are subject to change without prior notice.