TECHNICAL SPECIFICATIONS

Manufacturer Magnetic Control Factory


Brand Name Magnetic Control & Electricals
Model. No MCE-IT-TPC-45KVA
Part Number 1 2 C 45 B P2 N5 T2
Country of Origin Saudi Arabia
Our Ref# MCFE1-2402148 R0
General Data
Item Description General Purpose Transformer
Type of Transfromer Dry Type Transformer
Product Name Isolation Transformer (Vacuum Pressure Impregnated)
Type of Cooling AN (Air Natural)
Construction Standards SASO/IEC 60076-11 & IEC 61558-1 & IEC 61558-2-4
Duty ( Continuous / Intermittent) Continuous
Electrical Specifications
Rated Power in kVA 45kVA Vector Group Dyn11
No of Phases ( 1Ø / 3Ø) 3Ø No. of Tapping 5 (Off Circuit tap Links)
Rated Frequency in Hz 60Hz +/-3% Taps Range +/-5% IN STEPS OF 2.5%
K Factor -- Winding Material COPPER
Input Voltage 480V (L-L) Output Voltage 400V (L-L) 230.94V (L-N)
3 Phase 3 Wire, Delta, 3 Phase 4 Wire, Star With
Input Connection Output Connection
Ungrounded Neutral and Ground
Max. Input Current 54.13A Max. Output Current 64.95A
No-Load Loss in Watts 585 Watts Load Loss in watts @135˚C 1870 Watts
%Z @135˚C 4% (+/-IEC TOLERANCE) Efficiency @ Full Load > 94.54%
Average Sound Level < 45 dB Dielectric Strength (BIL) AC3/ AC3
Insulation resistance @Pri > 500MΩ at 1000V DC Insulation resistance @Sec > 500MΩ at 1000V DC
Insulation Class H (Class 180) Avg. Winding Temp. Rise 115°C
Environmental Conditions Construction and Materials
Altitude <1000M Core Construction CRNGO (Rectangular)
Ambient Temperature 50°C Winding Type Rectangular
99.9% electrolytic, Dual coated copper
Operating Humidity 0 – 95 % Winding Material
conductor
Relative Humidity 91% High Grade CRNGO core with specific loss
Grade of core less than 3W/Kg@1.5T , low core
saturation
Enclosure
Degree of Protection NEMA 3R (VENTILATED) Place of installation Outdoor
Type of Mounting Floor Mounting Cable Entry Bottom Entry
760 X 900 X 910 (+/-10%
Enclosure Material Galvanized Iron Dimension (W*D*H) in mm
tolerence)
Enclosure Colour RAL 7042 Weight in Kg Aprx. 360kgs
Additional Accessories Notes
-- -- Tapping Ratio Tolerance Will Be +/-0.5% for Nominal Tap Only
-- --
-- --
-- --
-- --
THIS DRAWING IS CONFIDENTIAL. IT MUST BE COPIED TO A THIRD PARTY WITHOUT WRITTEN CONSENT. WE RESERVE ALL THE RIGHTS ON NEW IDEAS/CHACRACTERISTICS ESPECIALLY FOR PATENT PURPOSES.

900
760 760 760 760
Air Vent Slots
of 12x3mm
Secondary
on Inner side
of weather shield 55 80 55 Primary & Terminals
Secondary R2 Y2 B2 N Manufacturer
Name Plate Terminals Scope
R1 Y1 B1 R2 Y2 B2 N
Fixation point
Handle of Bus Bar
Tapping's
Customer Cable Bus Bar For
Termination Point Coil
910 with Dia 11mm Primary and 910
Secondary Winding
ALL DIMENSIONS ARE IN MM UNLESS SPECIFIED. ALL SHARP CORNERS ARE TO BE A RADIUS OF 2 MM.

160 Gland plate at

ALL DIMENSIONS ARE IN MM UNLESS SPECIFIED. ALL SHARP CORNERS ARE TO BE A RADIUS OF 2 MM.
Side Same will be Termination
reflected
to opposite side
220 180
Earth
Bus Bar
120

Earth Stud
100 Cable
Ø8 mm
entry
Front View Left Side View Internal Front View Internal Rear View

750
750 Floor Mounting
555 Holes

PANEL DIMENSION:
25X13mm
slot 80 Primary & PARAMETERS L mm (Depth) W mm H mm
55 55 Secondary
Transformer Terminals DIMENSION 760 900 910

700 mounting 700 550 INGRESS PROTECTION NEMA 3R - Ventilated Type


R1 Y1 B1 R2 Y2 B2 N
support Fixation point BOTTOM (Optional - Side Entry)
CABLE ENTRY
of Bus Bar
OUTDOOR
150 Cable Customer Cable Bus Bar For
PLACE OF INSTALLATION
Termination Point Terminal Details Primary and
110 Gland with Dia 11mm Secondary PAINTING DETAILS:

Plate Termination
POWDER COATING EPOXY BASED POWDER COATED

Base U Channel COLOUR SHADE RAL 7042


for Floor Mounting ENCLOSURE MATERIAL Galvanized Iron Sheet

TOTAL WEIGHT Appx. 360 Kgs


Internal Bottom View Foundation Details NOTE:
All dimensions are +/-10 % tolerance. During manufacturing it could be possible to change anything
with Transformer mounting support & Gland regarding the size and dimensions provided knowing we assure that we will maintain the dimensions
capacity and quality of the transformer as submitted. Tapping View may change according to the design
Plate details criteria. Louvers and slots quantity may vary according to the design criteria or dissipation factor

DATE REV. DESCRIPTION DRAWN B.A.S.I

CHECKED K.P

APPROVED P.T.M
CUSTOMER NAME : Diamond Gulf General Contracting Est, Al Jubail, KSA
TITLE : GA drawing for Dry Type Three Phase Isolation Transformer (VPI)
CAPACITY : 45 kVA
Model. No : MCE-IT-TPC-45KVA SCALE
Al-Kharj Industrial City, Kingdom of Saudi Arabia
DRAWING NO. SHT. No. No. OF SHT REVISION. No Tel: +966-3 858 7517 / 18, Mob: +966-563675505 NTS
E-mail: sales@magneticcontrol.com
Web: www.magneticcontrol.com 28.02.2024 R0 GA DRAWING
MCE-02-24-GA-28-1/MCFE1-2402148 01 02 R0
THIS DRAWING IS CONFIDENTIAL. IT MUST BE COPIED TO A THIRD PARTY WITHOUT WRITTEN CONSENT. WE RESERVE ALL THE RIGHTS ON NEW IDEAS/CHACRACTERISTICS ESPECIALLY FOR PATENT PURPOSES.

THREE PHASE ISO. TRANSFORMER


PRIMARY L-L = 480V (+/-5% in steps of 2.5%)
SECONDARY L-L = 400V (L-N = 230.94V)

PRIMARY SECONDARY

OUTPUT
INPUT

ALL DIMENSIONS ARE IN MM UNLESS SPECIFIED. ALL SHARP CORNERS ARE TO BE A RADIUS OF 2 MM.
ALL DIMENSIONS ARE IN MM UNLESS SPECIFIED. ALL SHARP CORNERS ARE TO BE A RADIUS OF 2 MM.

+2.5%
-2.5%

480V

+5%
-5%

0V
R1 230.94V
R1 R2
(+/-2x2.5%)

+2.5%

3PH 4 WIRE L-L: 400V, L-N:230.94V


-2.5%

480V

+5%
-5%

0V
Y1 230.94V
Y1 Y2
3PH 3 WIRE L-L:480V

+2.5%
-2.5%

480V

+5%
-5%

0V
B1 230.94V
B1 B2
ELECTROSTATIC
SHEILDING
N

Primary Delta Connection


Voltage R-PHASE Y-PHASE B-PHASE
456V -5% -5% -5%
468V -2.5% -2.5% -2.5%
480V 480V 480V 480V
492V +2.5% +2.5% +2.5%
504V +5% +5% +5%

PRIMARY : L-L: 480V, 3PHASE, 3 WIRE, Delta Connected, 60Hz


PRIMARY TAPPING'S : +/- 5% in steps of 2.5% DATE REV. DESCRIPTION DRAWN B.A.S.I
SECONDARY : L-L: 400V (L-N:230.94V), 3PHASE, 4 WIRE, With Neutral and Ground, Star Connected, 60Hz
VECTOR GROUP : Dyn-11 CHECKED K.P
CAPACITY : 45kVA
APPROVED P.T.M
CUSTOMER : Diamond Gulf General Contracting Est, Al Jubail, KSA
TITLE : Wiring Drawings for 45KVA Three Phase Dry Type Isolation Transformer (VPI)
MODEL.NO : MCE-IT-TPC-45KVA
Al-Kharj Industrial City, Kingdom of Saudi Arabia SCALE
Tel: +966-3 858 7517 / 18, Mob: +966-563675505
DRAWING NO. SHT. No. No. OF SHT REVISION. No E-mail: sales@magneticcontrol.com NTS
Web: www.magneticcontrol.com
MCE-02-24-SLD-28-1/MCFE1-2402148 02 02 R0 28.02.2024 R0 WIRING DRAWING
TECHNICAL SPECIFICATIONS
Manufacturer Magnetic Control Factory
Brand Name Magnetic Control & Electricals
Model. No MCE-IT-TPC-75KVA
Part Number 1 2 C 75 B P2 N5 T2
Country of Origin Saudi Arabia
Our Ref# MCFE1-2402148 R0
General Data
Item Description General Purpose Transformer
Type of Transfromer Dry Type Transformer
Product Name Isolation Transformer (Vacuum Pressure Impregnated)
Type of Cooling AN (Air Natural)
Construction Standards SASO/IEC 60076-11 & IEC 61558-1 & IEC 61558-2-4
Duty ( Continuous / Intermittent) Continuous
Electrical Specifications
Rated Power in kVA 75kVA Vector Group Dyn11
No of Phases ( 1Ø / 3Ø) 3Ø No. of Tapping 5 (Off Circuit tap Links)
Rated Frequency in Hz 60Hz +/-3% Taps Range +/-5% IN STEPS OF 2.5%
K Factor -- Winding Material COPPER
Input Voltage 480V (L-L) Output Voltage 400V (L-L) 230.94V (L-N)
3 Phase 3 Wire, Delta, 3 Phase 4 Wire, Star With
Input Connection Output Connection
Ungrounded Neutral and Ground
Max. Input Current 90.21A Max. Output Current 108.25A
No-Load Loss in Watts 900 Watts Load Loss in watts @135˚C 3020 Watts
%Z @135˚C 4% (+/-IEC TOLERANCE) Efficiency @ Full Load > 94.77%
Average Sound Level < 50 dB Dielectric Strength (BIL) AC3/ AC3
Insulation resistance @Pri > 500MΩ at 1000V DC Insulation resistance @Sec > 500MΩ at 1000V DC
Insulation Class H (Class 180) Avg. Winding Temp. Rise 115°C
Environmental Conditions Construction and Materials
Altitude <1000M Core Construction CRNGO (Rectangular)
Ambient Temperature 50°C Winding Type Rectangular
99.9% electrolytic, Dual coated copper
Operating Humidity 0 – 95 % Winding Material
conductor
Relative Humidity 91% High Grade CRNGO core with specific loss
Grade of core less than 3W/Kg@1.5T , low core
saturation
Enclosure
Degree of Protection NEMA 3R (VENTILATED) Place of installation Outdoor
Type of Mounting Floor Mounting Cable Entry Bottom Entry
760 X 900 X 910 (+/-10%
Enclosure Material Galvanized Iron Dimension (W*D*H) in mm
tolerence)
Enclosure Colour RAL 7042 Weight in Kg Aprx. 410kgs
Additional Accessories Notes
-- -- Tapping Ratio Tolerance Will Be +/-0.5% for Nominal Tap Only
-- --
-- --
-- --
-- --
THIS DRAWING IS CONFIDENTIAL. IT MUST BE COPIED TO A THIRD PARTY WITHOUT WRITTEN CONSENT. WE RESERVE ALL THE RIGHTS ON NEW IDEAS/CHACRACTERISTICS ESPECIALLY FOR PATENT PURPOSES.

900
760 760 760 760
Air Vent Slots
of 12x3mm
Secondary
on Inner side
of weather shield 55 80 55 Primary & Terminals
Secondary R2 Y2 B2 N Manufacturer
Name Plate Terminals Scope
R1 Y1 B1 R2 Y2 B2 N
Fixation point
Handle of Bus Bar
Tapping's
Customer Cable Bus Bar For
Termination Point Coil
910 with Dia 11mm Primary and 910
Secondary Winding
ALL DIMENSIONS ARE IN MM UNLESS SPECIFIED. ALL SHARP CORNERS ARE TO BE A RADIUS OF 2 MM.

160 Gland plate at

ALL DIMENSIONS ARE IN MM UNLESS SPECIFIED. ALL SHARP CORNERS ARE TO BE A RADIUS OF 2 MM.
Side Same will be Termination
reflected
to opposite side
220 180
Earth
Bus Bar
120

Earth Stud
100 Cable
Ø8 mm
entry
Front View Left Side View Internal Front View Internal Rear View

750
750 Floor Mounting
555 Holes

PANEL DIMENSION:
25X13mm
slot 80 Primary & PARAMETERS L mm (Depth) W mm H mm
55 55 Secondary
Transformer Terminals DIMENSION 760 900 910

700 mounting 700 550 INGRESS PROTECTION NEMA 3R - Ventilated Type


R1 Y1 B1 R2 Y2 B2 N
support Fixation point BOTTOM (Optional - Side Entry)
CABLE ENTRY
of Bus Bar
OUTDOOR
150 Cable Customer Cable Bus Bar For
PLACE OF INSTALLATION
Termination Point Terminal Details Primary and
110 Gland with Dia 11mm Secondary PAINTING DETAILS:

Plate Termination
POWDER COATING EPOXY BASED POWDER COATED

Base U Channel COLOUR SHADE RAL 7042


for Floor Mounting ENCLOSURE MATERIAL Galvanized Iron Sheet

TOTAL WEIGHT Appx. 410 Kgs


Internal Bottom View Foundation Details NOTE:
All dimensions are +/-10 % tolerance. During manufacturing it could be possible to change anything
with Transformer mounting support & Gland regarding the size and dimensions provided knowing we assure that we will maintain the dimensions
capacity and quality of the transformer as submitted. Tapping View may change according to the design
Plate details criteria. Louvers and slots quantity may vary according to the design criteria or dissipation factor

DATE REV. DESCRIPTION DRAWN B.A.S.I

CHECKED K.P

APPROVED P.T.M
CUSTOMER NAME : Diamond Gulf General Contracting Est, Al Jubail, KSA
TITLE : GA drawing for Dry Type Three Phase Isolation Transformer (VPI)
CAPACITY : 75 kVA
Model. No : MCE-IT-TPC-75KVA SCALE
Al-Kharj Industrial City, Kingdom of Saudi Arabia
DRAWING NO. SHT. No. No. OF SHT REVISION. No Tel: +966-3 858 7517 / 18, Mob: +966-563675505 NTS
E-mail: sales@magneticcontrol.com
Web: www.magneticcontrol.com 28.02.2024 R0 GA DRAWING
MCE-02-24-GA-28-2/MCFE1-2402148 01 02 R0
THIS DRAWING IS CONFIDENTIAL. IT MUST BE COPIED TO A THIRD PARTY WITHOUT WRITTEN CONSENT. WE RESERVE ALL THE RIGHTS ON NEW IDEAS/CHACRACTERISTICS ESPECIALLY FOR PATENT PURPOSES.

THREE PHASE ISO. TRANSFORMER


PRIMARY L-L = 480V (+/-5% in steps of 2.5%)
SECONDARY L-L = 400V (L-N = 230.94V)

PRIMARY SECONDARY

OUTPUT
INPUT

ALL DIMENSIONS ARE IN MM UNLESS SPECIFIED. ALL SHARP CORNERS ARE TO BE A RADIUS OF 2 MM.
ALL DIMENSIONS ARE IN MM UNLESS SPECIFIED. ALL SHARP CORNERS ARE TO BE A RADIUS OF 2 MM.

+2.5%
-2.5%

480V

+5%
-5%

0V
R1 230.94V
R1 R2
(+/-2x2.5%)

+2.5%

3PH 4 WIRE L-L: 400V, L-N:230.94V


-2.5%

480V

+5%
-5%

0V
Y1 230.94V
Y1 Y2
3PH 3 WIRE L-L:480V

+2.5%
-2.5%

480V

+5%
-5%

0V
B1 230.94V
B1 B2
ELECTROSTATIC
SHEILDING
N

Primary Delta Connection


Voltage R-PHASE Y-PHASE B-PHASE
456V -5% -5% -5%
468V -2.5% -2.5% -2.5%
480V 480V 480V 480V
492V +2.5% +2.5% +2.5%
504V +5% +5% +5%

PRIMARY : L-L: 480V, 3PHASE, 3 WIRE, Delta Connected, 60Hz


PRIMARY TAPPING'S : +/- 5% in steps of 2.5% DATE REV. DESCRIPTION DRAWN B.A.S.I
SECONDARY : L-L: 400V (L-N:230.94V), 3PHASE, 4 WIRE, With Neutral and Ground, Star Connected, 60Hz
VECTOR GROUP : Dyn-11 CHECKED K.P
CAPACITY : 75kVA
APPROVED P.T.M
CUSTOMER : Diamond Gulf General Contracting Est, Al Jubail, KSA
TITLE : Wiring Drawings for 75KVA Three Phase Dry Type Isolation Transformer (VPI)
MODEL.NO : MCE-IT-TPC-75KVA
Al-Kharj Industrial City, Kingdom of Saudi Arabia SCALE
Tel: +966-3 858 7517 / 18, Mob: +966-563675505
DRAWING NO. SHT. No. No. OF SHT REVISION. No E-mail: sales@magneticcontrol.com NTS
Web: www.magneticcontrol.com
MCE-02-24-SLD-28-2/MCFE1-2402148 02 02 R0 28.02.2024 R0 WIRING DRAWING
TECHNICAL SPECIFICATIONS
Manufacturer Magnetic Control Factory
Brand Name Magnetic Control & Electricals
Model. No MCE-IT-TPC-112.5KVA
Part Number 1 2 C 112.5 B P2 N5 T2
Country of Origin Saudi Arabia
Our Ref# MCFE1-2402148 R0
General Data
Item Description General Purpose Transformer
Type of Transfromer Dry Type Transformer
Product Name Isolation Transformer (Vacuum Pressure Impregnated)
Type of Cooling AN (Air Natural)
Construction Standards SASO/IEC 60076-11 & IEC 61558-1 & IEC 61558-2-4
Duty ( Continuous / Intermittent) Continuous
Electrical Specifications
Rated Power in kVA 112.5kVA Vector Group Dyn11
No of Phases ( 1Ø / 3Ø) 3Ø No. of Tapping 5 (Off Circuit tap Links)
Rated Frequency in Hz 60Hz +/-3% Taps Range +/-5% IN STEPS OF 2.5%
K Factor -- Winding Material COPPER
Input Voltage 480V (L-L) Output Voltage 400V (L-L) 230.94V (L-N)
3 Phase 3 Wire, Delta, 3 Phase 4 Wire, Star With
Input Connection Output Connection
Ungrounded Neutral and Ground
Max. Input Current 135.32A Max. Output Current 162.38A
No-Load Loss in Watts 675 Watts Load Loss in watts @135˚C 3653 Watts
%Z @135˚C 4% (+/-IEC TOLERANCE) Efficiency @ Full Load > 96.15%
Average Sound Level < 50 dB Dielectric Strength (BIL) AC3/ AC3
Insulation resistance @Pri > 500MΩ at 1000V DC Insulation resistance @Sec > 500MΩ at 1000V DC
Insulation Class H (Class 180) Avg. Winding Temp. Rise 115°C
Environmental Conditions Construction and Materials
Altitude <1000M Core Construction CRGO (Rectangular)
Ambient Temperature 50°C Winding Type Rectangular
99.9% electrolytic, Dual coated copper
Operating Humidity 0 – 95 % Winding Material
conductor
Relative Humidity 91% High Grade CRGO core with specific loss
Grade of core less than 0.7W/Kg@1.2T , low core
saturation
Enclosure
Degree of Protection NEMA 3R (VENTILATED) Place of installation Outdoor
Type of Mounting Floor Mounting Cable Entry Bottom Entry
815 X 950 X 970 (+/-10%
Enclosure Material Galvanized Iron Dimension (W*D*H) in mm
tolerence)
Enclosure Colour RAL 7042 Weight in Kg Aprx. 495kgs
Additional Accessories Notes
-- -- Tapping Ratio Tolerance Will Be +/-0.5% for Nominal Tap Only
-- --
-- --
-- --
-- --
THIS DRAWING IS CONFIDENTIAL. IT MUST BE COPIED TO A THIRD PARTY WITHOUT WRITTEN CONSENT. WE RESERVE ALL THE RIGHTS ON NEW IDEAS/CHACRACTERISTICS ESPECIALLY FOR PATENT PURPOSES.

950
815 825 815 815
Air Vent Slots
of 12x3mm 95
on Inner side
Secondary
of weather shield 55 55 Primary & Terminals
Handle
Secondary R2 Y2 B2 N Manufacturer
Name Plate Terminals Scope
R1 Y1 B1 R2 Y2 B2 N
Fixation point
of Bus Bar
Tapping's
Customer Cable Bus Bar For
Termination Point Coil
970 with Dia 13mm Primary and 970
Secondary Winding
ALL DIMENSIONS ARE IN MM UNLESS SPECIFIED. ALL SHARP CORNERS ARE TO BE A RADIUS OF 2 MM.

150 Side Cable Entry

ALL DIMENSIONS ARE IN MM UNLESS SPECIFIED. ALL SHARP CORNERS ARE TO BE A RADIUS OF 2 MM.
Same will be reflected Termination
to opposite side
Earth
210 180
Bus Bar
120

Earth Stud
120
Ø8 mm

Front View Left Side View Internal Front View Internal Rear View
810
810 Floor Mounting
610 Holes

PANEL DIMENSION:
25X13mm
slot 95 Primary & PARAMETERS L mm (Depth) W mm H mm
55 55 Secondary
Transformer Terminals DIMENSION 815 950 970

765 mounting 765 615 INGRESS PROTECTION NEMA 3R - Ventilated Type


R1 Y1 B1 R2 Y2 B2 N
support Fixation point BOTTOM (Optional - Side Entry)
CABLE ENTRY
of Bus Bar
OUTDOOR
150 Cable Customer Cable Bus Bar For
PLACE OF INSTALLATION
Termination Point Terminal Details Primary and
110 Gland with Dia 11mm Secondary PAINTING DETAILS:

Plate Termination
POWDER COATING EPOXY BASED POWDER COATED

COLOUR SHADE RAL 7042


Base U Channel
ENCLOSURE MATERIAL Galvanized Iron Sheet
for Floor Mounting
TOTAL WEIGHT Appx. 495 Kgs
Internal Bottom View Foundation Details NOTE:
All dimensions are +/-10 % tolerance. During manufacturing it could be possible to change anything
with Transformer mounting support & Gland regarding the size and dimensions provided knowing we assure that we will maintain the dimensions
capacity and quality of the transformer as submitted. Tapping View may change according to the design
Plate details criteria. Louvers and slots quantity may vary according to the design criteria or dissipation factor

DATE REV. DESCRIPTION DRAWN B.A.S.I

CHECKED K.P

APPROVED P.T.M
CUSTOMER NAME : Diamond Gulf General Contracting Est, Al Jubail, KSA
TITLE : GA drawing for Dry Type Three Phase Isolation Transformer (VPI)
CAPACITY : 112.5 kVA
Model. No : MCE-IT-TPC-112.5KVA SCALE
Al-Kharj Industrial City, Kingdom of Saudi Arabia
DRAWING NO. SHT. No. No. OF SHT REVISION. No Tel: +966-3 858 7517 / 18, Mob: +966-563675505 NTS
E-mail: sales@magneticcontrol.com
MCE-02-24-GA-28-3/MCFE1-2402148 Web: www.magneticcontrol.com 28.02.2024 R0 AS BUILT GA DRAWING
01 02 R0
THIS DRAWING IS CONFIDENTIAL. IT MUST BE COPIED TO A THIRD PARTY WITHOUT WRITTEN CONSENT. WE RESERVE ALL THE RIGHTS ON NEW IDEAS/CHACRACTERISTICS ESPECIALLY FOR PATENT PURPOSES.

THREE PHASE ISO. TRANSFORMER


PRIMARY L-L = 480V (+/-5% in steps of 2.5%)
SECONDARY L-L = 400V (L-N = 230.94V)

PRIMARY SECONDARY

OUTPUT
INPUT

ALL DIMENSIONS ARE IN MM UNLESS SPECIFIED. ALL SHARP CORNERS ARE TO BE A RADIUS OF 2 MM.
ALL DIMENSIONS ARE IN MM UNLESS SPECIFIED. ALL SHARP CORNERS ARE TO BE A RADIUS OF 2 MM.

+2.5%
-2.5%

480V

+5%
-5%

0V
R1 230.94V
R1 R2
(+/-2x2.5%)

+2.5%

3PH 4 WIRE L-L: 400V, L-N:230.94V


-2.5%

480V

+5%
-5%

0V
Y1 230.94V
Y1 Y2
3PH 3 WIRE L-L:480V

+2.5%
-2.5%

480V

+5%
-5%

0V
B1 230.94V
B1 B2
ELECTROSTATIC
SHEILDING
N

Primary Delta Connection


Voltage R-PHASE Y-PHASE B-PHASE
456V -5% -5% -5%
468V -2.5% -2.5% -2.5%
480V 480V 480V 480V
492V +2.5% +2.5% +2.5%
504V +5% +5% +5%

PRIMARY : L-L: 480V, 3PHASE, 3 WIRE, Delta Connected, 60Hz


PRIMARY TAPPING'S : +/- 5% in steps of 2.5% DATE REV. DESCRIPTION DRAWN B.A.S.I
SECONDARY : L-L: 400V (L-N:230.94V), 3PHASE, 4 WIRE, With Neutral and Ground, Star Connected, 60Hz
VECTOR GROUP : Dyn-11 CHECKED K.P
CAPACITY : 112.5kVA
APPROVED P.T.M
CUSTOMER : Diamond Gulf General Contracting Est, Al Jubail, KSA
TITLE : Wiring Drawings for 112.5KVA Three Phase Dry Type Isolation Transformer (VPI)
MODEL.NO : MCE-IT-TPC-112.5KVA
Al-Kharj Industrial City, Kingdom of Saudi Arabia SCALE
Tel: +966-3 858 7517 / 18, Mob: +966-563675505
DRAWING NO. SHT. No. No. OF SHT REVISION. No E-mail: sales@magneticcontrol.com NTS
Web: www.magneticcontrol.com
MCE-02-24-SLD-28-3/MCFE1-2402148 02 02 R0 28.02.2024 R0 WIRING DRAWING

You might also like