TECHNICAL SPECIFICATION
OF
MITSUBISHI BASIC DIESEL GENERATOR SET
This specification covers the indoor use MITSUBISHI diesel engine generator set
and attached equipment.
MGS Model MGS1400B
Code Name 5S-L50V1 5P-L50V1 6S-L50V18 6P-L50V18 6S-L50L8 6P-L50L8
Generator Frequency (Hz) 50 60
Set Voltage 1 (V) 380 380 480
Duty Stand-by Prime Stand-by Prime Stand-by Prime
Rated Output 1 (kVA) 1600 1450 1775 1600 1775 1600
(kW) 1280 1160 1420 1280 1420 1280
Engine Model S12R-PTA2-S
Speed (min-1) 1500 1800
Output 2 (kWm) 1351 1225 1494 1353 1494 1353
Fuel Consumption 3, 5
248 225 294 268 294 267
(liter/hr)
Lub.Oil Consumption 4
1.22 1.11 1.36 1.23 1.36 1.22
(liter/hr)
Cooling System Closed looped circuit by integral radiator (Oversize Radiator)
Generator Model MG-L50V1 MG-L50V18 MG-L50L8
Phase & Wire 3Phase 4 Wire
Power Factor 0.8 lagging
D/G Set Length (mm) TBA TBA 4595
Dimension Width (mm) TBA TBA 2485
& Weight Height (mm) TBA TBA 2915
Weight (kg) TBA TBA 10290
Note 1 For actual voltage and output, refer to the “Scope of supply” sheet
Note 2 Output at 40 deg C , 1000m ASL with Fan
Note 3 Fuel Consumption at 75% Load
Note 4 Lub. Oil Consumption at 100% Load
Note 5 Fuel Consumption may differ subject to site condition and specification of fuel.
Not guaranteed value
RATING DEFINITION
Duty Stand-by Prime
Over Load Not Available 10%
Yearly Average Less than 60% Less than 60%
Load Factor
Yearly Operating Hours Less than 100 hours Less than 500 hours
Allowable Average Load 1) 80% of Rated Power 1) 90% of Rated Power
Factor For 24 Hours 2) 100% of Rated Power is 2) More than 100% of Rated
available intermittently for Power is available intermittently
less than 12 hours per year. for less than 1 hour per
12 hours.
(Max. 12 hours per year)
-1-
Spec. No. MGS-1400B_A_E040_G04_501_73_00
1. BASIC CONDITIONS
1.1 MEASUREMENT
Unit of measurement, weight, and capacity concerning all of the equipment
supplied by us, SI unit and English letter are used.
1.4 GUARANTEE
The guarantee shall be valid for the period of twelve (12) calendar months after
completion of commissioning test at site or for the period of eighteen (18) calendar
months after B/L date, whichever comes earlier. The guarantee shall cover against
manufacturer defect, bad materials and workmanship only, and shall not be applicable to
damage sustained through mishandling of the equipment and force majeure. The
guarantee shall not be liable for any consequential or resultant loss or damage
howsoever occurring. The guarantee shall be subject to the proper maintenance of
machinery and equipment according to the maintenance schedule to be submitted
separately.
1.5 PAINTING
Mitsubishi standard (Dark Blue) Munsell 6.0PB 4.4/5.2
-2-
Spec. No. MGS-1400B_A_E040_G04_501_73_00
2. DIESEL ENGINE
-3-
Spec. No. MGS-1400B_A_E040_G04_501_73_00
3. AC GENERATOR
The brushless AC Generator coupled with the diesel engine and installed onto
a common bed.
The AC Generator provided the following characteristics.
-4-
Spec. No. MGS-1400B_A_E040_G04_501_73_00
(7) Overspeed
The AC Generator is capable of withstanding overspeeds to 125% of the rated
speed for two minutes under no load.
-5-
Spec. No. MGS-1400B_A_E040_G04_501_73_00
4.1 General
Automatic start engine management and instrumentation system module
in fabricated cubicle is installed on individual bracket with anti-vibration isolator.
-6-
Spec. No. MGS-1400B_A_E040_G04_501_73_00
1) Frequency / RPM
2) AC voltage phase
3) AC voltage phase-phase
4) AC Line Current
5) Oil pressure
6) Coolant temperature
7) Oil temperature λ
8) Engine hours run
9) DC battery voltage
10) Generator frequency
11) Generator load / kW
12) Generator load / kVA
13) Power factor / pf
14) Generator load / kVAr
15) Generator load / kWh, kVAh, kVarh
16) Generator phase sequence
17) Generator Nominals
18) Engine crankcase internal pressure ※λ
19) Exhaust gas temperature ※λ
20) Winding temperature (U,V,W) ※λ
21) Bearing temperature ※λ
※ These values shall be displayed on the alarm box adjacent to MGS7310GCP
λ Optional item upon request
-7-
Spec. No. MGS-1400B_A_E040_G04_501_73_00
NOTE :
1. “×” marks are applicable items.
2. “-” marks are not applicable items.
3. Eng stop by Electrical trip signal will be done after Eng cooled.
4. Regarding *, in case of “Prime” duty, that value is 145℃
5. Regarding **, in case of “Prime” duty, that value is 110%
6. Regarding ***, in case of “Prime” duty, that value is 115%
7. Optional items installed upon request.
-8-
Spec. No. MGS-1400B_A_E040_G04_501_73_00
4.7 Operation
Generator control panel has three positions of key switch.
Each position is written in below.
・STOP / RESET : Engine stop and controller reset operation are available.
・ACTIVE : Auto and manual mode can be selected by auto and manual button
on controller.
・PANEL LOCK : Even if auto or manual button is pushed, mode selection is not
applicable.
Engine start and stop shall be done by operator. When engine trouble occurred engine
should be stopped by generator panel automatically.
Remote start and stop control are available, when auto mode is selected by auto mode
button.
-9-
Spec. No. MGS-1400B_A_E040_G04_501_73_00
- End of Specification -