DG Set Specifications (320 to 625 kVA)

Parameters Genset Mod


Unit KG320 WS4 KG380 WS KG 400 WS2 KG 500
Prime Rating at 0.8 pf kVA (kW) 320 (256) 380 (304) 400 (320) 500 (400)

Voltage V 415 415 415 415

Frequency Hz 50 50 50 50

Overall Dimensions with canopy(L W H) mm 570020002555 570020002555 570020002555 62002000

Dry Weight of genset with canopy (Aprox) kg. 5200 6000 6000 6655

Electrical starting system Volt-DC 24 (212 V) 24 (212 V) 24 (212 V) 24 (212 V

Battery Capacity Ah 180 180 180 180

DG set Noise level as per CPCB Norms dBA < 75 < 75 < 75 < 75

Engine Specifications
Parameters Engine Mode
Unit DV6I TA SR1 DV8 SR2 DV8 DV10
Rated output (prime rating as per ISO 3046) kW (hp) 284 (386) 346 (470) 360 (490) 448(608)

No. of cylinder Nos. 6 8 8 10

Bore Stroke mm 123x155 130x15O 130x15O 130x15O

Aspiration TA TA TA TA

Governing Class Electronic A0 Electronic A0 Electronic A0 Electronic A0

SFC at 75% load* (g/Hp-hr) 147 145 144 146

SFC at 100% load* (g/Hp-hr) 147 143 143 143

Lub oil Consumption* LPH 0.11 0.10 0.10 0.13

Lub oil change period** hrs 250 500 500 500

Lub oil Sump capacity Ltrs 23 41 41 45

Alternator Specifications
Parameters Alternator M
Unit KG 284 C KG 354 S1 KG 354 S2 KG 35
Rating kVA 320 380 400 500

Insulation Class H H H H

Protection IP IP23 IP23 IP23 IP23

Time to built up rated voltage at rated RPM sec <5 <5 <5 <5

Alternator Efficiency at 100% load % 93.8 94.1 94.1 94.8

Voltage regulation % +1 +1 +1 +1
Wave form Distortion at No load & at Non-distorting
% < 1.8 & < 4 < 1.8 & < 4 < 1.8 & < 4 < 1.8 & <
balanced linear Load

Permissible transient voltage dip at full load 0.8 pf lag*** % < 18 < 18 < 18 < 18

In the view of continuous product updation and design changes, all above specifications &
dimensions are subject to change without prior notice

Notes :
Genset ratings as per ISO 8528 performance class is G3.
Prime Power Rating is the maximum power available continuously for a variable electrical load
for unlimited number of hours per year under standard operating conditions.
For the site conditions other than standard operating conditions, consult KOEL for available
prime power.
*+5 % tolerance as per ISO 3046. For LPH calculation specific gravity of diesel is considered as
0.845.
All canopy dimensions have tolerance of + 50 mm.
**First oil change at 50 hours.
***Permissible transient % voltage dip at full load 0.8 pf lag (alternator tested alone) as per IS
4722.