The document provides technical specifications for diesel generator sets including power ratings, features, enclosures/canopies, and control panel options.

The power ratings mentioned are Prime Power and Standby Power. Prime Power is available continuously at variable load and Standby Power is for emergency use during utility power failures.

Some standard features listed are a water cooled diesel engine, radiator, brushless alternator, heavy duty mountings, and base fuel tank. Some optional features include an automatic transfer switch, extra filters, heaters, and fuel/battery options.

Technical Data

190-600V DIESEL 01-01-2012

CUMMINS Alternator: Leroy-somer


TCM250 (Open)
Engine: LSA46.2L9 Generator
6LTAA8.9-G2 Optioanl: Stamford UCDI274K Model:
Electronic Governor TCM250C (Silent)
Tide TPA274L10

50Hz 3 Phase Power Factor: Emissions


N/A
1500 r.p.m 4 Wires Cos ¢ = 0.8 Certification:

Prime Power Standby Power Rated Current


RATINGS (PRP) (LTP) (A)
Voltage (V) kW kVA kW kVA Amps
440/254 200 250 220 275 328.0
415/240 200 250 220 275 347.8
400/230 200 250 220 275 360.9
380/220 200 250 220 275 379.8

RATINGS:
All three Phase generator sets are rated at 0.8 power factor. All single-phase generator sets are rated at 0.8 or 1.0 power
factor. TIDE Power reserves the right to change the design or specifications without notice and without any obligation
or liability whatsoever.
Prime Power:
Standby Power:
Available continuously at variable load in lieu of
Emergency Standby Power in variable load applications in
commercially purchased power for an unlimited number
accordance with ISO8528-1 in the event of a utility power
of hours per year in accordance with ISO8528-1, and an
failure. No overload available for this service as relevant
overload of 10% permitted for one hour in every twelve
alternators are peak continuous rated at 27℃.
hours of operation in accordance with ISO 3046-1.

Distributed by City Generators 35A Technology Drive Warana 4575 QLD, Australia for Tide Power System Co., Ltd.
Ph (07) 54923220 Web www.citygenerators.com.au
Standard Features
▲ High efficient water cooled diesel engine ▲ Radiator with cap and drain point.
▲ Brushless alternators (Class H, with AVR.) ▲ Fully guarded engine driven fan
▲ Heavy duty rubber anti-vibration mountings ▲ Circuit Breaker - 3 pole (MCCB)
▲ 12/24V starter batteries and connecting cables ▲ Base fuel tank for 8 hours running at 100% load
▲ Separate engine-drive battery charging alternator ▲ Oil filter - Diesel filter - Air filter
▲ Industrial silencer for open type generator sets ▲ Fully welded steel baseframe with lifting and
▲ Residential silencer for open type generator sets fork-lifting facilities.
▲ Auto start / Digital Tide Easycon Control Panel ▲ Sound proof & Weather protective enclosures for
▲ Wiring with IEC standard silent type generator sets.
▲ Factory Test Certificate
▲ Operation & Maintenance Manual & Diagrams
▲ Worldwide Product / Technical Support

Optional
△ Automatic Transfer Switch (ATS) △Extra air filters for time-maintenance
△ Water - fuel separator △Extra diesel filters for time-maintenance
△ Water heater for severe cold weather △Extra oil filters for time-maintenance
△ Lub-oil heater for severe cold weather △Separated standing fuel tank
△ 50℃-60℃ Radiator △Low coolant level sensor
△Dual wall fuel tank base △Full range of attachments and options available
△Fuel level sensor for alternator
△Maintenance free battery
△Additional CE Features Selection

Overall Dimensions (mm) & Weight (kg)

Open Type Silent Type

Length: Length:
2550 3700
Width: Width:
1000 1120
机组尺寸简图由技术部提供
Height: Height:
1670 1900
Weight: Weight:
1600 3500
Dimension and design are subject to change without notice.
Warranty

The goods of Tide Power System are under warranty against defects in materials and
workmanship for a period of 12 months or 1000 hours whichever come first from the
date of delivery to the end user (except the damageable spare parts of genset caused by
incorrect man-made operation), and that the aforementioned warranty for the same token
is back up by the engine & alternator manufactures and their global distributors.

Distributed by City Generators 35A Technology Drive Warana 4575 QLD, Australia for Tide Power System Co., Ltd.
Ph (07) 54923220 Web www.citygenerators.com.au
Engine Specification 50HZ

General Performance Lubrication System


Manufacture DCEC Cummins Oil Capacity (High - Low) N/A
Engine Model 6LTAA8.9-G2 Maximum Oil Temperature 121℃
Engine Type 4 cycle, in-line, 6-cylinder Minimum Required Lube System Capacity
Engine Speed 1500 r.p.m - Sump plus Filters 27.6Litres
Base Output Power 220kW/295hp
Standby Power 240kW/322hp Fuel System
Governor Type Electronic Type Injection System BYC P7100 Direct Injection
Governor Make / Model BYC P7100/GAC Fuel Consumption at 100% Standby power 58 Litres/hour
Air Intake Way Turbocharged and Charge Air Cooled Fuel Consumption at 100% Prime power 53 Litres/hour
Displacement 8.9L Fuel Consumption at 75% Prime power 39 Litres/hour
Cylinder Bore * Stroke 114mm × 145mm Fuel Consumption at 50% Prime power 27 Litres/hour
NO. of Cylinders 6 Fuel Consumption at 25% Prime power 15 Litres/hour
Compression Ratio 16.6:1 Fuel Tank Capacity
Engine Idle Speed 800-1000 r/min - Open Type Genset 8 Hours at Full Load
Piston Speed 7.3 m/s - Silent Type Gensets 424 Litres
Intake Air Flow 254 Litres/sec.
Air Clearner Type Dry Cooling System
Coolant Capacity - Engine Only 11.1 Litres
Exhaust System Standard Thermostat (Modulating) Range 82 - 93℃
Exhaust Gas Flow 634 Litres/sec. Maximum Top Tank Temperature
Exhaust Gas Temperature 430 - 470℃ - Standby Power 110℃
Maximum Back Pressure 10kPa - Prime Power 104℃
Exhaust Pipe Size N/A
Electric System
Air Intake System Electrical System Voltage 24V
Recommended intake piping size N/A Battery Maintenance-free
Maximum Intake Air Restriction Connecting Cables Auailable
- Dirty Element 6kPa
- Clean Element 4kPa Thermal
Radiated Heat to Ambient 22-23kW
Heat Rejection to Coolant 95-105kW
Heat Rejection to Exhaust N/A
Alternator Specification
General Data 50HZ/1500R.P.M
Manufacture / Brand Leroy-somer Prime Output Power 224kW/280kVA
Model LSA46.2L9 Standby Output Power 246kW/308kVA
AVR Model R250 Insulation class H
Coupling / Bearing Direct / Single Bearing Voltage regulation ± 0,5 %
Phase 3 Phase Total harmonic TGH / THC at no load<2.5 %-on load<2.5%
Power Factor Cos¢ = 0.8 Wave form : NEMA = TIF - (*) < 50
Winding pitch - Code 2/3 - (N° 6) Wave form : I.E.C. = THF - (*) <2%
Drip Proof IP 23 Altitude ≤ 1000 m
Excitation Shunt Overspeed 2250 min -1

Distributed by City Generators 35A Technology Drive Warana 4575 QLD, Australia for Tide Power System Co., Ltd.
Ph (07) 54923220 Web www.citygenerators.com.au
TIDE Easycon Control Systems “Let your Generator always in Control”

TIDE Power comprehensive Easycon range control panels are compact, versatile and easy to use.

Easycon 2.0L/H (GU601A / Deepsea DSE3110) panel is a key-start


auto control panel, it’s a basic control panel fits for generators up to
100kVA to provide basic operating parameters display and
protection.

Easycon 3.0 L/H (GU641B / Deepsea DSE7210) panel is an


auto & digital control panel, it’s an entry level control panel
which provides full power monitoring and protection facilities.
All operating parameters are with LCD display.
(Auto Main Failure Version DSE7220 also Available.)

Easycon 4.0L/H (GU620A / Deepsea DSE7310) panel is an


auto & digital & Remote control panel which includes all the
features of Easycon 3.0, and plus data communication of full
telemetry via the RS232/RS485 interfaces, CANBus is
also included.
(Auto Main Failure Version DSE7320 also Available.)

Specifications
2 Over Speed pre-alarm & shutdown - Auto Start -
. Low Oil Pressure Pre-Alarm & shutdown - Oil Pressure -
3 0 High Water Temp. Pre-alarm & shutdown - Genset Running Hours -
4 . L Volts, Current, Frequency, Rpm (Instruments)- Battery Voltage and Charging -
. 0 / Fuel Sensor as optional -
0 L H AMF Module as optional -
L / Digital Control Panel - Switch Opening as Optional -
/ H Overcurrent Pre-alarm - AMF Module as optional -
H Overcurrent Shutdown - Power Factor -
Prefix Start, Service Indicate, Fault History for Deepsea Module.-
Remote Start (Data communication of full telemetry via the RS232/RS485) -
CANBus -

Options
Easycon 5.0H (Deepsea DSE8610) panel fits for Easycon 6.0H (Deepsea DSE8620) panel fits for Single Gen
Gen-Gen automatic Synchronising and load sharing. - Mains automatic Synchronising.

Deepsea DSE7560 Synchronising Controller for Multi


gen – Mains Synchronising. This is a separate control (For details specifications of Control Panels,
unit which enables multiple Easycon 5.0 equipped Gens please consult our sale department.)
to be synchronised with the Mains supply.

Distributed by City Generators 35A Technology Drive Warana 4575 QLD, Australia for Tide Power System Co., Ltd.
Ph (07) 54923220 Web www.citygenerators.com.au
Circuit Breaker 3 Pole MCCB - Standard (4 Pole as optional)

The generators are supplied together with a circuit breaker that permits a thermal protection against overloads and
magnetic protection against short-circuit.

Automatic Transfer Switch A.T.S - 4 Poles

TIDE Power offers not only a changeover switch but also an


integrated mains detection and switch system for your 24 Hour Power
Protection. The system enables automatic start-up and operation of the
generating set in the event of a mains power failure, overvoltage or
loss of phase; and also mains automatic re-transfer once it come back.

ATS: Automatically transfer and re-transfer load from main power to


gen-power without operator intervention. (Both Automatic and manual
operation.)
Please consult our sales department for specifications.

Enclosure / Canopy (Sound-attenuated & Weather Protective)

“Ensure a quieter life with our sound attenuation system.”


Features:

Extremely Rugged & Security and Safety


Highly Corrosion ResistantConstruction ▲Earth leakage protection
▲Body made from 2.0mm sheet steel components ▲40-50mm non-inflammable sponge inside
with powder coating ▲Control panel viewing window in a lockable access door
▲8-12 hours built-in fuel tank integrated ▲Emergency stop button mounted on canopy exterior

into the skid-mount base ▲Fuel fill and battery can only be reached via lockable
▲Excellent design and craftmanship access doors
▲Zinc alloy with black powder coated ▲Exhaust silencing system enclosed for operator safety

or Bright polished stainless steel hinges tested ▲Excellent cooling system to avoid high water temp.,

and proven to withstand corrosive conditions. reliable operation under harshest conditions.
▲Compact structure and longer service life ▲(Ambient temp.upto 40-52℃ and altitudes up to 1000M)

Easy Commissioning and Maintenance Transportability


▲Separate & Standing control cabinet at one side, ▲Lifting points on baseframe

quick fix electrical power connections. ▲<4L engine drive genset, single hook on top prepared
▲1ph and 3ph easy accessible electric sockets
▲Side doors allowing 180°opening rotation Quiet (Reduce Sound and Vibration)
▲Radiator fill access through cover in canopy roof. Noice Level:
▲Lube oil drain and radiator drain 72-78dBA at 1m & 64-70dBA at 7m

Distributed by City Generators 35A Technology Drive Warana 4575 QLD, Australia for Tide Power System Co., Ltd.
Ph (07) 54923220 Web www.citygenerators.com.au