1 Overview
Frequency inverters of the NORDAC PRO series have a communication interface for Industrial Ethernet
on board. This interface is based on NORD’s new “multi-protocol hardware philosophy” and supports
the PROFINET IO, EtherNet/IP, EtherCAT and POWERLINK dialects. The selection of a required
dialect takes place via parameterisation during commissioning by the customer.
In connection with the CANopen-based system bus, which each NORD frequency inverter is equipped
with, up to 7 additional frequency inverters can be connected to a frequency inverter with Industrial
Ethernet interface and can be integrated into the communication. The frequency inverters integrated
into the network do not require their own interface for Industrial Ethernet and therefore significantly
contribute to cost savings.
2 Solution approach
For the creation of a corresponding network and the integration into Industrial Ethernet, you will need
the following devices:
– 1x SK 550P frequency inverter
– Up to 7x frequency inverters SK 500P and higher
3 Connections
Contact
Designation
Designation Function
Contact
1 CAN_H CAN/CANopen
Function
2 CAN_L signal
90 SHD Cable shield
3 CAN_GND Reference potential
40 GND Reference potential 0 V 0V
76 CAN- CAN_L CAN/CANopen 4 n.c.
75 CAN+ CAN_H signal No function
5 n.c.
ON - OFF 6 CAN_SHLD Cable shield
7 CAN_GND Reference potential
0V
8 CAN_24V 24 V DC potential
The terminating resistors for CAN [DIP S2] must be set correctly (default = “OFF”) before commissioning
the communication via the system bus.
4 Parameterisation
No. Designation FI 1 1) FI 2 FI 3 FI 4 FI 5 FI 6 FI 7 FI 8
P503 Leading func. output Setting 4 = “Systembus active“
Parameter P899
Selection Protocol
0 No change
1 PROFINET IO
2 EtherCAT
3 EtherNet/IP
4 POWERLINK
1) After confirming the selection, the display
jumps back to setting “0”.
Information
For the frequency inverters to adopt this configuration and addressing, they must be switched off entirely
for 30 s after the configurations are complete.
For smooth integration of the project into an automation system, NORD provides the device
configuration files under the following link:
Device configuration files: Field bus files