Ancon 25-14 Restraint System
Ancon 25-14 Restraint System
Ancon 25-14 Restraint System
Ancon 25/14
Restraint System
The Ancon 25/14 Restraint System fixes an outer leaf
of brickwork to a light steel frame, through any type
of insulation.
Self-drilling high-thread screws fix through the channel and the
insulation, into the steel. Once the channel is installed, stainless
steel SD25 or basalt fibre Teplo-BF-CT 25 wall ties can be
positioned at any point along its length and are built into the bed
joints of the outer leaf of brickwork.
Self-drilling high-thread screws are available for use with a
maximum combined insulation and backing board thickness
of 220mm. When using any thickness of rigid insulation board
or ROCKWOOL Rainscreen Duo Slab®, Isover Polterm Max
Plus, Kingspan Facades K-Roc Rainscreen Slab, Knauf
Insulation Rocksilk® Rainscreen Slab, Xtratherm Stonewool and
ROCKWOOL Nyrock® Rainscreen 032 with a maximum thickness
of 180mm, the screws can be installed directly through the
insulation. When using other thicknesses of these insulations
or other semi-rigid/flexible insulations, an Ancon Compression
Sleeve (the same depth as the insulation) should be used around
the fixing screws to provide the necessary support.
System Components
25/14 Channel
Lengths: 2700, 3000mm
High-thread Fixing Screws
Lengths: For an insulation depth up to 220mm
SD25 or Teplo-BF-CT 25 Wall Ties
Lengths: For open cavities up to 334mm*
*up to 259mm for SD25 ties
55mm
Design
Embedment
the design performance for 60 years. When using our zinc plated fixing screws, to download from Ancon Compression Sleeves may be required
a 25 year warranty is offered. Contact us for full details and conditions. www.ancon.co.uk/approvals around the fixing screws with some insulations
Ancon 25/14 Channel Ancon High-Thread Fixing Screws
25/14 channel is available in lengths of Screws are available to accommodate a combined backing board and insulation thickness
2700mm and 3000mm. It features pre- of up to 220mm and a steel thickness from 1.2mm to 3mm. Ancon Fixing Screws feature a
punched holes at close centres to ensure a shaped drill tip of hardened steel that allows installation without pre-drilling. Drive sockets
fixing position is always located near the end, are available. See tables for correct screw reference and fixing centres.
even when it is cut on site. The channel has a Stainless Steel Fixing Screws
16mm opening to easily accommodate a drive Insulation/Backing Material Ancon Screw Screw Length
socket and washer for the fixing screws. Thickness (mm) Reference (mm)
30-46 HTSS-65-2PT-W 65
35-61 HTSS-82-2PT-W 82
43-79 HTSS-100-2PT-W 100
60-94 HTSS-115-2PT-W 115
14mm 65-114 HTSS-135-2PT-W 135
80-129 HTSS-150-2PT-W 150
110-159 HTSS-180-2PT-W 180
16mm 165-220 HTSS-240-2PT-W 240
25mm Notes: Suitable for use without an Ancon Compression Sleeve when using rigid insulations up to 220mm or
ROCKWOOL Rainscreen Duo Slab®, Isover Polterm Max Plus, Kingspan Facades K-Roc Rainscreen Slab, Knauf
Ancon 25/14 Channel Profile Insulation Rocksilk® Rainscreen Slab, Xtratherm Stonewool and ROCKWOOL Nyrock® Rainscreen 032 up to
180mm. The Ancon 25/14 system is also suitable for fixing to timber and concrete. Contact us for more details.
Ancon 25/14 channel features Ancon SD25 and Teplo-BF-CT 25 Wall Ties
alternate 5.3mm and 9.5mm Ancon wall ties are available in various lengths to suit open cavities from 35mm to 334mm.
diameter holes to accept They are located in the channel by rotating through 90° and can be easily moved to the
different fixings. required position where they are built into the masonry bed joint. See tables for wall tie
references and fixing centres.
The smaller diameter holes
should be used when fixing to Wall Tie Lengths/References
steel or timber with Ancon Ancon Tie Reference
Open Cavity Tie Length
High-Thread Screws. (mm) (mm) SD25 Teplo-BF-CT 25
The larger diameter holes are to 35-59 100 SD25/100 -
60-84 125 SD25/125 -
accommodate fixings
85-109 150 SD25/150 Teplo-BF-CT - 150
for concrete.
110-134 175 SD25/175 Teplo-BF-CT - 175
Note: Using the incorrect hole and 135-159 200 SD25/200 Teplo-BF-CT - 200
fixing screw combination invalidates 160-184 225 SD25/225 Teplo-BF-CT - 225
the system performance
185-209 250 SD25/250 Teplo-BF-CT - 250
210-234 275 SD25/275 Teplo-BF-CT - 275
235-259 300 SD25/300 Teplo-BF-CT - 300
260-284 325 - Teplo-BF-CT - 325
285-309 350 - Teplo-BF-CT - 350
310-334 375 - Teplo-BF-CT - 375
Light duty tie, Suitable for flat sites (less than 1 in 20) in towns and
cities where the fundamental basic wind velocity
Type 4 suitable for box-form 10 does not exceed 27m/s and altitude is not more
domestic dwellings than 150m above sea level.
Notes: Fundamental basic wind velocity must be calculated for the specific altitude of the site, refer to Clause NA.2.4 Information adapted from NA to BS EN 1991-1-4:2005
in NA to BS EN 1991-1-4:2005. The table above provides only a brief summary of information. Refer to PD 6697:2019 for use with PD 6697:2019, calculating calt for an altitude
and NA to BS EN 1991-1-4:2005 for complete information. For information on the certified management systems and of 150m above sea level. For some projects this may be
standards see Ancon.co.uk conservative. Contact Leviat for further details.
Leviat
President Way, President Park, Sheffield, S4 7UR
Tel: +44 (0) 114 275 5224, Email: info.uk@leviat.com
System Components
25/14 Channel
Lengths: 2700, 3000mm
Fixing Screws
Lengths: For an insulation depth up to 270mm
Compression Sleeve
Lengths: To suit insulation depth
SD25 or Teplo-BF-CT 25 Wall Ties
Lengths: For open cavities up to 334mm*
*up to 259mm for SD25 ties
Wall Tie
Length
14
Screw Length
55mm
Design
Embedment
Light duty tie, Suitable for flat sites (less than 1 in 20) in towns and
cities where the fundamental basic wind velocity
Type 4 suitable for box-form 10 does not exceed 27m/s and altitude is not more
domestic dwellings than 150m above sea level
Information adapted from NA to BS EN 1991-1-4:2005
Notes: Fundamental basic wind velocity must be calculated for the specific altitude of the site, refer to Clause NA.2.4
for use with PD 6697:2019, calculating calt for an altitude
in NA to BS EN 1991-1-4:2005. The table above provides only a brief summary of information. Refer to PD 6697:2019
of 150m above sea level. For some projects this may be
and NA to BS EN 1991-1-4:2005 for complete information. For information on the certified management systems and
conservative. Contact Leviat for further details.
standards see Ancon.co.uk