BAY MODULE

Protection Gateway

The BM9100 and BM9200 are dedicated to the supervisory


Implementation possibilities:
control of electrical processes through direct inputs/outputs,
protective relays or Intelligent Electronic Devices (IEDs) specially • Stand-alone control
tailored for the PSCN3020 Substation Control System. • Integrated in a control system
• Local control
Gateways:
• EFI.P-network and process
• EFI.P network and K-BUS,
MODBUS or OPN-BUS
Number of I/O per module:
• 16 digital inputs
• 16 digital outputs with common
• 8 independent digital outputs
• 3 high power digital outputs
• Up to 4 analogue inputs
Total system capacity:
They act as a gateway between the with the application-specific control
• 1 upper network (EFI.P)
EFI.P upper network and a lower sequence logic and the interlocking
• 1 lower network
Local Area Network such as logic.
(K-BUS, MODBUS,
K-BUS, MODBUS, OPN-BUS and
OPN-BUS or IEC60870-5-103),
IEC60870-5-103(VDEW). They can A network interface such as
using up to 16 devices
also operate as a stand alone K-BUS, MODBUS, OPN-BUS and
• 9 I/O boards for BM9100
equipment. IEC60870-5-103 (VDEW) provides
• 4 I/O boards for BM9200
a lower network connection where
• 250 DI via upper network
The highly modular construction each protection device is seen by
• 256 I/O points for the control
of BM9100 and BM9200 makes it the EFI.P upper network as if it was
sequence logic and inter
ideally suited to integrate the directly connected to it. Local
locking.
minimum functions for specific process control is possible through
the mimic diagram man/machine A variety of processing
applications. The device includes
interface. operations are performed
Digital Input, Analogue Input and
on I/O, such as :
Digital Output coupler modules
used to remotely or locally acquire An alphanumeric VDU or laptop • Under two user-definable trigger
status and measurement input, and computer connected to the Bay conditions, each AI can be used
Module front-panel RS-232 port lets as an internal DI for the local
to output process controls.
you set parameters, display data, control sequence;
send control commands, perform • DI are filtered using a
The EFI.P network interface allows
maintenance operations, and user-selectable time ranging
exchanges of data (signals, from 10 to 64 ms.
change the application software
controls, measurements and time
and the control sequence logic.
synchronisation); date/time setting
on BM9100 and BM9200 via the
PSCN3020 operator's station; and
downloading of the application
software and configuration, along
Technical specifications

Performances: Communication • HF disturbance withstand


• DI: • PC link IEC60255-22-1:
Time tagging: 1 ms RS-232, 2 wires, half duplex common mode 2.5kV 1Mhz
10 states changes/s. in 19200 baud rate differential mode 1kV 1Mhz
continuous flow; • Upper EFI.P IEC60255-22-2:
288 states changes/s. in dual optical fibre token ring CL 4, 15kV air; 8kV contact
avalanche condition; Data rate: 3,5 Mbits/s. IEC60255-22-3, IEC601000-4-3:
288 states changes/s. on the • Lower K-BUS CL3,10kV/m, 27MHZ-1GHz
upper network. RS-485 sync, 64 kbits/s., IEC60255-22-4:
• AI: Courier protocol CL 4, 4kV
Time tagging: 20 ms • Lower MODBUS IEC61000-4-11
Resolution: 16 bits RS-485, 300 to 19200 baud IEC61000-4-6: CL3.
Accuracy: 0.05% @ 25°C; ModBus protocol: RTU IEC61000-4-8:
0.1% over the whole temp range • Lower OPN-BUS level 5, 100A/m permanent
• Sequence control: High performance token ring 1000 A/m for short time
Typical cycle time: 20 ms network running at 9,6 kbits/s., EN55022: group 1, class A
• Time accuracy: • Lower IEC60870-5-103 (VDEW)
Environmental
1ms for synchronisation and time RS485, 300 to 19200 baud
• Temperature :
setting Protocol: IEC60870-5-103
operation: -10 to +55°C
Digital inputs Standard compliance storage: -40 to +70°C
Input current • Isolation resistance according to • Climatic category:
• 24-30V: 10 mA IEC60255-5: IEC 60068.2, BS 2011
• 48-60V: 10 mA >100MΩ, 500Vdc • Mechanical withstand :
• 110-125V: 5 mA • Dielectric: 2 kV 50/60 Hz, IEC60255-21-1,2,3:
vibration, shock, CL1

Our policy is one of continuous developtment and the right is reserved to supply equipment which may vary from that described
• 220V: 2 mA 1 mn according to IEC60255-5,
BS 142 - ANSI C37.90 seismic, CL2
Digital outputs • HV impulse withstand: free fall, 2 falls from 0.5m
Currents 5 kV, 1.2/50 µs according to -19” or 8”, 4U rack, 12kg.
• Make and carry IEC60255-5, BS 142
0.5s.: 30A, or 90A Compliant to CE marking
30 ms: 100A, or 200A
• Carry continuously:
Other
5A, or 15A
devices
• Break
135 VDC (L/R = 30 ms):
0.3A, or 1A
EFI.P-network upper network
220 VAC @ 50/60 Hz
cos  = 0.6: 5A, or 15A

Analogue inputs BAY Module


Electrical
• Input Current Ranges BM9100 or
process
4-20mA, 0-10mA, 0 -1mA BM9200
0-20mA, ±10mA, ±20mA
• Input impedance
Current input: 200 Ω or 2 kΩ
Lower network : K-BUS, MODBUS,
Auxiliary power supply OPN-BUS or IEC60870-5-103
24-30, 48-60, 110-125, 220-250
VDC or VAC 50/60 Hz; ±20%;
Protection
Consumption : < 30 W 1 2 16
devices

TRANSMISSION & DISTRIBUTION Protection & Control, HQ, 60 Route de Sartrouville, BP58, 78230 Le Pecq Cedex. France
Tel: +33 (0) 134 80 79 00 Fax: +33 (0) 134 80 79 13 Email: protection.control@tde.alstom.com Internet: www.tde.alstom.com

Publication: L1.6364B © 2000 ALSTOM 050002 Imprimerie CLÉMENT - Printed in France