Technical Data: Voltage Monitoring in 3-Phase Mains For 500V Resp. 690V
Technical Data: Voltage Monitoring in 3-Phase Mains For 500V Resp. 690V
Technical Data: Voltage Monitoring in 3-Phase Mains For 500V Resp. 690V
VSYL20
for 500V resp. 690V
Technical data
1. Functions Overvoltage category: III (in accordance with IEC 60664-1)
Voltage monitoring in 3-phase mains with adjustable thresholdes, Rated surge voltage: 6kV
adjustable tripping delay, monitoring of phase sequence and phase
failure, monitoring of asymmetry with adjustable threshold and the 6. Output circuit
following functions which are selectable by means of rotary switch: 2 potential free change over contacts
Rated voltage: 250V AC
UNDER Undervoltage monitoring Switching capacity: 1250VA (5A/250V AC)
UNDER+SEQ Undervoltage monitoring and monitoring of Fusing: 5A fast acting
phase sequence Mechanical life: 20 x 106 operations
WIN Monitoring the window between min and max Electrical life: 2 x 105 operations at 1000VA resistive load
WIN+SEQ Monitoring the window between min and max Switching frequency: max. 60/min at 100VA resistive load
and monitoring of phase sequence max. 6/min at 1000VA resistive load
UNDER+Latch Undervoltage monitoring with fault latch (in accordance with IEC 60947-5-1)
UNDER+SEQ+Latch Undervoltage monitoring and monitoring of Overvoltage category: III (in accordance with IEC 60664-1)
phase sequence with fault latch Rated surge voltage: 6kV
WIN+Latch WIN with fault latch
WIN+SEQ+Latch Monitoring the window between min and max 7. Measuring circuit
and monitoring of phase sequence Fusing: max. 20A (in accordance with UL 508)
with fault latch Measured variable: AC Sinus (48 to 63Hz)
Measured input:
2. Time ranges 3 ~ 500V terminals (N)-L1-L2-L3 (G4PM500VSYL20)
Adjustment range 3(N)~ 690/400V terminals (N)-L1-L2-L3 (G4PM690VSYL20)
Start-up suppression time: - Overload capacity:
Tripping delay: 0.1s 10s 3(N)~ 500V 3(N)~ 700V (G4PM500VSYL20)
3(N)~ 690/400V 3(N)~ 950/550V (G4PM690VSYL20)
3. Indicators Input resistance:
Red LED Asym ON: indication asymmetry failure 3~ 500V 1MΩ (G4PM500VSYL20)
Ree LED max/min ON/OFF: indication of failure of the 3(N)~ 690/400V 1MΩ (G4PM690VSYL20)
corresponding threshold Switching threshold
Red LED max/min flashes: indication of tripping delay of the Max: -20% to +30% of UN
corresponding threshold Min: -30% to +20% of UN
Red LED SEQ ON: indication phase sequence failure Asymmetry: 5% to 25%
Yellow LED ON/OFF: indication of relay output Overvoltage category: III (in accordance with IEC 60664-1)
Rated surge voltage: 6kV
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40 8. Accurary
Mounting on DIN-Rail TS 35 according to EN 60715 Base accurary: ≤3% of maximum scale value
Mounted position: any. Shockproof terminal connection according to VBG Frequency response: -
4 (PZ1 required), IP rating IP20. Tightening torque: max. 1Nm Adjustment accurary: ≤5% of maximum scale value
Terminal capacity: Repetition accurary: ≤2%
1 x 0.5 to 2.5mm² with/without multicore cable end Voltage influence: -
1 x 4mm² without multicore cable end Temperature influence: ≤0.05% / °C
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end 9. Ambient conditions
Ambient temperature: -25 to +55°C (in accordance with IEC 60068-1)
5. Input circuit -25 to +40°C (in accordance with UL 508)
Supply voltage: Storage temperature: -25 to +70°C
12 to 500V AC terminals A1-A2 (galvanically seperated) Transport temperature: -25 to +70°C
selectable via power modulesTR3 Relative humidity: 15% to 85%
Tolerance: according to specification of power module (in accordance with IEC 60721-3-3 class 3K3)
Rated frequency: according to specification of power module Pollution degree: 3 (in accordance with IEC 60664-1)
Rated consumption: 4VA (3W) Vibration resistance: 10 bis 55Hz 0.35mm
Duration of operation: 100% (in accordance with IEC 60068-2-6)
Reset time: 500ms Shock resistance: 15g 11ms (in accordance with IEC 60068-2-27)
Residual ripple for DC: -
Drop-out voltage: >30% of the supply voltage
www.tele-online.com
G4PM...VSYL20
Delay
Asymmetry monitoring
If the asymmetry of the phase-to-phase voltages exceeds the value set
at the ASYM-regulator, the set interval of the tripping delay (DELAY)
begins (red LED ASYM flashes). After the interval has expired (red
LED ASYM illuminated), the output relay switches into off-position
(yellow LED not illuminated). If the neutral wire is connected to the
device, the asymmetry of the phase voltages referred to the neutral wire
(Y-voltage) is monitored also. In that case both values of the asymmetry
are evaluated and if one of the values exceeds the value set at the
ASYM-regulator, the set interval of the tripping delay (DELAY) begins
Windowfunction (WIN, WIN+SEQ) (red LED ASYM flashes). After the interval has expired (red LED ASYM
The output relay switches into on-position (yellow LED illuminated) illuminated), the output relay switches into off-position (yellow LED not
when the measured voltage (mean value of phase-to-phase voltages) illuminated).
exceeds the value adjusted at the MIN-regulator. When the measured
voltage exceeds the value adjusted at the MAX-regulator, the set interval
of the tripping delay (DELAY) begins (red LED MAX flashes). After the LED ASYM
interval has expired (red LED MAX illuminated) the output relay switches
into off-position (yellow LED not illuminated). The output relay again
switches into on-position (yellow LED illuminated) when the measured Asym.
voltage falls below the value adjusted at the MAX-regulator (red LED
MAX not illuminated). When the measured voltage falls below the value L1 L2 L3
adjusted at the MIN-regulator, the set interval of tripping delay (DELAY)
begins again (red LED MIN flashes). After the interval has expired (red
LED MIN illuminated), the output relay switches into off-position (yellow Delay
LED not illuminated).
LED SEQ
Fault latch
The functions UNDER+L, UNDER+SEQ+L, WIN+L and WIN+SEQ+L
include a fault latch. The fault latch is active for all monitoring functions
UNDER or WIN, asymmetry and phase sequence. Faults will be stored
if the tripping delay has expired and the fault is effective on the output
relay. The fault latch keeps the output in off-position after a fault and
L1 L2 L3 freezes the LEDs for fault indication.
Saved faults may be reset by interruption the supply voltage.