Technical Data: Voltage Monitoring in 3-Phase Mains For 500V Resp. 690V

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Voltage monitoring in 3-phase mains G4PM...

VSYL20
for 500V resp. 690V

Monitoring relays - GAMMA series


Multifunction, fault latch
Monitoring of phase sequence and phase failure
Monitoring of asymmetry selectable
Connection of neutral wire optional
Detection of loss of neutral wire
Supply voltage selectable via power modules
2 change-over contacts
Width 45 mm
Industrial design

Technical data
1. Functions Overvoltage category: III (in accordance with IEC 60664-1)
Voltage monitoring in 3-phase mains with adjustable thresholdes, Rated surge voltage: 6kV
adjustable tripping delay, monitoring of phase sequence and phase
failure, monitoring of asymmetry with adjustable threshold and the 6. Output circuit
following functions which are selectable by means of rotary switch: 2 potential free change over contacts
Rated voltage: 250V AC
UNDER Undervoltage monitoring Switching capacity: 1250VA (5A/250V AC)
UNDER+SEQ Undervoltage monitoring and monitoring of Fusing: 5A fast acting
phase sequence Mechanical life: 20 x 106 operations
WIN Monitoring the window between min and max Electrical life: 2 x 105 operations at 1000VA resistive load
WIN+SEQ Monitoring the window between min and max Switching frequency: max. 60/min at 100VA resistive load
and monitoring of phase sequence max. 6/min at 1000VA resistive load
UNDER+Latch Undervoltage monitoring with fault latch (in accordance with IEC 60947-5-1)
UNDER+SEQ+Latch Undervoltage monitoring and monitoring of Overvoltage category: III (in accordance with IEC 60664-1)
phase sequence with fault latch Rated surge voltage: 6kV
WIN+Latch WIN with fault latch
WIN+SEQ+Latch Monitoring the window between min and max 7. Measuring circuit
and monitoring of phase sequence Fusing: max. 20A (in accordance with UL 508)
with fault latch Measured variable: AC Sinus (48 to 63Hz)
Measured input:
2. Time ranges 3 ~ 500V terminals (N)-L1-L2-L3 (G4PM500VSYL20)
Adjustment range 3(N)~ 690/400V terminals (N)-L1-L2-L3 (G4PM690VSYL20)
Start-up suppression time: - Overload capacity:
Tripping delay: 0.1s 10s 3(N)~ 500V 3(N)~ 700V (G4PM500VSYL20)
3(N)~ 690/400V 3(N)~ 950/550V (G4PM690VSYL20)
3. Indicators Input resistance:
Red LED Asym ON: indication asymmetry failure 3~ 500V 1MΩ (G4PM500VSYL20)
Ree LED max/min ON/OFF: indication of failure of the 3(N)~ 690/400V 1MΩ (G4PM690VSYL20)
corresponding threshold Switching threshold
Red LED max/min flashes: indication of tripping delay of the Max: -20% to +30% of UN
corresponding threshold Min: -30% to +20% of UN
Red LED SEQ ON: indication phase sequence failure Asymmetry: 5% to 25%
Yellow LED ON/OFF: indication of relay output Overvoltage category: III (in accordance with IEC 60664-1)
Rated surge voltage: 6kV
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40 8. Accurary
Mounting on DIN-Rail TS 35 according to EN 60715 Base accurary: ≤3% of maximum scale value
Mounted position: any. Shockproof terminal connection according to VBG Frequency response: -
4 (PZ1 required), IP rating IP20. Tightening torque: max. 1Nm Adjustment accurary: ≤5% of maximum scale value
Terminal capacity: Repetition accurary: ≤2%
1 x 0.5 to 2.5mm² with/without multicore cable end Voltage influence: -
1 x 4mm² without multicore cable end Temperature influence: ≤0.05% / °C
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end 9. Ambient conditions
Ambient temperature: -25 to +55°C (in accordance with IEC 60068-1)
5. Input circuit -25 to +40°C (in accordance with UL 508)
Supply voltage: Storage temperature: -25 to +70°C
12 to 500V AC terminals A1-A2 (galvanically seperated) Transport temperature: -25 to +70°C
selectable via power modulesTR3 Relative humidity: 15% to 85%
Tolerance: according to specification of power module (in accordance with IEC 60721-3-3 class 3K3)
Rated frequency: according to specification of power module Pollution degree: 3 (in accordance with IEC 60664-1)
Rated consumption: 4VA (3W) Vibration resistance: 10 bis 55Hz 0.35mm
Duration of operation: 100% (in accordance with IEC 60068-2-6)
Reset time: 500ms Shock resistance: 15g 11ms (in accordance with IEC 60068-2-27)
Residual ripple for DC: -
Drop-out voltage: >30% of the supply voltage

www.tele-online.com
G4PM...VSYL20

Functions Phase failure monitoring (SEQ)


If one of the phase voltages fails, the set interval of the tripping delay
(DELAY) begins (red LED SEQ flashes). After the interval has expired
For all the functions the LEDs Min and Max are flashing alternating, (red LED SEQ illuminated), the output relay switches into off-position
when the minimum value for the measured voltage was chosen to be (yellow LED not illuminated).
greater than the maximum value. If a failure already exists when the Reverse voltages of a consumer (e.g. a motor which conitnues to run on
device is activated, the output relay remains in off-position and the LED two phases only) do not effect the disconnection but can be monitoring
for the corresponding threshold is illuminated. by using a proper value for the asymmetry.
Under voltage monitoring (UNDER, UNDER+SEQ)
When the measured voltage (mean value of phase-to-phase voltages) LED SEQ
falls below the value adjusted at the MIN-regulator, the set interval of the
tripping delay (DELAY) begins (red LED MIN flashes). After the interval
has expired (red LED MIN illuminated), the output relay switches into
off-position (yellow LED not illuminated), the output relay again switches
into on-position (yellow LED illuminated), when the measured voltage
exceeds the value adjusted at the MAX-regulator. L1 L2 L3

Delay

Asymmetry monitoring
If the asymmetry of the phase-to-phase voltages exceeds the value set
at the ASYM-regulator, the set interval of the tripping delay (DELAY)
begins (red LED ASYM flashes). After the interval has expired (red
LED ASYM illuminated), the output relay switches into off-position
(yellow LED not illuminated). If the neutral wire is connected to the
device, the asymmetry of the phase voltages referred to the neutral wire
(Y-voltage) is monitored also. In that case both values of the asymmetry
are evaluated and if one of the values exceeds the value set at the
ASYM-regulator, the set interval of the tripping delay (DELAY) begins
Windowfunction (WIN, WIN+SEQ) (red LED ASYM flashes). After the interval has expired (red LED ASYM
The output relay switches into on-position (yellow LED illuminated) illuminated), the output relay switches into off-position (yellow LED not
when the measured voltage (mean value of phase-to-phase voltages) illuminated).
exceeds the value adjusted at the MIN-regulator. When the measured
voltage exceeds the value adjusted at the MAX-regulator, the set interval
of the tripping delay (DELAY) begins (red LED MAX flashes). After the LED ASYM
interval has expired (red LED MAX illuminated) the output relay switches
into off-position (yellow LED not illuminated). The output relay again
switches into on-position (yellow LED illuminated) when the measured Asym.
voltage falls below the value adjusted at the MAX-regulator (red LED
MAX not illuminated). When the measured voltage falls below the value L1 L2 L3
adjusted at the MIN-regulator, the set interval of tripping delay (DELAY)
begins again (red LED MIN flashes). After the interval has expired (red
LED MIN illuminated), the output relay switches into off-position (yellow Delay
LED not illuminated).

Loss of neutral wire by means of evaluation of asymmetry


A break of the neutral wire between power line and machinery is
detected as soon as asymmetry between phase-to-phase voltage and
neutral wire occurs. If the asymmetry exceeds the value set at the
ASYM-regulator, the set interval of the tripping delay (DELAY) begins
(red LED ASYM flashes). After the interval has expired (red LED ASYM
illuminated). A break of the neutral wire between our device and the
machinery can not be detected.

Phase sequence monitoring (SEQ)


Phase sequence monitoring is selectable for all functions.
If a change in phase sequence ist detected (red LED SEQ illuminated),
the output relay switches into off-position immetiately (yellow LED not
illuminated).

LED SEQ
Fault latch
The functions UNDER+L, UNDER+SEQ+L, WIN+L and WIN+SEQ+L
include a fault latch. The fault latch is active for all monitoring functions
UNDER or WIN, asymmetry and phase sequence. Faults will be stored
if the tripping delay has expired and the fault is effective on the output
relay. The fault latch keeps the output in off-position after a fault and
L1 L2 L3 freezes the LEDs for fault indication.
Saved faults may be reset by interruption the supply voltage.

www.tele-online.com
G4PM...VSYL20

Connections G4PM500VSYL20 mit Powermodul 500V AC

G4PM690VSYL20 mit Powermodul 24V AC

N
24V AC Reset F1-3
0V max. 20A

Reset F1-3
max. 20A

15 25

15 25
16 18 26 28

16 18 26 28

G4PM690VSYL20 mit Powermodul 400V AC


Dimensions
N

Reset F1-3
max. 20A Power-
modul

90mm
15 25

16 18 26 28
5mm
103mm 45mm

RELEASE 2010/10