Design Fire Fighting System
Design Fire Fighting System
Design Fire Fighting System
You can use various methods and tools to estimate the fire water
demand, such as the ISO method, the NFPA method, the Fire
Suppression Rating Schedule, or the Hazen-Williams equation.
You should also consider the domestic and industrial water demand,
as well as the peak and average demand patterns.
You should follow the codes and standards, such as NFPA 13, NFPA
14, and NFPA 24, to determine the number, type, spacing, and location
of the devices.
You should also coordinate with the fire department, the building
owners, and the users to ensure the accessibility, visibility, and
functionality of the devices.
You should conduct field tests, such as flow tests, pressure tests, and
leakage tests, to measure the actual performance of the system and
compare it with the design criteria.
You should also conduct computer simulations, such as fire scenarios,
to evaluate the system response and identify any potential problems
or improvements.
Home
About
Services
Projects
Plumbing
Fire Fighting
CAD
Resources
Contact
Hydraulic Calculations for Fire Fighting System
We designing a fire protection system, hydraulic calculations are very important to ensure that
the flow rate in piping network will be enough to control fires effectively. In NFPA, the
calculation procedures are established and verified by the three basic elements of firefighting
system:
1. Water delivery requirements of fire sprinkler system
2. Available water supply
3. The piping network system and its related friction losses.
Occupancy Classification
Any hydraulic design of sprinkler systems must begin with an analysis of the commodity being
protected. The National Fire Protection Association, Standard No. 13 “Installation of Sprinkler
Systems” (NFPA-13) defines three basic commodity classification: Light Hazard, Ordinary
Hazard and Extra Hazard. These classifications are defined in NFPA-13 and examples are
given in that document. Ordinary Hazard occupancies are divided into two categories: Ordinary
Hazard Group 1 and Ordinary Hazard Group 2. Extra Hazard occupancies are also divided
into two categories: Extra Hazard Group 1 and Extra Hazard Group 2. Once a hazard
classification is chosen for a known occupancy, the water requirements may be established from
NFPA-13, (2007) Figure 11.2.3.1.1
Density/ Area Curve for water requirements
NFPA-13, (2007) Figure 11.2.3.1.1 displays five density/area curves overlain on a graph. These
five curves correspond to the previously discussed hazard classifications: Light Hazard, Ordinary
Group 1 Hazard, Ordinary Group 2 Hazard, Extra Hazard Group 1 and Extra Hazard Group 2.
These curves stipulate the required minimum densities and remote areas that establish minimum
water requirements for sprinkler systems.
Density - The amount of water that must be delivered every minute for every square foot of floor
space. The English units for density is (gallons per minute per square foot (gpm/sq.ft.) For
example, a Light Hazard occupancy could be designed for a density of 0.1-gpm/sq.ft. This means
that 0.1-gallons must discharge every minute for every square foot of floor space over a specified
area.
Remote Area – the minimum area of floor space over which the density must discharge.
As an example, Figure 11.2.3.1.1 indicates that an acceptable design for an Ordinary Hazard
Group 1 occupancy is 0.15-gpm/sq.ft. over 1500-sq.ft.
This means the sprinkler system designer will choose the most hydraulically demanding 1500-
sq.ft. of the sprinkler system layout and perform a calculation of all sprinklers within that 1500-
sq.ft. area. Therefore, only a portion of sprinklers on a sprinkler system are expected to operate
during a typical fire, not all. If all sprinklers on a sprinkler system operate the water supply most
likely will not be adequate to control the fire.
Calculating number of sprinklers in Remote Area
Total number of sprinklers = Remote Area (Design Area) / Area covered by one sprinkler.
For example, if Remote area = 1500 sq-ft and area covered by one sprinkler = 130 sq -ft
This means that every square foot of the 1500-sq.ft. remote area must be covered with at least
0.15- gpm. By extension, this means that the floor area under each sprinkler, called the
Protection Area of Coverage, must be provided with 0.15-gpm/sq.ft. In other words, each
sprinkler must discharge enough water to provide a minimum of 0.15-gallons per minute for
every square foot it protects.
The end sprinkler must discharge 19.5-gallons every minute over the 130-sq.ft. it protects in
order to meet the minimum density requirement of NFPA-13. We might start the calculation
process at this point, however there is one other item that must be verified. NFPA-13, (2007)
section 22.4.4.10.1 states that no sprinkler may operate at less than 7-psi. This means that we
must verify that our end sprinkler satisfies this condition. For our example, we have chosen a
sprinkler with a k-factor of 8.0.
Remote Area
Calculation Summary
Click here for....
SAMPLE MANUAL HYDRAULIC CALCULATION FOR LIGHT
HAZARD FOR BEGINNERS
Sample Calculation 2