8202-531 Jun22 Past Paper Mark Scheme-Pdf - Ashx
8202-531 Jun22 Past Paper Mark Scheme-Pdf - Ashx
8202-531 Jun22 Past Paper Mark Scheme-Pdf - Ashx
1
List three technical specifications relating to the selection of a wall mounted light AO1
switch when recording on a materials list. (3 marks)
LO (unit title): 301 Planning and overseeing work activities. Test spec: 8202.301.03.02
Answers
Any three (1 mark each);
Any other suitable answer but do not allow duplicate marks where same feature is given more than
one name.
2
State the two types of losses associated with a transformer core. AO1
(2 marks)
Answers
The two acceptable (1 mark each);
Iron
Copper
Will accept eddy current loss or hysteresis as alternatives to iron loss but no other answers are
acceptable. If eddy current loss or hysteresis is given with iron loss, 1 mark only.
Will also accept heat loss as an alternative to copper loss. Question does state ‘the two’, so mark
first two if more given.
3
State two types of single-phase AC motor. AO1
(2 marks)
Answers
Capacitor start
Split phase
Universal
Induction
Accept induction and split-phase or capacitor start separate answers for 1 mark each even though
each are induction motors. Accept squirrel cage as alternative to induction or wound for universal.
4
State two types of fuse commonly found in electrical installations protecting circuits. AO1
(2 marks)
Answers
HRC or HBC
Cartridge
Semi-enclosed or rewireable
Plug fuse
Accept BS numbers as alternative answers. Do not accept duplicates e.g., BS88-3 and Cartridge;
or BS88-3 (or BS88) and BS1361, as separate answers. Mark first two only and these must be
fuses for the marks.
5
List three protective conductors commonly installed in electrical installations as given AO1
in BS 7671. (3 marks)
LO (unit title): 303 Electrical design and installation practices Test spec: 8202.303.02.01
and procedures.
Answers
Earthing conductor
Main protective bonding conductor
cpc
Supplementary equipotential bonding conductor
High integrity protective conductor
Protective bonding conductor
Accept variations that are fully understandable and cannot be misunderstood. Do not accept
functional earth as this is not protective.
6
List the first three tests carried out on a newly installed radial lighting circuit. AO1
(3 marks)
LO (unit title): 304 Principles of inspection, testing and Test spec: 8202.304.02.01
commissioning electrical systems.
Answers
No other answers acceptable - order not important. Do not accept continuity of bonding etc or ring
final.
7
List three documents that would assist in fault diagnosis which are to be kept by the AO1
client. (3 marks)
LO (unit title): 306 Electrical system fault diagnosis and Test spec: 8202.306.02.01
rectification.
Answers
Exact wording not essential and other similar or separate documents allowed such as schedule of
test results but no duplications such as inspection schedule for periodic and inspection schedule
for certificate.
If electrical installation certificate (or EICR) is given and schedules as alternatives, one mark only
as these form one document.
8
List three factors that affect the decision between repairing or replacing a faulty item AO1
of equipment. (3 marks)
LO (unit title): 306 Electrical system fault diagnosis and Test spec: 8202.306.05.01
rectification.
Answers
Cost
Availability
Downtime
Legal responsibility
Safety responsibility
Accessibility
Frequency of use
Other suitable but do not accept duplications such as cost to repair, cost to replace as this would
attract one mark only or how badly it is damaged (simple language for quantifying) for 1 mark.
9
State the two methods of providing Basic Protection within a dwelling in accordance AO1
with BS 7671. (2 marks)
LO (unit title): 307 Requirements for electrical installations. Test spec: 8202.307.02.01
Answers
Insulation
Barriers or enclosures
SELV
Barriers and enclosures only count as one mark and must be given in full for the one mark. If
barriers and enclosures are given as two separate items, one mark only. Obstacles or placing out
of reach not acceptable for a dwelling. (restrict to first two answers but take care to keep barriers
and enclosures as one answer. Eg. barriers, enclosures is 1 mark only but could be presented as
two answers.
10
List three labels, as given in BS 7671, that would be located on the installation AO1
consumer unit at the origin of an electrical installation. (3 marks)
LO (unit title): 307 Requirements for electrical installations. Test spec: 8202.307.03.01
Answers
Other suitable notices or labels. Accept circuit chart even though this is not a label. Do not accept
bonding label as this would not be on the consumer unit. Do not accept sections/parts of a circuit
chart. Do not apply first three rule as many could be complex descriptions.
11
A 20 kVA transformer has a turns ratio of 8:3 and an input voltage of 400 V single- AO2
phase. (3 marks)
Determine the output current.
LO (unit title): 302 Principles of electrical science Test spec: 8202.302.01.05
Answers
20000
= 50𝐴 𝑖𝑛𝑝𝑢𝑡 (1)
400
8 𝐼 50 × 8
= 𝑠𝑜 (1) = 133.33 𝐴 (1)
3 50 3
12
Determine, for the circuit shown in figure 1, AO2
the circuit (4 marks)
a) supply current (Is) (1 mark)
b) power factor 5 total
Figure 1
LO (unit title): 302 Principles of electrical science Test spec: 8202.302.02.02 & 03
Answers
2𝜋 × 50 × 78 × 10 = 24.5 Ω (2)
200
= 𝟑. 𝟗 𝑨 (1)
51.23
45
= 0.88 (1)
51.23
Allow 1 mark only for recalling basic formula (with or without figures).
If formula is incorrect in stage 1 or 2, marks for answers should not be given or carried over. If
correct formula used but wrong answer, carry over value.
Accept values without units of measure if values are correct.
13
A three-phase installation had the following load characteristics. AO2
L1 = 45 A (4 marks)
L2 = 72 A
L3 = 66 A
Answers
14
Determine the illuminance level on a surface 3 m directly below a lamp having a AO2
luminous intensity of 800 candela. (3 marks)
Answers
800
(1) = 88.9 (1)𝑙𝑢𝑥(1)
3
15
Explain the difference between an earth fault and a short circuit including if circuit AO2
breakers or RCDs operate under each condition. (4 marks)
LO (unit title): 303 Electrical design and installation practices Test spec: 8202.303.03.01
and procedures
Answers
Earth fault is low impedance path between live (or line) and earth
Short is low impedance path between live conductors
If impedance between line and earth is low enough, circuit breaker will operate for both
RCDs will not detect short circuits
16
AO2
(2 marks)
Figure 2
Determine the overall voltage drop across the distribution and final circuit shown in
figure 2.
LO (unit title): 303 Electrical design and installation practices Test spec: 8202.303.04.01-02
and procedures
Answers
2.8 × 42 × 38
= 4.46 𝑉(1)
1000
4.46 + 1.3 = 5.7 𝑉(1)
17
A continuity of ring-final circuit test is being undertaken during an initial verification. AO2
During step 1, the following measurements were made (3 marks)
r1 – 0.8 Ω
rn – 0.8 Ω
r2 – 1.34 Ω
Explain the relationship between these results and the expected results when line
and neutral are cross connected and tested at each socket-outlet.
LO (unit title): 304 Principles of inspection, testing and Test spec: 8202.304.02.04
commissioning electrical systems
Answers
The results indicate a reduced size cpc in the circuit and Line and N are the same csa (1 for some
of this relationship).
0.8 + 0.8
(1) = 0.4 Ω (1)
4
LO (unit title): 304 Principles of inspection, testing and Test spec: 8202.304.03.02
commissioning electrical systems
Answers
19
Figure 3 shows the intended location of a new AO2
socket-outlet within a room, as requested by the (7 marks)
client. The cable used to supply the socket-outlet
is to be concealed in the plastered wall to a
depth of 35 mm and run from point A in the
ceiling void above.
Figure 3
LO (unit title): 307 Requirements for electrical installations Test spec: 8202.307.03.01
Answers
cable run above window within 150 mm of ceiling (or above ceiling) (2 marks if both options
explored)
cable to be run within 150 mm (1) of corner of the walls(1)
cable to be run directly horizontal to socket-outlet (1)
cable/circuit to be protected by 30 mA RCD (1) known as Additional Protection (1)
Identifying that the cable is less than 50 mm so requires measures of some type
Alternatively, description may take route to the left of the window but description must include
earthed metallic covering for duration of route up to the socket (to enable earthing).
Accept diagrams as an alternative answer but must include dimensions for the marks.
20
Figure 4 shows the complete earth fault loop path and supply network for a radial
power circuit in an electrical installation. (15 marks)
Figure 4
Evaluate the 230 V single-phase circuit for compliance with BS 7671 in terms of
current capacity, voltage drop and disconnection under earth fault conditions.
LO (unit title): 307 Requirements for AO4 (see below for test spec references)
electrical installations
Band 1 (1-5 marks) Indicative Content
Poor coverage of the question with no or
basic calculations undertaken but may have Design current
recalled some points in the process by 4800
showing basic formula required. Very few = 𝟐𝟗. 𝟖𝟏 𝑨
230 × 0.7
points considered with little relevance or
sequence. Limited use of reference
materials and little or no evidence that the Protective device therefore 32 A (consider
relevant information can be used in the reasoning of device type, C type more suitable for
calculations. No conclusions drawn. machine).
302.02.01
302.02.04
303.02.01
303.02.02
303.02.03
303.04.01
303.04.02
303.05.06
303.05.08
307.02.01
307.03.01
307.05.02